Transformers - Fire Protection

14
REVISITING THE PREFORMANCE OBJECTIVES OF FIRE PROTECTION FOR TRANSFORMERS Kenneth W. Dungan, P.E. SFPE Professional Development Conference, Portland OR October 23-28, 2011

Transcript of Transformers - Fire Protection

Page 1: Transformers - Fire Protection

REVISITING THE PREFORMANCE OBJECTIVES OF FIRE PROTECTION

FOR TRANSFORMERS Kenneth W. Dungan, P.E.

SFPE Professional Development Conference, Portland OR

October 23-28, 2011

Page 2: Transformers - Fire Protection

REVISITING THE PREFORMANCE OBJECTIVES OF FIRE PROTECTION FOR TRANSFORMERS

• EXISTING GUIDEANCE DOCUMENTS • LOSS CONTROL GOALS • PERFORMANCE OBJECTIVES • DESIGN CRITERIA

Page 3: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

• EEI TRANSFORMER FIRE PROTECTION, MARCH 2001 • NFPA 850, RECOMMENDED PRACTICE FOR FIRE

PROTECTION FOR ELECTRIC GENERATING PLANTS AND HIGH VOLTAGE DIRECT CURRENT CONVERTER STATIONS

• NFPA 851, RECOMMENDED PRACTICE FOR FIRE PROTECTION FOR HYDROELECTRIC GENERATING PLANTS

Page 4: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

• FM GLOBAL PROPERTY LOSS PREVENTION DATA SHEET 5-4, TRANSFORMERS

• IEEE STD 979-1994, IEEE GUIDE FOR SUBSTATION FIRE PROTECTION

• NFPA 15, STANDARD FOR WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION

Page 5: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

NFPA 850 & NFPA 851 – SEPARATION CRITERIA

• 500 GAL< VOLUME<5000 GAL – 2HR BARRIER OR 25FT • VOLUME>5000 GAL – 2HR BARRIER OR 50 FT

– DRAIN/CONTAIN OIL • DRAINAGE • CONTAINMENT

– ROCK FILLED PITS » KEEP FREE OF DUST, DIRT, ASH TO KEEP POROUS

– OPEN PITS » WATER SPRAY » FLAME ARRESTOR

– WATER SPRAY – NFPA 15

Page 6: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

FM GLOBAL PROPERTY LOSS CONTROL DATASHEET 5-4, TRANSFORMERS

Buildings or equipment exposed by transformers should be protected by separation, a fire barrier or a water spray system on the transformers.

SEPARATION CONTAINMENT PROTECTION

Page 7: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

IEEE STD979-1994, IEEE GUIDE FOR SUBSTATION FIRE PROTECTION

SEPARATION BETWEEN BUILDINGS AND TRANSFORMERS 2000 GAL OR MORE – 20FT (REGARDLESS OF PROTECTION)

2000 GAL OR MORE – 50FT OR 2-HR RATING

SEPARATION BETWEEN TRANSFORMERS 75 kVA – 10 FT 76 – 333kVA – 20 FT >333kVA – 30 FT OPTION 1-HR BARRIER

Page 8: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS EXISTING GUIDEANCE DOCUMENTS

NFPA 15, STANDARD FOR WATER SPRAY FIXED SYSTEMS FOR FIRE PROTECTION

SECTION 7.4 TRANSFORMERS COMPLETE WATER SPRAY ON ALL EXPOSED EXTERIOR SURFACES 0.25 GPM/SQFT ON TRANSFORMER SURFACES 0.15 GPM/SQFT ON NONABSORBING GROUND AREA OF EXPOSURE NO DIRECT IMPINGEMENT ON BUSHINGS OR LIGHTNING ARRESTERS

Page 9: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS LOSS CONTROL GOALS

• MINIMIZE PROPERTY DAMAGE • MINIMIZE DOWNTIME – INTERRUPTION TO

SERVICE • MINIMIZE ENVIRONMENTAL INSULTS -

RELEASES

Page 10: Transformers - Fire Protection

FIRE PROTECTION FOR TRANSFORMERS

LOSS CONTROL GOALS – MINIMIZE PROPERTY

DAMAGE – MINIMIZE DOWNTIME –

INTERRUPTION TO SERVICE

– MINIMIZE ENVIRONMENTAL INSULTS - RELEASES

PERFORMANCE OBJECTIVE – MINIMIZE FIRE SPREAD

(LIMIT DAMAGE TO SINGLE TRANSFORMER)

• CONTROL FLOW OF OIL • CONTROL THERMAL

EXPOSURE • CONTROL PROJECTILES

– SUPPRESS/EXTINGUISH OIL FIRE

Page 11: Transformers - Fire Protection

LOSS CONTROL GOALS

DESIGN CRITERIA CONTROL FLOW OF OIL (CONTAIN OR DRAIN?)

– CONTAIMENT • VOLUME OF OIL • VOLUME OF WATER SPRAY (FLOW RATE

& DURATION) – HEAT SINK / ABSORBING SURFACE

• CRUSHED ROCK • ROCK FLAME ARRESTOR (12-INCHES OF

STONE) – DRAINAGE

• OIL VOLUME - NEED TO ESTABLISH DRAIN RATE

• WATER SPRAY FLOW RATE • RAIN WATER

– RETENTION • VOLUME • LOCATION • OIL/WATER SEPARATER

MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES

PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)

CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES

SUPPRESS/EXTINGUISH OIL FIRE

Page 12: Transformers - Fire Protection

LOSS CONTROL GOALS

DESIGN CRITERIA CONTROL OF THERMAL EXPOSURE

– SEPARATION • SPACE (HOW MUCH?) • BARRIERS

– WATER SPRAY • NFPA 15 CRITERIA – 0.25GPM/SQFT

OF TRANSFORMER SURFACES

MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES

PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)

CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES

SUPPRESS/EXTINGUISH OIL FIRE

Page 13: Transformers - Fire Protection

LOSS CONTROL GOALS

DESIGN CRITERIA CONTROL OF PROJECTILES

– SEPARATION • SPACE (HOW MUCH?) • BARRIERS

– EXPLOSION PROTECTION

MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES

PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)

CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES

SUPPRESS/EXTINGUISH OIL FIRE

Page 14: Transformers - Fire Protection

LOSS CONTROL GOALS

DESIGN CRITERIA FIRE SUPPRESSION

– TYPE/LOCATION OF FIRE • TANK FIRE • SPILL FIRE

– WATER SPRAY • DENSITY • AREA

– FOAM WATER SPRAY • CAF • AFFF

MINIMIZE PROPERTY DAMAGE MINIMIZE DOWNTIME – INTERRUPTION TO SERVICE MINIMIZE ENVIRONMENTAL INSULTS - RELEASES

PERFORMANCE OBJECTIVES MINIMIZE FIRE SPREAD (LIMIT DAMAGE TO SINGLE TRANSFORMER)

CONTROL FLOW OF OIL CONTROL THERMAL EXPOSURE CONTROL PROJECTILES

SUPPRESS/EXTINGUISH OIL FIRE