TS-324 Panel Guide - Welcome to Triad Corrugated · PDF fileTS-324 Panel Guide TRIAD...

12
COMMERCIAL | RESIDENTIAL | AGRICULTURAL TS-324 Panel Guide TRIAD CORRUGATED METAL, INC. The TS-324 Roof System is a heavy-duty structural roof system designed for use where water penetration resistance, expansion / contraction control, and load capacity are of prime importance. The Triad Corrugated Metal TS-324 is designed to have superior wind and water resistance, flexibility of application, and long lifespan for commercial and industrial roof instal- lations. Three levels of uplift resistance are available with Single-Lok, Double-Lok, or Triple-Lok seaming. General Information 1 TS-324 Panel Description & Summary Test Data 2 Eave Section - Eave Gutter 3 Eave Gutter - ISO View 4 Eave Section - High Eave Trim 5 High Endwall Section - Transition Flashing 6 Ridge Section 7 Ridge - ISO View 8 Starting Rake Section - Rake Trim 9 Valley Section 10 Table of Contents

Transcript of TS-324 Panel Guide - Welcome to Triad Corrugated · PDF fileTS-324 Panel Guide TRIAD...

C O M M E R C I A L | R E S I D E N T I A L | A G R I C U L T U R A L

TS-324 Panel Guide

TRIAD CORRUGATED METAL, INC.

The TS-324 Roof System is a heavy-duty structural roof system designed for use where water penetration resistance, expansion / contraction control, and load capacity are of prime importance.The Triad Corrugated Metal TS-324 is designed to have superior wind and water resistance, flexibility of application, and long lifespan for commercial and industrial roof instal-lations. Three levels of uplift resistance are available with Single-Lok, Double-Lok, or Triple-Lok seaming.

General Information 1

TS-324 Panel Description & Summary Test Data 2

Eave Section - Eave Gutter 3

Eave Gutter - ISO View 4

Eave Section - High Eave Trim 5

High Endwall Section - Transition Flashing 6

Ridge Section 7

Ridge - ISO View 8

Starting Rake Section - Rake Trim 9

Valley Section 10

Table of Contents

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com1 REV01.10

• Finishes: Classic Sil-Poly & Premium Kynar • Metals: Galvanized, Galvalume® and Aluminum• Gauges: 26ga, 24ga & 22ga• Features : ∆ Applies over open framing or solid substrate ∆ Lengths cut to the inch ∆ Minimum roof slope: 1/4:12 ∆ Self ventilating

36

ACCESSORIES

Number in circles refer to page numbers in TCM Metal Roofing Guide.

The TS-324 Trapezoidal SSR System with the Double-Lok seam is installed with the recom-mended anchor clip, then the panels are snapped together and hand seamed at each clip loca-tion, providing added separation and uplift resistance. The Triple-Lok seam is made by running a power seamer over the Double-Lok, forming a tight seam the full length of the panel. The Triple-Lok seam becomes more tightly engaged as the panel is subjected to wind uplift loads. Where maximum wind load resistance is called for, the Quad-Lok seam is formed by using the power seamer to provide an additional fold to the Triple-Lok for the full panel length.

TS-324

3”2”

24”

Female Seam Male Seam

32

31

31

31 32

3131

Roof Structural

2"

11

"2

Male�Corrugation

"43

FemaleCorrugation

or1

Stan

doff

Seam Sealant�(factory applied inside seam)

Sidelap Section

Panel ClipTa b

Base

FastenerPanel Clip

Panel Clip

TripleLok Fully seamed from end to end

Panel Clip

Panel Clip

Roof Structural

2"

11

"2

Fastener

Male FemaleCorrugation

or1

Stan

doff

Base

TabPanel Clip

Corrugation

Sidelap Section

(factory appliedSeam Sealant

inside seam)

QuadLok Adds final 90° bend

DoubleLok Crimp seamed at clips only

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com 2REV01.10

TS-324Panel Description

& Summary Test Data

Underwriters Labratories Inc. Construction # 552, 552A, 552B. UL 580/UL1897 test.Factory Mutual 4471 Uplift Test ASTM E 1592 Uplift Test

AIR INFITRATION WATER LEAKAGE

PANEL WIDTH PANEL GAUGEPURLIN

SPACING SEAM UL FM 4471ASTM E-1592

Allowable Uplift ASTM E 1680 ASTM E 1646

24 GA. ROLL-LOCK UL-90 Jan-60 24.1 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. ROLL-LOCK 1-90 33.8 .0005 CFM/sq.ft. NONE @ 12PSF.

24 GA. TRIPLE-LOCK UL-90 1-90 42.1 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. TRIPLE-LOCK 1-165 24.1 .0005 CFM/sq.ft. NONE @ 12PSF.

24GA. QUAD LOCK 1-165 48.3 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. QUAD LOCK NA NO TEST NA NA

24 GA. ROLL-LOCK 1-90 42.2 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. ROLL-LOCK 1-90 57.2 .0005 CFM/sq.ft. NONE @ 12PSF.

24 GA. TRIPLE-LOCK 62.4 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. TRIPLE-LOCK 1-165 59.8 .0005 CFM/sq.ft. NONE @ 12PSF.

24 GA. QUAD LOCK 1-165 90.5 .0005 CFM/sq.ft. NONE @ 12PSF.

22 GA. QUAD LOCK NA NO TEST NA NA

** Additional design criteria and performance testing available on request.

PANEL DESCRIPTION: 3" Trapizoidal Mechanical Seam Panel, 24 gauge standard (0.023" min.), (ASTM 792, Grade 50), AZ50 aluminum/zinc coated steel, 24" max. width, 3" tall rib, painted or unpainted. Bare galvanized limited warranty - 20 years for integrity and corrosion perforation, "Galvalume" limited warranty - 25 years.

PANEL CLIP & FASTENER: Clips -One piece 22 GA,G90 Galvanized, 3.75" long @ each purlin spacing. Fastener (2) #14 X 1-1/4", #2 Phillips Drive, Low profile head screw per clip. Alternate -Two piece floating, 22GA(upper) 16GA(lower), G90 galvanized, 4.9" long @ each purlin spacing, Fastener (2) #10-12 X 1", #2 Phillips Drive, Low profile head screw per clip. (Corrosion resistant per FBC 2007 Section 1507.4.4)

MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE: Per testing listed below based on UL 580/UL 1897 testing, ASTM E-1592 testing, FM 4471 testing.

MINIMUM ROOF SLOPE: 1/4:12 Minimum slope, 6:12 Maximum recommended.

24 GA. TS 324 MECHANICAL SEAM, 3" HIGH / 24" WIDEUPLOAD TEST RESULTS

24" 5'-0"

24" 2'-6"

Tested: 24 gauge 24" wide trapizoidal panel with 3" rib installed over steel purlin @ 5', and 2.5' spacing, with MPS 602 or MPS 603 Clip.TEST BASIS:

Triad Corrugated Metal - Panel Description & Summary Test Data

TESTING ( Dated July, 2008) **

PANEL: TCM 324 (24G / 22 GA 3" x 24")

PAINT SYSTEMS: Silicone polyester (Limited warranty 40 year for integrity and adhesion, 30 year for chalking, 30 year for fade resistance.) Kynar Fluoropon (Limited warranty 35 years for integrity and adhesion, 30 years for chalking, 30 years for fade

ROOF PANEL FIRE RATING: Panel has a Class A fire exposure rating in accordance with FBC Section 1505.3 without an additional fire barrier.

SUBSTRATE: Steel purlins spaced 5'-0" O.C. Purlins support capacity is not addressed in this testing.

VAPOR BARRIER: N/A

Triad Corrugated Metal, Inc. 12/23/09

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com3 REV01.10

TS-324 Eave Section - Eave Gutter

2"panel seam)

GutterEave Trim

Eave Structural

Wall Closure

Wall Fastener

Panel Clip Fastener

Roof Panel

Fastener

Roof Fastener

And ClosureEave Plate

(at every otherGutter Support

Fastener

1"1" or 12 2

Eave

Wall Panel

Endlap Sealant

Roof Insulation Is Not ShownNote: For Clarity Of Detail,

*

* See TCM standard gutter design.

*

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com 4REV01.10

RakeTrim

inside Rake TrimSlide Corner Box

Rivets (typ.)1/8" dia.Gutter

Box over GutterPosition Corner

PanelRoof

(2) 3/16" dia. beadTube Sealant

1/2"

TrimRake

(2) 3/16" dia. beadTube Sealant

RoofPanel

Gutter

CornerBox

1/2"

Closure / Bird Stop

Blind Rivet1/8" dia.

EAVE GUTTERDETAIL

Eave Gutter ISO View

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com5 REV01.10

TS-324 Eave Section -High Eave Trim

Wall Fastener

Wall Panel

High EaveStructural

Wall Closure

Roof Panel ClipPanel Clip Fastener

"or 112

Roof Panel

"21

High Eave Trim

Back-up

Wall Fastener

Plate

End Sealant

End Fastener

Fastener

Flashing Sealant End Dam

*

* See TCM trim design

*

2"1 1/2"

2 1/2"

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com 6REV01.10

High Endwall Section -

Transition FlashingTS-324

or 121" "1

2

"21

* Varies With Roof Pitch*

Back-up Plate

FlashingTransition

Endlap SealantEndlap Fastener

Or Counter FlashWall Panel, Reglet

End DamRoof Panel

Lap FastenerFlashing Sealant

StructuralRoof

~

~

Wall Fastener

ClipRoof Panel

FastenerPanel Clip

2"

4"(min.) 1'-6"(max.)

3"

2 1/2"

5 * *

* *

* * Varies With Roof Run Length

High Eave Section Transition Flashing

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com7 REV01.10

TS-324 Ridge Section

RIDGE SECTION

Varies With Roof Pitch*

PlateBack-up

Panel ClipFastener

Roof Panel StructuralRoof

Clip

End Dam

Flashing SealantLap Fastener

Endlap Sealant

Ridge Flashing

~

"21 or 1 "

21

12"

Roof Panel

* FastenerEndlap2"

3"

2 1/2"

4"(min.) 1'-6"(max.) ~

EndlapFastener

5 Varies With Roof Run Length* * * *

* *

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com 8REV01.10

Ridge ISO View

Roof Panel

Lap Fasteners(typ.)

End Plate

Ridge Cover

Lap Fastener@ 12" o.c.

ProtectivePaper

End Dam ( ZEE )

RakeAngle

1/4" dia. BeadTube Sealant

Side Wall

Butt end of Ridge cover flush against End Plate

Flashing Sealant

Ridge Cover

TS-324

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com9 REV01.10

Starting Rake Section -

Rake Trim

Starting Rake Section

Rake Angle

Wall Fastener

Panel Clip Fastener

Wall Panel

Wall ClosureFastener

Rake Trim

Wall

ClosureWall

Wall PanelFastener

TrimWall

Rake

Slide

Trim

24" O.C.

StructuralRoof

Panel Clip

Panel Clip Fastener

SealantFlashing

Panel Clip

Roof Insulation Is Not ShownNote: For Clarity Of Detail,

**Determined By Manufacturer.

24"

Starting Roof Panel

Lap Fastener2 1/2"

*

Alternate Sliding Rake

Trim (Allows Expansion Movement Of Rake Trim, Required When Roof Run Exceeds 50')

Rake Trim

TS-324

For additional information call Triad Corrugated Metal. (336) 625-9727 | www.triadmetalroof.com 10REV01.10

Valley Section

Valley Section

With Low Panel ClipsValley For Roof Systems

6" (min.)

2"

Valley For Roof SystemsWith High Panel Clips

Varies With Roof Pitch* * Valley Plate

12

"

DiverterWater

1 2"

ClosureCorrugation

Roof Panel

FlashingValley

Roof FastenerEndlap Sealant 12 "

(min

.)

Valley Plate

Roof Panel

FlashingValley

Roof Insulation Is Not ShownNote: For Clarity Of Detail,

Roof Fastener(locate to clearroof structurals)

1

"2 11

TS-324

2 0 8 L u c k R o a d A s h e b o r o , N C 2 7 2 0 5P h o n e : 3 3 6 6 2 5 9 7 2 7 • F a x : 3 3 6 6 2 5 9 7 2 2

w w w . t r i a d m e t a l r o o f . c o m

reener