Transforming a 120 Year Old Building in Use to a Green Building
A case Study of “Die Direktion” Muenster, transforming in a Multi-Tenant Green Building
Hermann Lebherz und Annelie Stumpp present:
![Page 2: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/2.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Muenster, is situated in the north of Germany, close to the dutch border, with an uneployment rate of 2,5 %
Wien/Vienna
Muenster
![Page 3: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/3.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
aurelis Real Estate GmbH – a joint venture of HOCHTIEF SOLUTIONS AG and REDWOOD GROVE International L.P. – bought approx. 50 % of all disused German railway buildings and plots of railway good yards to redevelop the properties and to give them a new lease of live . WLS has been appointed as project manager and tenant coordinator for this project from aurelis R E.
![Page 4: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/4.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
The case study reports about a 120 year old railway building, which got partly damaged in the second world war and afterwards ceaply rebuilt in the late 50s.
![Page 5: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/5.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
•Originally the building was laid out as a single tenant building, as a former railway head quarter. •The new lease of live should transform the building in a multi-tenant building for various uses including retail on the ground floor.
![Page 6: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/6.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
- Subdividing the whole building in mutiple 400 sqm units with own services and rest rooms. - Energy shafts had to be broken through all floor slabs for each next left and right to all stairwells, to cater for water, sewage, heating, water and ventilation ducts, etc.
![Page 7: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/7.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
• The use of the revitalized building of 28.000 sqm caters for tenants such as:
Federal police, 3.000 sqm German rail way agencies, 6.000 sqm German language schools, 2.500 sqm Federal pension scheme, 3.000 sqm Various office uses Retail shops 1.500 sqm
![Page 8: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/8.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
.
Creating own entrances for the individual tenants for approx 30 diffent tenants
![Page 9: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/9.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
The wohle building was subdividedin 400 sqm self contained unitswith own entrances
![Page 10: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/10.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
2nd floor layout
![Page 11: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/11.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Up to recently the consumption of energy could not be metered and billed to the tenants.
Strategy: -Splitting up the building into letable areas of 400 sqm each. -Infrastructure shafts, for water, sewage, heating and electricity had to be broken through on going rented spaces. -Each unit is now being metered.
![Page 12: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/12.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
A energy pass shows the
bench mark how the building is performing: -33 KWh / sqm a-Well below the bench mark figures as shown on the graph, -Revitalized buildings should perform with 190 kWh / sqm a
![Page 13: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/13.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
- table showing U-values of the building components after revitalization
![Page 14: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/14.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
New district heating ducts – with energy form a waste incineration plant - were implemented with much better insulation of the ducts.
![Page 15: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/15.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
A whole new efficient low temperature water heating system was built in.
![Page 16: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/16.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
The plant rooms were totally new laid out with new electronically adjusted heating pumps, to reduce the carbon footprint.
![Page 17: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/17.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
All energy consumption - for each letable unit - is being metered to save the utmost energy.
![Page 18: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/18.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
- Water saving fixtures and urinals and wc´s are introduced to save water.
- Partly implemented turfed roofs give a better micro climate to the court yards.
- To save further energy presence detectors for the energy saving lighting fixtures were introduced.
![Page 19: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/19.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Water retaining artificial trenches under a car park were introduced to retain more water from the partly new turfed roofs.
![Page 20: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/20.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
- A low temperature heating system with individual adjustable thermostats are beeing implemented
- New cables for electricity and new meters were introduced.
![Page 21: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/21.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Highly insulated windows were implemented,
to save energy, yet to get thermal gain, through the window openings.
![Page 22: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/22.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
The whole facade was worked over with fixing new double glazed windows encompassing a
U-value of 1,0
![Page 23: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/23.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Replacment of double glazed windows takes place
![Page 24: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/24.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Mechanical ventialation is implemented to safeguard the areas of the federal police
![Page 25: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/25.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Energy saving for this green building is as follows : -Primary energy factor 0,0 (waste incineration) by reducing the carbon footprint to 0,0 % -Renewal of heating system 24 %-Highly efficient district heating network 20 %-Renewal of highly insulated windows 12 % -thermal insulation of the Facades 8 %-Insulation of last ceiling or roof 12 % -Ventilation with energy reucuperation 6 %-Metering electricity for each tenant 12 %-Electrical presence switch 6 %
![Page 26: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/26.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
situation of internal rebuilding with entirely new efficient services with improoved Insulation
![Page 27: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/27.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Showing part of the retail new units,
Children section of a drug store
![Page 28: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/28.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
The replacement
of building services is accompanied with of the first German BREEAM in use and BREEAM.de certificate
![Page 29: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/29.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Introduction of a consultncy firm in project management of complicated projects e. g. green buildings – shopping centres – revitalization – or trouble shooting
![Page 30: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/30.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
![Page 31: Transforming a 120 Year Old Building in Use to a Green Building A case Study of](https://reader035.fdocuments.us/reader035/viewer/2022062314/56813aa3550346895da29d0d/html5/thumbnails/31.jpg)
Conference 2013
Vienna – University of Economics and Business
WLS E N G I N E E R I N G+ PROJEKTMANAGEMENTGmbH & Co. KG WiesbadenLEBHERZ STUMPP + EXPERTEN
Thank you very much for your kind attention.