Trouble Error Report for Civil, Building and Steel Structure

8
ODAV ONLINE TER Report Presentation Civil, Building & Steel Structure ENGINEER’S FIELD NOTE

Transcript of Trouble Error Report for Civil, Building and Steel Structure

Page 1: Trouble Error Report for Civil, Building and Steel Structure

ODAV ONLINE TER Report Presentation

Civil, Building & Steel StructureENGINEER’S FIELD NOTE

Page 2: Trouble Error Report for Civil, Building and Steel Structure

B1B1B1

• PROBLEM Area• The support of the

platform did not coincide w/ Pedestal B1 (as shown in the fig.)

• RESOLUTION• Cut the support &

relocate on the exact position of Pedestal B1(as shown in the fig.)

I. P/F support V-1206A/B did not coincide Ped. B1

Page 3: Trouble Error Report for Civil, Building and Steel Structure

• PROBLEM Area• The equipment

support did not coincide w/ Pedestal P1 (as shown in the fig.)

• RESOLUTION• Chip the existing

pavement

II. EQ. support did not coincide Ped. P1 of PN-1203

• Form a mat FDN w/ 2-Pedestal(as shown in the fig.)

Page 4: Trouble Error Report for Civil, Building and Steel Structure

III. Anchor Bolt Orientation of Ecodyne P/R FDN F1 at PN-1203

F1

Delivered Pkge STR.

• PROBLEM Area• The base plate of

delivered vendor pkge str. member did not coincide w/ Pedestal F1 w/c constructed as per plan (as shown in the fig.)• RESOLUTION• Cut the base plate

(as shown in the fig.)

• Rotate 90 deg. shown in the fig.)

Page 5: Trouble Error Report for Civil, Building and Steel Structure

Scrubber Recirc.Pump A 4Q-1781B

CABLE TRENCH

Scrubber Recirc.Pump B

IV. Local T-SUPPORTs (LTS-53/54/55/56) Interference w/

Cable Trench Cover & Incinerator Pump• PROBLEM Area

• LTS 53,54,55,56 ped. & base PL interfered with CT cover & SR Pump A/B (as shown in the fig.)• RESOLUTION

• Cut the base plate except 2ea ped. Of LTS 55.56(as shown in the fig.)• Rotate 90 deg. shown in the fig.)

Page 6: Trouble Error Report for Civil, Building and Steel Structure

LF-24A-10

Existing Paving Level

Type D(as per plan)

4” Ø Pipe

Type B(proposed)

• PROBLEM Area• An installed 4” Ø

GRP Pipe interfered w/ Type D Local FDN. (as shown in the fig.)

• RESOLUTION• Change the type

of FDN. From Type D into Type Bshown in the fig.)

V. Local FDN. LF-24A-10 Ped. Interference w/ GRP Pipe

Page 7: Trouble Error Report for Civil, Building and Steel Structure

LF-23A-02

Existing Paving Level

Type D(as per plan)

Electrical Conduit

Type B(proposed)

• PROBLEM Area• A concrete

encased electrical conduit interfered w/ Type D Local FDN. (as shown in the fig.)• RESOLUTION

• Change the type of FDN. From Type D into Type Bshown in the fig.)

VI. Local FDN. LF-23A-02 Ped. Interference w/ Elec’l Conduit