IQ 3 Controller OverviewIQ 3 Controller Overview
Honeywell
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S2 File Number
Honeywell
Introduction
Hardware
Ethernet Network
Configuration Setup
Portable Display Panel
Supervisor Software
Interface
Field devices
2 File Number
Course Objective
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S3 File Number
Honeywell
INTRODUCTIONINTRODUCTION
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S4 File Number
HoneywellEthernet –TCP/IP Networks
Introduction to TCP/IP
Ethernet TCP/IP is a suite of protocols Original intent of development was to have multiple routes which could be
used by computers communicating with each other. Developed by the “US Department of Defence” in 1973, mainly for the purpose
of interconnecting different brands of computers. TCP/IP is a non- proprietary product and is now the accepted communication
protocol on the Internet For more details on TCP/IP, visit the following website:
http://www.cisco.com
TCP = Transmission Control ProtocolTCP = Transmission Control ProtocolIP = Internet ProtocolIP = Internet Protocol
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S5 File Number
HoneywellTREND Ethernet –TCP/IP Networks
Why TCP/IP network ?
Demand for simple and fast information access WWW becoming de-facto standard for B2B connectivity Total data connectivity (http, xml,.etc) Distribution of live information (mobile devices etc.) “Open” solution with lowest proprietary content (harness the IT and
Web world of solutions)
Increasing regulations Energy issues (Part L, Carbon taxes, cost volatility, etc.) requiring
control solutions
Changing building infrastructure On-line buildings linked directly to the Internet Flood-wired Ethernet networks becoming standard inside buildings
Market FactorMarket Factor
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S6 File Number
HoneywellEthernet –TCP/IP Networks
Why TCP/IP network ?
IT / Web-based technology is widely implemented all over the world. Most widely used OPEN protocol network.
Even more popular than BACnet, LONwork, MODbus, etc. Make use of building or structure existing IT backbone setup.
Reduce cost and installation works. The smartest and best cost means of “liberating” field data for both operators
and other information systems. Move away from expensive but slow Lease Line.
Move away from a typical Building Management System network. No need of expensive software or specialised hardware for remote
access. Using commonly available web-browser for access such as INTERNET
EXPLORER
Employing Ethernet in Building SolutionEmploying Ethernet in Building Solution
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S7 File Number
HoneywellEthernet –TCP/IP Networks
AdvantagesAdvantages
WWW
From anywhere, ... From anywhere, ... at anytimeat anytime
Web enabled: Makes it easy to access and control the building, in real-time, from a standard Web browser
Managers and operators can remotely; find out what’s going on in their buildings, take rapid action to help manage costs, correct comfort problems, etc.
Why TCP/IP network ?
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S8 File Number
HoneywellEthernet –TCP/IP Networks
TREND Strategy..
Creating a WebCreating a Web--based Technology Systembased Technology System
Field level
Control level
Management level
IT levelIP
N
etw
orkin
g
D
irect w
eb
-servin
g
X
M
L etc..
Use IP networking as far down the system as is economically viable
Build native embedded web-serving capability as far down the system as is economically viable
And ultimately……Management and IT level communications in IT compatible formats
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S9 File Number
HoneywellTREND IQ 3xx Controllers
IQ 3 XCITE : WHAT IS IT ?
INTRODUCTIONINTRODUCTION
A new platform controllerA new platform controller
Uses Ethernet and TCP/IP networking technologies, IT Uses Ethernet and TCP/IP networking technologies, IT network enable, accessible from anywhere.network enable, accessible from anywhere.
BuiltBuilt--in webin web--server, no proprietary software required to server, no proprietary software required to access controller or view user specified web pagesaccess controller or view user specified web pages
Modular Hardware Modular Hardware –– Extendibility and Flexibility, up to 96 Extendibility and Flexibility, up to 96 Input / Output pointsInput / Output points
DIN Rail MountedDIN Rail Mounted
Flexible number of strategy modules Flexible number of strategy modules –– Controllers optimised to applicationControllers optimised to application
Backward compatibility with predecessor controllers Backward compatibility with predecessor controllers –– IQ2 series of IQ2 series of controllercontroller
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S10 File Number
Honeywell
Types of TREND IQ 3xx Controller :
TREND IQ 3xx Controllers
TRENDIQ 3Xact Controller
TRENDIQ 3Xcite Controller
Non-Expandable
(A) IQ 3Xact Series
(B) IQ 3Xcite Series
TRENDIQ 3Xcite Controller
Expandable
Controller Inputs & Outputs
IQ3xact/12 6 Analogue outputs & 6 Universal inputs
IQ3xcite/16 6 Analogue outputs & 10 Universal inputsonly
IQ3xcite/966 Analogue outputs & 10 Universal inputsPlus up to 80 extra points via I/O expansion modules
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S11 File Number
HoneywellTREND IQ 3xx Series Controller
TREND IQ 3Xcite Expandable CONTROLLER
The following module board are available :The following module board are available :
NoteXcite 16DI module and Xcite 8DI module can accept both voltage free contact and 24 Vac supply.
Input / Output Modules :Input / Output Modules :
Modules is connected via a rigid connector or Belden cable 3084A for up to 30 metres Maximum up to 15 boards can be fitted, limited to an additional of 80 Input / Output
points
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S12 File Number
HoneywellTREND Ethernet System
TRENDSupervisor Software
Management / Integration Level
TRENDIQ 3xx Controller
DDC / Field Controller Level
Field Devices LevelSensors Actuators
TRENDDevices
System Architecture :
3 Levels Hierarchy3 Levels Hierarchy Management Level Field Controller Level Field Devices Level
PeerPeer--toto--Peer, Distributed SystemPeer, Distributed System
Intelligence in Every ControllerIntelligence in Every Controller
Network or Standalone OperationNetwork or Standalone Operation
Compatible with Standard Protocols BACnet/IP LONworks Open Protocol Communication (OPC)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S13 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
BuiltBuilt--in microprocessor, intelligence in every controller.in microprocessor, intelligence in every controller. MCF 5272 microprocessor, speed 66MHzMCF 5272 microprocessor, speed 66MHz Memory 16 Mbytes SDRAM & 8 Mbytes FlashMemory 16 Mbytes SDRAM & 8 Mbytes Flash BuiltBuilt--in Real in Real –– Time Clock Time Clock
No replaceable fuse required.No replaceable fuse required. Protected by a self resetting thermal solid state breakerProtected by a self resetting thermal solid state breaker AutoAuto--restart capabilitiesrestart capabilities
PeerPeer--toto--Peer ControllerPeer Controller Share Global Data among the Ethernet networkShare Global Data among the Ethernet network
Ethernet PlatformEthernet Platform
Network or standNetwork or stand--alone operationalone operation Ideal for individual or small equipment application for standIdeal for individual or small equipment application for stand--alone operationalone operation Able to support up to more than 13,400 controllers in a single network, sufficient for Able to support up to more than 13,400 controllers in a single network, sufficient for
large building services or application.large building services or application.
IQ 3XCITEIQ 3XCITE
IQ 3XCITEIQ 3XCITE
StandardStandard TRENDTREND IQ Controller FeaturesIQ Controller Features
IQIQ 33XCITEXCITE FEATURESFEATURES
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S14 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
StandardStandard TRENDTREND IQ Controller FeaturesIQ Controller Features
IQIQ 33XCITEXCITE FEATURESFEATURES
Optional Portable Display PanelOptional Portable Display Panel Smart Display Panel (SDU)Smart Display Panel (SDU) IQVIEW (Network Display Panel)IQVIEW (Network Display Panel)
Fully programmable to suit different applicationFully programmable to suit different application Proportional Integral Derivatives Control Proportional Integral Derivatives Control Boolean Algebraic & Logic ModuleBoolean Algebraic & Logic Module Function ModulesFunction Modules Optimisation Start/Stop ControlOptimisation Start/Stop Control Plant Rotation / Duty CyclingPlant Rotation / Duty Cycling Sequential ControlSequential Control Etc.Etc.
SMART SMART DISPLAY DISPLAY UNITUNIT
IQVIEWIQVIEW
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S15 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
Comply to Different Standards Comply to Different Standards UL Listed Standard (24 Vac)UL Listed Standard (24 Vac) EN Standards (100 EN Standards (100 –– 230Vac) 230Vac) BSI Standard : BS EN ISO 9001:2000BSI Standard : BS EN ISO 9001:2000 CE CertifiedCE Certified
Electromagnetic Compatibility Directive Electromagnetic Compatibility Directive (89/336/EEC)(89/336/EEC)
Low Voltage Directive (73123/EEC)Low Voltage Directive (73123/EEC)
StandardStandard TRENDTREND IQ Controller FeaturesIQ Controller Features
IQIQ 33XCITEXCITE FEATURESFEATURES
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S16 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
Additional FeaturesAdditional Features
IQIQ 33XCITEXCITE FEATURESFEATURES
Faster Network speedFaster Network speed Ethernet 10 Base T NetworkEthernet 10 Base T Network Network baud rate up to 10 Mbytes/secNetwork baud rate up to 10 Mbytes/sec
No memory battery backNo memory battery back--up required.up required. All strategy and data stored in nonAll strategy and data stored in non--volatile memoryvolatile memory
BuiltBuilt--in Web browser Capabilityin Web browser Capability
Use commonly available webUse commonly available web--browser for access browser for access
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S17 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
Individual Time Scheduling capabilities Allow more than 5 time zones per controller Unlimited number of switching per 24 hours duration period Incorporate override facilities for special events
Enhance security features More than 6 user can be set up Maximum up to 99 access level Support alphanumeric password up to 30 characters Automatic sign-off capabilities
Additional FeaturesAdditional Features
IQIQ 33XCITEXCITE FEATURESFEATURES
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S18 File Number
HoneywellIntroduction to TREND IQ 3XCITE Controller
Enhance Alarm handling capabilities
Points in alarms will be highlighted in web pages Retransmit alarm to Supervisor software via IP address Retransmit alarm via SMTP to email server address
Additional LED Indicator
Power Indicator (Status & Fault) Watchdog Indicator (Software & RAM fault) Input / Output Bus Indicator (I/O Module Bus fault) Input / Output Terminal Indicator Network Transmission Indicator
Additional FeaturesAdditional Features
IQIQ 33XCITEXCITE FEATURESFEATURES
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S19 File Number
Honeywell
HARDWAREHARDWARE
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S20 File Number
Honeywell
Hardware Physical Layout
TREND IQ 3xx Controllers
Optional Battery CardIf an IQ 3Xcite Controller is set up to be a time master, an optional battery card is recommended to be installed. The battery shall help to maintain the Real Time Clock (RTC) for several years. However it need to be replaced every 5 years.
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S21 File Number
Honeywell
Battery Back-up (Optional)
TREND IQ 3xx Controllers
IQ 3Xcite Battery CardIQ 3Xcite Battery Card
Battery CardBattery Card The optional battery card is used only to maintained the Real Time Clock. As memory is stored in Flash, hence no battery required.
Battery Card Battery Card –– Real Time ClockReal Time Clock
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S22 File Number
Honeywell
Controller Power Supply
TREND IQ 3xx Controllers
Power Supply : 100 ~ 230 VacPower Supply : 100 ~ 230 Vac
Power Supply : 24 ~ 36 VdcPower Supply : 24 ~ 36 Vdc
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S23 File Number
Honeywell
Controller Interface
TREND IQ 3xx Controllers
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S24 File Number
Honeywell
Controller Data Storage
TREND IQ 3xx Controllers
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S25 File Number
Honeywell
Hardware Physical Layout
TREND IQ 3xx Controllers
Expandable ModuleExpandable Module
BUS I/O ConnectionBUS I/O Connection
Power SupplyPower Supply
Module Address Module Address SwitchSwitch
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S26 File Number
Honeywell
Hardware Physical Layout
TREND IQ 3xx Controllers
Expandable Module RangeExpandable Module Range
8 Channel Module8 Channel Module
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S27 File Number
Honeywell
Hardware Physical Layout
TREND IQ 3xx Controllers
Expandable Module RangeExpandable Module Range
4 Channel Module4 Channel Module
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S28 File Number
Honeywell
Hardware Physical Layout
TREND IQ 3xx Controllers
Expandable Module RangeExpandable Module Range
16 Channel Module16 Channel Module
I/O ModulesI/O Modules
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S29 File Number
HoneywellTREND IQ 3xx Series Controller
Rigid ConnectorRigid Connector
Expandable ModuleExpandable Module
EndEnd--ofof--Line TerminatorLine Terminator
Adjacent Rigid InterAdjacent Rigid Inter--connectorconnector
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S30 File Number
HoneywellTREND IQ 3xx Series Controller
Cable ConnectorCable Connector
Expandable ModuleExpandable Module
Wire Connector (terminator)Wire Connector (terminator)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S31 File Number
HoneywellTREND IQ 3xx Controllers
Auxiliary Power Supply Auxiliary Power Supply –– 24Vdc24Vdc
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S32 File Number
HoneywellTREND IQ 3xx Controllers
Power Supply (I/O Modules)Power Supply (I/O Modules)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S33 File Number
HoneywellTREND IQ 3xx Controllers
Power Supply (I/O Modules)Power Supply (I/O Modules)
24 Vdc Power Supply (max 1.3 A)24 Vdc Power Supply (max 1.3 A)
24 Vdc Power Supply (max 2.5 A)24 Vdc Power Supply (max 2.5 A)
24 Vdc Power Supply (max 5 A)24 Vdc Power Supply (max 5 A)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S34 File Number
Honeywell
ETHERNET NETWORKSETHERNET NETWORKS
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S35 File Number
HoneywellEthernet Networks
TREND Ethernet Networks SUPERVISORSUPERVISOR
IQ 3XCITEIQ 3XCITE
TREND ETHERNETTREND ETHERNET
IQ 3 series controllerIQ 3 series controller
Uses Ethernet and TCP/IP networking technologies, IT Uses Ethernet and TCP/IP networking technologies, IT network enable, accessible from anywhere.network enable, accessible from anywhere.
WAN
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S36 File Number
HoneywellEthernet Networks
Physical MediumNetwork CableNetwork Cable
10 Base T10 Base T Use a Physical “STAR” Topology, but uses a Logical “BUS” Topology for communicationUse a Physical “STAR” Topology, but uses a Logical “BUS” Topology for communication Device attach to HUB using a CAT3 or higher twisted pair cableDevice attach to HUB using a CAT3 or higher twisted pair cable HUBs & devices have LINK LED which indicates the segment is healthy HUBs & devices have LINK LED which indicates the segment is healthy Expand the network by daisy chaining HUB,Expand the network by daisy chaining HUB, Other similar networks in this styleOther similar networks in this style
100 Base T 100 Base T –– CAT5 (100Mbytes/s)CAT5 (100Mbytes/s) 1000 Base T 1000 Base T –– CAT6 (1Gbytes/s)CAT6 (1Gbytes/s)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S37 File Number
HoneywellEthernet Networks
Physical MediumNetwork CableNetwork Cable
Types of cable (Ethernet)Types of cable (Ethernet)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S38 File Number
HoneywellEthernet Networks
Physical MediumTREND Ethernet Devices (Industrial Rate)TREND Ethernet Devices (Industrial Rate)
Industrial rate network equipment is designed to operate in harsh industrial environmental.Industrial rate network equipment is designed to operate in harsh industrial environmental. DIN rail mounting and suitable for use in controller enclosureDIN rail mounting and suitable for use in controller enclosure
TREND EDA-2055 port switch
TREND EDS-3055 port switch
4 x 10/100 Base T & 1 x 100 Base T
TREND IMC-101Media Convertor
10/100 Base T to 100 Base Fx
EDAEDA--205 205 –– 5 port Ethernet Switch5 port Ethernet Switch
EDSEDS--305 305 –– 5 port Ethernet Switch5 port Ethernet Switch
IMCIMC--101 101 –– Media ConvertorMedia Convertor
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S39 File Number
HoneywellConfiguration
Web Pages ConfigurationIntroduction Introduction
IQ 3 controllers incorporate a web server which can deliver userIQ 3 controllers incorporate a web server which can deliver user--specific pages to a specific pages to a computer running standard internet browser software.computer running standard internet browser software.
IQ 3XCITEIQ 3XCITE
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S40 File Number
HoneywellConfiguration
Web Pages ConfigurationWelcome Page Welcome Page
IQ 3 controllers incorporate a web server which can deliver userIQ 3 controllers incorporate a web server which can deliver user--specific pages to a specific pages to a computer running standard internet browser software.computer running standard internet browser software.
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S41 File Number
HoneywellConfiguration
Web Pages ConfigurationModule Page Module Page
Module page options allows the user to see the controller strategy.Module page options allows the user to see the controller strategy. Values can be changed with the keyboard and sent with either”Enter” or one of the Values can be changed with the keyboard and sent with either”Enter” or one of the
adjustment icons.adjustment icons.
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S42 File Number
HoneywellConfiguration
Web Pages ConfigurationPlant GraphIQsPlant GraphIQs
Using Display & Directory Modules we can create Plant Graphics Using Display & Directory Modules we can create Plant Graphics
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S43 File Number
HoneywellConfiguration
Web Pages ConfigurationCreate GraphIQsCreate GraphIQs
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S44 File Number
HoneywellConfiguration
Security ConfigurationDefault Default –– System GuestSystem Guest
IQ 3 controllers incorporate a security features to prevent unathuorised access to IQ 3 controllers incorporate a security features to prevent unathuorised access to the parameter of the controller.the parameter of the controller.
However, as default, no user is set up at the controller. However, as default, no user is set up at the controller. Although no user is set up, one user still exist; System Guest with L100 (level 100) Although no user is set up, one user still exist; System Guest with L100 (level 100)
access).access). If you do not Log into the IQ 3 controller, you are log in as a System Guest which If you do not Log into the IQ 3 controller, you are log in as a System Guest which
allow you full access for an unprotected controllerallow you full access for an unprotected controller
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S45 File Number
HoneywellConfiguration
Security ConfigurationDefault Default –– System GuestSystem Guest
As soon as you configure a user, the System Guess access level is changed to LAs soon as you configure a user, the System Guess access level is changed to L--1 1 (level (level --1).1).
Hence basic read only access is givenHence basic read only access is given However, user 1 should always be configured at level 99 first and removed last.However, user 1 should always be configured at level 99 first and removed last.
System Guest with readSystem Guest with read--only accessonly access
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S46 File Number
HoneywellConfiguration
Security ConfigurationLevel of AccessLevel of Access
Once Users are configured, the module view window will only show appropriate Once Users are configured, the module view window will only show appropriate modules depending on level accessmodules depending on level access
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S47 File Number
Honeywell
PORTABLE DISPLAY PANELPORTABLE DISPLAY PANEL
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S48 File Number
HoneywellPortable Display
Display PanelIntroductionIntroduction
TREND have provided portable display panel for the new IQ 3 network systemTREND have provided portable display panel for the new IQ 3 network system
TREND IQ VIEW Display TREND Smart Display Unit (SDU)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S49 File Number
Honeywell
TREND Network Display Panel
A touch screen network display panel for interface to the TREND System
IQ VIEW Portable Display
Features
Provide a user interface to the TREND IQ system Self-configuration Display graphs View & adjustment of system values View alarms Trend Loop or Ethernet Connection Password user protection
Portable Display
TREND IQ VIEW Display
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S50 File Number
HoneywellPortable Display
Display PanelIQ View IQ View –– Overview Overview
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S51 File Number
HoneywellPortable Display
Display PanelIQ View IQ View –– PhysicalPhysical
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S52 File Number
HoneywellPortable Display
Display PanelIQ View IQ View –– ConnectionConnection
Via the BuiltVia the Built--in Vcncin Vcnc
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S53 File Number
HoneywellPortable Display
Display PanelIQ View IQ View –– ConnectionConnection
Via thirdVia third--Party VcncParty Vcnc
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S54 File Number
Honeywell
TREND Portable Display Panel
A small display panel for interface to the TREND System
Smart Display Unit (SDU)
Portable Display
Features
Electroluminescent 4 x 20 character display
Illuminated button for selection or adjustment
Allows viewing and adjustment of plant parameters.
Display the alarm log
Access IQ via supervisor port only.
Variant of smart display unit
IQ Current loop controllers
IQ Xcite Ethernet controller
IQL LON Controllers.
TREND Smart Display Unit (SDU)
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S55 File Number
Honeywell
SUPERVISOR SOFTWARESUPERVISOR SOFTWARE
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S56 File Number
Honeywell
INTRODUCTION
SUPERVISOR SOFTWARESUPERVISOR SOFTWARE : WHAT IS IT ?
A real time, user interface independent of the A real time, user interface independent of the TRENDTREND System to allow System to allow monitoring and parameter adjustment to the system controllers.monitoring and parameter adjustment to the system controllers.
Supervisor Software
Main Features :
Device Viewer Device Viewer Graph DisplayGraph Display Password Access Password Access Scheduling CapabilitiesScheduling Capabilities Alarm ManagementAlarm Management
Types of TREND Supervisor Software:
Workstation Supervisor - 963 Supervisor Software Pocket PC Supervisor - 916 Mobile Display Software (MDS)
TREND963 Supervisor
Software
TREND916 MDS Software
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S57 File Number
HoneywellSupervisor Software
Time Schedules Set-point AdjustmentRecord Trend Logs
Alarm Database Password Protection Email Retransmission
TREND 963 Supervisor Software
Client -Server
Schematics Page
Features :
A graphicalgraphical, real-time interface software for monitor / control for the TREND building system – Workstation Supervisor
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S58 File Number
Honeywell
Available in different version:
963 Lite963 LiteMost basic package which provide all the fundamental features required of a supervisory package
963 Server963 ServerSimilar facilities with 963 Lite in addition of enabling the 963 to act as a web server allowing access through a web browser software such as Internet Explorer
963 Secure963 SecureSimilar facilities with 963 Lite plus an additional security features to comply to FDA Regulation 21 CPR Part 11 for pharmaceutical application
963 SNMP963 SNMPSimilar facilities with 963 Lite plus the capabilities of retransmitting alarm in Simple Network Management Protocol (SNMP) format
963 SMS Direct963 SMS DirectSimilar facilities with 963 Lite plus the capabilities of retransmitting alarm in Short Message Services (SMS) text messaging. GSM modem included
TREND Workstation Supervisor
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S59 File Number
HoneywellSupervisor Software
TREND 916MDS Software
A portableportable, real-time interface software for monitor / control for the TREND building system – Pocket PC Supervisor
Navigator Alarm LogsMonitoring Data Trend Logs
Features Small hand held device – true portability Instant operation, fast connection, Any Where Simple interface, easy to train, easy to use Ethernet (wireless), GSM, Bluetooth, Serial connection Trend parameters can be viewed and adjusted
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S60 File Number
Honeywell
INTERFACEINTERFACE
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S61 File Number
Honeywell
TREND Relay Module Single Relay Module (SRMV) :
Enables a controller analogue voltage output signal to drive a single changeover relay (Digital Output)
Maximum resistive load 8 Amps TREND
Single Relay Module Voltage
Interface Device
2 Single Relay Module AC (2 SRM) :
Enables two controller analogue voltage output signal to drive two single changeover relay independently (Digital Output)
Maximum resistive load 5 Amps with manual override link TREND
Single Relay Module AC
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S62 File Number
Honeywell
Two Voltage (V) to two Current (I) Converter Driver Module (2VID)
Converts two channel controller analogue voltage output signal (0 to 10Vdc) to two current output signal (0 mA to 20 mA)
Manual override links for aid of commissioning. TREND
2VID Module
Interface Device
TREND Signal Converter Module
Voltage (V) to Pneumatic Converter Driver Module (PN/VPC)
Converts a controller analogue voltage output signal (0 to 10Vdc) to a proportional pneumatic signal (0.2 bar to 1bar)
Requires an external 24 Vac power supply. TRENDPN/VPC Converter
Module
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S63 File Number
Honeywell
FIELD DEVICESFIELD DEVICES
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S64 File Number
Honeywell
TREND provides a wide range of field devices to suit the need of many different applications.
Field Devices
Range of Field Devices
Field Sensors Temperature, Humidity, Pressure, Air Quality, Carbon Dioxide, Velocity
Field Switches Differential Pressure
Electricity Meters Current Transformer, Multi-parameter meter
Detectors Occupancy
Electronic Actuators Valve, Damper
Valves Threaded, Flanged
Variable Speed Drive
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S65 File Number
Honeywell
Plant Temperature sensor Receiver
coverage of up to 32 sensors with a single receiver covering up to 17,000m2
No cable, no screwdriver, no hassle Simple set-up software Battery life in excess of 5 years
TREND Wireless Temperature Sensors
TRENDWireless Sensor
Field Devices
TRENDTW/S Sensor
TRENDTW/P Sensor
TRENDXW/R/IQ Transmitter
TRENDIQ 3Xcite Controller
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S66 File Number
Honeywell
Space temperature sensor c/w 3 digit display Indication & Adjustment of Set-point Indication of fan speed and occupancy
Connect to the controller via supervisor port (T-Bus) Can display reading in either Celsius or Fahrenheit Available in two variants
IQ version : IQ 2xx & IQ 3xx controllers IQL version : IQL controllers
TREND LCD Temperature Sensors
TRENDRoom Display Unit
Field Devices
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S67 File Number
HoneywellSummary
TREND Network Summary
IQ VIEW
TMNG
TMNG
GSM
LAN
ENC2
IQ VIEW
EM/MPO
SUPERVISOR
MOBILE SOFTWARE
ETHERNET
IQ 3XACT
CNC2
LAN
IQ 242
PNC
LINC
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S68 File Number
HoneywellTREND System
Applications
Typical Building Application
N O V A R I N T E L L I G E N T B U I L D I N G S Y S T E M S69 File Number