REVISITING THE PREFORMANCE OBJECTIVES OF FIRE PROTECTION
FOR TRANSFORMERS Kenneth W. Dungan, P.E.
SFPE Professional Development Conference, Portland OR
October 23-28, 2011
REVISITING THE PREFORMANCE OBJECTIVES OF FIRE PROTECTION FOR TRANSFORMERS
• EXISTING GUIDEANCE DOCUMENTS • LOSS CONTROL GOALS • PERFORMANCE OBJECTIVES • DESIGN CRITERIA
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
• EEI TRANSFORMER FIRE PROTECTION, MARCH 2001 • NFPA 850, RECOMMENDED PRACTICE FOR FIRE
PROTECTION FOR ELECTRIC GENERATING PLANTS AND HIGH VOLTAGE DIRECT CURRENT CONVERTER STATIONS
• NFPA 851, RECOMMENDED PRACTICE FOR FIRE PROTECTION FOR HYDROELECTRIC GENERATING PLANTS
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
• FM GLOBAL PROPERTY LOSS PREVENTION DATA SHEET 5-4, TRANSFORMERS
• IEEE STD 979-1994, IEEE GUIDE FOR SUBSTATION FIRE PROTECTION
• NFPA 15, STANDARD FOR WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
NFPA 850 & NFPA 851 – SEPARATION CRITERIA
• 500 GAL< VOLUME<5000 GAL – 2HR BARRIER OR 25FT • VOLUME>5000 GAL – 2HR BARRIER OR 50 FT
– DRAIN/CONTAIN OIL • DRAINAGE • CONTAINMENT
– ROCK FILLED PITS » KEEP FREE OF DUST, DIRT, ASH TO KEEP POROUS
– OPEN PITS » WATER SPRAY » FLAME ARRESTOR
– WATER SPRAY – NFPA 15
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
FM GLOBAL PROPERTY LOSS CONTROL DATASHEET 5-4, TRANSFORMERS
Buildings or equipment exposed by transformers should be protected by separation, a fire barrier or a water spray system on the transformers.
SEPARATION CONTAINMENT PROTECTION
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
IEEE STD979-1994, IEEE GUIDE FOR SUBSTATION FIRE PROTECTION
SEPARATION BETWEEN BUILDINGS AND TRANSFORMERS 2000 GAL OR MORE – 20FT (REGARDLESS OF PROTECTION)
2000 GAL OR MORE – 50FT OR 2-HR RATING
SEPARATION BETWEEN TRANSFORMERS 75 kVA – 10 FT 76 – 333kVA – 20 FT >333kVA – 30 FT OPTION 1-HR BARRIER
FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS
NFPA 15, STANDARD FOR WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION
SECTION 7.4 TRANSFORMERS COMPLETE WATER SPRAY ON ALL EXPOSED EXTERIOR SURFACES 0.25 GPM/SQFT ON TRANSFORMER SURFACES 0.15 GPM/SQFT ON NONABSORBING GROUND AREA OF EXPOSURE NO DIRECT IMPINGEMENT ON BUSHINGS OR LIGHTNING ARRESTERS
FIRE PROTECTION FOR TRANSFORMERS LOSS CONTROL GOALS
• MINIMIZE PROPERTY DAMAGE • MINIMIZE DOWNTIME – INTERRUPTION TO
SERVICE • MINIMIZE ENVIRONMENTAL INSULTS -
RELEASES
FIRE PROTECTION FOR TRANSFORMERS
LOSS CONTROL GOALS – MINIMIZE PROPERTY
DAMAGE – MINIMIZE DOWNTIME –
INTERRUPTION TO SERVICE
– MINIMIZE ENVIRONMENTAL INSULTS - RELEASES
PERFORMANCE OBJECTIVE – MINIMIZE FIRE SPREAD
(LIMIT DAMAGE TO SINGLE TRANSFORMER)
• CONTROL FLOW OF OIL • CONTROL THERMAL
EXPOSURE • CONTROL PROJECTILES
– SUPPRESS/EXTINGUISH OIL FIRE
LOSS CONTROL GOALS
DESIGN CRITERIA CONTROL FLOW OF OIL (CONTAIN OR DRAIN?)
– CONTAIMENT • VOLUME OF OIL • VOLUME OF WATER SPRAY (FLOW RATE
& DURATION) – HEAT SINK / ABSORBING SURFACE
• CRUSHED ROCK • ROCK FLAME ARRESTOR (12-INCHES OF
STONE) – DRAINAGE
• OIL VOLUME - NEED TO ESTABLISH DRAIN RATE
• WATER SPRAY FLOW RATE • RAIN WATER
– RETENTION • VOLUME • LOCATION • OIL/WATER SEPARATER
MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES
PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)
CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES
SUPPRESS/EXTINGUISH OIL FIRE
LOSS CONTROL GOALS
DESIGN CRITERIA CONTROL OF THERMAL EXPOSURE
– SEPARATION • SPACE (HOW MUCH?) • BARRIERS
– WATER SPRAY • NFPA 15 CRITERIA – 0.25GPM/SQFT
OF TRANSFORMER SURFACES
MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES
PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)
CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES
SUPPRESS/EXTINGUISH OIL FIRE
LOSS CONTROL GOALS
DESIGN CRITERIA CONTROL OF PROJECTILES
– SEPARATION • SPACE (HOW MUCH?) • BARRIERS
– EXPLOSION PROTECTION
MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES
PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)
CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES
SUPPRESS/EXTINGUISH OIL FIRE
LOSS CONTROL GOALS
DESIGN CRITERIA FIRE SUPPRESSION
– TYPE/LOCATION OF FIRE • TANK FIRE • SPILL FIRE
– WATER SPRAY • DENSITY • AREA
– FOAM WATER SPRAY • CAF • AFFF
MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES
PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)
CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES
SUPPRESS/EXTINGUISH OIL FIRE