Relion ® 650 series Transformer protection RET650 Application manual

Transcript of Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in...

Page 1: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Relion® 650 series

Transformer protection RET650Application manual

Page 2: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not
Page 3: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Document ID: 1MRK 504 134-UENIssued: October 2016

Revision: AProduct version: 1.3

© Copyright 2013 ABB. All rights reserved

Page 4: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Copyright

This document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a third party,nor used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license andmay be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in theOpenSSL Toolkit. (http://www.openssl.org/)

This product includes cryptographic software written/developed by: Eric Young([email protected]) and Tim Hudson ([email protected]).

TrademarksABB and Relion are registered trademarks of the ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.

WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

ABB AB

Grid Automation Products

SE-721 59 Västerås

Sweden

Telephone: +46 (0) 21 32 50 00

Facsimile: +46 (0) 21 14 69 18

http://www.abb.com/protection-control

Page 5: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Disclaimer

The data, examples and diagrams in this manual are included solely for the concept orproduct description and are not to be deemed as a statement of guaranteed properties.All persons responsible for applying the equipment addressed in this manual mustsatisfy themselves that each intended application is suitable and acceptable, includingthat any applicable safety or other operational requirements are complied with. Inparticular, any risks in applications where a system failure and/or product failurewould create a risk for harm to property or persons (including but not limited topersonal injuries or death) shall be the sole responsibility of the person or entityapplying the equipment, and those so responsible are hereby requested to ensure thatall measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requested tonotify the manufacturer. Other than under explicit contractual commitments, in noevent shall ABB be responsible or liable for any loss or damage resulting from the useof this manual or the application of the equipment.

Page 6: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Conformity

This product complies with the directive of the Council of the European Communitieson the approximation of the laws of the Member States relating to electromagneticcompatibility (EMC Directive 2004/108/EC) and concerning electrical equipment foruse within specified voltage limits (Low-voltage directive 2006/95/EC). Thisconformity is the result of tests conducted by ABB in accordance with the productstandards EN 50263 and EN 60255-26 for the EMC directive, and with the productstandards EN 60255-1 and EN 60255-27 for the low voltage directive. The product isdesigned in accordance with the international standards of the IEC 60255 series.

Page 7: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table of contents

Section 1 Introduction.....................................................................15This manual...................................................................................... 15Intended audience............................................................................ 15Product documentation.....................................................................16

Product documentation set..........................................................16Document revision history........................................................... 17Related documents......................................................................17

Symbols and conventions.................................................................18Symbols.......................................................................................18Document conventions................................................................19

Section 2 Application......................................................................21RET650 application.......................................................................... 21Available functions............................................................................26

Main protection functions.............................................................26Back-up protection functions....................................................... 26Control and monitoring functions.................................................27Station communication................................................................ 31Basic IED functions..................................................................... 32

RET650 application examples..........................................................33Adaptation to different applications............................................. 33Two-winding HV/MV, Y/Δ-transformer.........................................33Two-winding HV/MV, Y/Y-transformer.........................................34Functionality table........................................................................35Three-winding HV/MV1/MV2, Y/Y/Δ-transformer........................ 37Three-winding HV/MV1/MV2, Y/Y/Δ-transformer........................ 38Functionality table........................................................................38

Section 3 RET650 setting examples.............................................. 41Setting example for a two-winding HV/MV transformer, Y/Δ-transformer....................................................................................... 41

Calculating general settings for analogue inputs 8I 2U............... 42Calculating settings for global base values GBASVAL................43Calculating settings for transformer differential protectionT2WPDIF ....................................................................................44Calculating settings for restricted earth fault protectionREFPDIF .................................................................................... 48Calculating settings for instantaneous phase overcurrentprotection, HV-side, PHPIOC ..................................................... 49

Table of contents

1Application manual

Page 8: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Calculating settings for four step phase overcurrentprotection 3-phase output, HV-side, OC4PTOC .........................50

Calculating general settings .................................................. 50Calculating settings for step 1................................................ 50

Calculating settings for four step phase overcurrentprotection 3-phase output, LV-side OC4PTOC .......................... 53

Calculating general settings................................................... 54Calculating settings for step 1 ............................................... 54Calculating settings for step 4................................................ 55

Calculating settings for four step residual overcurrentprotection, zero or negative sequence direction HV-sideEF4PTOC ...................................................................................57

Calculating general settings................................................... 58Calculating settings for step 1................................................ 58Calculating settings for step 2................................................ 60Calculating settings for step 4................................................ 61

Calculating settings for two step residual overvoltageprotection LV-side, ROV2PTOV .................................................62Calculating settings for HV-side breaker failure protection,CCRBRF .....................................................................................63Calculating settings for LV-side breaker failure protection,CCRBRF .....................................................................................64

Section 4 Analog inputs..................................................................67Introduction.......................................................................................67Setting guidelines............................................................................. 67

Setting of the phase reference channel.......................................67Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protection IED.. 68Setting of current channels..........................................................68

Example 1.............................................................................. 69Example 2.............................................................................. 70Examples on how to connect, configure and set CT inputsfor most commonly used CT connections.............................. 71Example on how to connect a star connected three-phaseCT set to the IED....................................................................72Example how to connect delta connected three-phase CTset to the IED..........................................................................75Example how to connect single-phase CT to the IED............ 78

Setting of voltage channels......................................................... 80Example................................................................................. 80Examples how to connect, configure and set VT inputs formost commonly used VT connections....................................80Examples on how to connect a three phase-to-earthconnected VT to the IED........................................................ 81

Table of contents

2Application manual

Page 9: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Example on how to connect a phase-to-phase connectedVT to the IED..........................................................................83Example how to connect the open delta VT to the IED forlow impedance earthed or solidly earthed power systems.....85Example on how to connect a neutral point VT to the IED.....86

Section 5 Local human-machine interface..................................... 89Local HMI......................................................................................... 89

Display.........................................................................................89LEDs............................................................................................91Keypad........................................................................................ 91Local HMI functionality................................................................ 92

Protection and alarm indication.............................................. 92Parameter management ........................................................94Front communication..............................................................94

Section 6 Differential protection..................................................... 97Transformer differential protection T2WPDIF and T3WPDIF .......... 97

Identification................................................................................ 97Application...................................................................................97Setting guidelines........................................................................ 98

Inrush restraint methods.........................................................98Overexcitation restraint method............................................. 98Cross-blocking between phases............................................ 99Restrained and unrestrained differential protection................99Elimination of zero sequence currents................................. 100Internal/External fault discriminator...................................... 101Differential current alarm...................................................... 103Switch onto fault feature.......................................................103

Setting example.........................................................................103CT Connections....................................................................103

Restricted earth-fault protection, low impedance REFPDIF .......... 105Identification.............................................................................. 105Application.................................................................................105

Application examples........................................................... 106Setting guidelines...................................................................... 109

Setting and configuration......................................................109Settings................................................................................ 110

1Ph High impedance differential protection HZPDIF .....................110Identification.............................................................................. 110Application.................................................................................111

The basics of the high impedance principle......................... 111Connection examples for high impedance differentialprotection...................................................................................117

Table of contents

3Application manual

Page 10: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Connections for 1Ph restricted earth fault and highimpedance differential protection......................................... 117

Setting guidelines...................................................................... 118Configuration........................................................................ 118Settings of protection function.............................................. 119Restricted earth fault protection REFPDIF........................... 119Alarm level operation............................................................121

Section 7 Impedance protection...................................................123Power swing detection ZMRPSB ...................................................123

Identification.............................................................................. 123Application.................................................................................123

General.................................................................................123Basic characteristics.............................................................124

Setting guidelines...................................................................... 124Underimpedance protection for generators and transformersZGCPDIS .......................................................................................132

Identification.............................................................................. 132Application.................................................................................132Setting guidelines...................................................................... 132

Load enchroachment LEPDIS........................................................ 134Identification.............................................................................. 134Application.................................................................................134Setting guidelines...................................................................... 134

Resistive reach with load encroachment characteristic........134

Section 8 Current protection.........................................................137Instantaneous phase overcurrent protection 3-phase outputPHPIOC .........................................................................................137

Identification.............................................................................. 137Application.................................................................................137Setting guidelines...................................................................... 138

Meshed network without parallel line................................... 138Meshed network with parallel line........................................ 140

Four step phase overcurrent protection 3-phase outputOC4PTOC ..................................................................................... 142

Identification.............................................................................. 142Application.................................................................................142Setting guidelines...................................................................... 143

Settings for steps 1 to 4 .......................................................1442nd harmonic restrain...........................................................146

Instantaneous residual overcurrent protection EFPIOC ................ 151Identification.............................................................................. 151Application.................................................................................151

Table of contents

4Application manual

Page 11: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Setting guidelines...................................................................... 151Four step residual overcurrent protection, zero, negativesequence direction EF4PTOC .......................................................153

Identification.............................................................................. 154Application.................................................................................154Setting guidelines...................................................................... 156

Settings for steps 1 and 4 ....................................................156Common settings for all steps.............................................. 1582nd harmonic restrain...........................................................159Transformer application example......................................... 160

Thermal overload protection, two time constants TRPTTR ...........163Identification.............................................................................. 163Application.................................................................................163Setting guideline........................................................................164

Breaker failure protection 3-phase activation and output CCRBRF 166Identification.............................................................................. 167Application.................................................................................167Setting guidelines...................................................................... 167

Pole discordance protection CCRPLD .......................................... 170Identification.............................................................................. 170Application.................................................................................170Setting guidelines...................................................................... 171

Directional over-/under-power protection GOPPDOP/GUPPDUP. 171Application.................................................................................172Directional overpower protection GOPPDOP ...........................174

Identification......................................................................... 174Setting guidelines................................................................. 174

Directional underpower protection GUPPDUP..........................177Identification......................................................................... 177Setting guidelines................................................................. 177

Negative sequence based overcurrent function DNSPTOC ..........181Identification.............................................................................. 181Application.................................................................................181Setting guidelines...................................................................... 181

Section 9 Voltage protection........................................................ 183Two step undervoltage protection UV2PTUV ................................183

Identification.............................................................................. 183Application.................................................................................183Setting guidelines...................................................................... 184

Equipment protection, such as for motors and generators...184Disconnected equipment detection...................................... 184Power supply quality ........................................................... 184Voltage instability mitigation................................................. 184

Table of contents

5Application manual

Page 12: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Backup protection for power system faults...........................184Settings for Two step undervoltage protection..................... 185

Two step overvoltage protection OV2PTOV ..................................186Identification.............................................................................. 186Application.................................................................................186Setting guidelines...................................................................... 187

Two step residual overvoltage protection ROV2PTOV ................. 189Identification.............................................................................. 189Application.................................................................................189Setting guidelines...................................................................... 190

Equipment protection, such as for motors, generators,reactors and transformers.................................................... 190Power supply quality............................................................ 190High impedance earthed systems........................................ 190Direct earthed system.......................................................... 191Settings for Two step residual overvoltage protection..........192

Overexcitation protection OEXPVPH ............................................ 193Identification.............................................................................. 193Application.................................................................................194Setting guidelines...................................................................... 195

Recommendations for input and output signals................... 195Settings................................................................................ 195

Section 10 Frequency protection....................................................197Underfrequency protection SAPTUF ............................................. 197

Identification.............................................................................. 197Application.................................................................................197Setting guidelines...................................................................... 197

Overfrequency protection SAPTOF ...............................................198Identification.............................................................................. 198Application.................................................................................198Setting guidelines...................................................................... 199

Rate-of-change frequency protection SAPFRC .............................199Identification.............................................................................. 200Application.................................................................................200Setting guidelines...................................................................... 200

Section 11 Secondary system supervision.....................................203Fuse failure supervision SDDRFUF............................................... 203

Identification.............................................................................. 203Application.................................................................................203Setting guidelines...................................................................... 204

General.................................................................................204Setting of common parameters............................................ 204

Table of contents

6Application manual

Page 13: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Negative sequence based....................................................205Zero sequence based...........................................................206Delta U and delta I ...............................................................206Dead line detection...............................................................207

Breaker close/trip circuit monitoring TCSSCBR............................. 207Identification.............................................................................. 207Application.................................................................................207

Section 12 Control..........................................................................213Apparatus control .......................................................................... 213

Identification.............................................................................. 213Application.................................................................................213Interaction between modules.....................................................220Setting guidelines...................................................................... 222

Switch controller (SCSWI)....................................................223Bay control (QCBAY)........................................................... 223

Interlocking..................................................................................... 224Identification.............................................................................. 224Application.................................................................................224Configuration guidelines............................................................225Interlocking for busbar earthing switch BB_ES .........................225

Application............................................................................226Signals in single breaker arrangement.................................226Signals in double-breaker arrangement............................... 230Signals in 1 1/2 breaker arrangement.................................. 231

Interlocking for bus-section breaker A1A2_BS..........................231Application............................................................................231Signals from all feeders........................................................232Configuration setting............................................................ 235

Interlocking for bus-section disconnector A1A2_DC ................ 236Application............................................................................236Signals in single breaker arrangement.................................236Signals in double-breaker arrangement............................... 239Signals in 1 1/2 breaker arrangement.................................. 242

Interlocking for bus-coupler bay ABC_BC ................................ 243Application............................................................................243Configuration........................................................................ 244Signals from all feeders........................................................244Signals from bus-coupler......................................................246Configuration setting............................................................ 248

Interlocking for 1 1/2 CB BH .....................................................249Application............................................................................249Configuration setting............................................................ 250

Interlocking for double CB bay DB ........................................... 251

Table of contents

7Application manual

Page 14: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Application............................................................................251Configuration setting............................................................ 252

Interlocking for line bay ABC_LINE .......................................... 252Application............................................................................252Signals from bypass busbar................................................. 253Signals from bus-coupler......................................................254Configuration setting............................................................ 257

Interlocking for transformer bay AB_TRAFO ............................ 258Application............................................................................258Signals from bus-coupler......................................................258Configuration setting............................................................ 259

Voltage control ...............................................................................260Identification.............................................................................. 260Application.................................................................................260Setting guidelines...................................................................... 287

TR8ATCC general settings.................................................. 287TR8ATCC Setting group ..................................................... 288TCMYLTC general settings.................................................. 293

Logic rotating switch for function selection and LHMIpresentation SLGGIO..................................................................... 294

Identification.............................................................................. 294Application.................................................................................295Setting guidelines...................................................................... 295

Selector mini switch VSGGIO.........................................................296Identification.............................................................................. 296Application.................................................................................296Setting guidelines...................................................................... 296

IEC61850 generic communication I/O functions DPGGIO............. 297Identification.............................................................................. 297Application.................................................................................297Setting guidelines...................................................................... 297

Single point generic control 8 signals SPC8GGIO......................... 297Identification.............................................................................. 297Application.................................................................................297Setting guidelines...................................................................... 298

Automation bits AUTOBITS............................................................298Identification.............................................................................. 298Application.................................................................................298Setting guidelines...................................................................... 299

Section 13 Logic.............................................................................301Tripping logic common 3-phase output SMPPTRC .......................301

Identification.............................................................................. 301Application.................................................................................301

Table of contents

8Application manual

Page 15: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Three-phase tripping ........................................................... 301Lock-out................................................................................302Blocking of the function block...............................................302

Setting guidelines...................................................................... 302Trip matrix logic TMAGGIO............................................................ 303

Identification.............................................................................. 303Application.................................................................................303Setting guidelines...................................................................... 303

Configurable logic blocks................................................................304Identification.............................................................................. 304Application.................................................................................305

Configuration........................................................................ 305Fixed signals FXDSIGN..................................................................306

Identification.............................................................................. 306Application.................................................................................306

Boolean 16 to integer conversion B16I...........................................307Identification.............................................................................. 307Application.................................................................................308Setting guidelines...................................................................... 308

Boolean 16 to integer conversion with logic node representationB16IFCVI........................................................................................ 308

Identification.............................................................................. 308Application.................................................................................308Setting guidelines...................................................................... 308

Integer to boolean 16 conversion IB16A........................................ 308Identification.............................................................................. 308Application.................................................................................309Setting guidelines...................................................................... 309

Integer to boolean 16 conversion with logic node representationIB16FCVB.......................................................................................309

Identification.............................................................................. 309Application.................................................................................309Settings......................................................................................309

Elapsed time integrator with limit transgression and overflowsupervision TEIGGIO..................................................................... 310

Identification.............................................................................. 310Application.................................................................................310Setting guidelines...................................................................... 310

Section 14 Monitoring.....................................................................311IEC61850 generic communication I/O functions SPGGIO............. 311

Identification.............................................................................. 311Application.................................................................................311Setting guidelines...................................................................... 311

Table of contents

9Application manual

Page 16: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC61850 generic communication I/O functions 16 inputsSP16GGIO..................................................................................... 311

Identification.............................................................................. 311Application.................................................................................311Setting guidelines...................................................................... 312

IEC61850 generic communication I/O functions MVGGIO.............312Identification.............................................................................. 312Application.................................................................................312Setting guidelines...................................................................... 312

Measurements................................................................................313Identification.............................................................................. 313Application.................................................................................313Setting guidelines...................................................................... 315Setting examples.......................................................................318

Measurement function application for a 110kV OHL............318Measurement function application for a power transformer. 320

Event counter CNTGGIO................................................................322Identification.............................................................................. 322Application.................................................................................322Setting guidelines...................................................................... 322

Limit counter L4UFCNT..................................................................322Function description.................................................................. 323Application.................................................................................323

Setting guidelines................................................................. 323Disturbance report ......................................................................... 323

Identification.............................................................................. 323Application.................................................................................324Setting guidelines...................................................................... 325

Binary input signals.............................................................. 327Analog input signals............................................................. 328Sub-function parameters...................................................... 328Consideration....................................................................... 329

Measured value expander block MVEXP....................................... 330Identification.............................................................................. 330Application.................................................................................330Setting guidelines...................................................................... 330

Station battery supervision SPVNZBAT......................................... 330Identification.............................................................................. 330Application.................................................................................330

Insulation gas monitoring function SSIMG..................................... 331Identification.............................................................................. 331Application.................................................................................331

Insulation liquid monitoring function SSIML....................................331

Table of contents

10Application manual

Page 17: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Identification.............................................................................. 331Application.................................................................................332

Circuit breaker condition monitoring SSCBR..................................332Identification.............................................................................. 332Application.................................................................................332

Section 15 Metering....................................................................... 337Pulse counter PCGGIO.................................................................. 337

Identification.............................................................................. 337Application.................................................................................337Setting guidelines...................................................................... 337

Energy calculation and demand handling EPTMMTR....................338Identification.............................................................................. 338Application.................................................................................338Setting guidelines...................................................................... 339

Section 16 Station communication.................................................341IEC61850-8-1 communication protocol ......................................... 341

Identification.............................................................................. 341Application.................................................................................341

Horizontal communication via GOOSE................................ 343Setting guidelines...................................................................... 346

DNP3 protocol................................................................................ 346IEC 60870-5-103 communication protocol..................................... 346IEC 61850-8-1 redundant station bus communication................... 347Application...................................................................................... 347Setting guidelines........................................................................... 348

Section 17 Basic IED functions...................................................... 351Self supervision with internal event list ..........................................351

Identification.............................................................................. 351Application.................................................................................351

Time synchronization......................................................................352Identification.............................................................................. 352Application.................................................................................352Setting guidelines...................................................................... 353

Parameter setting group handling.................................................. 355Identification.............................................................................. 355Application.................................................................................355Setting guidelines...................................................................... 356

Test mode functionality TESTMODE..............................................356Identification.............................................................................. 356Application.................................................................................356Setting guidelines...................................................................... 356

Table of contents

11Application manual

Page 18: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Change lock CHNGLCK................................................................. 357Identification.............................................................................. 357Application.................................................................................357Setting guidelines...................................................................... 358

IED identifiers TERMINALID.......................................................... 358Identification.............................................................................. 358Application.................................................................................358

Customer specific settings................................................... 358Product information PRODINF....................................................... 358

Identification.............................................................................. 358Application.................................................................................359

Factory defined settings....................................................... 359Primary system values PRIMVAL...................................................360

Identification.............................................................................. 360Application.................................................................................360

Signal matrix for analog inputs SMAI............................................. 360Identification.............................................................................. 360Application.................................................................................360Setting guidelines...................................................................... 361

Summation block 3 phase 3PHSUM.............................................. 363Identification.............................................................................. 363Application.................................................................................364Setting guidelines...................................................................... 364

Global base values GBASVAL....................................................... 364Identification.............................................................................. 364Application.................................................................................364Setting guidelines...................................................................... 365

Authority check ATHCHCK.............................................................365Identification.............................................................................. 365Application.................................................................................365

Authorization handling in the IED......................................... 366Authority status ATHSTAT............................................................. 367

Identification.............................................................................. 367Application.................................................................................367

Denial of service............................................................................. 368Identification.............................................................................. 368Application.................................................................................368Setting guidelines...................................................................... 368

Section 18 Requirements...............................................................369Current transformer requirements.................................................. 369

Current transformer classification..............................................369Conditions..................................................................................370Fault current.............................................................................. 370

Table of contents

12Application manual

Page 19: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Secondary wire resistance and additional load......................... 371General current transformer requirements................................ 371Rated equivalent secondary e.m.f. requirements......................372

Transformer differential protection....................................... 3721 Ph high impedance differential protection......................... 373Breaker failure protection..................................................... 374Non-directional instantaneous and definitive time, phaseand residual overcurrent protection......................................374Non-directional inverse time delayed phase and residualovercurrent protection.......................................................... 375Directional phase and residual overcurrent protection......... 376

Current transformer requirements for CTs according to otherstandards...................................................................................376

Current transformers according to IEC 61869-2, class P, PR376Current transformers according to IEC 61869-2, class PX,PXR (and old IEC 60044-6, class TPSand old British Standard, class X)........................................ 377Current transformers according to ANSI/IEEE..................... 377

Voltage transformer requirements.................................................. 378SNTP server requirements............................................................. 378

SNTP server requirements........................................................378

Section 19 Glossary....................................................................... 379

Table of contents

13Application manual

Page 20: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14

Page 21: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1 Introduction

1.1 This manual

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provides assistance forcalculating settings.

1.2 Intended audience

This manual addresses the protection and control engineer responsible for planning,pre-engineering and engineering.

The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as protection schemesand communication principles.

1MRK 504 134-UEN A Section 1Introduction

15Application manual

Page 22: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1.3 Product documentation

1.3.1 Product documentation set

IEC07000220-3-en.vsd

Pla

nnin

g &

pur

chas

e

Eng

inee

ring

Inst

allin

g

Com

mis

sion

ing

Ope

ratio

n

Mai

nten

ance

Dec

omm

issi

onin

gD

eins

talli

ng &

dis

posa

l

Application manual

Operation manual

Installation manual

Engineering manual

Communication protocol manual

Technical manual

Commissioning manual

IEC07000220 V3 EN

Figure 1: The intended use of manuals throughout the product lifecycle

The engineering manual contains instructions on how to engineer the IEDs using thevarious tools available within the PCM600 software. The manual providesinstructions on how to set up a PCM600 project and insert IEDs to the projectstructure. The manual also recommends a sequence for the engineering of protectionand control functions, LHMI functions as well as communication engineering for IEC60870-5-103, IEC 61850 and DNP 3.0.

The installation manual contains instructions on how to install the IED. The manualprovides procedures for mechanical and electrical installation. The chapters areorganized in the chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. Themanual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for the checkingof external circuitry and energizing the IED, parameter setting and configuration aswell as verifying settings by secondary injection. The manual describes the process oftesting an IED in a substation which is not in service. The chapters are organized in the

Section 1 1MRK 504 134-UEN AIntroduction

16Application manual

Page 23: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

chronological order in which the IED should be commissioned. The relevantprocedures may be followed also during the service and maintenance activities.

The operation manual contains instructions on how to operate the IED once it has beencommissioned. The manual provides instructions for the monitoring, controlling andsetting of the IED. The manual also describes how to identify disturbances and how toview calculated and measured power grid data to determine the cause of a fault.

The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purpose atypical protection function can be used. The manual can also provides assistance forcalculating settings.

The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data, sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.

The communication protocol manual describes the communication protocolssupported by the IED. The manual concentrates on the vendor-specificimplementations.

The point list manual describes the outlook and properties of the data points specificto the IED. The manual should be used in conjunction with the correspondingcommunication protocol manual.

1.3.2 Document revision historyDocument revision/date History-/March 2013 First release

A/October 2016 Minor corrections made

1.3.3 Related documentsDocuments related to RET650 Identity numberApplication manual 1MRK 504 134-UEN

Technical manual 1MRK 504 135-UEN

Commissioning manual 1MRK 504 136-UEN

Product Guide, configured 1MRK 504 137-BEN

Type test certificate 1MRK 504 137-TEN

Application notes for Circuit Breaker Control 1MRG006806

650 series manuals Identity numberCommunication protocol manual, DNP 3.0 1MRK 511 280-UEN

Communication protocol manual, IEC 61850–8–1 1MRK 511 281-UEN

Communication protocol manual, IEC 60870-5-103 1MRK 511 282-UEN

Table continues on next page

1MRK 504 134-UEN A Section 1Introduction

17Application manual

Page 24: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

650 series manuals Identity numberCyber Security deployment guidelines 1MRK 511 285-UEN

Point list manual, DNP 3.0 1MRK 511 283-UEN

Engineering manual 1MRK 511 284-UEN

Operation manual 1MRK 500 096-UEN

Installation manual 1MRK 514 016-UEN

Accessories, 650 series 1MRK 513 023-BEN

MICS 1MRG 010 656

PICS 1MRG 010 660

PIXIT 1MRG 010 658

1.4 Symbols and conventions

1.4.1 Symbols

The electrical warning icon indicates the presence of a hazard whichcould result in electrical shock.

The warning icon indicates the presence of a hazard which couldresult in personal injury.

The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presence ofa hazard which could result in corruption of software or damage toequipment or property.

The information icon alerts the reader of important facts andconditions.

The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understandthat under certain operational conditions, operation of damaged equipment may resultin degraded process performance leading to personal injury or death. It is importantthat the user fully complies with all warning and cautionary notices.

Section 1 1MRK 504 134-UEN AIntroduction

18Application manual

Page 25: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1.4.2 Document conventions

• Abbreviations and acronyms in this manual are spelled out in the glossary. Theglossary also contains definitions of important terms.

• Push button navigation in the LHMI menu structure is presented by using thepush button icons.For example, to navigate between the options, use and .

• HMI menu paths are presented in bold.For example, select Main menu/Settings.

• LHMI messages are shown in Courier font.For example, to save the changes in non-volatile memory, select Yes and press

.• Parameter names are shown in italics.

For example, the function can be enabled and disabled with the Operation setting.• Each function block symbol shows the available input/output signal.

• the character ^ in front of an input/output signal name indicates that thesignal name may be customized using the PCM600 software.

• the character * after an input/output signal name indicates that the signalmust be connected to another function block in the applicationconfiguration to achieve a valid application configuration.

1MRK 504 134-UEN A Section 1Introduction

19Application manual

Page 26: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

20

Page 27: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 2 Application

2.1 RET650 application

RET650 provides fast and selective protection, monitoring and control for two- andthree-winding transformers, autotransformers, generator-transformer units and shuntreactors. The IED is designed to operate correctly over a wide frequency range inorder to accommodate power system frequency variations during disturbances andgenerator start-up and shut-down. Apparatus control for up to 8 apparatuses withinterlocking can be included in one IED by function block engineering.

A very fast differential protection function with built-in transformer ratio matchingand vector group compensation makes this IED the ideal solution even for the mostdemanding applications. Since RET650 has very low requirements on the main CTs,no interposing CTs are required. The differential protection function is provided with2nd harmonic and wave-block restraint features to avoid tripping for magnetizinginrush current, and 5th harmonic restraint to avoid tripping for overexcitation.

The differential function offers a high sensitivity for low-level internal faults. Theunique and innovative sensitive differential protection feature of the RET650provides the best possible coverage for winding internal turn-to-turn faults, based onthe theory of symmetrical components .

A low impedance restricted earth-fault protection function is available as acomplimentary sensitive and fast main protection against winding earth faults. Thisfunction includes a directional zero-sequence current criterion for additional security.

Tripping from pressure relief/Buchholz and temperature devices can be implementedthrough the IED's binary inputs, where trip signal conditioning can be performed(pulsing, lockout, additional logics, etc). The binary inputs are thoroughly stabilizedagainst disturbances in order to prevent incorrect operations due to for example DCsystem capacitive discharges or DC earth faults.

Versatile phase, earth, negative and zero sequence overcurrent functions withdirectional capability provide further alternative backup protections. Thermaloverload with two time-constants, overexcitation (volts per hertz) and over/undervoltage protection functions are also available.

A built-in disturbance and event recorder provides valuable data to the user aboutstatus and operation for post-fault disturbance analysis.

Breaker failure protection allows high speed back-up tripping of surroundingbreakers.

1MRK 504 134-UEN A Section 2Application

21Application manual

Page 28: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Three packages have been defined for the following applications:

• Two-winding transformer in single breaker arrangements (A01)• Three-winding transformer in single breaker arrangements (A05)• One or two transformer tap changer control (A07)

The packages are preconfigured and ready for direct use. Analog and tripping IO hasbeen pre-defined for basic use. Other signals need to be applied as required for eachapplication.

The graphical configuration tool ensures simple and fast testing and commissioning.

Section 2 1MRK 504 134-UEN AApplication

22Application manual

Page 29: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

T2W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

50/51 3I>

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

YY

P

ROV2 PTOV

59N 3U0>

RET650 A01 - 2 Winding Transformer protection 10AI (8I+2U)

20 MVA110±11*1.5% / 21 kV

105 / 550 AYNd5

20 kV Bus

110 kV Bus

200/1

600/120kV/100V

200/1

600/1

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

W1

W2

IEC09000645-4-en.vsd

IEC09000645 V4 EN

Figure 2: A typical protection application for a two-winding transformer insingle breaker arrangement

1MRK 504 134-UEN A Section 2Application

23Application manual

Page 30: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U)

W1

T3W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

51/67 3I>

CC RPLD

52PD PD

CC RBRF

50BF 3I> BF

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

TR PTTR

49 Ith

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

REF PDIF

87N IdN/I

OEX PVPH

24 U/f>

OC4 PTOC

51/67 3I>

EF4 PTOC

51N/67N IN>

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

CV MMXN

Meter.

YY

@

ROV2 PTOV

59N 3UO>

35 kV Bus

110 kV Bus

10 kV Bus

IEC61850

ANSI IEC

Function Onin Settings

IEC61850

ANSI IEC

Function Off in Settings

Transformer Data:40/40/15 MVA

110±11*1.5% / 36.75 / 10.5 kV210/628/825 A

YNyn0d5

110kV/100V

300/1

1000/1

800/1

800/1

300/1

10kV/100V

35kV/100V

1000/1W3 W2

IEC09000646-3-en.vsd

IEC09000646 V3 EN

Figure 3: A typical protection application for a three-winding transformer insingle breaker arrangement

Section 2 1MRK 504 134-UEN AApplication

24Application manual

Page 31: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

RET650 A07 – OLTC Control for 1 or 2 Transformers 10AI (6I+4U)

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.

T1

OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV PTOV

59N 3U0>

T2TRx ATCC

90 UUV2 PTOV

27 U<

OV2 PTOV

59 U>

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV2 PTOV

59N 3Uo>TR8 ATCC

90 U

UV2 PTUV

27 U<

OV2 PTOV

59 U>

T1

T2

YY

Ø

YY

Ø

TCM YLTC

84

TCM YLTC

84

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

DRP RDRE

Mont.

T1 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

T2 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

20 kV Bus #1 20 kV Bus #2

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

600/1

20kV/100V

600/1

20kV/100V

W2

W2

IEC09000647-4-en.vsd

IEC09000647 V4 EN

Figure 4: A typical tap changer control application for one or two transformers

1MRK 504 134-UEN A Section 2Application

25Application manual

Page 32: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2.2 Available functions

2.2.1 Main protection functionsIEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Differential protection

T2WPDIF 87T Transformer differential protection, two winding 0–1 1

T3WPDIF 87T Transformer differential protection, three winding 0–1 1

REFPDIF 87N Restricted earth fault protection, low impedance 0–3 2 3

HZPDIF 87 1Ph High impedance differential protection 0–2 2 2

Impedance protection

ZMRPSB 68 Power swing detection 0–1

ZGCPDIS 21G Underimpedance protection for generators andtransformers

0–1

LEPDIS Load encroachment 0–1

2.2.2 Back-up protection functionsIEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Current protection

PHPIOC 50 Instantaneous phase overcurrent protection, 3–phase output

0–3 2 3

OC4PTOC 51/67 Four step phase overcurrent protection, 3-phaseoutput

0–3 2 3 2

EFPIOC 50N Instantaneous residual overcurrent protection 0–3 2 3

EF4PTOC 51N/67N Four step residual overcurrent protection, zero/negative sequence direction

0–3 2 3 2

TRPTTR 49 Thermal overload protection, two time constants 0–3 2 3 2

CCRBRF 50BF Breaker failure protection, 3–phase activation andoutput

0–3 2 3

CCRPLD 52PD Pole discordance protection 0–3 2 3

GUPPDUP 37 Directional underpower protection 0–2 1 1 2

GOPPDOP 32 Directional overpower protection 0–2 1 1 2

DNSPTOC 46 Negative sequence based overcurrent function 0–2 1 2

Table continues on next page

Section 2 1MRK 504 134-UEN AApplication

26Application manual

Page 33: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850 orFunction name

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Voltage protection

UV2PTUV 27 Two step undervoltage protection 0–2 1 1 2

OV2PTOV 59 Two step overvoltage protection 0–2 1 1 2

ROV2PTOV 59N Two step residual overvoltage protection 0–2 1 1 2

OEXPVPH 24 Overexcitation protection 0–1 1 1

Frequency protection

SAPTUF 81 Underfrequency function 0–4 4 4 4

SAPTOF 81 Overfrequency function 0–4 4 4 4

SAPFRC 81 Rate-of-change frequency protection 0–4 2 2 4

2.2.3 Control and monitoring functionsIEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Control

TR8ATCC 90 Automatic voltage control for tap changer,parallel control

0–2 1 1 2

TCMYLTC 84 Tap changer control and supervision, 6 binaryinputs

0–2 1 1 2

SLGGIO Logic Rotating Switch for function selectionand LHMI presentation

15 15 15 15

VSGGIO Selector mini switch 20 20 20 20

DPGGIO IEC 61850 generic communication I/Ofunctions double point

16 16 16 16

SPC8GGIO Single point generic control 8 signals 5 5 5 5

AUTOBITS AutomationBits, command function forDNP3.0

3 3 3 3

I103CMD Function commands for IEC60870-5-103 1 1 1 1

I103IEDCMD IED commands for IEC60870-5-103 1 1 1 1

I103USRCMD Function commands user defined forIEC60870-5-103

4 4 4 4

I103GENCMD Function commands generic forIEC60870-5-103

50 50 50 50

I103POSCMD IED commands with position and select forIEC60870-5-103

50 50 50 50

Table continues on next page

1MRK 504 134-UEN A Section 2Application

27Application manual

Page 34: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Apparatus control and Interlocking

APC8 Apparatus control for single bay, max 8 app.(1CB) incl. interlocking

0–1

SCILO 3 Logical node for interlocking

BB_ES 3 Interlocking for busbar earthing switch

A1A2_BS 3 Interlocking for bus-section breaker

A1A2_DC 3 Interlocking for bus-section disconnector

ABC_BC 3 Interlocking for bus-coupler bay

BH_CONN 3 Interlocking for 1 1/2 breaker diameter

BH_LINE_A 3 Interlocking for 1 1/2 breaker diameter

BH_LINE_B 3 Interlocking for 1 1/2 breaker diameter

DB_BUS_A 3 Interlocking for double CB bay

DB_BUS_B 3 Interlocking for double CB bay

DB_LINE 3 Interlocking for double CB bay

ABC_LINE 3 Interlocking for line bay

AB_TRAFO 3 Interlocking for transformer bay

SCSWI Switch controller

QCBAY Bay control 1 1 1 1

LOCREM Handling of LR-switch positions 1 1 1 1

LOCREMCTRL LHMI control of Permitted Source To Operate(PSTO)

1 1 1 1

CBC2 Circuit breaker control for 2CB 0–1 1

CBC3 Circuit breaker control for 3CB 0–1 1

CBC4 Circuit breaker control for 4CB 0–1 1

Secondary system supervision

SDDRFUF Fuse failure supervision 0–1

TCSSCBR Breaker close/trip circuit monitoring 3 3 3 3

Logic

SMPPTRC 94 Tripping logic, common 3–phase output 1–3 2 3 2

TMAGGIO Trip matrix logic 12 12 12 12

OR Configurable logic blocks 283 283 283 283

INVERTER Configurable logic blocks 140 140 140 140

PULSETIMER Configurable logic blocks 40 40 40 40

GATE Configurable logic blocks 40 40 40 40

XOR Configurable logic blocks 40 40 40 40

LOOPDELAY Configurable logic blocks 40 40 40 40

Table continues on next page

Section 2 1MRK 504 134-UEN AApplication

28Application manual

Page 35: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

TIMERSET Configurable logic blocks 40 40 40 40

AND Configurable logic blocks 280 280 280 280

SRMEMORY Configurable logic blocks 40 40 40 40

RSMEMORY Configurable logic blocks 40 40 40 40

Q/T Configurable logic blocks Q/T 0–1

ANDQT Configurable logic blocks Q/T 0–120

ORQT Configurable logic blocks Q/T 0–120

INVERTERQT Configurable logic blocks Q/T 0–120

XORQT Configurable logic blocks Q/T 0–40

SRMEMORYQT Configurable logic blocks Q/T 0–40

RSMEMORYQT Configurable logic blocks Q/T 0–40

TIMERSETQT Configurable logic blocks Q/T 0–40

PULSETIMERQT Configurable logic blocks Q/T 0–40

INVALIDQT Configurable logic blocks Q/T 0–12

INDCOMBSPQT Configurable logic blocks Q/T 0–20

INDEXTSPQT Configurable logic blocks Q/T 0–20

FXDSIGN Fixed signal function block 1 1 1 1

B16I Boolean 16 to Integer conversion 16 16 16 16

B16IFCVI Boolean 16 to Integer conversion with logicnode representation

16 16 16 16

IB16A Integer to Boolean 16 conversion 16 16 16 16

IB16FCVB Integer to Boolean 16 conversion with logicnode representation

16 16 16 16

TEIGGIO Elapsed time integrator with limittransgression and overflow supervision

12 12 12 12

Monitoring

CVMMXN Measurements 6 6 6 6

CMMXU Phase current measurement 10 10 10 10

VMMXU Phase-phase voltage measurement 6 6 6 6

CMSQI Current sequence component measurement 6 6 6 6

VMSQI Voltage sequence measurement 6 6 6 6

VNMMXU Phase-neutral voltage measurement 6 6 6 6

AISVBAS Function block for service values presentationof the analog inputs

1 1 1 1

TM_P_P2 Function block for service values presentationof primary analog inputs 600TRM

1 1 1 1

AM_P_P4 Function block for service values presentationof primary analog inputs 600AIM

1 1 1 1

Table continues on next page

1MRK 504 134-UEN A Section 2Application

29Application manual

Page 36: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

TM_S_P2 Function block for service values presentationof secondary analog inputs 600TRM

1 1 1 1

AM_S_P4 Function block for service values presentationof secondary analog inputs 600AIM

1 1 1 1

CNTGGIO Event counter 5 5 5 5

L4UFCNT Event counter with limit supervision 12 12 12 12

DRPRDRE Disturbance report 1 1 1 1

AnRADR Analog input signals 4 4 4 4

BnRBDR Binary input signals 6 6 6 6

SPGGIO IEC 61850 generic communication I/Ofunctions

64 64 64 64

SP16GGIO IEC 61850 generic communication I/Ofunctions 16 inputs

16 16 16 16

MVGGIO IEC 61850 generic communication I/Ofunctions

16 16 16 16

MVEXP Measured value expander block 66 66 66 66

SPVNZBAT Station battery supervision 0–1 1 1 1

SSIMG 63 Insulation gas monitoring function 0–2 2 2 2

SSIML 71 Insulation liquid monitoring function 0–2 2 2 2

SSCBR Circuit breaker condition monitoring 0–3 2 3 2

I103MEAS Measurands for IEC60870-5-103 1 1 1 1

I103MEASUSR Measurands user defined signals forIEC60870-5-103

3 3 3 3

I103AR Function status auto-recloser forIEC60870-5-103

1 1 1 1

I103EF Function status earth-fault forIEC60870-5-103

1 1 1 1

I103FLTPROT Function status fault protection forIEC60870-5-103

1 1 1 1

I103IED IED status for IEC60870-5-103 1 1 1 1

I103SUPERV Supervison status for IEC60870-5-103 1 1 1 1

I103USRDEF Status for user defined signals forIEC60870-5-103

20 20 20 20

Metering

PCGGIO Pulse counter 16 16 16 16

ETPMMTR Function for energy calculation and demandhandling

3 3 3 3

Section 2 1MRK 504 134-UEN AApplication

30Application manual

Page 37: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2.2.4 Station communicationIEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

Station communication

IEC61850-8-1 IEC 61850 communication protocol 1 1 1 1

DNPGEN DNP3.0 communication general protocol 1 1 1 1

RS485DNP DNP3.0 for RS-485 communicationprotocol

1 1 1 1

CH1TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH2TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH3TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

CH4TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

OPTICALDNP DNP3.0 for optical RS-232 communicationprotocol

1 1 1 1

MSTSERIAL DNP3.0 for serial communication protocol 1 1 1 1

MST1TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST2TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST3TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

MST4TCP DNP3.0 for TCP/IP communicationprotocol

1 1 1 1

RS485GEN RS485 1 1 1 1

OPTICALPROT Operation selection for optical serial 1 1 1 1

RS485PROT Operation selection for RS485 1 1 1 1

DNPFREC DNP3.0 fault records for TCP/IPcommunication protocol

1 1 1 1

OPTICAL103 IEC60870-5-103 Optical serialcommunication

1 1 1 1

RS485103 IEC60870-5-103 serial communication forRS485

1 1 1 1

GOOSEINTLKRCV Horizontal communication via GOOSE forinterlocking

59 59 59 59

GOOSEBINRCV GOOSE binary receive 4 4 4 4

GOOSEVCTRCONF GOOSE VCTR configuration for send andreceive

1 1 1 1

VCTRSEND Voltage control sending block for GOOSE 1 1 1 1

Table continues on next page

1MRK 504 134-UEN A Section 2Application

31Application manual

Page 38: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850 or Functionname

ANSI Function description Transformer

RET

650

RET

650

(A01

)2W

/1C

B

RET

650

(A05

)3W

/1C

B

RET

650

(A07

)O

LTC

GOOSEVCTRRCV Voltage control receiving block for GOOSE 3 3 3 3

ETHFRNTETHLAN1GATEWAY

Ethernet configuration of front port, LAN1port and gateway

1 1 1 1

ETHLAN1_AB Ethernet configuration of LAN1 port 1

PRPSTATUS System component for parallellredundancy protocol

1

CONFPROT IED Configuration Protocol 1 1 1 1

ACTIVLOG Activity logging parameters 1 1 1 1

SECALARM Component for mapping security events onprotocols such as DNP3 and IEC103

1 1 1 1

AGSAL Generic security application component 1 1 1 1

GOOSEDPRCV GOOSE function block to receive a doublepoint value

32 32 32 32

GOOSEINTRCV GOOSE function block to receive aninteger value

32 32 32 32

GOOSEMVRCV GOOSE function block to receive ameasurand value

16 16 16 16

GOOSESPRCV GOOSE function block to receive a singlepoint value

64 64 64 64

2.2.5 Basic IED functionsIEC 61850/Functionblock name

Function description

Basic functions included in all products

INTERRSIG Self supervision with internal event list 1

SELFSUPEVLST Self supervision with internal event list 1

TIMESYNCHGEN Time synchronization 1

SNTP Time synchronization 1

DTSBEGIN, DTSEND,TIMEZONE

Time synchronization, daylight saving 1

IRIG-B Time synchronization 1

SETGRPS Setting group handling 1

ACTVGRP Parameter setting groups 1

TESTMODE Test mode functionality 1

CHNGLCK Change lock function 1

PRIMVAL Primary system values 1

Table continues on next page

Section 2 1MRK 504 134-UEN AApplication

32Application manual

Page 39: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC 61850/Functionblock name

Function description

SMAI_20_1 -SMAI_20_12

Signal matrix for analog inputs 2

3PHSUM Summation block 3 phase 12

GBASVAL Global base values for settings 6

ATHSTAT Authority status 1

ATHCHCK Authority check 1

AUTHMAN Authority management 1

FTPACCS FTPS access with password 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSLAN1 Denial of service, frame rate control for LAN1A and LAN1B ports 1

DOSSCKT Denial of service, socket flow control 1

2.3 RET650 application examples

2.3.1 Adaptation to different applications

The IED can be used in a wide range of applications. This is done by selecting fromthe comprehensive function library in the IED. A selection of common applicationsare described below.

• Application 1: Two-winding HV/MV, Y/Δ-transformer; HV:solidly earthed,MV:high impedance earthed

• Application 2: Two-winding HV/MV, Y/Y-transformer; HV:solidly earthed,MV:high impedance earthed

• Application 3: Three-winding HV/MV1/MV2, Y/Y/Δ- transformer; HV:solidlyearthed, MV1:solidly earthed, MV2:high impedance earthed

• Application 4: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2:solidly earthed

2.3.2 Two-winding HV/MV, Y/Δ-transformer

This application example is a two-winding HV/MV, Y/Δ-transformer with thefollowing properties:

• High voltage solidly earthed• Medium voltage high impedance earthed

1MRK 504 134-UEN A Section 2Application

33Application manual

Page 40: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

11

1

33

IEC09000435-1-en.vsd

RET650

Ph-Ph

IEC09000435 V1 EN

Figure 5: Two-winding HV/MV transformer, Y/Δ-transformer; HV:solidlyearthed, MV:high impedance earthed

Table 1: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 220 kV

Medium voltage side system voltage (UM,HV) 11 – 110 kV

Transformer rated power (SN) 15 – 150 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV-side 0 – 5 000 MVA

2.3.3 Two-winding HV/MV, Y/Y-transformer

This application example is a two-winding HV/MV Y/Y-transformer with thefollowing properties:

• High voltage solidly earthed• Medium voltage high impedance earthed

Section 2 1MRK 504 134-UEN AApplication

34Application manual

Page 41: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1

33

1

1

1

IEC09000436-1-en.vsd

Ph-Ph

RET650

IEC09000436 V1 EN

Figure 6: Two-winding HV/MV, Y/Y-transformer; HV:solidly earthed, MV:highimpedance earthed

Table 2: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 220 kV

Medium voltage side system voltage (UM,HV) 11 – 110 kV

Transformer rated power (SN) 15 – 150 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV-side 0 – 5 000 MVA

2.3.4 Functionality table

The proposal for functionality choice for the different application cases are shown intable 3.

In the table the recommendations have the following meaning:

• On: It is recommended to have the function activated in the application• Off: It is recommended to have the function deactivated in the application• Application dependent: The decision to have the function activated or not is

dependent on the specific conditions in each case

Application 1 and Application 2 in table 3 are according to applicationexamples given in previous sections.

1MRK 504 134-UEN A Section 2Application

35Application manual

Page 42: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 3: Selection of functions in different applications

Function Application 1 Application 2Transformer differential protection, twowinding T2WPDIF

On On

Restricted earth fault protection REFPDIF(instance 1)

On On

Restricted earth fault protection REFPDIF(instance 2)

Application dependent Application dependent

Instantaneous phase overcurrent protectionPHPIOC (instance 1 on HV side)

On On

Instantaneous phase overcurrent protectionPHPIOC (instance 2 on MV side)

Off Off

Four step phase overcurrent protectionOC4PTOC (instance 1 on HV-side)

On On

Four step phase overcurrent protectionOC4PTOC (instance 2 on MV-side)

On On

Instantaneous residual overcurrentprotection EFPIOC (instance 1 on HV-sideneutral point)

On On

Instantaneous residual overcurrentprotection EFPIOC (instance 2 on MV-sideneutral point)

Off Off

Four step residual overcurrent protectionEF4PTOC (instance 1 on HV-side)

On On

Four step residual overcurrent protectionEF4PTOC (instance 2 on MV-side)

Application dependent Application dependent

Thermal overload protection TRPTTR(instance 1 on HV-side)

On On

Thermal overload protection, two timeconstants TRPTTR (instance 2 on MV-side)

Application dependent Application dependent

Breaker failure protection CCRBRF(instance 1 on HV-side)

On On

Breaker failure protection CCRBRF(instance 2 on MV-side)

On On

Pole discordance protection CCRPLD Application dependent Application dependent

Directional under-power protectionGUPPDUP

Application dependent Application dependent

Directional over-power protectionGOPPDOP

Application dependent Application dependent

Negative sequence based overcurrentprotection DNSPTOC

On On

Two step undervoltage protection UV2PTUV Application dependent Application dependent

Two step overvoltage protection OV2PTOV Application dependent Application dependent

Two step residual overvoltage protectionROV2PTOV

On On

Overexcitation protection OEXPVPH Off Off

Under frequency protection SAPTUF Application dependent Application dependent

Over frequency protection SAPTOF Application dependent Application dependent

Table continues on next page

Section 2 1MRK 504 134-UEN AApplication

36Application manual

Page 43: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Function Application 1 Application 2Rate-of-change frequency protectionSAPFRC

Application dependent Application dependent

Breaker close/trip circuit monitoringTCSSCBR

On On

Automatic voltage control for tap changer,single control TR1ATCC

On On

2.3.5 Three-winding HV/MV1/MV2, Y/Y/Δ-transformer

This application example is a three-winding HV/MV1/MV2, Y/Y/Δ-transformer withthe following properties:

• High voltage solidly earthed• Medium voltage 1 solidly earthed• Medium voltage 2 Delta

IEC09000437-2-en.vsd

1

3

33

1

3

3

1

1

RET650

IEC09000437 V2 EN

Figure 7: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2: Delta

Table 4: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV) 110 – 400 kV

Medium voltage side1 system voltage (UM1,HV) 11 – 110 kV

Medium voltage side2 system voltage (UM2,HV) 11 – 110 kV

Transformer rated power (SN) 25 – 500 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV1-side 0 – 5 000 MVA

Short circuit power level infeed at MV2-side 0 – 5 000 MVA

1MRK 504 134-UEN A Section 2Application

37Application manual

Page 44: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2.3.6 Three-winding HV/MV1/MV2, Y/Y/Δ-transformer

This application example is a three-winding HV/MV1/MV2, Y/Y/Δ-transformer withthe following properties:

• High voltage solidly earthed• Medium voltage 1 solidly earthed• Medium voltage 2 Delta

IEC09000438-2-en.vsd

RET650

1

3

33

1

3

3

1

1

.

IEC09000438 V2 EN

Figure 8: Three-winding HV/MV1/MV2, Y/Y/Δ-transformer; HV:solidlyearthed, MV1:solidly earthed, MV2:Delta

Table 5: Typical data for the transformer application

Item DataHigh voltage side system voltage (UN,HV): 110 – 400 kV

Medium voltage side1 system voltage (UM1,HV) 11 – 110 kV

Medium voltage side2 system voltage (UM2,HV) 11 – 110 kV

Transformer rated power (SN) 25 – 500 MVA

On line tap changer On the HV-side winding

Short circuit power level infeed at HV-side 500 – 10 000 MVA

Short circuit power level infeed at MV1-side 0 – 5 000 MVA

Short circuit power level infeed at MV2-side 0 – 5 000 MVA

2.3.7 Functionality table

The proposal for functionality choice for the different application cases are shown intable 6. In the table the recommendations has the following meaning:

Section 2 1MRK 504 134-UEN AApplication

38Application manual

Page 45: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• On: It is recommended to have the function activated in the application• Off: It is recommended to have the function deactivated in the application• Application dependent: The decision to have the function activated or not is

dependent on the specific conditions in each case

Application 3 and Application 4 in table 6 are according to applicationexamples given in previous sections.

Table 6: Selection of functions in different applications

Function Application 3 Application 4Transformer differential protection, three winding T3WPDIF On On

Restricted earth fault protection REFPDIF (instance 1 on HV-side) On On

Restricted earth fault protection REFPDIF (instance 2 on MV1-side) On Application dependent

Restricted earth fault protection REFPDIF (instance 3 on MV2-side) Application dependent Application dependent

Instantaneous phase overcurrent protection PHPIOC (instance 1 on HV side) On On

Instantaneous phase overcurrent protection PHPIOC (instance 2 on MV1-side)

Off Off

Instantaneous phase overcurrent protection PHPIOC (instance 3 on MV2-side)

Off Off

Four step phase overcurrent protection OC4PTOC (instance 1 on HV-side) On On

Four step phase overcurrent protection OC4PTOC (instance 2 on MV1-side) On On

Four step phase overcurrent protection OC4PTOC (instance 3 on MV2-side) On On

Instantaneous residual overcurrent protection EFPIOC (instance 1 on HV-side)

On On

Instantaneous residual overcurrent protection EFPIOC (instance 2 on MV1-side)

Application dependent Application dependent

Instantaneous residual overcurrent protection EFPIOC (instance 3 on MV2-side)

Off Application dependent

Four step residual overcurrent protection EF4PTOC (HV side neutral point) On On

Four step residual overcurrent protection EF4PTOC (MV1 side neutral point) On On

Four step residual overcurrent protection EF4PTOC (MV2 side neutral point) Application dependent On

Thermal overload protection, two time constants TRPTTR (instance 1 on HV-side)

On On

Thermal overload protection, two time constants TRPTTR (instance 2 onMV1-side)

Application dependent Application dependent

Thermal overload protection, two time constants TRPTTR (instance 3 onMV2-side)

Application dependent Application dependent

Breaker failure protection CCRBRF (instance 1 on HV-side) On On

Breaker failure protection CCRBRF (instance 2 on MV1-side) On On

Breaker failure protection CCRBRF (instance 3 on MV2-side) On On

Pole discordance protection CCRPLD Application dependent Application dependent

Directional under-power protection GUPPDUP Application dependent Application dependent

Directional over-power protection GOPPDOP Application dependent Application dependent

Table continues on next page

1MRK 504 134-UEN A Section 2Application

39Application manual

Page 46: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Function Application 3 Application 4Two step undervoltage protection UV2PTUV Application dependent Application dependent

Two step overvoltage protection OV2PTOV Application dependent Application dependent

Two step residual overvoltage protection ROV2PTOV On On

Overexcitation protection OEXPVPH On On

Under frequency protection SAPTUF Application dependent Application dependent

Over frequency protection SAPTOF Application dependent Application dependent

Rate-of-change of frequency protection SAPFRC Application dependent Application dependent

Breaker close/trip circuit monitoring TCSSCBR On On

Automatic voltage control for tap changer, single control TR1ATCC On On

Section 2 1MRK 504 134-UEN AApplication

40Application manual

Page 47: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 3 RET650 setting examples

3.1 Setting example for a two-winding HV/MVtransformer, Y/Δ-transformer

The application example has a 145/22 kV transformer as shown in figure 9.

11

1

33

Ph-Ph

145 kV 22 kV

IEC09000446-1-en.vsd

RET650

IEC09000446 V1 EN

Figure 9: Two-winding HV/MV transformer, Y/Δ-transformer

Table 7: Typical data for the transformer applicationThe following data is assumed:Item DataTransformer rated power SN 60 MVA

Transformer high voltage side rated voltage UN1 145 kV ±9 · 1.67 % (with on load tap changer)

Transformer low voltage side rated voltage UN2 22 kV

Transformer vector group YNd11

Transformer impedance voltage at tap changermid point: ek

12 %

Maximum allowed continuous overload 1.30 · SN

Phase CT ratio at 145 kV level 300/1 A

CT at 145 kV earth point 300/1 A

Phase CT ratio at 22 kV level 2 000/1 A

22 kV VT ratio/22

30 11

3. 0 11

3./ kV

High positive sequence source impedance at theHV side

j10 Ω (about 2 100 MVA)

Low positive sequence source impedance at theHV side

j3.5 Ω (about 6 000 MVA)

Table continues on next page

1MRK 504 134-UEN A Section 3RET650 setting examples

41Application manual

Page 48: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Item DataHigh zero sequence source impedance at the HVside

j20 Ω

Low zero sequence source impedance at the HVside

j15 Ω

Positive sequence source impedance at the LVside

∞ (no generation in the 22 kV network)

Only settings that need adjustment due to the specific application aredescribed in setting examples. It is recommended to keep the defaultvalues for all settings that are not described. Refer to the technicalmanual for setting tables for each protection and control function.

Refer to the setting guideline section in the Application manual forguidelines on how to set functions that are not presented in the settingexamples.

Use the parameter setting tool in PCM600 to set the IED according tothe calculations for the particular application.

3.1.1 Calculating general settings for analogue inputs 8I 2U

The analogue input module has the capability of 8 current inputs (1 A) and 2 voltageinputs.

The 145 kV current CTs (three phase current transformer group) are connected toinputs 1 – 3 (L1, L2, L3).

The 22 kV current CTs (three phase current transformer group) are connected to inputs4 – 6 (L1, L2, L3).

The 145 kV neutral point CT is connected to input 7 (IN).

The input 8 is not used. The input is used for connection of the low voltage side neutralpoint CT (not in this application)

The 22 kV phase-to-phase (L1 – L2) VT is connected to input 9.

The 22 kV open delta connected VT (residual voltage) is connected to input 10.

1. Set the 145 kV current transformer input 1.1.1. Set CTStarPoint1 to ToObject

Section 3 1MRK 504 134-UEN ARET650 setting examples

42Application manual

Page 49: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

(The CT secondary is earthed towards the protected transformer)1.2. Set CTSec1 to 1 A

(The rated secondary current of the CT)1.3. Set CTPrim1 to 300 A

(The rated primary current of the CT)2. Set current inputs 2 and 3 to the same values as for current input 1.3. Set the 22 kV current transformer input 4.

3.1. Set CTStarPoint4 to ToObject(The CT secondary is earthed towards the protected transformer)

3.2. Set CTSec4 to 1 A(The rated secondary current of the CT)

3.3. Set CTPrim4 to 2000 A(The rated primary current of the CT)

4. Set current inputs 5 and 6 to the same values as for current input 4.5. Set the 145 kV neutral point current transformer input 7.

5.1. Set CTStarPoint7 to ToObject(The CT secondary is earthed towards the protected line)

5.2. Set CTSec7 to 1 A(The rated secondary current of the CT)

5.3. Set CTPrim7 to 300 A(The rated primary current of the CT)

Current input 8 is intended for connection of a low voltage sideneutral point CT. In this application the input is not used.

6. Set the voltage transformer inputs 9 and 10.6.1. Set VTSec9 to 110 V

(The rated secondary voltage of the VT, given as phase-phase voltage)6.2. Set VTPrim9 to 22 kV

(The rated secondary voltage of the VT, given as phase-phase voltage)6.3. Set VTSec10 to 110 V/√3

(The rated secondary voltage of the VT, given as phase-phase voltage)6.4. Set VTPrim10 to 22 kV

(The rated secondary voltage of the VT, given as phase-phase voltage)

3.1.2 Calculating settings for global base values GBASVAL

Each function uses primary base values as a reference for the settings. The base valuesare defined in Global base values for setting GBASVAL function. It is possible toinclude up to GBASVAL function. In this application GBASVAL instance 1 is usedto define the base for 145 kV inputs and GBASVAL instance 2 for 22 kV inputs.

1MRK 504 134-UEN A Section 3RET650 setting examples

43Application manual

Page 50: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

For transformer protection it is recommended to set the base parameters according tothe power transformer primary rated values:

1. Set Global Base 11.1. Set IBase to 239 A1.2. Set UBase to 145 kV1.3. Set SBase to 60 MVA (SBase=√3·UBase·IBase)

2. Set Global Base 22.1. Set IBase to 1575 A2.2. Set UBase to 22 kV2.3. Set SBase to 60 MVA (SBase=√3·UBase·IBase)

There are six instances of global base GBASVAL function, eachinstance includes the three parameters: IBase, UBase, SBase. TheGlobalBaseSel setting which can be found in the different IEDfunctions references a specific instance of the GBASVAL function.

3.1.3 Calculating settings for transformer differential protectionT2WPDIF

1. Set GlobalBaseSelW1 to 1 (HV)2. Set GlobalBaseSelW2 to 2 (LV)

To relate the function settings to the rated data of the transformer, the twowindings should be referenced to GlobalBaseSelW1 and GlobalBaseSelW2 1(HV-side) and 2 (LV-side).

3. Set the vector group of the transformer3.1. Set ConnectTypeW1 to WYE (Y)3.2. Set ConnectTypeW2 to Delta (D)3.3. Set ClockNumberW2 to 11 [30 deg lead]

4. Set system residual current elimination4.1. Set ZSCurrSubtrW1 to On4.2. Set ZSCurrSubtrW2 to Off

The transformer is solidly earthed at the 145 kV side. In case of an earth-fault inthe 145 kV system residual current flows from the transformer. This residualcurrent is seen as a differential current. To prevent an unwanted trip during anexternal earth-fault the zero sequence current shall be eliminated from themeasured transformer current. Since zero sequence currents can not flow in adelta winding this elimination is only needed for the solidly earthedY winding.

5. Set I2/I1Ratio to 15 % (default)When the transformer is energized an inrush current occurs. This current is seenas a differential current. With a combination of the second harmonic restraint

Section 3 1MRK 504 134-UEN ARET650 setting examples

44Application manual

Page 51: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

and the waveform restraint methods it is possible to get a protection with highsecurity and stability against inrush effects and at the same time maintain highperformance in case of heavy internal faults even if the current transformers aresaturated. Both these restraint methods are used. It is recommended to use theparameter I2/I1Ratio = 15% as the default value in case no special reasons existto choose a different value.

6. Set I5/I1Ratio to 25 % (default)When the transformer is overexcited due to high voltage and/or low networkfrequency, the excitation current increases significantly. This current is seen asa differential current. The differential protection function is provided with a fifthharmonic restraint to prevent the protection from operation during anoverexcitation condition of the power transformer. It is recommended to use theparameter I5/I1Ratio = 25% as the default value in case no special reasons existto choose a different value.

7. Set CrossBlockEn to OnIf any of the above mentioned restrain functions (waveform restrain, secondharmonic restrain or fifth harmonic restrain) is activated in one phase, cross-blocking can be used to prevent operation of the differential protection in theother phases as well. It is recommended to set the cross-blocking on.

8. Set restrain characteristics8.1. Set EndSection1 to 1.25 IBase8.2. Set EndSection2 to 3 IBase8.3. Set SlopeSection2 to 40 %8.4. Set SlopeSection3 to 80 %

The characteristic of the restrained and unrestrained differential protection isshown in figure 10. The differential current limit for operation of the protectionis shown as a function of the restrain current. The restrain current is equal to thehighest transformer phase current. The restrain characteristic is defined by theparameters: IdMin, EndSection1, EndSection2, SlopeSection2 andSlopeSection3. The settings of EndSection1, EndSection2, SlopeSection2 andSlopeSection3 are defined as advanced parameters and the default values arerecommended.

1MRK 504 134-UEN A Section 3RET650 setting examples

45Application manual

Page 52: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1

Operate conditionally

UnrestrainedLimit

Section 2 Section 3

Restrain

Operate unconditionally

5

4

3

2

1

00 1 2 3 4 5

IdMin

EndSection1

EndSection2restrain current

[ times I1r ]

operate current[ times I1r ]

SlopeSection2

SlopeSection3

en05000187.vsd

GUID-F6F9E16D-A762-4518-A9E1-A4B2A962821B V1 EN

Figure 10: Transformer differential protection operation characteristic

9. Set IdMin to ≥0.3 IBaseDuring normal operation there is a ”false” differential current measured by theprotection due to the following:• Deviation tap changer position compared to the nominal transformer ratio• Difference in current transformer error

The measured differential current with the tap changer position in the extremepositions can be calculated:• At the tap position giving the lowest LV voltage the transformer ratio is

166.8/22 kV. At 1.25 times the rated power (EndSection1) the 145 kVcurrent is:

1.25 60 0.2603 166.8HVI kA×

= =×

GUID-5461E726-C83D-4B02-B2A6-E3F376308529 V1 EN (Equation 1)

This corresponds to 1.088 times the rated current. The low voltage side currentis 1.25 times the rated current and thus the differential current is about 0.16 timesthe rated transformer current.

Section 3 1MRK 504 134-UEN ARET650 setting examples

46Application manual

Page 53: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• At the tap position giving the highest LV voltage the transformer ratio is123.2/22 kV. At 1.25 times the rated power (EndSection1) the 145 kVcurrent is:

1.25 60 0.3523 123.2HVI kA×

= =×

GUID-6C914C3F-86A8-450C-9CCF-16BCA07A48E2 V1 EN (Equation 2)

This corresponds to 1.471 times the rated current. The low voltage side currentis 1.25 times the rated current and thus the differential current is about 0.22 timesthe rated transformer current.The current transformers class is 5P which gives a maximum amplitude error ofcirca 1 %. The IED accuracy is given as circa 5% at nominal values to assure thatthe load current does not cause unwanted operation IdMin is set to 0.30 times therated transformer current.

10. Set IdUnre to 10.0 IBaseThe unrestrained differential protection function operates without anystabilization. The setting principle is that the unrestrained function shall only beable to detect internal faults. This means that the current setting shall be largerthan the largest fault current through the transformer during external faults. Avery simple way to estimate this current is as:

1 1 8.330.12k

IdUnre IBase IBase IBasee

³ × = × = ×

GUID-D44EC374-13ED-4E91-A420-F9C7460F71C2 V2 EN (Equation 3)

If instead the feeding network is considered and a three-phase-fault at the lowvoltage side of the transformer is calculated, the following current resultsthrough the transformer (145 kV level):

2145 145 1 83

3 1453 3 5 0 1260

net TI . kA

( Z Z )( . . )

= = =× +

× + ×

GUID-D49C58EF-F9FD-4BAD-943A-55C186968C2F V2 EN (Equation 4)

This corresponds to 7.6 times the transformer rated current. If we consider 80%saturation the differential current will approximately be 0.8 * 1.83kA =1.464kA. An additional safety margin of 1.2 is chosen. The setting of IdUnrshould then comply with the following formula with respect to the performedcalculations:

1.83kAIdUnr >= 1.2 0.8 = 7.4 IBase239

× × ×

IECEQUATION2412 V1 EN (Equation 5)11. Set NegSeqDiffEn, IMinNegSeq and NegSeqROA

11.1. Set NegSeqDiffEn to On (default)11.2. Set IMinNegSeq to >0.04 IBase (default)11.3. Set NegSeqROA to 60º (default)

The transformer differential protection has external/internal fault discriminatorfunction, based on negative sequence current. The settings of NegSeqDiffEn,

1MRK 504 134-UEN A Section 3RET650 setting examples

47Application manual

Page 54: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IMinNegSeq and NegSeqROA are defined as advanced parameters and thedefault values are recommended.

3.1.4 Calculating settings for restricted earth fault protectionREFPDIF

The restricted earth fault protection is applied to the solidly earthed 145 kV windingas shown in figure 11.

Restricted earth-fault protection

IEC09000448-1-en.vsd

IEC09000448 V1 EN

Figure 11: Restricted earth fault protection application

1. Set GlobalBaseSel to 1.The (HV) winding data should be related to Global base 1

2. Set IdMin to 30 % of IBase

Section 3 1MRK 504 134-UEN ARET650 setting examples

48Application manual

Page 55: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC98000017-3-en.vsd

bias current in per unit

0 1 2 3 4 5 6

1

2

3

4

5operate current in pu

default base sensitivity 30 %

operate

Base Sensitivity Idmin

*************************************Range : 4 % to 100 % rated currentStep : 1 % transformer rated current

minimum base sensitivity 100 %

maximum base sensitivity 5 % block

zone 1 zone 2

1.25 pu

second slope

first slope

IEC98000017 V4 EN

Figure 12: Restricted earth fault protection trip characteristic

The operate characteristic is shown in figure 12. The only setting to be made isto set IdMin. The default value is 30 % of IBase. This setting is recommended.

3.1.5 Calculating settings for instantaneous phase overcurrentprotection, HV-side, PHPIOC

1. Set GlobalBaseSel to 1The (HV) winding data should be related to Global base 1.

2. Set IP>> to 1000 % of IBaseThe instantaneous phase overcurrent protection on the high voltage side is usedfor fast trip ping during severe internal faults. The protection shall be selectivewith respect to the protections of the outgoing 22 kV feeders. Therefore themaximum 145 kV current during a three-phase short circuit on the 22 kV side ofthe transformer is calculated:

2145 145 1.83

3 ( ) 1453 (3.5 0.12)60

net TI kA

Z Z= = =

× +× + ×

GUID-662F8080-2FA3-47D9-B030-CDB4D502DB53 V2 EN (Equation 6)

The dynamic overreach, due to fault current DC-component, shall be consideredin the setting. This factor is less that 5 %. The setting is chosen with a safetymargin of 1.2:

1MRK 504 134-UEN A Section 3RET650 setting examples

49Application manual

Page 56: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Iset ≥ 1.2 · 1.05 · 1 830 = 2 306 ASettingIP>> = 1000 % of IBase

3.1.6 Calculating settings for four step phase overcurrentprotection 3-phase output, HV-side, OC4PTOC

The phase overcurrent protection is difficult to set as the short circuit current is highlydependent of the switching state in the power system as well as the fault type. In orderto achieve setting that assure a selective fault clearance, a large number of calculationshave to be made with different fault locations, different switching states in the systemand different fault types.

The 145 kV phase overcurrent protection has the following tasks:

• Backup protection for short circuits on the transformer• Backup protection for short circuits on 22 kV busbar• Backup protection for short circuits on outgoing 22 kV feeders (if possible)

Although it is possible to make hand calculations of the different faults it isrecommended to use computer based fault calculations.

The following principle for the phase overcurrent protection is proposed:

• Only one step (step 1) is used. The time delay principle is chosen according tonetwork praxis, in this case inverse time characteristics using IEC Normalinverse.

3.1.6.1 Calculating general settings

1. Set GlobalBaseSel to 1For the (HV) winding data should be related to Global base 1

2. Set DirMode1 to Non-directionalThe function shall be non-directional

3. Set Characterist1 to IEC Norm.inv.For the choice of the time delay characteristic IEC Normal inverse is used in thisnetwork.

3.1.6.2 Calculating settings for step 1

1. Set I1> to 140% of IBase (334 A primary current)

Section 3 1MRK 504 134-UEN ARET650 setting examples

50Application manual

Page 57: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The first requirement is that the phase overcurrent protection shall never trip forload current during the extreme high load situations. It is assumed that thetransformer shall be able to be operated up to 130 % of the rated power duringlimited time. The protection resetting ratio shall be considered as well. The resetratio is 0.95. The minimum setting can be calculated as:

1 60 10001 3 3270 95 3 145puI . A

³ × × =×

GUID-23DBA3B9-4E20-4210-901B-3CB4B8B2BC38 V1 EN (Equation 7)

The next requirement is that the protection shall be able to detect all short circuitswithin the defined protected zone. In this case it is required, if possible, that theprotection shall detect phase-to-phase short circuit at the most remote point ofthe outgoing feeders as shown in figure 13.

RET 650

11

1

33

Ph-Ph

145 kV 22 kV

I>

IEC09000450_1_en.vsd

IEC09000450 V1 EN

Figure 13: Fault calculation for phase overcurrent protection setting

A phase-phase-earth short circuit is applied. In this calculation the short circuitpower of the feeder shall be minimized (the source impedance maximized).The longest 22 kV feeder has an impedance of Z = 3 + j10 Ω. The externalnetwork has a maximum source impedance of Zsc = j10 Ω (145 kV level). Thisimpedance is transformed to the 22 kV level:

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-FA8FA533-48E3-45FA-A22A-584CD0F754BF V1 EN (Equation 8)

The transformer impedance referred to 22 kV level is:

2

,2222 0.12 0.9760TZ j j= × = W

GUID-78CEC42F-9A02-411B-B6D3-95017467242B V1 EN (Equation 9)

The fault current can be calculated as follows:

2

220003 3 948

2 0.23 0.97 3 10sc phI Aj j j

= × =+ + +

GUID-2C4DC073-E49B-45BB-8136-96B455CC57A1 V1 EN (Equation 10)

This fault current is recalculated to the 145 kV level:

1MRK 504 134-UEN A Section 3RET650 setting examples

51Application manual

Page 58: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2 ,14522 948 144

145sc phI A= × =

GUID-2E36019B-9370-4703-9B31-91870BBD7BDB V1 EN (Equation 11)

This current is smaller than the required minimum setting to avoid an unwantedtrip when experiencing a large load current. This means that the 145 kV phaseovercurrent protection cannot serve as complete back-up protection for theoutgoing 22 kV feeders.

2. Set k1 to 0.15The time setting must be coordinated with the feeder protections to assureselectivity. It can be stated that there is no need for selectivity between the highvoltage side phase overcurrent protection and the low voltage side phaseovercurrent protection.The feeder short circuit protections have the following setting:I>: 300 A which corresponds to 45 A on 145 kV level.I>>: 6 000 A which corresponds to 910 A on 145 kV level.Characterist: IEC Normal Inverse (IEC Norm. inv.) with k-factor = 0.25The setting of the k-factor for the 145 kV phase overcurrent protection is derivedfrom graphical study of the inverse time curves. It is required that the smallesttime difference between the inverse time curves shall be 0.4 s. With the setting k1= 0.15 the time margin between the characteristics is about 0.4 s as shown infigure 14.

Section 3 1MRK 504 134-UEN ARET650 setting examples

52Application manual

Page 59: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000451 V1 EN

Figure 14: Inverse time operation characteristics for selectivity

3.1.7 Calculating settings for four step phase overcurrentprotection 3-phase output, LV-side OC4PTOC

The 22 kV phase overcurrent protection has the following purpose:

• Main protection for short circuits on 22 kV busbar• Backup protection for short circuits on outgoing 22 kV feeders (if possible)

The reach of the phase overcurrent line protection is dependent on the operation stateand the fault type. Therefore the setting must be based on fault calculations made fordifferent faults, fault points and switching states in the network. Although it is possibleto make manual calculations of the different faults it is recommended to use computerbased fault calculations.

The following principle for the phase overcurrent protection is proposed:

1MRK 504 134-UEN A Section 3RET650 setting examples

53Application manual

Page 60: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Step 1 serves as the main protection for the 22 kV busbar. This step has a shortdelay and also has blocking input from the phase overcurrent protections of the 22kV feeders. This is a way to achieve a fast trip of 22 kV busbar short circuits whilethe selectivity is realized by means of the blocking from the feeder protections.

• Step 4 is used as back-up short circuit protection for the 22 kV feeders as far aspossible. The time delay principle is chosen according to network praxis, in thiscase inverse time characteristics using IEC Normal inverse. As the step shall havean inverse time characteristic the step 4 function is used.

An inverse time characteristics is not available for step 2 and 3.

3.1.7.1 Calculating general settings

1. Set GlobalBaseSel to 2The settings are made in primary values. These values are given in the basesettings in Global base 2.

2. Set directional mode2.1. Set DirMode1 to Non-directional2.2. Set DirMode4 to Non-directional

The function shall be non-directional.3. Set Characterist1 to IEC Def.Time

Step 1 shall have definite time delay4. Set Characterist4 to IEC Norm.inv

Step 4: For the choice of the time delayed characteristic IEC Normal inverse isused in this network.

3.1.7.2 Calculating settings for step 1

1. Set I1> to 500 % of IBaseThe requirement is that step 1 shall detect all short circuits on the 22 kV busbar.The external network has a maximum source impedance of Zsc = j10 Ω (145 kVlevel). This impedance is transformed to 22 kV level:

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-A4805F4D-20EC-4B39-A39D-925513515FA5 V1 EN (Equation 12)

The transformer impedance, referred to 22 kV level, is:

2

,2222 0.12 0.9760TZ j j= × = W

GUID-CB0D94B6-5BFA-42EB-AE4A-B0EE898A0D78 V1 EN (Equation 13)

Calculation of a phase-to-phase short circuit at this busbar:

Section 3 1MRK 504 134-UEN ARET650 setting examples

54Application manual

Page 61: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

23 22000 / 3 9167

2 0.23 0.97sc phI Aj j

= × =+

GUID-846C7A33-F976-45DF-95E9-75124D6A24D2 V1 EN (Equation 14)

The setting is chosen to 5 IBase which corresponds to 7 875 A primary current.2. Set t1 to 0.1 s

The time delay must be chosen so that the blocking signal shall be able to preventunwanted operation during feeder short circuits. 0.1 s should be sufficient.

3.1.7.3 Calculating settings for step 4

The first requirement is that the phase overcurrent protection shall never trip for loadcurrent during extreme high load situations. It is assumed that the transformer shall beable to be operated up to 130% of the rated power during the limited time. Theprotection resetting ratio of 0.95 shall also be considered. The minimum setting can becalculated as follows:

1 60 10001.3 21550.95 3 22puI A×

³ × × =×

GUID-4D6B62EC-32DC-433E-B1C8-D23E8D06D017 V1 EN (Equation 15)

The next requirement is that the protection shall be able to detect all short circuitswithin the defined protected zone. In this case it is required, if possible, that theprotection shall detect phase-to-phase short circuit at the most remote point of theoutgoing feeders as shown in figure 15.

145kV

11

1

33

IEC09000452-1-en.vsd

RET650

Ph-Ph

22kV

I>

IEC09000452 V1 EN

Figure 15: Fault calculation for phase overcurrent protection

A phase-phase-earth short circuit is applied. In this calculation the short circuit powerof the feeder shall be minimized (the source impedance maximized).

1. Set I2> to 140 % of IBase2205 A primary current.The longest 22 kV feeder has an impedance of Z = 3 + j10 Ω. The externalnetwork has a maximum source impedance of Zsc = j10 Ω (145 kV level). Thisimpedance is transformed to the 22 kV level:

1MRK 504 134-UEN A Section 3RET650 setting examples

55Application manual

Page 62: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2

,2222 10 0.23

145scZ j jæ ö= × = Wç ÷è ø

GUID-BA67F1FC-2DCE-4E04-BBB3-FABB86FDEA3A V1 EN (Equation 16)

The transformer impedance, referred to 22 kV level is:The phase-to-phase fault current can be calculated as follows:

23 22000 / 3 949

2 0.23 0.97 3 10sc phI Aj j j

= × =+ + +

GUID-BAA8989B-EF8F-4277-9B2B-EBBCA35ED7C2 V1 EN (Equation 17)

This current is smaller than the required minimum setting to avoid unwanted tripat large load current. This means that the 22 kV phase overcurrent protectioncannot serve as complete back-up protection for the outgoing 22 kV feeders.

2. Set k4 to 0.15The feeder short circuit protections has the following setting:I>: 300 A.I>>: 6 000 A.Characteristic: IEC Normal Inverse with k-factor = 0.25The setting of the k-factor for the 22 kV phase overcurrent protection is derivedfrom graphical study of the inverse time curves. It is required that the smallesttime difference between the inverse time curves is 0.4 s. With the setting k4=0.15 the time margin between the characteristics is about 0.4 s as shown in figure16.

Section 3 1MRK 504 134-UEN ARET650 setting examples

56Application manual

Page 63: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000453 V1 EN

Figure 16: Inverse time operation characteristics for selectivity

3.1.8 Calculating settings for four step residual overcurrentprotection, zero or negative sequence direction HV-sideEF4PTOC

The protection is fed from the 145 kV neutral point of the current transformer.

The residual overcurrent protection is more difficult to set as the earth-fault current ishighly dependent on the network configuration of the power system. In order toachieve settings that assure selective fault clearance, a large number of calculationshave to be made with different fault locations, different switching states in the systemand different earth-fault types. Below one example of setting of residual overcurrentprotection for a line in a meshed solidly earthed system is given.

1MRK 504 134-UEN A Section 3RET650 setting examples

57Application manual

Page 64: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

If there is no generation at the low voltage side of the generator the transformer canonly feed earth-fault currents as long as any of the non faulted lines are still inoperation. If there is generation connected to the low voltage side of the transformerthe transformer can only feed 145 kV earth-faults.

The residual overcurrent protection has the following purpose:

• Fast and sensitive protection for earth-faults on the 145 kV busbar• Backup protection for earth-faults in the 145 kV transformer winding• Backup protection for earth-faults on the outgoing 145 kV lines• Sensitive detection of high resistive earth-faults and series faults in the 145 kV

network

The reach of the residual overcurrent line protection is dependent on the operationstate and the fault type. Therefore the setting must be based on fault calculations madefor different faults, fault points and switching states in the network. Although it ispossible to make hand calculations of the different faults it is recommended to usecomputer based fault calculations.

The following principle for the residual overcurrent protection is proposed:

• Step 1 (IN1>) with a high current setting and a short delay (about 0.4 s). Step 1is a non-directional function. This step gives a fast trip for busbar earth-faults andsome earth-faults on the lines.

• Step 2 (IN2>) with a current setting, if possible, that enables detection of earth-faults on the 145 kV lines out from the substation. Step 2 is a non-directionalfunction. The function has a delay to enable selectivity with respect to the lineprotections.

• Step 4 (IN4>) with a current setting that enables detection of high resistive earth-faults and series faults in the network. Step 3 is a non-directional function. Thefunction has a longer delay to enable selectivity.

3.1.8.1 Calculating general settings

The (HV) winding data should be related to Global base 1.

1. Set GlobalBaseSel to 1, IBase = 240 A2. Set DirMode1, DirMode2 and DirMode4 to Non-directional3. Set DirMode3 to Off

3.1.8.2 Calculating settings for step 1

Set the operating residual current level and time delay

1. Set IN1> to 689% of IBase, corresponding to 1650 A

Section 3 1MRK 504 134-UEN ARET650 setting examples

58Application manual

Page 65: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Faults are applied at the 145 kV busbar as shown in figure 17.

11

1

33

IEC09000454-1-en.vsd

IN>

RET650

Ph-Ph

22kV145kV

IEC09000454 V1 EN

Figure 17: Fault calculation for 145 kV residual overcurrent protectionsetting

The following fault types are applied: phase-phase-earth short circuit and phase-earth-fault. The source impedance (both positive sequence and zero sequence) atthe 145 kV level gives the following residual current from the transformerduring a phase-to-earth busbar fault (the current is hand-calculated but isnormally calculated in a computer).The zero sequence transformer impedance is assumed to be equal to the positivesequence short circuit impedance:

2 2

0145 0.12 42

60N

T kN

UZ j e j jS

= × = × = W

GUID-50CCC0F7-742D-45C4-84BC-923222214C69 V1 EN (Equation 18)

The residual current from the transformer during a single phase-earth-fault andwith maximum short circuit power is:

0,0

0, 00, 01,

0, 0

3 15 3 1453 3.715 4215 42 2 3.52 15 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + × +× +++

GUID-CC2E2412-4939-4285-A491-FCCC0AE0F939 V1 EN (Equation 19)

The residual current from the transformer during a single phase-earth-fault andwith minimum short circuit power is:

0,0

0, 00, 01,

0, 0

3 20 3 1453 2.420 4220 42 2 102 20 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + × +× +++

GUID-991D27BC-4413-4A9B-BF49-F25986545C73 V1 EN (Equation 20)

The residual current from the transformer during a phase-to-phase to earth-faultand with maximum short circuit power is:

1MRK 504 134-UEN A Section 3RET650 setting examples

59Application manual

Page 66: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

0,0

0, 00, 01,

0, 0

3 15 3 1453 2.615 4215 42 3.5 22 15 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + + ×+ ×++

GUID-CA17A1A5-E141-4F0B-B7C0-74683F9F9AD1 V1 EN (Equation 21)

The residual current from the transformer during a phase-to-phase to earth-faultand with minimum short circuit power is:

0,0

0, 00, 01,

0, 0

3 20 3 1453 2.220 4220 42 10 22 20 42

netT

net Tnet Tnet

net T

Z U jI kAZ Z j jZ Z j j jZ j jZ Z

× ×= × = × =

× ×+ + + ×+ ×++

GUID-933BE756-31CD-45BA-B3EB-5DC00CA25DC0 V1 EN (Equation 22)

To assure that the protection detects all earth-faults on the 145 kV busbar theprotection should be set as follows:IN1> ≤ 0.75 · 2.2 = 1.65 kA = 687 % IBase

11

1

33

IEC09000455-1-en.vsd

IN>

145kV RET650

Ph-Ph

22kV85%

IEC09000455 V1 EN

Figure 18: Fault calculation for 145 kV residual overcurrent protectionselectivity

The calculations show that the largest residual current from the transformer = 1.2kA.To assure selectivity the setting must fulfil:Ihigh,set ≥ 1.2 · k · 3I0 maxwhich gives about 1 500 A ,where k is the transient overreach (due to the faultcurrent DC-component) of the overcurrent function. For the four step residualovercurrent function; k = 1.05.

2. Set t1 to 0.4 sCharacterist1: ANSI Def.TimeAs the protection should be set for a time delay of 0.4 s the selectivity to the lineprotections should be assured. Therefore earth-faults should be calculated wherethe fault point on the lines is at zone 1 reach (about 85 % out on the line).

3.1.8.3 Calculating settings for step 2

Section 3 1MRK 504 134-UEN ARET650 setting examples

60Application manual

Page 67: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1. Set IN2> to 400% of IBase, corresponding to 956 ATo assure that step 2 detects all earth-faults on the outgoing lines earth-faultscalculations are made where single phase-faults and phase-to-phase-to earth-faults are applied to the adjacent busbars.

11

1

33

IEC09000456-1-en.vsd

IN>

145kV RET650 22kV

Ph-Ph

IEC09000456 V1 EN

Figure 19: Fault calculation for sufficient reach of the 145 kV residualovercurrent protection

The minimum residual current to detect works out as 3I0AB,min = 1.0 kA.2. Set t2 to 0.8 s

Characteristic2: ANSI Def.TimeThe delay of IN2> should be set longer than the distance protection zone 2(normally 0,4 s). 0.8 s is proposed.

3.1.8.4 Calculating settings for step 4

1. Set IN4> to 42 % of IBase, corresponding to 100 AThe current setting of step 4 should be chosen according to standard procedurein the grid. From experience it can be concluded that a setting down to about 100A can be used. This setting is however highly dependent on the lineconfiguration, mainly if the line is transposed or not.The delay of IN4> should be set larger than the delay of the sensitive residualcurrent protection of the lines.

2. Set k4 to 0.3Characterist4: RD type

3. Set t4Min to 1.2 s4. Set inverse time delay of type RD to logarithmic

If definite time delay is used there is some risk of unselective trip during highresistive earth-faults or series faults. If a dependent time delay (inverse time) isused some degree of selectivity can be achieved.Here an inverse time delay of the RD type is selected: logarithmic

1MRK 504 134-UEN A Section 3RET650 setting examples

61Application manual

Page 68: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

3.1.9 Calculating settings for two step residual overvoltageprotection LV-side, ROV2PTOV

The residual overvoltage protection is fed from the open delta connected voltagetransformer at the 22 kV side of the transformer.

The residual overvoltage protection has the following purpose:

• Back-up protection for earth-faults on the 22 kV feeders out from the substation.• Main protection for earth-faults on the 22 kV busbar• Main protection for earth-faults on the 22 kV transformer winding

The residual voltage protection has two steps. In this application step 1 should trip the22 kV circuit breaker and if the earth-fault is situated in the transformer 22 kV windingor between the transformer and the 22 kV breaker the 145 kV breaker is tripped fromstep 2.

The voltage setting of the protection is dependent on the required sensitivity and thesystem earthing. The 22 kV system has earthing through a Petersen coil (connected tothe system via a separate earthing transformer) and a parallel neutral point resistor.The Petersen coil is tuned to compensate for the capacitive earth-fault current in the22 kV system. The neutral point resistor gives a 10 A earth-fault current during a zeroresistance earth-fault. This means that the resistance is

22000 3 127010N

/R W= =

GUID-4ECDF824-B17E-436D-A668-ACA06BB375F7 V2 EN (Equation 23)

The total zero sequence impedance of the 22 kV system is:

Z0 = 3RN // j3XN // — jXC Ω / phase

As the Petersen coil is tuned the zero sequence impedance is:

Z0 = 3RN Ω / phase

The residual voltage during a resistive earth-fault in the 22 kV system is:

0

0 0

13 3

1 1

Phaseo

f fphase

U UU orR RUZ Z

= =× ×

+ +

GUID-AD49C138-F37B-4690-9E37-BA2BAD678A17 V1 EN (Equation 24)

In our case the requirement is that earth-faults with a resistance up to 5 000 Ω shall bedetected. This gives:

0 1 0 203 500013 1270

phase

U .U

= =×

GUID-42D376ED-052F-4E9B-B4D9-8D679127BC0C V1 EN (Equation 25)

Section 3 1MRK 504 134-UEN ARET650 setting examples

62Application manual

Page 69: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Step 1 and step 2 is given the same voltage setting but step 2 shall have longer timedelay.

The residual earth-fault protection shall have a definite time delay. The time setting isset longer than the time delay of the earth-fault protection of the outgoing feedershaving maximum 2 s delay. The time delay for step 1 is set to 3 s and the time delayfor step 2 is set to 4 s.

1. Set GlobalBaseSel to 2The (LV) winding data should be related to Global base 2.

2. Set Characterist1 to Definite time3. Set U1> to 20 % of UBase4. Set t1 to 3.0 s5. Set U2> to 20 % of UBase6. Set t2 to 4.0 s

3.1.10 Calculating settings for HV-side breaker failure protection,CCRBRF

The breaker failure protection can use either the position indication of the circuitbreaker or measure the current going through the CT in order to detect correct breakerfunctioning. For transformer protections it is most suitable to use currentmeasurement as a circuit breaker failure check.

1. Set GlobalBaseSel to 1The (HV) winding data should be related to Global base 1.

2. Set FunctionMode to Current3. Set BuTripMode to 1 out of 4

The current measurement function uses the three-phase currents from the lineCT and either, a measured residual current or a calculated 3I0. Based on thisanalogue data one of the following rules can be chosen in order to determine abreaker failure:• 1 out of 3: at least one of the three-phase current shall be larger than the set

level to detect failure to break• 1 out of 4: at least one of the three-phase current and the residual current

shall be larger than the set level to detect failure to break• 2 out of 4: at least two of the three-phase current and the residual current

shall be larger than the set level to detect failure to break.

As the residual current protection is one of the protection functions to initiate thebreaker failure protection the setting 1 out of 4 is chosen.

4. Set IP> to 20 % of IBaseIP> should be set lower than the smallest current to be detected by thedifferential protection which is set 30% of IBase.

5. Set IN> to 20 % of IBase

1MRK 504 134-UEN A Section 3RET650 setting examples

63Application manual

Page 70: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IN> should be set lower than the smallest current to be detected by the mostsensitive step of the residual ovecurrent protection which is 100 A.

6. Set the re-tip time delay t1 to 07. Set t2 to 0.17 s

The delay time of the breaker failure protection (BuTrip) is chosen according tofigure 20.The maximum opening time of the circuit breaker is considered to be 100 ms.The breaker failure protection BFP maximum reset time is 15 ms.A margin of about 2 cycles should be chosen. This gives a minimum setting ofback-up trip delay t2 of about 155ms.

Time

The fault occurs

Protection operate time

Trip and Start BFP

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

en05000479.vsd

EN05000479 V1 EN

Figure 20: Overexcitation protection characteristics

3.1.11 Calculating settings for LV-side breaker failure protection,CCRBRF

The breaker failure protection can use either the position indication of the circuitbreaker or measure the current going through the CT in order to detect correct breakerfunctioning. For transformer protections it is most suitable to use currentmeasurement as a circuit breaker failure check.

1. Set GlobalBaseSel to 2

Section 3 1MRK 504 134-UEN ARET650 setting examples

64Application manual

Page 71: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The (LV) winding data should be related to Global base 2.2. Set FunctionMode to Current3. Set BuTripMode to 1 out of 3

The current measurement function uses the three-phase currents from the lineCT and either, a measured residual current or a calculated 3I0. Based on thisanalogue data one of the following rules can be chosen in order to determine abreaker failure:• 1 out of 3: at least one of the three-phase current shall be larger than the set

level to detect failure to break• 1 out of 4: at least one of the three-phase current and the residual current

shall be larger than the set level to detect failure to break• 2 out of 4: at least two of the three-phase current and the residual current

shall be larger than the set level to detect failure to break.

There is no residual current measurement protection on the 22 kV side of thetransformer. Therefore 1 out of 3 is chosen.

4. Set IP> to 20 % of IBaseIP> should be set lower than the smallest current to be detected by thedifferential protection which is set 25 % of IBase.

5. Set the re-tip time delay t1 to 0 s6. Set t2 to 0.17 s

The delay time of the breaker failure protection (BuTrip) is chosen according tofigure 20.The maximum open time of the circuit breaker is considered to be 100 ms.The BFP maximum reset time is 15 ms.A margin of about 2 cycles should be chosen. This gives a minimum setting ofback-up trip delay t2 of about 155ms.

1MRK 504 134-UEN A Section 3RET650 setting examples

65Application manual

Page 72: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Time

The fault occurs

Protection operate time

Trip and Start BFP

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

en05000479.vsd

EN05000479 V1 EN

Figure 21: Time sequences for breaker failure protection setting

Section 3 1MRK 504 134-UEN ARET650 setting examples

66Application manual

Page 73: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 4 Analog inputs

4.1 Introduction

Analog input channels in the IED must be set properly in order to get correctmeasurement results and correct protection operations. For power measuring and alldirectional and differential functions the directions of the input currents must bedefined in order to reflect the way the current transformers are installed/connected inthe field ( primary and secondary connections ). Measuring and protection algorithmsin the IED use primary system quantities. Consequently the setting values areexpressed in primary quantities as well and therefore it is important to set thetransformation ratio of the connected current and voltage transformers properly.

The availability of CT and VT inputs, as well as setting parameters depends on theordered IED.

A reference PhaseAngleRef must be defined to facilitate service values reading. Thisanalog channels phase angle will always be fixed to zero degrees and all other angleinformation will be shown in relation to this analog input. During testing andcommissioning of the IED the reference channel can be changed to facilitate testingand service values reading.

4.2 Setting guidelines

4.2.1 Setting of the phase reference channel

All phase angles are calculated in relation to a defined reference. An appropriateanalog input channel is selected and used as phase reference. The parameterPhaseAngleRef defines the analog channel that is used as phase angle reference.

The initially connected phase-to-earth voltage is usually chosen as PhaseAngleRef. Aphase-to-phase voltage can also be used in theory, but a 30 degree phase shift betweenthe current and voltage is observed in this case.

If no suitable voltage is available, the initially connected current channel can be used.Although the phase angle difference between the different phases will be firm, thewhole system will appear to rotate when observing the measurement functions.

The phase reference does not work if the current channel is notavailable. For example, when the circuit breaker is opened and no

1MRK 504 134-UEN A Section 4Analog inputs

67Application manual

Page 74: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

current flows. Although the phase angle difference between thedifferent phases is firm, the whole system appears to be rotating whenthe measurement functions are observed.

4.2.2 Relationships between setting parameter Base Current, CTrated primary current and minimum pickup of a protectionIED

Note that for all line protection applications the parameter Base Current (i.e. IBasesetting in the IED) used by the relevant protection function, shall always be set equalto the largest rated CT primary current among all CTs involved in the protectionscheme. The rated CT primary current value is set as parameter CTPrim under the IEDTRM settings.

For all other protection applications (e.g. transformer protection) it is typicallydesirable to set IBase parameter equal to the rated current of the protected object.However this is only recommended to do if the rated current of the protected object iswithin the range of 40% to 120% of the selected CT rated primary current. If for anyreason (e.g. high maximum short circuit current) the rated current of the protectedobject is less than 40% of the rated CT primary current, it is strongly recommended toset the parameter IBase in the IED to be equal to the largest rated CT primary currentamong all CTs involved in the protection scheme and installed on the same voltagelevel. This will effectively make the protection scheme less sensitive; however, suchmeasures are necessary in order to avoid possible problems with loss of themeasurement accuracy in the IED.

Regardless of the applied relationship between the IBase parameter and the rated CTprimary current, the corresponding minimum pickup of the function on the CTsecondary side must always be verified. It is strongly recommended that the minimumpickup of any instantaneous protection function (e.g. differential, restricted earthfault, distance, instantaneous overcurrent, etc.) shall under no circumstances be lessthan 4% of the used IED CT input rating. This corresponds to 40mA secondary formain CTs with 1A rating and to 200mA secondary for main CTs with 5A rating. Thisshall be individually verified for all current inputs involved in the protection scheme.

4.2.3 Setting of current channels

The direction of a current depends on the connection of the CT. Unless indicatedotherwise, the main CTs are supposed to be star connected. The IED can be connectedwith its earthing point towards the object or away from the object. This informationmust be set in the IED via the parameter CTStarPoint, which can be changed betweenFromObject and ToObject. Internally in the IED algorithms and IED functions, theconvention of the directionality is defined as follows:

Section 4 1MRK 504 134-UEN AAnalog inputs

68Application manual

Page 75: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

A positive value of current, power, and so on (forward) means that the quantity has adirection towards the object. - A negative value of current, power, and so on (reverse)means a direction away from the object. See figure 22.

Protected ObjectLine, transformer, etc

ForwardReverse

Definition of directionfor directional functions

Measured quantity ispositive when flowing

towards the object

e.g. P, Q, I

ReverseForward

Definition of directionfor directional functions

e.g. P, Q, IMeasured quantity ispositive when flowing

towards the object

Set parameterCTStarPoint

Correct Setting is"ToObject"

Set parameterCTStarPoint

Correct Setting is"FromObject" en05000456.vsd

IEC05000456 V1 EN

Figure 22: Internal convention of the directionality in the IED

With correct setting of the primary CT direction, CTStarPoint set to FromObject orToObject, a positive quantity always flows towards the protected object and adirection defined as Forward is always looking towards the protected object. Thefollowing examples show the principle.

4.2.3.1 Example 1

Two IEDs used for protection of two objects.

1MRK 504 134-UEN A Section 4Analog inputs

69Application manual

Page 76: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Transformerprotection

TransformerLine

Line

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

ForwardReverse

Definition of direction for directional functions

Line protection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

Setting of current input:Set parameter

CTStarPoint withLine as

reference object.Correct setting is

"ToObject"

IEC11000020-2-en.vsd

IsIs

Ip Ip Ip

IED IED

IEC11000020 V2 EN

Figure 23: Example how to set CTStarPoint parameters in the IED

The figure 23 shows the most common case where the objects have their own CTs. Forthe transformer protection, the protected object is the transformer. Therefore bothCTStarPoint directions should be set ToObject. For the line protection, the protectedobject is the line. The line CT is earthed towards the busbar, therefore the CTStarPointshould be set FromObject.

4.2.3.2 Example 2

Two IEDs used for protection of two objects and sharing a CT.

Section 4 1MRK 504 134-UEN AAnalog inputs

70Application manual

Page 77: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Transformerprotection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"ToObject"

ForwardReverse

Definition of direction for directional

functions

Line protection

Setting of current input:Set parameter

CTStarPoint with Transformer as

reference object.Correct setting is

"FromObject"

Setting of current input:Set parameter

CTStarPoint withLine as

reference object.Correct setting is

"ToObject"

IED IED

IEC11000021_1_en.vsdIEC11000021 V2 EN

Figure 24: Example how to set CTStarPoint parameters in the IED

This example is similar to example 1, but the power transformer is feeding just oneline; both line protection IED and transformer protection IED use the same CT. TheCT direction is set with different reference objects for the two IEDs though it is thesame current from the same CT that is feeding the two IEDs. With these settings thedirectional functions of the line protection shall be set to Forward to look towards theline.

4.2.3.3 Examples on how to connect, configure and set CT inputs for mostcommonly used CT connections

Figure 25 defines the marking of current transformer terminals commonly usedaround the world:

In the SMAI function block, you have to set if the SMAI block ismeasuring current or voltage. This is done with the parameter:AnalogInputType: Current/voltage. The ConnectionType: phase -phase/phase-earth and GlobalBaseSel.

1MRK 504 134-UEN A Section 4Analog inputs

71Application manual

Page 78: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

ISec

I Pri

S1 (X1)

P1(H1)

P2(H2)

S2 (X2)

P2(H2)

P1(H1)

x x

a) b) c)

en06000641.vsd

S2 (X2) S1 (X1)

IEC06000641 V1 EN

Figure 25: Commonly used markings of CT terminals

Where:

a) is symbol and terminal marking used in this document. Terminals marked with a dot indicates theprimary and secondary winding terminals with the same (that is, positive) polarity

b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that forthese two cases the CT polarity marking is correct!

It shall be noted that depending on national standard and utility practices, the ratedsecondary current of a CT has typically one of the following values:

• 1A• 5A

However in some cases the following rated secondary currents are used as well:

• 2A• 10A

The IED fully supports all of these rated secondary values.

4.2.3.4 Example on how to connect a star connected three-phase CT set to theIED

Figure 26 gives an example about the wiring of a star connected three-phase CT set tothe IED. It gives also an overview of the actions which are needed to make thismeasurement available to the built-in protection and control functions within the IEDas well.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

Section 4 1MRK 504 134-UEN AAnalog inputs

72Application manual

Page 79: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1

IL1

IL2

IL3

L2 L3

Protected Object

CT 600/5Star Connected

IL1

IL2

IL3

IED

IEC13000002-4-en.vsdx

1 2

3

4

SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

5

IN

IEC13000002 V4 EN

Figure 26: Star connected three-phase CT set with star point towards the protected object

Where:

1) The drawing shows how to connect three individual phase currents from a star connectedthree-phase CT set to the three CT inputs of the IED.

2) The current inputs are located in the TRM. It shall be noted that for all these current inputs thefollowing setting values shall be entered for the example shown in figure 26.

• CTprim=600A• CTsec=5A• CTStarPoint=ToObject

Inside the IED only the ratio of the first two parameters is used. The third parameter(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.In other words, currents are already measured towards the protected object.

Table continues on next page

1MRK 504 134-UEN A Section 4Analog inputs

73Application manual

Page 80: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

3) These three connections are the links between the three current inputs and the three inputchannels of the preprocessing function block 4). Depending on the type of functions, whichneed this current information, more than one preprocessing block might be connected inparallel to the same three physical CT inputs.

4) The preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequencequantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For this applicationmost of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required only forIEDs installed in power plants), then the setting parameters DFTReference shall be setaccordingly.Section SMAI in this manual provides information on adaptive frequency tracking for thesignal matrix for analogue inputs (SMAI).

5) AI3P in the SMAI function block is a grouped signal which contains all the data about thephases L1, L2, L3 and neutral quantity; in particular the data about fundamental frequencyphasors, harmonic content and positive sequence, negative and zero sequence quantitiesare available.AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain thefundamental frequency phasors and the harmonic content of the corresponding inputchannels of the preprocessing function block.AIN is the signal which contains the fundamental frequency phasors and the harmoniccontent of the neutral quantity. In this example, GRP2N is not connected so this datda iscalculated by the preprocessing function block on the basis of the inputs GRPL1, GRPL2 andGRPL3. If GRP2N is connected, the data reflects the measured value of GRP2N.

Another alternative is to have the star point of the three-phase CT set as shown infigure below:

Section 4 1MRK 504 134-UEN AAnalog inputs

74Application manual

Page 81: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1IL

1

IL2

IL3

L2 L3

Protected Object

CT 800/1Star Connected

IL1

IL2

IL3

IED

IEC11000026-4-en.vsdx

4 12

3

SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

5

IN

IEC11000026 V4 EN

Figure 27: Star connected three-phase CT set with its star point away from the protected object

In the example in figure 27 case everything is done in a similar way as in the abovedescribed example (figure 26). The only difference is the setting of the parameterCTStarPoint of the used current inputs on the TRM (item 2 in the figure):

• CTprim=600A• CTsec=5A• CTStarPoint=FromObject

Inside the IED only the ratio of the first two parameters is used. The third parameteras set in this example will negate the measured currents in order to ensure that thecurrents are measured towards the protected object within the IED.

4.2.3.5 Example how to connect delta connected three-phase CT set to the IED

Figure 28 gives an example how to connect a delta connected three-phase CT set to theIED. It gives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions in the IED aswell.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

1MRK 504 134-UEN A Section 4Analog inputs

75Application manual

Page 82: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1

IL1

IL2

IL3

L2 L3

Protected Object

IED

CT

600/

5 in

Del

taD

AB

Con

nect

ed

IL1-IL2

IL2-IL3

IL3-IL1

1 2

3

4

IEC11000027-2-en.vsd

SMAI_20

IEC11000027 V2 EN

Figure 28: Delta DAB connected three-phase CT set

Section 4 1MRK 504 134-UEN AAnalog inputs

76Application manual

Page 83: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Where:

1) shows how to connect three individual phase currents from a delta connected three-phaseCT set to three CT inputs of the IED.

2) is the TRM or AIM where these current inputs are located. It shall be noted that for all thesecurrent inputs the following setting values shall be entered.

600 3463

sec 5

primCT A

CT A

= =

=

IECEQUATION2413 V1 EN (Equation 26)

• CTStarPoint=ToObject

3) are three connections, which connect these three current inputs to three input channels of thepreprocessing function block 4). Depending on the type of functions which need this currentinformation, more then one preprocessing block might be connected in parallel to these threeCT inputs.

4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all three input channels• harmonic content for all three input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequencequantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For this applicationmost of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required only forIEDs installed in the generating stations) then the setting parameters DFTReference shall beset accordingly.

Another alternative is to have the delta connected CT set as shown in figure 29:

1MRK 504 134-UEN A Section 4Analog inputs

77Application manual

Page 84: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1

IL1

IL2

IL3

L2 L3

Protected Object

IED

CT

800/

1 in

Del

taD

CA

Con

nect

ed

IL3-IL2

IL2-IL1

IL1-IL3

2

3

4

IEC11000028-2-en.vsd

SMAI_20

IEC11000028 V2 EN

Figure 29: Delta DAC connected three-phase CT set

In this case, everything is done in a similar way as in the above described example,except that for all used current inputs on the TRM the following setting parametersshall be entered:

sec

800 4623

1

primCT A

CT A

= =

=IECEQUATION2414 V1 EN (Equation 27)

• CTStarPoint=ToObject

4.2.3.6 Example how to connect single-phase CT to the IED

Figure 30 gives an example how to connect the single-phase CT to the IED. It givesan overview of the required actions by the user in order to make this measurementavailable to the built-in protection and control functions within the IED as well.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

Section 4 1MRK 504 134-UEN AAnalog inputs

78Application manual

Page 85: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Protected Object

L1 L2 L3

IED IN

P

INS

INS

2

IEC11000029-4-en.vsdx

4

3

CT

10

00

/1

a)

b)

(+)

(+)

(-)

(-)(+)

(-)

1 SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

IEC11000029 V4 EN

Figure 30: Connections for single-phase CT input

Where:

1) shows how to connect single-phase CT input in the IED.

2) is TRM where these current inputs are located. It shall be noted that for all these currentinputs the following setting values shall be entered.For connection (a) shown in figure 30:CTprim = 1000 ACTsec = 1ACTStarPoint=ToObject For connection (b) shown in figure 30:CTprim = 1000 ACTsec = 1ACTStarPoint=FromObject

3) shows the connection made in SMT tool, which connect this CT input to the fourth inputchannel of the preprocessing function block 4).

4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate values. The calculated values are then available for all built-in protection andcontrol functions within the IED, which are connected to this preprocessing function block.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the power plants) then the setting parameters DFTReference shall beset accordingly.

1MRK 504 134-UEN A Section 4Analog inputs

79Application manual

Page 86: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

4.2.4 Setting of voltage channels

As the IED uses primary system quantities the main VT ratios must be known to theIED. This is done by setting the two parameters VTsec and VTprim for each voltagechannel. The phase-to-phase value can be used even if each channel is connected to aphase-to-earth voltage from the VT.

4.2.4.1 Example

Consider a VT with the following data:

132 1103 3kV V

EQUATION2016 V1 EN (Equation 28)

The following setting should be used: VTprim=132 (value in kV) VTsec=110 (valuein V)

4.2.4.2 Examples how to connect, configure and set VT inputs for mostcommonly used VT connections

Figure 31 defines the marking of voltage transformer terminals commonly usedaround the world.

A(H1)

B(H2)

b(X2)

a(X1)

A(H1)

N(H2)

n(X2)

a(X1)

b) c)

A(H1)

N(H2)

dn(X2)

da(X1)

d)

UPri

+ +USec

a)

en06000591.vsd

IEC06000591 V1 EN

Figure 31: Commonly used markings of VT terminals

Where:

a) is the symbol and terminal marking used in this document. Terminals marked with a dotindicate the primary and secondary winding terminals with the same (positive) polarity

b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-earth connected VTs

c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open deltaconnected VTs

d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-phase connected VTs

Section 4 1MRK 504 134-UEN AAnalog inputs

80Application manual

Page 87: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

It shall be noted that depending on national standard and utility practices the ratedsecondary voltage of a VT has typically one of the following values:

• 100 V• 110 V• 115 V• 120 V• 230 V

The IED fully supports all of these values and most of them will be shown in thefollowing examples.

4.2.4.3 Examples on how to connect a three phase-to-earth connected VT tothe IED

Figure 32 gives an example on how to connect a three phase-to-earth connected VT tothe IED. It as well gives overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IED.

For correct terminal designations, see the connection diagrams validfor the delivered IED.

1MRK 504 134-UEN A Section 4Analog inputs

81Application manual

Page 88: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1

IED L2

L3

66

3110

3

kV

V

1

3

2

66

3110

3

kV

V

66

3110

3

kV

V

.

#Not used

5

IEC06000599-4-en.vsdx

4

SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

IEC06000599 V4 EN

Figure 32: A Three phase-to-earth connected VT

Where:

1) shows how to connect three secondary phase-to-earth voltages to three VT inputs on theIED

2) is the TRM where these three voltage inputs are located. For these three voltage inputs,the following setting values shall be entered:VTprim =66 kVVTsec = 110 VInside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of one individual VT.

6666 3

1101103

=

EQUATION1903 V1 EN (Equation 29)

Table continues on next page

Section 4 1MRK 504 134-UEN AAnalog inputs

82Application manual

Page 89: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

3) are three connections made in Signal Matrix Tool (SMT), which connect these threevoltage inputs to first three input channels of the preprocessing function block 5).Depending on the type of functions which need this voltage information, more then onepreprocessing block might be connected in parallel to these three VT inputs.

4) shows that in this example the fourth (that is, residual) input channel of the preprocessingblock is not connected in SMT tool. Thus the preprocessing block will automaticallycalculate 3Uo inside by vectorial sum from the three phase to earth voltages connected tothe first three input channels of the same preprocessing block. .

4) is a Preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference forsequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left to thedefault values. However the following settings shall be set as shown here:UBase=66 kV (that is, rated Ph-Ph voltage)If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReferenceshall be set accordingly.

4.2.4.4 Example on how to connect a phase-to-phase connected VT to the IED

Figure 33 gives an example how to connect a phase-to-phase connected VT to theIED. It gives an overview of the required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IEDas well. It shall be noted that this VT connection is only used on lower voltage levels(that is, rated primary voltage below 40 kV).

For correct terminal designations, see the connection diagrams validfor the delivered IED.

1MRK 504 134-UEN A Section 4Analog inputs

83Application manual

Page 90: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

L1

IED

L2

L3

1

2 3

4

13.8120

kVV

IEC11000032-1-en.vsd

SMAI_20

IEC11000032 V1 EN

Figure 33: A Phase-to-phase connected VT

Where:

1) shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on the IED

2) is the TRM or AIM where this voltage input is located. The following setting values shall beentered:VTprim=13.8 kVVTsec=120 V

3) are three connections, which connects these three voltage inputs to three input channels ofthe preprocessing function block 4). Depending on the type of functions, which need thisvoltage information, more than one preprocessing block might be connected in parallel tothese three VT inputs

4) Preprocessing block has a task to digitally filter the connected analog inputs and calculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequencequantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block. For this applicationmost of the preprocessing settings can be left to the default values. However the followingsettings shall be set as shown here:ConnectionType=Ph-PhUBase=13.8 kVIf frequency tracking and compensation is required (this feature is typically required only forIEDs installed in the generating stations) then the setting parameters DFTReference shall beset accordingly.

Section 4 1MRK 504 134-UEN AAnalog inputs

84Application manual

Page 91: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

4.2.4.5 Example how to connect the open delta VT to the IED for lowimpedance earthed or solidly earthed power systems

Figure 34 gives an example about the connection of an open delta VT to the IED forlow impedance earthed or solidly earthed power systems. It shall be noted that thistype of VT connection presents secondary voltage proportional to 3U0 to the IED.

In case of a solid earth fault close to the VT location the primary value of 3Uo will beequal to:

33

Ph PhPh E

UUo U-

-= =

EQUATION1926 V1 EN (Equation 30)

The primary rated voltage of such VT is always equal to UPh-E Therefore, three seriesconnected VT secondary windings will give the secondary voltage equal only to oneindividual VT secondary winding rating. Thus the secondary windings of such opendelta VTs quite often has a secondary rated voltage close to rated phase-to-phase VTsecondary voltage, that is, 115V or 115/√3V as in this particular example. Figure 34gives an overview of the actions which are needed to make this measurement availableto the built-in protection and control functions within the IED.

1

L1

IED L2

L3

138

3115

3

kV

V

+3Uo

138

3115

3

kV

V

138

3115

3

kV

V

IEC06000602-4-en.vsdx

# Not Used

# Not Used

# Not Used

SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

2

3

4

5

IEC06000602 V4 EN

Figure 34: Open delta connected VT in low impedance or solidly earthed power system

1MRK 504 134-UEN A Section 4Analog inputs

85Application manual

Page 92: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Where:

1) shows how to connect the secondary side of open delta VT to one VT input in the IED.

+3Uo shall be connected to the IED.

2) is TRM where this voltage input is located. It shall be noted that for this voltage input thefollowing setting values shall be entered:

1383 138

3VTprim kV= × =

EQUATION1928 V1 EN (Equation 31)

115sec 3 115

3VT V= × =

EQUATION1929 V1 EN (Equation 32)

Inside the IED, only the ratio of these two parameters is used. It shall be noted that theratio of the entered values exactly corresponds to ratio of one individual open delta VT.

138138 3

1151153

=

EQUATION1930 V1 EN (Equation 33)

4) shows the connection made in Signal Matrix Tool (SMT), which connect this voltageinput to the fourth input channel of the preprocessing function block 4).

5) preprocessing block has a task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental

frequency phasors for the first three input channels (channel one taken asreference for sequence quantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in theconfiguration tool. For this application most of the preprocessing settings can be left tothe default values.If frequency tracking and compensation is required (this feature is typically required onlyfor IEDs installed in the generating stations) then the setting parameters DFTReferenceshall be set accordingly.

4.2.4.6 Example on how to connect a neutral point VT to the IED

Figure 35 gives an example on how to connect a neutral point VT to the IED. This typeof VT connection presents secondary voltage proportional to U0 to the IED.

Section 4 1MRK 504 134-UEN AAnalog inputs

86Application manual

Page 93: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

In case of a solid earth fault in high impedance earthed or unearthed systems theprimary value of Uo voltage will be equal to:

03

Ph PhPh E

UU U--= =

EQUATION1931 V2 EN (Equation 34)

Figure 35 gives an overview of required actions by the user in order to make thismeasurement available to the built-in protection and control functions within the IEDas well.

L1 L2 L3

IED

6.6

3100

kV

V

RUo

IEC06000603-4-en.vsdx

# Not Used

# Not Used

# Not Used

Protected Object

SMAI2

BLOCK

REVROT

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

AI3P

AI1

AI2

AI3

AI4

AIN

1

2

3

4

5

IEC06000603 V4 EN

Figure 35: Neutral point connected VT

1MRK 504 134-UEN A Section 4Analog inputs

87Application manual

Page 94: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Where:

1) shows how to connect the secondary side of neutral point VT to one VT input in the IED.

U0 shall be connected to the IED.

2) is the TRM or AIM where this voltage input is located. For this voltage input the followingsetting values shall be entered:

6.63.81

3VTprim kV= =

EQUATION1933 V1 EN (Equation 35)

sec 100VT V=

EQUATION1934 V1 EN (Equation 36)

Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratioof the entered values exactly corresponds to ratio of the neutral point VT.

3) shows that in this example the first three input channel of the preprocessing block is notconnected in SMT tool.

4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool(ACT), which connects this voltage input to the fourth input channel of the preprocessingfunction block 5).

5) is a preprocessing block that has the task to digitally filter the connected analog inputs andcalculate:

• fundamental frequency phasors for all four input channels• harmonic content for all four input channels• positive, negative and zero sequence quantities by using the fundamental frequency

phasors for the first three input channels (channel one taken as reference for sequencequantities)

These calculated values are then available for all built-in protection and control functionswithin the IED, which are connected to this preprocessing function block in the configurationtool. For this application most of the preprocessing settings can be left to the default values.If frequency tracking and compensation is required (this feature is typically required only forIEDs installed in the generating stations) then the setting parameters DFTReference shall beset accordingly.

Section 4 1MRK 504 134-UEN AAnalog inputs

88Application manual

Page 95: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 5 Local human-machine interface

5.1 Local HMI

IEC12000175 V1 EN

Figure 36: Local human-machine interface

The LHMI of the IED contains the following elements:

• Display (LCD)• Buttons• LED indicators• Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

5.1.1 Display

The LHMI includes a graphical monochrome display with a resolution of 320 x 240pixels. The character size can vary. The amount of characters and rows fitting the viewdepends on the character size and the view that is shown.

The display view is divided into four basic areas.

1MRK 504 134-UEN A Section 5Local human-machine interface

89Application manual

Page 96: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC13000063-1-en.vsd

IEC13000063 V1 EN

Figure 37: Display layout

1 Path

2 Content

3 Status

4 Scroll bar (appears when needed)

The function button panel shows on request what actions are possible with thefunction buttons. Each function button has a LED indication that can be used as afeedback signal for the function button control action. The LED is connected to therequired signal with PCM600.

IEC12000025-2-en.vsd

IEC12000025 V2 EN

Figure 38: Function button panel

Section 5 1MRK 504 134-UEN ALocal human-machine interface

90Application manual

Page 97: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The alarm LED panel shows on request the alarm text labels for the alarm LEDs. Threealarm LED pages are available.

GUID-D20BB1F1-FDF7-49AD-9980-F91A38B2107D V1 EN

Figure 39: Alarm LED panel

The function button and alarm LED panels are not visible at the same time. Each panelis shown by pressing one of the function buttons or the Multipage button. Pressing theESC button clears the panel from the display. Both the panels have dynamic width thatdepends on the label string length that the panel contains.

5.1.2 LEDs

The LHMI includes three protection status LEDs above the display: Ready, Start andTrip.

There are 15 programmable alarm LEDs on the front of the LHMI. Each LED canindicate three states with the colors: green, yellow and red. The alarm texts related toeach three-color LED are divided into three pages.

There are 3 separate pages of LEDs available. The 15 physical three-color LEDs inone LED group can indicate 45 different signals. Altogether, 135 signals can beindicated since there are three LED groups. The LEDs can be configured withPCM600 and the operation mode can be selected with the LHMI or PCM600.

5.1.3 Keypad

The LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured either asmenu shortcut or control buttons.

1MRK 504 134-UEN A Section 5Local human-machine interface

91Application manual

Page 98: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC11000247 V2 EN

Figure 40: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

1...5 Function button

6 Close

7 Open

8 Escape

9 Left

10 Down

11 Up

12 Right

13 User Log on

14 Enter

15 Remote/Local

16 Uplink LED

17 Ethernet communication port (RJ-45)

18 Multipage

19 Menu

20 Clear

21 Help

22 Programmable alarm LEDs

23 Protection status LEDs

5.1.4 Local HMI functionality

5.1.4.1 Protection and alarm indication

Protection indicatorsThe protection indicator LEDs are Ready, Start and Trip.

Section 5 1MRK 504 134-UEN ALocal human-machine interface

92Application manual

Page 99: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The start and trip LEDs are configured via the disturbance recorder.The yellow and red status LEDs are configured in the disturbancerecorder function, DRPRDRE, by connecting a start or trip signalfrom the actual function to a BxRBDR binary input function blockusing the PCM600 and configure the setting to Off, Start or Trip forthat particular signal.

Table 8: Ready LED (green)

LED state DescriptionOff Auxiliary supply voltage is disconnected.

On Normal operation.

Flashing Internal fault has occurred.

Table 9: Start LED (yellow)

LED state DescriptionOff Normal operation.

On A protection function has started and an indication message is displayed.

• The start indication is latching and must be reset via communication orby pressing .

Flashing A flashing yellow LED has a higher priority than a steady yellow LED.The IED is in test mode and protection functions are blocked.

• The indication disappears when the IED is no longer in test mode andblocking is removed.

Table 10: Trip LED (red)

LED state DescriptionOff Normal operation.

On A protection function has tripped and an indication message is displayed.

• The trip indication is latching and must be reset via communication orby pressing .

Alarm indicatorsThe 15 programmable three-color LEDs are used for alarm indication. An individualalarm/status signal, connected to any of the LED function blocks, can be assigned toone of the three LED colors when configuring the IED.

1MRK 504 134-UEN A Section 5Local human-machine interface

93Application manual

Page 100: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 11: Alarm indications

LED state DescriptionOff Normal operation. All activation signals are off.

On • Follow-S sequence: The activation signal is on.• LatchedColl-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedAck-F-S sequence: The indication has been acknowledged, but the

activation signal is still on.• LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedReset-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.

Flashing • Follow-F sequence: The activation signal is on.• LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication

has not been acknowledged.• LatchedAck-S-F sequence: The indication has been acknowledged, but the

activation signal is still on.

5.1.4.2 Parameter management

The LHMI is used to access the IED parameters. Three types of parameters can be readand written.

• Numerical values• String values• Enumerated values

Numerical values are presented either in integer or in decimal format with minimumand maximum values. Character strings can be edited character by character.Enumerated values have a predefined set of selectable values.

5.1.4.3 Front communication

The RJ-45 port in the LHMI enables front communication.

• The green uplink LED on the left is lit when the cable is successfully connectedto the port.

Section 5 1MRK 504 134-UEN ALocal human-machine interface

94Application manual

Page 101: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

GUID-D71BA06D-3769-4ACB-8A32-5D02EA473326 V1 EN

Figure 41: RJ-45 communication port and green indicator LED

1 RJ-45 connector

2 Green indicator LED

When a computer is connected to the IED front port with a crossed-over cable, theIED's DHCP server for the front interface assigns an IP address to the computer ifDHCPServer = On. The default IP address for the front port is 10.1.150.3.

Do not connect the IED front port to a LAN. Connect only a singlelocal PC with PCM600 to the front port.

1MRK 504 134-UEN A Section 5Local human-machine interface

95Application manual

Page 102: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

96

Page 103: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 6 Differential protection

6.1 Transformer differential protection T2WPDIF andT3WPDIF

6.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Transformer differential protection, two-winding

T2WPDIF

3Id/I

SYMBOL-BB V1 EN

87T

Transformer differential protection,three-winding

T3WPDIF

3Id/I

SYMBOL-BB V1 EN

87T

6.1.2 Application

The transformer differential protection is a unit protection. It serves as the mainprotection of transformers in case of winding failure. The protective zone of adifferential protection includes everything between the connected CTs. This includesthe transformer and may include the bus-works or cables and also the generator statorwindings when implemented as a block scheme.

A transformer differential protection compares the current flowing into thetransformer with the current leaving the transformer. A correct analysis of faultconditions by the differential protection must take into consideration changes due tothe voltage, current and phase angle transformation caused by the protectedtransformer. Traditional transformer differential protection functions requiredauxiliary transformers for correction of the phase shift and transformation ratio. Thenumerical microprocessor based differential algorithm as implemented in theRET670 compensates for both the turns-ratio and the phase shift internally in thesoftware. No auxiliary current transformers are necessary.

The differential current should theoretically be zero during normal load or duringexternal faults if the turn-ratio and the phase shift are correctly compensated for.However, there are several different phenomena other than internal faults that will

1MRK 504 134-UEN A Section 6Differential protection

97Application manual

Page 104: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

cause result in unwanted and false differential currents. The main reasons forunwanted differential currents are:

• mismatch due to varying tap changer positions• different characteristics, loads and operating conditions of the current

transformers• zero sequence currents that only flow on one side of the power transformer• normal magnetizing currents• magnetizing inrush currents• overexcitation magnetizing currents

6.1.3 Setting guidelines

The parameters for the Transformer differential protection function are set via thelocal HMI or Protection and Control IED Manager (PCM600).

IED values for the primary current (setting IBase), the primary voltage (settingUBase) and the primary power (setting SBase) for a particular winding are set as aglobal base value GBASVAL. The settings GlobalBaseSelW1, GlobalBaseSelW2 andGlobalBaseSelW3 in the differential protection function are used to select thecorresponding GBASVAL function as a reference.

6.1.3.1 Inrush restraint methods

With a combination of the second harmonic restraint and the waveform restraintmethods it is possibly to create a protection with high security and stability againsttransformer inrush effects and at the same time maintain stability in case of heavyexternal faults, even if the current transformers are saturated. The second harmonicrestraint function has a settable level. If the ratio of the second harmonic tofundamental harmonic content in the differential current is above the settable limit, theoperation of the differential protection is restrained. It is recommended to keep theparameter I2/I1Ratio = 15% as the default value in case no special reasons exist tochoose a different value.

6.1.3.2 Overexcitation restraint method

In case of an overexcited transformer, the winding currents contain odd harmoniccomponents because the currents waveform are symmetrical relative to the time axis.As the third harmonic currents cannot flow into a delta winding, the fifth harmonic isthe lowest harmonic which can serve as a criterion for overexcitation. The differentialprotection function is provided with a fifth harmonic restraint to prevent the protectionfrom operation during an overexcitation condition of a power transformer. If the ratioof the fifth harmonic to fundamental harmonic in the differential current is above asettable limit the operation is restrained. It is recommended to use I5/I1Ratio = 25%as default value in case no special reasons exist to choose another setting.Transformers likely to be exposed to overvoltage or underfrequency conditions (thatis, generator step-up transformers in power stations) should be provided with an

Section 6 1MRK 504 134-UEN ADifferential protection

98Application manual

Page 105: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

overexcitation protection based on V/Hz to achieve a trip before the core thermal limitis reached.

6.1.3.3 Cross-blocking between phases

The basic definition of cross-blocking is that one of the three phases can blockoperation (that is, tripping) of the other two phases due to the harmonic pollution (2ndor 5th harmonic content) or waveform characteristic of the differential current in thatphase; the user can control the cross-blocking between the phases via the settingparameter CrossBlockEn.

When the parameter CrossBlockEn is set to On, cross blocking between phases will beintroduced. The phase with the operating point above the set bias characteristic will beable to cross-block the other two phases if it is self-blocked by any of the previouslyexplained restrain criteria. As soon as the operating point for this phase is below theset bias characteristic, cross blocking from that phase will be inhibited. The default(recommended) setting value for this parameter is On. When parameterCrossBlockEn is set to Off, any cross blocking between phases will be disabled.

6.1.3.4 Restrained and unrestrained differential protection

The first section of the restrain characteristic gives the highest sensitivity and is usedto determine small or high impedance fault within the protected zone.

The second section of the restrain characteristic has an increased slope in order to dealwith increased differential current due to additional power transformer losses duringheavy loading of the transformer and external fault currents. The third section of therestrain characteristic decreases the sensitivity of the restrained differential functionfurther in order to cope with CT saturation and transformer losses during heavythrough faults. A default setting for the operating characteristic with IdMin = 0.3 *IBase is recommended in normal applications. If the conditions are known in moredetail, higher or lower sensitivity can be chosen. The selection of suitablecharacteristic should in such cases be based on the knowledge of the class of thecurrent transformers, availability of information on the tap changer position, shortcircuit power of the systems, and so on.

The unrestrained operation level has a default value of IdUnre = 10pu, which istypically acceptable for most of the standard power transformer applications. In thefollowing case, this setting need to be changed accordingly:

• For differential applications on HV shunt reactors, due to the fact that there is noheavy through-fault condition, the unrestrained differential operation level canbe set to IdUnre = 1.75pu for additional security

The overall operating characteristic of the transformer differential protection is shownin figure 42.

1MRK 504 134-UEN A Section 6Differential protection

99Application manual

Page 106: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1

Operate conditionally

UnrestrainedLimit

Section 2 Section 3

Restrain

Operate unconditionally

5

4

3

2

1

00 1 2 3 4 5

IdMin

EndSection1

EndSection2restrain current[ times IBase ]

operate current[ times IBase ]

SlopeSection2

SlopeSection3

en05000187-2.vsdIEC05000187 V2 EN

Figure 42: Representation of the restrained-, and the unrestrained operatecharacteristics

100%Ioperateslope IrestrainD= D ×

EQUATION1246 V1 EN (Equation 37)

and where the restrained characteristic is defined by the settings:

1. IdMin

2. EndSection1

3. EndSection2

4. SlopeSection2

5. SlopeSection3

6.1.3.5 Elimination of zero sequence currents

A differential protection may operate unwanted due to external earth-faults in caseswhere the zero sequence current can flow on only one side of the power transformer.This is the case when zero sequence current cannot be properly transformed to theother side of the power transformer. Power transformer connection groups of the Yd

Section 6 1MRK 504 134-UEN ADifferential protection

100Application manual

Page 107: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

or Dy type cannot transform zero sequence current. If a delta winding of a powertransformer is earthed via an earthing transformer inside the zone protected by thedifferential protection there will be an unwanted differential current in case of anexternal earth-fault. The same is true for an earthed star winding. Even if both the starand delta winding are earthed, the zero sequence current is usually limited by theearthing transformer on the delta side of the power transformer, which may result indifferential current as well. To make the overall differential protection insensitive toexternal earth-faults in these situations the zero sequence currents must be eliminatedfrom the power transformer IED currents on the earthed windings, so that they do notappear as differential currents. The elimination of zero sequence current is donenumerically by setting ZSCurrSubtrWx=Off or On and doesn't require no auxiliarytransformers or zero sequence traps.

6.1.3.6 Internal/External fault discriminator

The internal/external fault discriminator operation is based on the relative position ofthe two phasors (in case of a two-winding transformer) representing the W1 and W2negative sequence current contributions. It performs a directional comparisonbetween these two phasors.

In order to perform a directional comparison of the two phasors their magnitudes mustbe high enough so that one can be sure that they are due to a fault. On the other hand,in order to guarantee a good sensitivity of the internal/external fault discriminator, thevalue of this minimum limit must not be too high. Therefore this limit value(IMinNegSeq) is settable in the range from 1% to 20% of the respective windingcurrent. The default value is 4%. Only if the magnitude of both negative sequencecurrent contributions are above the set limit, the relative position between these twophasors is checked. If either of the negative sequence current contributions is too small(less than the set value for IMinNegSeq), no directional comparison is made in orderto avoid the possibility to produce a wrong decision.

This magnitude check, guarantees stability of the algorithm when the powertransformer is energized, since no current will be measured on the low voltage side ofthe power transformer. In cases where the protected transformer can be energized witha load connected on the LV side (e.g. a step-up transformer in a power station withdirectly connected auxiliary transformer on its LV side) the value for this setting shallbe increased to at least 12%. This is necessary in order to prevent unwanted operationdue to LV side currents during the transformer energization.

The setting NegSeqROA represents the so-called Relay Operate Angle, whichdetermines the boundary between the internal and external fault regions. It can beselected in the range from 30 degrees to 90 degrees, with a step of 1 degree. The defaultvalue is 60 degrees. The default setting 60 degrees somewhat favors security incomparison to dependability. If the user has no well-justified reason for another value,60 degrees shall be applied.

If the above conditions concerning magnitudes are fulfilled, the internal/external faultdiscriminator compares the relative phase angle between the negative sequencecurrent contributions from the HV side and LV side of the power transformer using the

1MRK 504 134-UEN A Section 6Differential protection

101Application manual

Page 108: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

following two rules (assuming both CT's have their earthing point connected towardsthe object):

• If the negative sequence currents contributions from HV and LV sides are inphase or at least in the internal fault region, the fault is internal.

• If the negative sequence currents contributions from HV and LV sides are 180degrees out of phase or at least in the external fault region, the fault is external.

Under external fault condition and with no current transformer saturation, the relativeangle is theoretically equal to 180 degrees. During internal fault and with no currenttransformer saturation, the angle shall ideally be 0 degrees, but due to possibledifferent negative sequence source impedance angles on HV and LV side of powertransformer, it may differ somewhat from the ideal zero value.

The internal/external fault discriminator has proved to be very reliable. If a fault isdetected, and at the same time the internal/external fault discriminator characterizesthis fault as an internal, any eventual blocking signals produced by either the harmonicor the waveform restraints are ignored.

If the bias current is more than 110% of IBase, the negative sequence threshold(IMinNegSeq) is increased linearly to desensitize the internal/external faultdiscriminator during through faults and CT saturation, which will create falsenegative sequence currents. This assures response times of the differential protectionbelow one power system cycle (below 20 ms for 50 Hz system) for all more severeinternal faults. Even for heavy internal faults with severely saturated currenttransformers the internal/external fault discriminator will make the differentialprotection operate well below one cycle, since the harmonic distortions in thedifferential currents do not slow down the differential protection operation.

The sensitive negative sequence current based differential protection, which detectsminor internal faults, and where the speed is not as essential as stability againstunwanted trips, is restrained when the bias current is more than 150% of IBase. For thesensitive negative sequence protection to be reactivated, the bias current must dropback below 110% of IBase. The sensitive negative sequence protection is alwaysrestrained by the harmonic restraint.

External faults happen ten to hundred times more often than internal ones as far as thepower transformers are concerned. If a disturbance is detected and the internal/external fault discriminator characterizes this fault as an external fault, theconventional additional criteria (2nd harmonic, 5th harmonic, waveform block) areposed on the differential algorithm before its trip is allowed. This assures high stabilityduring external faults. However, at the same time the differential function is stillcapable of trip ping quickly for evolving faults.

The principle of the internal/external fault discriminator can be extended toautotransformers and transformers with three windings. If all three windings areconnected to their respective networks then three directional comparisons are made,but only two comparisons are necessary in order to positively determine the positionof the fault with respect to the protected zone. The directional comparisons are: W1 -

Section 6 1MRK 504 134-UEN ADifferential protection

102Application manual

Page 109: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

(W2 + W3); W2 - (W1 + W3); W3 - (W1 + W2). The rule applied by the internal/external fault discriminator in case of three-winding power transformers is:

• If all comparisons indicate an internal fault, then it is an internal fault.• If any comparison indicates an external fault, then it is an external fault

If one of the windings is not connected, the algorithm automatically reduces to thetwo-winding version. Nevertheless, the whole power transformer is protected,including the non-connected winding.

6.1.3.7 Differential current alarm

Differential protection continuously monitors the level of the fundamental frequencydifferential currents and gives an alarm if the pre-set value is simultaneously exceededin all three phases. Set the time delay defined by parameter tAlarmDelay two timeslonger than the on-load tap-changer mechanical operating time (For example, typicalsetting value 10s).

6.1.3.8 Switch onto fault feature

The Transformer differential (TW2PDIF for two winding and TW3PDIF for threewinding) function in the IED has a built-in, advanced switch onto fault feature. Thisfeature can be enabled or disabled by the setting parameter SOTFMode. WhenSOTFMode = On this feature is enabled. It shall be noted that when this feature isenabled it is not possible to test the 2nd harmonic blocking feature by simply injectingone current with superimposed second harmonic. In that case the switch on to faultfeature will operate and the differential protection will trip. However for a real inrushcase the differential protection function will properly restrain from operation.

For more information about the operating principles of the switch onto fault featureplease read the “Technical Manual”..

6.1.4 Setting example

6.1.4.1 CT Connections

The IED has been designed with the assumption that all main CTS are star connected.The IED can be used in applications where the main CTs are delta connected. For suchapplications the following shall be kept in mind:

1. The ratio for delta connected CTs shall be set √(3)=1.732 times smaller than theactual individual phase CT ratio.

2. The power transformer vector group shall typically be set as Yy0 because thecompensation for the actual phase shift is provided by the external delta CTconnection.

3. The zero sequence current is eliminated by the main CT delta connections. Thuson sides where CTs are connected in delta the zero sequence current eliminationshall be set to Off in the IED.

1MRK 504 134-UEN A Section 6Differential protection

103Application manual

Page 110: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The following table summarizes the most commonly used star-delta vector groupsaround the world and provides information about the required type of main CT deltaconnection on the star side of the protected transformer.

IEC vector group Positive sequence no-loadvoltage phasor diagram

Required delta CT connection type on star side ofthe protected power transformer and internalvector group setting in the IED

YNd1Y

IEC06000559 V1 EN

Yy0

Dyn1

Y

IEC06000560 V1 EN

Yy0

YNd11Y

IEC06000561 V1 EN

Yy0

Dyn11

Y

IEC06000562 V1 EN

Yy0

YNd5 Y

IEC06000563 V1 EN

Yy6

Dyn5

YIEC06000564 V1 EN

Yy6

Section 6 1MRK 504 134-UEN ADifferential protection

104Application manual

Page 111: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

6.2 Restricted earth-fault protection, low impedanceREFPDIF

6.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Restricted earth-fault protection, lowimpedance

REFPDIF

IdN/I

SYMBOL-AA V1 EN

87N

6.2.2 Application

A breakdown of the insulation between a transformer winding and the core or the tankmay result in a large fault current which causes severe damage to the windings and thetransformer core. A high gas pressure may develop, damaging the transformer tank.

Fast and sensitive detection of earth faults in a power transformer winding can beobtained in solidly earthed or low impedance earthed networks by the restricted earth-fault protection. The only requirement is that the power transformer winding isconnected to earth in the star point (in case of star-connected windings) or through aseparate earthing transformer (in case of delta-connected windings).

The low impedance restricted earth-fault protection REFPDIF is a winding protectionfunction. It protects the power transformer winding against faults involving earth.Observe that single phase-to-earth faults are the most common fault types intransformers. A sensitive earth-fault protection is therefore desirable.

A restricted earth-fault protection is the fastest and the most sensitive protection, apower transformer winding can have and will detect faults such as:

• earth faults in the transformer winding when the network is earthed through animpedance

• earth faults in the transformer winding in solidly earthed network when the pointof the fault is close to the winding star point.

The restricted earth-fault protection is not affected, as a differential protection, withthe following power transformer related phenomena:

• magnetizing inrush currents• overexcitation magnetizing currents• load tap changer• external and internal phase faults which do not involve earth• symmetrical overload conditions

1MRK 504 134-UEN A Section 6Differential protection

105Application manual

Page 112: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Due to its features, REFPDIF is often used as a main protection of the transformerwinding for all faults involving earth.

6.2.2.1 Application examples

Transformer winding, solidly earthedThe most common application is on a solidly earthed transformer winding. Theconnection is shown in figure 43.

IEC09000109-4-en.vsd

REFDIF

I3PW1CT1

I3P

IdN/I

Protected winding

IEC09000109-4-EN V1 EN

Figure 43: Connection of the low impedance Restricted earth-fault functionREFPDIF for a directly (solidly) earthed transformer winding

Transformer winding, earthed through zig-zag earthing transformerA common application is for low reactance earthed transformer where the earthing isthrough separate zig-zag earthing transformers. The fault current is then limited totypical 800 to 2000 A for each transformer. The connection for this application isshown in figure 44.

Section 6 1MRK 504 134-UEN ADifferential protection

106Application manual

Page 113: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

REFDIF - 1

I3PW1CT1

I3P

IdN/I

Protectedwinding W1

I3PW2CT1

I3P

IdN/I

REFDIF - 2

Protected winding W2

Earthingtransformer

IEC09000110-4-en.vsd

IEC09000110-4-EN V1 EN

Figure 44: Connection of the low impedance Restricted earth-fault functionREFPDIF for a zig-zag earthing transformer

Autotransformer winding, solidly earthedAutotransformers can be protected with the low impedance restricted earth-faultprotection function REFPDIF. The complete transformer will then be protectedincluding the HV side, the neutral connection and the LV side. The connection ofREFPDIF for this application is shown in figure 45.

1MRK 504 134-UEN A Section 6Differential protection

107Application manual

Page 114: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000111-4-en.vsd

Auto -transformer

REFDIF

I3PW1CT1

I3P

IdN/I

I3PW2CT1

HV (W1)

LV (W2)

IEC09000111-4-EN V1 EN

Figure 45: Connection of restricted earth fault, low impedance functionREFPDIF for an autotransformer, solidly earthed

Reactor winding, solidly earthedReactors can be protected with the low impedance restricted earth fault protectionfunction REFPDIF. The connection of REFPDIF for this application is shown infigure 46.

Section 6 1MRK 504 134-UEN ADifferential protection

108Application manual

Page 115: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Reactor

REFDIF

I3PW1CT1

I3P

IdN/I

IEC09000112-4-en.vsd

IEC09000112-4 V1 EN

Figure 46: Connection of the low impedance restricted earth-fault protectionfunction REFPDIF for a solidly earthed reactor

CT earthing directionTo make thelow impedance restricted earth-fault protection functionREFPDIFoperate correctly, the main CTs are always supposed to be star connected.The main CT's neutral (star) formation can be positioned in either way, ToObject orFromObject.

6.2.3 Setting guidelines

6.2.3.1 Setting and configuration

Analog input signalsI3P: Neutral point current .

I3PW1CT1: Phase currents for winding 1.

I3PW2CT1: Phase currents for winding 2. Used only for autotransformers.

1MRK 504 134-UEN A Section 6Differential protection

109Application manual

Page 116: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Binary input signalsBLOCK: The input will block the operation of the function. Can be used, for example,to block for a limited time the operation during special service conditions.

Binary output signalsSTART: The start output indicates that Idiff is in the operate region of thecharacteristic. It can be used to initiate disturbance recorder.

TRIP: The trip output is activated when all operating criteria are fulfilled.

DIROK: The output is activated when the directional criteria has been fulfilled. Theoutput can be used for information purposes normally during testing. It can be checkedfrom the debug tool or connected as a signal to the disturbance recorder. Theinformation is also available on the local HMI.

BLK2H: The output is activated when the function is blocked due to a too high levelof second harmonics. The output can be used for information purposes normallyduring testing. It can be checked from the debug tool or connected as a signal to thedisturbance recorder. The information is also available on the local HMI.

6.2.3.2 Settings

The parameters for the low impedance restricted earth fault protection functionREFPDIF are set via the local HMI or through the Protection and Control Manager(PCM600).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: The operation of REFPDIF can be switched On/Off.

IdMin: The setting gives the minimum operation value. The setting is in percent of theIBase value. The neutral current (I3P) must always be larger than half of this value. Anormal setting is 30% of power transformer-winding rated current for the solidlyearthed winding.

6.3 1Ph High impedance differential protection HZPDIF

6.3.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

1Ph High impedance differentialprotection HZPDIF Id

SYMBOL-CC V2 EN

87

Section 6 1MRK 504 134-UEN ADifferential protection

110Application manual

Page 117: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

6.3.2 Application

The 1Ph High impedance differential protection function HZPDIF can be used as arestricted earth fault protection.

Id

IEC05000177-2-en.vsd

IEC05000177 V2 EN

Figure 47: Application of a 1Ph High impedance differential protection HZPDIFfunction

6.3.2.1 The basics of the high impedance principle

The high impedance differential protection principle has been used for many yearsand is well documented in literature publicly available. Its operating principleprovides very good sensitivity and high speed operation. One main benefit offered bythe principle is an absolute stability (that is, no operation) for external faults even inthe presence of heavy CT saturation. The principle is based on the CT secondarycurrent circulating between involved current transformers and not through the IEDdue to high impedance in the measuring branch. This stabilizing resistance is in therange of hundreds of ohms and sometimes above one kilo Ohm. When an internal faultoccurs the current cannot circulate and is forced through the measuring branchcausing relay operation.

It should be remembered that the whole scheme, its built-in components and wiringmust be adequately maintained throughout the lifetime of the equipment in order to beable to withstand the high voltage peaks (that is, pulses) which may appear during aninternal fault. Otherwise any flash-over in CT secondary circuits or any other part ofthe scheme may prevent correct operation of the high impedance differential relay foran actual internal fault.

1MRK 504 134-UEN A Section 6Differential protection

111Application manual

Page 118: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Id

IEC05000164-2-en.vsd

R

Metrosil

IEC05000164 V3 EN

Figure 48: Example for the high impedance restricted earth fault protectionapplication

For a through fault one current transformer might saturate when the other CTs still willfeed current. For such a case a voltage will be developed across the measuring branch.The calculations are made with the worst situations in mind and a minimum operatingvoltage UR is calculated according to equation 38

( )maxUR IF Rct Rl> × +EQUATION1531 V1 EN (Equation 38)

where:

IFmax is the maximum through fault current at the secondary side of the CT

Rct is the current transformer secondary winding resistance and

Rl is the maximum loop resistance of the circuit at any CT.

Section 6 1MRK 504 134-UEN ADifferential protection

112Application manual

Page 119: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The minimum operating voltage has to be calculated (all loops) and the function is sethigher than the highest achieved value (setting U>Trip). As the loop resistance is thevalue to the connection point from each CT, it is advisable to do all the CT coresummations in the switchgear to have shortest possible loops. This will give lowersetting values and also a better balanced scheme. The connection in to the controlroom can then be from the most central bay.

For an internal fault, all involved CTs will try to feed current through the measuringbranch. Depending on the size of current transformer, relatively high voltages will bedeveloped across the series resistor. Note that very high peak voltages can appear. Toprevent the risk of flashover in the circuit, a voltage limiter must be included. Thevoltage limiter is a voltage dependent resistor (Metrosil).

The external unit with stabilizing resistor has a value of either 6800 ohms or 1800ohms (depending on ordered alternative) with a sliding link to allow adjustment to therequired value. Select a suitable value of the resistor based on the UR voltagecalculated. A higher resistance value will give a higher sensitivity and a lower valuea lower sensitivity of the relay.

The function has a recommended operating current range 40 mA to 1.0A for 1 A inputsand 200 mA to 5A for 5A inputs. This, together with the selected and set value, is usedto calculate the required value of current at the set U>Trip and SeriesResitor values.

The CT inputs used for 1Ph High impedance differential protectionHZPDIF function, shall be set to have ratio 1:1. So the parametersCTsecx and CTprimx of the relevant channel x of TRM and/or AIM shallbe set equal to 1 A by PST in PCM600; The parameter CTStarPointxmay be set to ToObject.

The tables 12, 13 below show, the operating currents for different settings of operatingvoltages and selected resistances. Adjust as required based on tables 12, 13 or tovalues in between as required for the application.

Minimum ohms can be difficult to adjust due to the small valuecompared to the total value.

Normally the voltage can be increased to higher values than the calculated minimumU>Trip with a minor change of total operating values as long as this is done byadjusting the resistor to a higher value. Check the sensitivity calculation below forreference.

Table 12: 1 A channels: input with minimum operating down to 40 mA

OperatingvoltageU>Trip

Stabilizingresistor Rohms

Operatingcurrent level 1A

Stabilizingresistor Rohms

Operatingcurrent level 1A

20 V 500 0.040 A -- --

40 V 1000 0.040 A -- --

60 V 1500 0.040 A 600 0.100 A

Table continues on next page

1MRK 504 134-UEN A Section 6Differential protection

113Application manual

Page 120: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

OperatingvoltageU>Trip

Stabilizingresistor Rohms

Operatingcurrent level 1A

Stabilizingresistor Rohms

Operatingcurrent level 1A

80 V 2000 0.040 A 800 0.100 A

100 V 2500 0.040 A 1000 0.100 A

150 V 3750 0.040 A 1500 0.100 A

200 V 5000 0.040 A 2000 0.100 A

Table 13: 5 A channels: input with minimum operating down to 200 mA

OperatingvoltageU>Trip

Stabilizingresistor R1ohms

Operatingcurrent level 5A

Stabilizingresistor R1ohms

Operatingcurrent level 5A

20 V 100 0.200 A -- --

40 V 200 0.200 A 100 0.400

60 V 300 0.200 A 150 0.400 A

80 V 400 0.200 A 200 0.400 A

100 V 500 0.200 A 250 0.400 A

150 V 750 0.200 A 375 0.400 A

200 V 1000 0.200 A 500 0.400 A

The current transformer saturation voltage must be at least 2 ˣ U>Trip to havesufficient operating margin. This must be checked after calculation of U>Trip.

When the R value has been selected and the U>Trip value has been set, the sensitivityof the scheme IP can be calculated. The sensitivity is decided by the total current in thecircuit according to equation 39.

( )IP n IR Ires lmag= × + +åEQUATION1747 V1 EN (Equation 39)

where:

n is the CT ratio

IP primary current at IED pickup,

IR IED pickup current (U>Trip/SeriesResistor)

Ires is the current through the non-linear resistorand

ΣImag is the sum of the magnetizing currents from all CTs in the circuit (for example, 4 CTs forrestricted earth fault protection, 2 CTs for reactor differential protection, 3-5 CTs forautotransformer differential protection , the number of feeders, including the buscoupler, forbusbar differential protection).

It should be remembered that the vectorial sum of the currents must be used (IEDs,Metrosil and resistor currents are resistive). The current measurement is insensitive to

Section 6 1MRK 504 134-UEN ADifferential protection

114Application manual

Page 121: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

DC component in fault current to allow the use of only the AC components of the faultcurrent in the above calculations.

The voltage dependent resistor (Metrosil) characteristic is shown in Figure 52.

A shunt can be added in parallel to the non-linear resistor in order to desensitize thefunction.

Series resistor thermal capacityThe series resistor is dimensioned for 200 W. Preferable the U>Trip2/SeriesResistorshould always be lower than 200 W to allow continuous activation during testing. Ifthis value is exceeded, testing should be done with a transient faults.

The series resistor is dimensioned for 200 W. The condition: U>Trip2/SeriesResistorshall be fulfilled. In this condition the continuous injection is allowed during testing.

1MRK 504 134-UEN A Section 6Differential protection

115Application manual

Page 122: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

I>

R

Rres

Rl

Rct Rct

Rl

UR

a) Through load situation

b) Through fault situation

UR

UR

c) Internal faults

UR

Protected Object

IEC05000427-2-en.vsd

IEC05000427 V2 EN

Figure 49: The high impedance principle for one phase with two currenttransformer inputs

Section 6 1MRK 504 134-UEN ADifferential protection

116Application manual

Page 123: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

6.3.3 Connection examples for high impedance differentialprotection

WARNING! USE EXTREME CAUTION! Dangerously highvoltages might be present on this equipment, especially on the platewith resistors. Do any maintenance ONLY if the primary objectprotected with this equipment is de-energized. If required by nationallaw or standard, enclose the plate with resistors with a protective coveror in a separate box.

6.3.3.1 Connections for 1Ph restricted earth fault and high impedancedifferential protection

Restricted earth fault protection REF is a typical application for 1Ph High impedancedifferential protection HZPDIF. Typical CT connections for high impedance basedREF protection scheme are shown in figure 50.

L1(A)

L2(B)

L3(C)

Protected Object

CT 1500/5Star/Wye

Connected

7

8

9

10

11

12

1

2

3

4

5

6

AI01 (I)

AI02 (I)

AI03 (I)

AI04 (I)

AI05 (I)

AI06 (I)

6

7

8

IED

X1

R1

12

4 5

U R2

13

4

2

1 2 3

N

1-Ph Plate with Metrosil and Resistor

23

5

4

9

N

L1(A)

L2(B)

L3(C)

CT

1500

/5

1

IEC07000194_2_en.vsd

AI3P

AI1

AI2

AI3

AI4

AIN

SMAI2

BLOCK

^GRP2L1

^GRP2L2

^GRP2L3

^GRP2N

TYPE

IEC07000194 V2 EN

Figure 50: CT connections for restricted earth fault protection

1MRK 504 134-UEN A Section 6Differential protection

117Application manual

Page 124: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Pos Description

1 Scheme earthing point

Note that it is of outmost importance to insure that only one earthing pointexist in such scheme.

2 One-phase plate with stabilizing resistor and metrosil.

3 Necessary connection for the metrosil. Shown connections are applicable for both types of one-phase plate.

4 Position of optional test switch for secondary injection into the high impedance differential IED.

5 Necessary connection for stabilizing resistor. Shown connections are applicable for both types ofone-phase plate.

6 How to connect REFPDIF high impedance scheme to one CT input in IED.

7 Transformer input module where this current input is located.

Note that the CT ratio for high impedance differential protection applicationmust be set as one.

• For main CTs with 1A secondary rating the following setting values shall be entered: CTprim= 1A and CTsec = 1A

• For main CTs with 5A secondary rating the following setting values shall be entered: CTprim= 5A and CTsec = 5A

• The parameter CTStarPoint shall always be left to the default value ToObject

8 Connection made in the Signal Matrix, which connects this current input to first input channel ofthe preprocessing function block (9). For high impedance differential protection preprocessingfunction block in 3ms task shall be used.

9 Preprocessing block, which has a task to digitally filter the connected analogue inputs.Preprocessing block output AI1 shall be connected to one instances of 1Ph high impedancedifferential protection function HZPDIF (for example, instance 1 of HZPDIF in the configurationtool).

6.3.4 Setting guidelines

The setting calculations are individual for each application. Refer to the differentapplication descriptions below.

6.3.4.1 Configuration

The configuration is done in the Application Configuration tool. For example, signalsfrom external check criteria shall be connected to the inputs as required for theapplication.

BLOCK input is used to block the function for example, from external check criteria.

BLKTR input is used to block the function tripping for example, from external checkcriteria. The alarm level will be operative.

Section 6 1MRK 504 134-UEN ADifferential protection

118Application manual

Page 125: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

6.3.4.2 Settings of protection function

Operation: The operation of the high impedance differential function can be switchedOn or Off.

U>Alarm: Set the alarm level. The sensitivity can roughly be calculated as a dividerfrom the calculated sensitivity of the differential level. A typical setting is 10% ofU>Trip It can be used as scheme supervision stage.

tAlarm: Set the time for the alarm. A typical setting is 2-3 seconds.

U>Trip: Set the trip level according to the calculations in the examples for eachapplication example. The level is selected with margin to the calculated requiredvoltage to achieve stability. Values can be 20-200 V dependent on the application.

SeriesResistor: Set the value of the stabilizing series resistor. Calculate the valueaccording to the examples for each application. Adjust the resistor as close as possibleto the calculated example. Measure the value achieved and set this value here.

The value shall always be high impedance. This means for example,for 1A circuits say bigger than 400 ohms (400 VA) and for 5 A circuitssay bigger than 100 ohms (2500 VA). This ensures that the currentwill circulate and not go through the differential circuit at throughfaults.

The settings of U>Alarm, U>Trip and SeriesResistor must be chosensuch that:

• U>Alarm/SeriesResistor is >2% of IRated of the used currentinput

• U>Trip/SeriesResistor is >4% of IRated of the used current input

Normally the settings shall also be such that U>Alarm/SeriesResistorand U>Trip/SeriesResistor both gives a value <4*IRated of the usedcurrent input. If not it must be considered the limitation in how longtime the actual current is allowed to persist not to overload the currentinput.

6.3.4.3 Restricted earth fault protection REFPDIF

For solidly earthed systems a restricted earth fault protection REF is often provided asa complement to the normal transformer differential IED. The advantage with therestricted earth fault IEDs is their high sensitivity. Sensitivities of 2-8% can beachieved whereas the normal differential IED will have sensitivities of 20-40%. Thelevel for high impedance restricted earth fault function is dependent of the currenttransformers magnetizing currents.

1MRK 504 134-UEN A Section 6Differential protection

119Application manual

Page 126: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Restricted earth fault IEDs have very fast response time due to the simple measuringprinciple and the measurement of one winding only.

The connection of a restricted earth fault IED is shown in figure 51. It is connectedacross each directly or low ohmic earthed transformer winding in figure 51.

It is quite common to connect the restricted earth fault IED in the same current circuitas the transformer differential IED. Due to the difference of measuring principle, thedetection of earth faults may be somewhat limited. Such faults are then only detectedby REF function. The mixed connection using the 1Ph High impedance differentialprotection HZPDIF function should be avoided and the low impedance scheme shouldbe used instead.

Id

IEC05000177-2-en.vsd

IEC05000177 V2 EN

Figure 51: Application of HZPDIF function as a restricted earth fault IED for anYNd transformer

Setting example

It is strongly recommended to use the highest tap of the CT wheneverhigh impedance protection is used. This helps in utilizing maximumCT capability, minimize the current, thereby reducing the stabilityvoltage limit. Another factor is that during internal faults, the voltagedeveloped across the selected tap is limited by the non-linear resistorbut in the unused taps, owing to auto-transformer action, voltagesmuch higher than design limits might be induced.

Section 6 1MRK 504 134-UEN ADifferential protection

120Application manual

Page 127: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Basic data: Transformer rated current on HV winding: 250 A

Current transformer ratio: 300/1 A (Note: Must be the same at all locations)

CT Class: 10 VA 5P20

Cable loop resistance: <50 m 2.5mm2 (one way) gives 2 · 0.4 ohm at 75° C

Max fault current: The maximum through fault current is limited by thetransformer reactance, use 15 · rated current of thetransformer

Calculation:

( )25015 0.66 0.8 18.25

300UR V> × × + =

EQUATION1219 V1 EN (Equation 40)

Select a setting of U>Trip=20 V.

The current transformer saturation voltage at 5% error can roughly be calculated from the rated values.

( )5 10 0.66 20 213.2E P V> + × =

EQUATION1220 V1 EN (Equation 41)

that is, greater than 2 · U>Trip

Check from the table of selected resistances the required series stabilizing resistorvalue to use. Since this application requires high sensitivity, select SeriesResistor=1000 ohm which gives a current of 20 mA.

To calculate the sensitivity at operating voltage, refer to equation 42 which isacceptable as it gives around 10% minimum operating current.

( )30020 0 5 0 4 20 60 .25.5

1IP approx A= × ° + ° + × - ° £

EQUATION1221 V1 EN (Equation 42)

The magnetizing current is taken from the magnetizing curve for the currenttransformer cores which should be available. The value at U>Trip is taken. For thevoltage dependent resistor current the top value of voltage 20 · √2 is used and the topcurrent used. Then the RMS current is calculated by dividing with√2. Use themaximum value from the curve.

6.3.4.4 Alarm level operation

The 1Ph High impedance differential protection HZPDIF function has a separatealarm level, which can be used to give alarm for problems with an involved current

1MRK 504 134-UEN A Section 6Differential protection

121Application manual

Page 128: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

transformer circuit. The setting level is normally selected to be around 10% of theoperating voltage U>Trip.

The setting of U>Alarm is related to the value of the stabilizing resistor and theminimum current sensitivity. The setting example shows the calculation procedure ofthe setting value of U> Alarm.

As seen in the setting examples above the sensitivity of HZPDIF function is normallyhigh, which means that the function will in many cases operate also for short circuitsor open current transformer secondary circuits. However the stabilizing resistor canbe selected to achieve sensitivity higher than normal load current and/or separatecriteria can be added to the operation, like a check zone. This can be either anotherIED, with the same HZPDIF function, or be a check about the fault condition, whichis performed by an earth overcurrent function or neutral point voltage function.

For such cases where operation is not expected during normal service the alarm outputshould be used to activate an external shorting of the differential circuit avoidingcontinuous high voltage in the circuit. A time delay of a few seconds is used before theshorting and alarm are activated. Auxiliary relays with contacts that can withstandhigh voltage shall be used, like RXMVB types.

IEC05000749 V1 EN

Figure 52: Current voltage characteristics for the non-linear resistors, in the range 10-200 V, the averagerange of current is: 0.01–10 mA

Section 6 1MRK 504 134-UEN ADifferential protection

122Application manual

Page 129: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 7 Impedance protection

7.1 Power swing detection ZMRPSB

7.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Power swing detection ZMRPSB

Zpsb

SYMBOL-EE V1 EN

68

7.1.2 Application

7.1.2.1 General

Various changes in power system may cause oscillations of rotating units. The mosttypical reasons for these oscillations are big changes in load or changes in powersystem configuration caused by different faults and their clearance. As the rotatingmasses strive to find a stable operate condition, they oscillate with dampedoscillations until they reach the final stability.

The extent of the oscillations depends on the extent of the disturbances and on thenatural stability of the system.

The oscillation rate depends also on the inertia of the system and on the total systemimpedance between different generating units. These oscillations cause changes inphase and amplitude of the voltage difference between the oscillating generating unitsin the power system, which reflects further on in oscillating power flow between twoparts of the system - the power swings from one part to another - and vice versa.

Distance IEDs located in interconnected networks see these power swings as theswinging of the measured impedance in relay points. The measured impedance varieswith time along a locus in an impedance plane, see figure 53. This locus can enter theoperating characteristic of a distance protection and cause, if no preventive measureshave been considered, its unwanted operation.

1MRK 504 134-UEN A Section 7Impedance protection

123Application manual

Page 130: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

R

jX

Operating characteristic

Impedance locus atpower swing

IEC09000224_1_en.vsdIEC09000224 V1 EN

Figure 53: Impedance plane with Power swing detection operatingcharacteristic and impedance locus at power swing

7.1.2.2 Basic characteristics

Power swing detection function (ZMRPSB) reliably detects power swings withperiodic time of swinging as low as 200 ms (which means slip frequency as high as10% of the rated frequency on the 50 Hz basis). It detects the swings under normalsystem operating conditions.

ZMRPSB function is able to secure selective operation for internal faults duringpower. The operation of the distance protection function remains stable for externalfaults during the power swing condition, even with the swing (electrical) centrelocated on the protected power line.

The operate characteristic of the ZMRPSB function is easily adjustable to the selectedimpedance operate characteristics of the corresponding controlled distance protectionzones as well as to the maximum possible load conditions of the protected power lines.

7.1.3 Setting guidelines

Setting guidelines are prepared in the form of a setting example for the protectedpower line as part of a two-machine system presented in figure 54.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Section 7 1MRK 504 134-UEN AImpedance protection

124Application manual

Page 131: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

99001019.vsd

~~

EA

dA= const dB= f(t)

EB

A BZSA ZSBZL

R

IEC99001019 V1 EN

Figure 54: Protected power line as part of a two-machine system

Reduce the power system with protected power line into equivalent two-machinesystem with positive sequence source impedances ZSA behind the IED and ZSB behindthe remote end bus B. Observe a fact that these impedances can not be directlycalculated from the maximum three-phase short circuit currents for faults on thecorresponding busbar. It is necessary to consider separate contributions of differentconnected circuits.

The required data is as follows:

400rU kV=EQUATION1321 V1 EN

Rated system voltage

min 380U kV=EQUATION1322 V1 EN

Minimum expected system voltage under critical systemconditions

50rf Hz=EQUATION1323 V1 EN

Rated system frequency

4003pU kV=

EQUATION1324 V1 EN

Rated primary voltage of voltage protection transformers used

0.113sU kV=

EQUATION1325 V1 EN

Rated secondary voltage of voltage instrument transformers used

1200pI A=EQUATION1326 V1 EN

Rated primary current of current protection transformers used

1sI A=EQUATION1327 V1 EN

Rated secondary current of current protection transformers used

( )1 10.71 75.6LZ j= + WEQUATION1328 V1 EN

Line positive sequence impedance

Table continues on next page

1MRK 504 134-UEN A Section 7Impedance protection

125Application manual

Page 132: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

( )1 1.15 43.5SAZ j= + WEQUATION1329 V1 EN

Positive sequence source impedance behind A bus

( )1 5.3 35.7SBZ j= + WEQUATION1330 V1 EN

Positive sequence source impedance behind B bus

max 1000S MVA=EQUATION1331 V1 EN

Maximum expected load in direction from A to B (with minimumsystem operating voltage Umin)

( )maxcos 0.95j =EQUATION1332 V1 EN

Power factor at maximum line loading

max 25j = °EQUATION1333 V1 EN

Maximum expected load angle

2.5sif Hz=EQUATION1334 V1 EN

Maximum possible initial frequency of power oscillation

7.0scf Hz=EQUATION1335 V1 EN

Maximum possible consecutive frequency of power oscillation

The impedance transformation factor, which transforms the primary impedances tothe corresponding secondary values is calculated according to equation 43. Considera fact that all settings are performed in primary values. The impedance transformationfactor is presented for orientation and testing purposes only.

1200 0.11 0.331 400

p s

s p

I UKIMPI U

= × = × =

EQUATION1336 V1 EN (Equation 43)

The minimum load impedance at minimum expected system voltage is equal toequation 44.

2 2min

minmax

380 144.41000L

UZS

= = = W

EQUATION1337 V1 EN (Equation 44)

The minimum load resistance RLmin at maximum load and minimum system voltageis equal to equation 45.

( )min min maxcos 144.4 0.95 137.2L LR Z j= × = × = WEQUATION1338 V1 EN (Equation 45)

Section 7 1MRK 504 134-UEN AImpedance protection

126Application manual

Page 133: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The system impedance ZS is determined as a sum of all impedance in an equivalenttwo-machine system, see figure 54. Its value is calculated according to equation 46.

( )1 1 1 17.16 154.8S SA L SBZ Z Z Z j= + + = + WEQUATION1339 V1 EN (Equation 46)

The calculated value of the system impedance is of informative nature and helpsdetermining the position of oscillation center, see figure 55, which is for general casecalculated according to equation 47.

1

1

SCO SA

B

A

ZZ ZEE

= -

+

EQUATION1340 V1 EN (Equation 47)

In particular cases, when

A BE E=EQUATION1342 V1 EN (Equation 48)

resides the center of oscillation on impedance point, see equation 49.

( )1 7.43 33.92

SCO SA

ZZ Z j= - = + W

EQUATION1341 V1 EN (Equation 49)

1MRK 504 134-UEN A Section 7Impedance protection

127Application manual

Page 134: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

R

jX

ArgLd(ZMRPSB)ArgLd

(FDPSPDIS)

Z S1

jXZ SA

1

Z L1

Z SB

1

Impedance locus for |EA| = |E

B|

R

Z CO

IEC09000225-1-en.vsdIEC09000225 V1 EN

Figure 55: Impedance diagrams with corresponding impedances underconsideration

The outer boundary of oscillation detection characteristic in forward directionRLdOutFw should be set with certain safety margin KL compared to the minimumexpected load resistance RLmin. When the exact value of the minimum load resistanceis not known, the following approximations may be considered for lines with ratedvoltage 400 kV:

Section 7 1MRK 504 134-UEN AImpedance protection

128Application manual

Page 135: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• KL = 0.9 for lines longer than 150 km• KL = 0.85 for lines between 80 and 150 km• KL = 0.8 for lines shorter than 80 km

Multiply the required resistance for the same safety factor KL with the ratio betweenactual voltage and 400kV when the rated voltage of the line under consideration ishigher than 400kV. The outer boundary RLdOutFw obtains in this particular case itsvalue according to equation 50.

min 0.9 137.2 123.5L LRLdOutFw K R= × = × = WEQUATION1343 V1 EN (Equation 50)

It is a general recommendation to set the inner boundary RLdInFw of the oscillationdetection characteristic to 80% or less of its outer boundary. Exceptions are alwayspossible, but must be considered with special care especially when it comes to settingsof timers tP1 and tP2 included in oscillation detection logic. This requires themaximum permitted setting values of factor kLdRFw = 0.8. Equation 51 presents thecorresponding maximum possible value of RLdInFw.

RLdInFw = kLdRFw·RLdOutFw = 98.8WEQUATION1344 V2 EN (Equation 51)

The load angles, which correspond to external δOut and internal δIn boundary ofproposed oscillation detection characteristic in forward direction, are calculated withsufficient accuracy according to equation 52 and 53 respectively.

155.752 arc tan 2 arc tan 64.52 2 123.5

dæ ö æ öç ÷= × = × = °ç ÷ç ÷× ×è øè ø

SOut

ZRLdOutFw

EQUATION1345 V1 EN (Equation 52)

max

155.752 arc tan 2 arc tan 76.52 2 98.8

dæ ö æ öç ÷= × = × = °ç ÷ç ÷× ×è øè ø

SIn

ZRLdInFw

EQUATION1346 V1 EN (Equation 53)

The required setting tP1 of the initial oscillation detection timer depends on the loadangle difference according to equation 54.

76.5 64.51 13.3360 2.5 360

In Out

si

tP msfd d- ° - °

= = =× ° × °

EQUATION1347 V1 EN (Equation 54)

The general tendency should be to set the tP1 time to at least 30 ms, if possible. Sinceit is not possible to further increase the external load angle δOut, it is necessary to

1MRK 504 134-UEN A Section 7Impedance protection

129Application manual

Page 136: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

reduce the inner boundary of the oscillation detection characteristic. The minimumrequired value is calculated according to the procedure listed in equation 55, 56, 57and 58.

min1 30tP ms=EQUATION1348 V1 EN (Equation 55)

min min360 1 360 2.5 0.030 64.5 91.5In si Outf tPd d- = ° × × + = ° × × + ° = °EQUATION1349 V1 EN (Equation 56)

max1min

155.75 75.891.52 tan2 tan

22d -

= = = Wæ ö æ ö×× ç ÷ç ÷ è øè ø

S

in

ZRLdInFw

EQUATION1350 V1 EN (Equation 57)

max1 75.8 0.61123.5

= = =RLdInFwkLdRFwRLdOutFw

EQUATION1351 V1 EN (Equation 58)

Also check if this minimum setting satisfies the required speed for detection ofconsecutive oscillations. This requirement will be satisfied if the proposed setting oftP2 time remains higher than 10 ms, see equation 59.

max91.5 64.52 10.7

360 7 360In Out

sc

tP msfd d- ° - °

= = =× ° × °

EQUATION1352 V1 EN (Equation 59)

The final proposed settings are as follows:

RLdOutFw = 123.5Ω

kLdRFw = 0.61

tP1 = 30 ms

tP2 = 10 ms

Consider RLdInFw = 75.0Ω.

Do not forget to adjust the setting of load encroachment resistanceRLdFw in Phase selection with load encroachment (FDPSPDIS) tothe value equal to or less than the calculated value RLdInFw. It is atthe same time necessary to adjust the load angle in FDPSPDIS tofollow the condition presented in equation 60.

Section 7 1MRK 504 134-UEN AImpedance protection

130Application manual

Page 137: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Index PHS designates correspondence to FDPSPDIS function andindex PSD the correspondence to ZMRPSB function.

( )tanarc tan³ PSD

PHS

ArgLdArgLd

kLdRFwEQUATION1353 V2 EN (Equation 60)

Consider equation 61,

max 25PSDArgLd j= = °EQUATION1354 V1 EN (Equation 61)

then it is necessary to set the load argument in FDPSPDIS function to not less thanequation 62.

( ) ( )tan tan 25arc tan arc tan 37.5

0.61é ù é ù°

³ = = °ê ú ê úë û ë û

PSDPHS

ArgLdArgLd

kLdRFwEQUATION1355 V1 EN (Equation 62)

It is recommended to set the corresponding resistive reach parameters in reversedirection (RLdOutRv and kLdRRv) to the same values as in forward direction, unlessthe system operating conditions, which dictate motoring and generating types ofoscillations, requires different values. This decision must be made on basis of possiblesystem contingency studies especially in cases, when the direction of transmittedpower may change fast in short periods of time. It is recommended to use differentsetting groups for operating conditions, which are changing only between differentperiods of year (summer, winter).

System studies should determine the settings for the hold timer tH. The purpose of thistimer is, to secure continuous output signal from Power swing detection function(ZMRPSB) during the power swing, even after the transient impedance leavesZMRPSB operating characteristic and is expected to return within a certain time dueto continuous swinging. Consider the minimum possible speed of power swinging ina particular system.

The tR1 inhibit timer delays the influence of the detected residual current on the inhibitcriteria for ZMRPSB. It prevents operation of the function for short transients in theresidual current measured by the IED.

The tR2 inhibit timer disables the output START signal from ZMRPSB function, if themeasured impedance remains within ZMRPSB operating area for a time longer thanthe set tR2 value. This time delay was usually set to approximately two seconds inolder power-swing devices.

1MRK 504 134-UEN A Section 7Impedance protection

131Application manual

Page 138: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

7.2 Underimpedance protection for generators andtransformers ZGCPDIS

7.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Underimpedance protection forgenerators and transformers

ZGCPDIS 21G

7.2.2 Application

In the case of a static excitation system receiving its power from the generatorterminals, the magnitude of a sustained phase-to-phase short-circuit current dependson the generator terminal voltage. In case of a nearby multi-phase fault, the generatorterminal voltage may drop to quite low level (for example <25%) and the generatorfault current may consecutively fall below the pickup of the overcurrent relay. Theshort-circuit current may drop below rated current after 0.5 - 1 s also for generatorswith excitation system not fed from the generator terminals if the fault occurs when theautomatic voltage regulator is out of service. The under impedance protection is thenthe best generator backup protection which can be used under such circumstances. Forthis reason, an impedance measuring relay is generally recommended for generatorback-up short-circuit protection.

The impedance relay is normally connected to current transformers on the generatorneutral side to provide back-up also when the generator is disconnected from thesystem. At reduced voltages, the current required for operation will be reduced. Atzero voltage, operation is obtained with a current bigger than 15 % of IBase (that is,generator rated current).

The underimpedance protection for generators and transformers function (ZGCPDIS)in the 650 series is designed to meet basic requirements for application as backupprotection for generators and transformers.

7.2.3 Setting guidelines

The settings for the underimpedance function are done in primary ohms. Theinstrument transformer ratios that have been set for the analogue input module is usedto automatically convert the measured secondary input signals to primary values usedin ZGCPDIS .

The following basics must be considered, depending on the application, whencalculating the setting values:

Section 7 1MRK 504 134-UEN AImpedance protection

132Application manual

Page 139: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Errors introduced by current and voltage instrument transformers, particularlyunder transient conditions.

The setting values of all parameters that belong to ZGCPDIS must correspond to theparameters of the protected object and coordinated to the selectivity plan for thenetwork.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

For ZGCPDIS function always use Global base values which settingcorrespond to the generator rated data.

ZGCPDIS function has an offset mho characteristic and evaluates three phase-to-phase impedance measuring loops. It has a forward and reverse impedance settingaccording to figure 56.

The relevant phase-to-phase measuring loop is released as soon as themeasured current is above 15% of IBase.

ZFwd

ZRev

ImpedanceAng

X

R

IEC10000184_2_en.vsd

IEC10000184 V2 EN

Figure 56: Operating characteristic for phase-to-phase loops

1MRK 504 134-UEN A Section 7Impedance protection

133Application manual

Page 140: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

7.3 Load enchroachment LEPDIS

7.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Load encroachment LEPDIS - -

7.3.2 Application

Heavy load transfer is common in many power networks and may make faultresistance coverage difficult to achieve. In such a case, Load encroachment LEPDISfunction can be used to enlarge the resistive setting of the underimpedance measuringzones without interfering with the load.

Each of the three measuring phase-to-phase loops has its own load encroachmentcharacteristic.

7.3.3 Setting guidelines

7.3.3.1 Resistive reach with load encroachment characteristic

The procedure for calculating the settings for the load encroachment consists basicallyof defining the load angle ArgLd and the blinder RLd, as shown in figure 57.

Section 7 1MRK 504 134-UEN AImpedance protection

134Application manual

Page 141: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

R

X

RLd

ArgLd

ArgLdArgLd

ArgLd

IEC10000144-1-en.vsd

RLd

IEC10000144 V2 EN

Figure 57: Load encroachment characteristic

The load angle ArgLd is the same in forward and reverse direction, so it could besuitable to begin to calculate the setting for that parameter. The parameter is set to themaximum possible load angle at the maximum active load. A value larger than 20°must be used considering a normal PF=0.8 corresponding to an angle of 36 deg.

The blinder, RLd, can be calculated according to equation:

= ×2 min

0.8expmax

URLd

PEQUATION2351 V1 EN (Equation 63)

where:

Pexp max is the maximum exporting active power

Umin is the minimum voltage for which the Pexp max occurs

0.8 is a security factor to ensure that the setting of RLd can be lesserthan the calculated minimal resistive load.

1MRK 504 134-UEN A Section 7Impedance protection

135Application manual

Page 142: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

136

Page 143: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 8 Current protection

8.1 Instantaneous phase overcurrent protection 3-phaseoutput PHPIOC

8.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous phase overcurrentprotection 3-phase output

PHPIOC

3I>>

SYMBOL-Z V1 EN

50

8.1.2 Application

Long transmission lines often transfer great quantities of electric power fromproduction to consumption areas. The unbalance of the produced and consumedelectric power at each end of the transmission line is very large. This means that a faulton the line can easily endanger the stability of a complete system.

The transient stability of a power system depends mostly on three parameters (atconstant amount of transmitted electric power):

• The type of the fault. Three-phase faults are the most dangerous, because nopower can be transmitted through the fault point during fault conditions.

• The magnitude of the fault current. A high fault current indicates that the decreaseof transmitted power is high.

• The total fault clearing time. The phase angles between the EMFs of thegenerators on both sides of the transmission line increase over the permittedstability limits if the total fault clearing time, which consists of the protectionoperating time and the breaker opening time, is too long.

The fault current on long transmission lines depends mostly on the fault position anddecreases with the distance from the generation point. For this reason the protectionmust operate very quickly for faults very close to the generation (and relay) point, forwhich very high fault currents are characteristic.

The instantaneous phase overcurrent protection 3-phase output PHPIOC can operatein 10 ms for faults characterized by very high currents.

1MRK 504 134-UEN A Section 8Current protection

137Application manual

Page 144: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.1.3 Setting guidelines

The parameters for instantaneous phase overcurrent protection 3-phase outputPHPIOC are set via the local HMI or PCM600.

This protection function must operate only in a selective way. So check all system andtransient conditions that could cause its unwanted operation.

Only detailed network studies can determine the operating conditions under which thehighest possible fault current is expected on the line. In most cases, this currentappears during three-phase fault conditions. But also examine single-phase-to-earthand two-phase-to-earth conditions.

Also study transients that could cause a high increase of the line current for shorttimes. A typical example is a transmission line with a power transformer at the remoteend, which can cause high inrush current when connected to the network and can thusalso cause the operation of the built-in, instantaneous, overcurrent protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

IP>>: Set operate current in % of IBase.

8.1.3.1 Meshed network without parallel line

The following fault calculations have to be done for three-phase, single-phase-to-earth and two-phase-to-earth faults. With reference to figure 58, apply a fault in B andthen calculate the current through-fault phase current IfB. The calculation should bedone using the minimum source impedance values for ZA and the maximum sourceimpedance values for ZB in order to get the maximum through fault current from A toB.

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsd

IEC09000022 V1 EN

Figure 58: Through fault current from A to B: IfB

Section 8 1MRK 504 134-UEN ACurrent protection

138Application manual

Page 145: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Then a fault in A has to be applied and the through fault current IfA has to be calculated,figure 59. In order to get the maximum through fault current, the minimum value forZB and the maximum value for ZA have to be considered.

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 59: Through fault current from B to A: IfA

The IED must not trip for any of the two through-fault currents. Hence the minimumtheoretical current setting (Imin) will be:

Imin MAX IfA IfB,( )³

EQUATION78 V1 EN (Equation 64)

A safety margin of 5% for the maximum protection static inaccuracy and a safetymargin of 5% for the maximum possible transient overreach have to be introduced. Anadditional 20% is suggested due to the inaccuracy of the instrument transformersunder transient conditions and inaccuracy in the system data.

The minimum primary setting (Is) for the instantaneous phase overcurrent protection3-phase output is then:

min1.3sI I³ ×

EQUATION79 V3 EN (Equation 65)

The protection function can be used for the specific application only if this settingvalue is equal to or less than the maximum fault current that the IED has to clear, IF infigure 60.

1MRK 504 134-UEN A Section 8Current protection

139Application manual

Page 146: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000024-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I F

Fault

IEC09000024 V1 EN

Figure 60: Fault current: IF

100Is

IPIBase

>>= ×

EQUATION1147 V3 EN (Equation 66)

8.1.3.2 Meshed network with parallel line

In case of parallel lines, the influence of the induced current from the parallel line tothe protected line has to be considered. One example is given in figure 61 where thetwo lines are connected to the same busbars. In this case the influence of the inducedfault current from the faulty line (line 1) to the healthy line (line 2) is consideredtogether with the two through fault currents IfA and IfB mentioned previously. Themaximal influence from the parallel line for the IED in figure 61 will be with a faultat the C point with the C breaker open.

A fault in C has to be applied, and then the maximum current seen from the IED (IM )on the healthy line (this applies for single-phase-to-earth and two-phase-to-earthfaults) is calculated.

Section 8 1MRK 504 134-UEN ACurrent protection

140Application manual

Page 147: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000025-1-en.vsd

~ ~ZA ZB

ZL1A B

I M

Fault

IED

ZL2

M

CLine 1

Line 2

IEC09000025 V1 EN

Figure 61: Two parallel lines. Influence from parallel line to the through faultcurrent: IM

The minimum theoretical current setting for the overcurrent protection function(Imin) will be:

Imin MAX IfA IfB IM, ,( )³

EQUATION82 V1 EN (Equation 67)

Where IfA and IfB have been described in the previous paragraph. Considering thesafety margins mentioned previously, the minimum setting (Is) for the instantaneousphase overcurrent protection 3-phase output is then:

Is ³1.3·IminEQUATION83 V2 EN (Equation 68)

The protection function can be used for the specific application only if this settingvalue is equal or less than the maximum phase fault current that the IED has to clear.

The IED setting value IP>> is given in percentage of the primary base current value,IBase. The value for IP>> is given from this formula:

100Is

IPIBase

>>= ×

EQUATION1147 V3 EN (Equation 69)

1MRK 504 134-UEN A Section 8Current protection

141Application manual

Page 148: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.2 Four step phase overcurrent protection 3-phaseoutput OC4PTOC

8.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Four step phase overcurrent protection3-phase output

OC4PTOC

44 alt

3I>

TOC-REVA V1 EN

51/67

8.2.2 Application

The Four step phase overcurrent protection 3-phase output OC4PTOC is used inseveral applications in the power system. Some applications are:

• Short circuit protection of feeders in distribution and subtransmission systems.Normally these feeders have radial structure.

• Back-up short circuit protection of transmission lines.• Back-up short circuit protection of power transformers.• Short circuit protection of different kinds of equipment connected to the power

system such as; shunt capacitor banks, shunt reactors, motors and others.• Back-up short circuit protection of power generators.

If VT inputs are not available or not connected, setting parameterDirModex (x = step 1, 2, 3 or 4) shall be left to default value Non-directionalor set to Off.

In many applications several steps with different current pick up levels and timedelays are needed. OC4PTOC can have up to four different, individual settable, steps.The flexibility of each step of OC4PTOC is great. The following options are possible:

Non-directional / Directional function: In most applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed from theprotected object itself. In order to achieve both selectivity and fast fault clearance, thedirectional function can be necessary.

Choice of delay time characteristics: There are several types of delay timecharacteristics available such as definite time delay and different types of inverse timedelay characteristics. The selectivity between different overcurrent protections isnormally enabled by co-ordination between the function time delays of the differentprotections. To enable optimal co-ordination between all overcurrent protections,

Section 8 1MRK 504 134-UEN ACurrent protection

142Application manual

Page 149: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

they should have the same time delay characteristic. Therefore a wide range ofstandardized inverse time characteristics are available: IEC and ANSI.

The time characteristic for step 1 and 4 can be chosen as definite time delay or inversetime characteristic. Step 2 and 3 are always definite time delayed and are used insystem where IDMT is not needed.

Power transformers can have a large inrush current, when being energized. Thisphenomenon is due to saturation of the transformer magnetic core during parts of theperiod. There is a risk that inrush current will reach levels above the pick-up currentof the phase overcurrent protection. The inrush current has a large 2nd harmoniccontent. This can be used to avoid unwanted operation of the protection. Therefore,OC4PTOC have a possibility of 2nd harmonic restrain if the level of this harmoniccurrent reaches a value above a set percentage of the fundamental current.

8.2.3 Setting guidelines

When inverse time overcurrent characteristic is selected, the operatetime of the stage will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that stage to zero.

The parameters for Four step phase overcurrent protection 3-phase output OC4PTOCare set via the local HMI or PCM600.

The following settings can be done for OC4PTOC.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

MeasType: Selection of discrete Fourier filtered (DFT) or true RMS filtered (RMS)signals. RMS is used when the harmonic contents are to be considered, for example inapplications with shunt capacitors.

Operation: The protection can be set to Off or On

2ndHarmStab: Operate level of 2nd harmonic current restrain set in % of thefundamental current. The setting range is 5 - 100% in steps of 1%. Default setting is20%.

1MRK 504 134-UEN A Section 8Current protection

143Application manual

Page 150: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Uref

Idir

IEC09000636_1_vsd

1

2

2

3

4

IEC09000636 V1 EN

Figure 62: Directional function characteristic

1. RCA = Relay characteristic angle 55°2. ROA = Relay operating angle 80°3. Reverse4. Forward

8.2.3.1 Settings for steps 1 to 4

n means step 1 and 4. x means step 1, 2, 3 and 4.

DirModex: The directional mode of step x. Possible settings are Off/Non-directional/Forward/Reverse.

Characteristn: Selection of time characteristic for step n. Definite time delay anddifferent types of inverse time characteristics are available according to table 14. Step2 and 3 are always definite time delayed.

Section 8 1MRK 504 134-UEN ACurrent protection

144Application manual

Page 151: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 14: Inverse time characteristics

Curve nameANSI Extremely Inverse

ANSI Very Inverse

ANSI Normal Inverse

ANSI Moderately Inverse

ANSI/IEEE Definite time

ANSI Long Time Extremely Inverse

ANSI Long Time Very Inverse

ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

ASEA RI

RXIDG (logarithmic)

The different characteristics are described in Technical manual.

Ix>: Operate phase current level for step x given in % of IBase.

tx: Definite time delay for step x. The definite time tx is added to the inverse time wheninverse time characteristic is selected.

kn: Time multiplier for inverse time delay for step n.

IMinn: Minimum operate current for step n in % of IBase. Set IMinn below Ix> forevery step to achieve ANSI reset characteristic according to standard. If IMinn is setabove Ix> for any step the ANSI reset works as if current is zero when current dropsbelow IMinn.

tnMin: Minimum operate time for all inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter the operation time of the step can never be shorter than the setting. Settingrange: 0.000 - 60.000s in steps of 0.001s.

1MRK 504 134-UEN A Section 8Current protection

145Application manual

Page 152: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000164-2

Operate time

Current

tx

tnMin

IMinn

IEC09000164 V2 EN

Figure 63: Minimum operate current and operation time for inverse timecharacteristics

In order to fully comply with curves definition setting parameter tnMin shall be set tothe value, which is equal to the operating time of the selected inverse curve formeasured current of twenty times the set current pickup value. Note that the operatingtime value is dependent on the selected setting value for time multiplier kn.

HarmRestrainx: Enable block of step n from the harmonic restrain function (2ndharmonic). This function should be used when there is a risk if power transformerinrush currents might cause unwanted trip. Can be set Off/On.

8.2.3.2 2nd harmonic restrain

If a power transformer is energized there is a risk that the transformer core will saturateduring part of the period, resulting in an inrush transformer current. This will give adeclining residual current in the network, as the inrush current is deviating betweenthe phases. There is a risk that the phase overcurrent function will give an unwantedtrip. The inrush current has a relatively large ratio of 2nd harmonic component. Thiscomponent can be used to create a restrain signal to prevent this unwanted function.

The settings for the 2nd harmonic restrain are described below.

2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal, to block chosen steps. The setting is given in % of thefundamental frequency residual current. The setting range is 5 - 100% in steps of 1%.The default setting is 20% and can be used if a deeper investigation shows that no othervalue is needed..

Section 8 1MRK 504 134-UEN ACurrent protection

146Application manual

Page 153: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

HarmRestrainx: This parameter can be set Off/On, to disable or enable the 2ndharmonic restrain.

The four step phase overcurrent protection 3-phase output can be used in differentways, depending on the application where the protection is used. A generaldescription is given below.

The operating current setting of the inverse time protection, or the lowest current stepof the definite time protection, must be defined so that the highest possible loadcurrent does not cause protection operation. Here consideration also has to be taken tothe protection reset current, so that a short peak of overcurrent does not causeoperation of the protection even when the overcurrent has ceased. This phenomenonis described in figure 64.

Operate current

Current I

The IED does not reset

Line phase current

Time t

Reset current

IEC05000203-en-2.vsdIEC05000203 V3 EN

Figure 64: Operate and reset current for an overcurrent protection

The lowest setting value can be written according to equation 70.

ImaxIpu 1.2k

³ ×

EQUATION1262 V2 EN (Equation 70)

where:

1.2 is a safety factor

k is the resetting ratio of the protection

Imax is the maximum load current

1MRK 504 134-UEN A Section 8Current protection

147Application manual

Page 154: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The maximum load current on the line has to be estimated. There is also a demand thatall faults, within the zone that the protection shall cover, must be detected by the phaseovercurrent protection. The minimum fault current Iscmin, to be detected by theprotection, must be calculated. Taking this value as a base, the highest pick up currentsetting can be written according to equation 71.

Ipu 0.7 Iscmin£ ×EQUATION1263 V2 EN (Equation 71)

where:

0.7 is a safety factor

Iscmin is the smallest fault current to be detected by the overcurrent protection.

As a summary the operating current shall be chosen within the interval stated inequation 72.

Imax1.2 Ipu 0.7 Iscmink

× £ £ ×

EQUATION1264 V2 EN (Equation 72)

The high current function of the overcurrent protection, which only has a short delayof the operation, must be given a current setting so that the protection is selective toother protection in the power system. It is desirable to have a rapid tripping of faultswithin as large portion as possible of the part of the power system to be protected bythe protection (primary protected zone). A fault current calculation gives the largestcurrent of faults, Iscmax, at the most remote part of the primary protected zone.Considerations have to be made to the risk of transient overreach, due to a possible DCcomponent of the short circuit current. The lowest current setting of the most rapidstage, of the phase overcurrent protection, can be written according to

max1.2 t schighI k I³ × ×

EQUATION1265 V1 EN (Equation 73)

where:

1.2 is a safety factor

kt is a factor that takes care of the transient overreach due to the DC component of the faultcurrent and can be considered to be less than 1.1

Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.

The operate times of the phase overcurrent protection has to be chosen so that the faulttime is so short that protected equipment will not be destroyed due to thermaloverload, at the same time as selectivity is assured. For overcurrent protection, in aradial fed network, the time setting can be chosen in a graphical way. This is mostlyused in the case of inverse time overcurrent protection. Figure 65 shows how the time-

Section 8 1MRK 504 134-UEN ACurrent protection

148Application manual

Page 155: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

versus-current curves are plotted in a diagram. The time setting is chosen to get theshortest fault time with maintained selectivity. Selectivity is assured if the timedifference between the curves is larger than a critical time difference.

en05000204.wmf

IEC05000204 V1 EN

Figure 65: Fault time with maintained selectivity

To assure selectivity between different protections, in the radial network, there haveto be a minimum time difference Dt between the time delays of two protections. Theminimum time difference can be determined for different cases. To determine theshortest possible time difference, the operation time of protections, breaker openingtime and protection resetting time must be known. These time delays can varysignificantly between different protective equipment. The following time delays canbe estimated:

Protection operationtime:

15-60 ms

Protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

Example for time coordinationAssume two substations A and B directly connected to each other via one line, asshown in the figure 66. Consider a fault located at another line from the station B. The

1MRK 504 134-UEN A Section 8Current protection

149Application manual

Page 156: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

fault current to the overcurrent protection of IED B1 has a magnitude so that theprotection will have instantaneous function. The overcurrent protection of IED A1must have a delayed function. The sequence of events during the fault can bedescribed using a time axis, see figure 66.

I> I>

A1 B1 Feeder

Time axis

t=0 t=t1 t=t2 t=t3The faultoccurs

ProtectionB1 trips

Breaker atB1 opens

ProtectionA1 resets

en05000205.vsd

IEC05000205 V1 EN

Figure 66: Sequence of events during fault

where:

t=0 is when the fault occurs

t=t1 is when the trip signal from the overcurrent protection at IED B1 is sent to the circuit breaker. Theoperation time of this protection is t1

t=t2 is when the circuit breaker at IED B1 opens. The circuit breaker opening time is t2 - t1

t=t3 is when the overcurrent protection at IED A1 resets. The protection resetting time is t3 - t2.

To ensure that the overcurrent protection at IED A1, is selective to the overcurrentprotection at IED B1, the minimum time difference must be larger than the time t3.There are uncertainties in the values of protection operation time, breaker openingtime and protection resetting time. Therefore a safety margin has to be included. Withnormal values the needed time difference can be calculated according to equation 74.

40 100 40 40 220t ms ms ms ms msD ³ + + + =EQUATION1266 V1 EN (Equation 74)

where it is considered that:

the operate time of overcurrent protection B1 is 40 ms

the breaker open time is 100 ms

the resetting time of protection A1 is 40 ms and

the additional margin is 40 ms

Section 8 1MRK 504 134-UEN ACurrent protection

150Application manual

Page 157: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.3 Instantaneous residual overcurrent protectionEFPIOC

8.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Instantaneous residual overcurrentprotection

EFPIOC

IN>>

IEF V1 EN

50N

8.3.2 Application

In many applications, when fault current is limited to a defined value by the objectimpedance, an instantaneous earth-fault protection can provide fast and selectivetripping.

The Instantaneous residual overcurrent EFPIOC, which can operate in 15 ms (50 Hznominal system frequency) for faults characterized by very high currents, is includedin the IED.

8.3.3 Setting guidelines

The parameters for the Instantaneous residual overcurrent protection EFPIOC are setvia the local HMI or PCM600.

Some guidelines for the choice of setting parameter for EFPIOC is given.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

The setting of the function is limited to the operate residual current to the protection(IN>>).

The basic requirement is to assure selectivity, that is EFPIOC shall not be allowed tooperate for faults at other objects than the protected object (line).

For a normal line in a meshed system single phase-to-earth faults and phase-to-phase-to-earth faults shall be calculated as shown in figure 67 and figure 68. The residualcurrents (3I0) to the protection are calculated. For a fault at the remote line end thisfault current is IfB. In this calculation the operational state with high source impedanceZA and low source impedance ZB should be used. For the fault at the home busbar thisfault current is IfA. In this calculation the operational state with low source impedanceZA and high source impedance ZB should be used.

1MRK 504 134-UEN A Section 8Current protection

151Application manual

Page 158: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

~ ~ZA ZBZ L

A B

IED

I fB

Fault

IEC09000022-1-en.vsd

IEC09000022 V1 EN

Figure 67: Through fault current from A to B: IfB

IEC09000023-1-en.vsd

~ ~ZA ZBZ L

A B

IED

I fA

Fault

IEC09000023 V1 EN

Figure 68: Through fault current from B to A: IfA

The function shall not operate for any of the calculated currents to the protection. Theminimum theoretical current setting (Imin) will be:

Imin MAX IfA IfA,( )³

EQUATION284 V1 EN (Equation 75)

A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5%for maximum possible transient overreach have to be introduced. An additional 20%is suggested due to inaccuracy of instrument transformers under transient conditionsand inaccuracy in the system data.

The minimum primary current setting (Is) is:

m1.3.Is inI ³EQUATION285 V2 EN (Equation 76)

In case of parallel lines with zero sequence mutual coupling a fault on the parallel line,as shown in figure 69, should be calculated.

Section 8 1MRK 504 134-UEN ACurrent protection

152Application manual

Page 159: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000025-1-en.vsd

~ ~ZA ZB

ZL1A B

I M

Fault

IED

ZL2

M

CLine 1

Line 2

IEC09000025 V1 EN

Figure 69: Two parallel lines. Influence from parallel line to the through faultcurrent: IM

The minimum theoretical current setting (Imin) will in this case be:

I m in M AX IfA I fB IM, ,( )³

EQUATION287 V1 EN (Equation 77)

Where:

IfA and IfB have been described for the single line case.

Considering the safety margins mentioned previously, the minimum setting (Is) is:

m1.3.Is inI ³EQUATION288 V2 EN (Equation 78)

Transformer inrush current shall be considered.

The setting of the protection is set as a percentage of the base current (IBase).

Operation: set the protection to On or Off.

IN>>: Set operate current in % of IBase. IBase is a global parameter valid for allfunctions in the IED.

8.4 Four step residual overcurrent protection, zero,negative sequence direction EF4PTOC

1MRK 504 134-UEN A Section 8Current protection

153Application manual

Page 160: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Four step residual overcurrentprotection, zero or negative sequencedirection

EF4PTOC

2

IEC11000263 V1 EN

51N/67N

8.4.2 Application

The four step residual overcurrent protection, zero or negative sequence directionEF4PTOC is used in several applications in the power system. Some applications are:

• Earth-fault protection of feeders in effectively earthed distribution systems.Normally these feeders have radial structure.

• Back-up earth-fault protection of subtransmission and transmission lines.• Sensitive earth-fault protection of transmission lines. EF4PTOC can have better

sensitivity to detect resistive phase-to-earth-faults compared to distanceprotection.

• Back-up earth-fault protection of power transformers with earth source atsubstation.

• Earth-fault protection of different kinds of equipment connected to the powersystem such as shunt capacitor banks, shunt reactors and others.

• Negative sequence direcitonal earth-fault protection of feeders with PTsconnected in Open Delta connection from which it is not possible to derive Zerosequence voltage.

• Negative sequence directional earth-fault protection of double-circuit medium orlong transmission lines with significant mutual coupling.

In many applications several steps with different current operating levels and timedelays are needed. EF4PTOC can have up to four, individual settable steps. Theflexibility of each step of EF4PTOC is great. The following options are possible:

Non-directional/Directional function: In some applications the non-directionalfunctionality is used. This is mostly the case when no fault current can be fed from theprotected object itself. In order to achieve both selectivity and fast fault clearance, thedirectional function can be necessary. This can be the case for earth-fault protectionin meshed and effectively earthed transmission systems. The directional residualovercurrent protection is also well suited to operate in teleprotection communicationschemes, which enables fast clearance of earth faults on transmission lines. Thedirectional function uses the polarizing quantity as decided by setting. Voltagepolarizing (3U0 or U2) is most commonly used, but alternatively current polarizing(3I0 or I2) where currents in transformer neutrals providing the neutral (zero sequence)source (ZN) is used to polarize (IPol · ZN) the function. Dual polarizing where the sumof both voltage and current components is allowed to polarize can also be selected.

Section 8 1MRK 504 134-UEN ACurrent protection

154Application manual

Page 161: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Choice of time characteristics: There are several types of time characteristicsavailable such as definite time delay and different types of inverse timecharacteristics. The selectivity between different overcurrent protections is normallyenabled by co-ordination between the operate time of the different protections. Toenable optimal co-ordination all overcurrent protections, to be co-ordinated againsteach other, should have the same time characteristic. Therefore a wide range ofstandardized inverse time characteristics are available: IEC and ANSI. The timecharacteristic for step 1 and 4 can be chosen as definite time delay or inverse timecharacteristic. Step 2 and 3 are always definite time delayed and are used in systemwhere IDMT is not needed.

Table 15: Time characteristics

Curve nameANSI Extremely Inverse

ANSI Very Inverse

ANSI Normal Inverse

ANSI Moderately Inverse

ANSI/IEEE Definite time

ANSI Long Time Extremely Inverse

ANSI Long Time Very Inverse

ANSI Long Time Inverse

IEC Normal Inverse

IEC Very Inverse

IEC Inverse

IEC Extremely Inverse

IEC Short Time Inverse

IEC Long Time Inverse

IEC Definite Time

ASEA RI

RXIDG (logarithmic)

Power transformers can have a large inrush current, when being energized. Thisinrush current can have residual current components. The phenomenon is due tosaturation of the transformer magnetic core during parts of the cycle. There is a riskthat inrush current will give a residual current that reaches level above the operatingcurrent of the residual overcurrent protection. The inrush current has a large secondharmonic content. This can be used to avoid unwanted operation of the protection.Therefore, EF4PTOC has a possibility of second harmonic restrain 2ndHarmStab ifthe level of this harmonic current reaches a value above a set percentage of thefundamental current.

1MRK 504 134-UEN A Section 8Current protection

155Application manual

Page 162: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.4.3 Setting guidelines

When inverse time overcurrent characteristic is selected, the operatetime of the stage will be the sum of the inverse time delay and the setdefinite time delay. Thus, if only the inverse time delay is required, itis important to set the definite time delay for that stage to zero.

The parameters for the four step residual overcurrent protection, zero or negativesequence direction EF4PTOC are set via the local HMI or PCM600.

The following settings can be done for the four step residual overcurrent protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

SeqTypeUPol: It is used to select type of voltage polarization quantity, i.e. ZeroSeqand NegSeq for direction detection.

SeqTypeIPol: It is used to select type of current polarization quantity, i.e. ZeroSeq andNegSeq for direction detection.

SeqTypeIDir: It is used to select type of operating quantity, i.e. ZeroSeq and NegSeqfor direction detection.

Operation: Sets the protection to On or Off.

EnaDir: Enables the directional calculation in addition to the directional modeselection in each step.

8.4.3.1 Settings for steps 1 and 4

n means step 1 and 4. x means step 1, 2, 3 and 4.

DirModex: The directional mode of step x. Possible settings are Off/Non-directional/Forward/Reverse.

Characteristn: Selection of time characteristic for step n. Definite time delay anddifferent types of inverse time characteristics are available.

Inverse time characteristic enables fast fault clearance of high current faults at thesame time as selectivity to other inverse time phase overcurrent protections can beassured. This is mainly used in radial fed networks but can also be used in meshednetworks. In meshed networks the settings must be based on network faultcalculations.

To assure selectivity between different protections, in the radial network, there haveto be a minimum time difference Dt between the time delays of two protections. Theminimum time difference can be determined for different cases. To determine the

Section 8 1MRK 504 134-UEN ACurrent protection

156Application manual

Page 163: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

shortest possible time difference, the operation time of protections, breaker openingtime and protection resetting time must be known. These time delays can varysignificantly between different protective equipment. The following time delays canbe estimated:

Protection operate time: 15-60 ms

Protection resetting time: 15-60 ms

Breaker opening time: 20-120 ms

The different characteristics are described in the Technical Manual (TM).

tx: Definite time delay for step x. The definite time tx is added to the inverse time wheninverse time characteristic is selected.

INx>: Operate residual current level for step x given in % of IBase.

kn: Time multiplier for inverse time delay for step n.

IMinn: Minimum operate current for step n in % of IBase. Set IMinn below INx> forevery step to achieve ANSI reset characteristic according to standard. If IMinn is setabove INx> for any step then signal will reset at current equals to zero.

tnMin: Minimum operating time for inverse time characteristics. At high currents theinverse time characteristic might give a very short operation time. By setting thisparameter the operation time of the step n can never be shorter than the setting.

IEC09000164-2

Operate time

Current

tx

tnMin

IMinn

IEC09000164 V2 EN

Figure 70: Minimum operate current and operate time for inverse timecharacteristics

1MRK 504 134-UEN A Section 8Current protection

157Application manual

Page 164: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

In order to fully comply with curves definition the setting parameter txMin shall be setto the value which is equal to the operate time of the selected IEC inverse curve formeasured current of twenty times the set current pickup value. Note that the operatetime value is dependent on the selected setting value for time multiplier kn.

8.4.3.2 Common settings for all steps

tx: Definite time delay for step x. Used if definite time characteristic is chosen.

AngleRCA: Relay characteristic angle given in degree. This angle is defined as shownin figure 71. The angle is defined positive when the residual current lags the referencevoltage (Upol = 3U0 or U2)

Upol = 3U0 or U2

I>Dir

RCA

Operation

en 05000135-4-nsi.vsd

IEC05000135 V4 EN

Figure 71: Relay characteristic angle given in degree

In a normal transmission network a normal value of RCA is about 65°. The settingrange is -180° to +180°.

polMethod: Defines if the directional polarization is from

• Voltage (3U0 or U2)• Current (3I0 · ZNpol or 3I2 ·ZNpol where ZNpol is RNpol + jXNpol), or• both currents and voltage, Dual (dual polarizing, (3U0 + 3I0 · ZNpol) or (U2 + I2

· ZNpol)).

Normally voltage polarizing from the internally calculated residual sum or an externalopen delta is used.

Section 8 1MRK 504 134-UEN ACurrent protection

158Application manual

Page 165: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Current polarizing is useful when the local source is strong and a high sensitivity isrequired. In such cases the polarizing voltage (3U0) can be below 1% and it is thennecessary to use current polarizing or dual polarizing. Multiply the required setcurrent (primary) with the minimum impedance (ZNpol) and check that thepercentage of the phase-to-earth voltage is definitely higher than 1% (minimum3U0>UPolMin setting) as a verification.

RNPol, XNPol: The zero-sequence source is set in primary ohms as base for thecurrent polarizing. The polarizing voltage is then achieved as 3I0 · ZNpol. The ZNpolcan be defined as (ZS1-ZS0)/3, that is the earth return impedance of the source behindthe protection. The maximum earth-fault current at the local source can be used tocalculate the value of ZN as U/(√3 · 3I0) Typically, the minimum ZNPol (3 · zerosequence source) is set. Setting is in primary ohms.

When the dual polarizing method is used it is important that the product INx>· ZNpolis not greater than 3U0. If so, there is a risk for incorrect operation for faults in thereverse direction.

IPolMin: is the minimum earth-fault current accepted for directional evaluation. Forsmaller currents than this value the operation will be blocked. Typical setting is 5-10%of IBase.

UPolMin: Minimum polarization (reference) residual voltage for the directionalfunction, given in % of UBase/√3.

I>Dir: Operate residual current release level in % of IBase for directional comparisonscheme. The setting is given in % of IBase and must be set below the lowest INx>setting, set for the directional measurement. The output signals, STFW and STRV canbe used in a teleprotection scheme. The appropriate signal should be configured to thecommunication scheme block.

8.4.3.3 2nd harmonic restrain

If a power transformer is energized there is a risk that the current transformer core willsaturate during part of the period, resulting in a transformer inrush current. This willgive a declining residual current in the network, as the inrush current is deviatingbetween the phases. There is a risk that the residual overcurrent function will give anunwanted trip. The inrush current has a relatively large ratio of 2nd harmoniccomponent. This component can be used to create a restrain signal to prevent thisunwanted function.

At current transformer saturation a false residual current can be measured by theprotection. Also here the 2nd harmonic restrain can prevent unwanted operation.

2ndHarmStab: The rate of 2nd harmonic current content for activation of the 2ndharmonic restrain signal. The setting is given in % of the fundamental frequencyresidual current.

HarmRestrainx: Enable block of step x from the harmonic restrain function.

1MRK 504 134-UEN A Section 8Current protection

159Application manual

Page 166: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.4.3.4 Transformer application example

Two main cases are of interest when residual overcurrent protection is used for apower transformer, namely if residual current can be fed from the protectedtransformer winding or not.

The protected winding will feed earth-fault (residual) current to earth faults in theconnected power system. The residual current fed from the transformer at externalphase-to-earth faults, is highly dependent of the total positive and zero-sequencesource impedances as well as the residual current distribution between the networkzero-sequence impedance and the transformer zero-sequence impedance. An exampleof this application is shown in figure 72.

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

en05000490.vsd

IEC05000490 V1 EN

Figure 72: Residual overcurrent protection application on a directly earthedtransformer winding

In this case the protection has two different tasks:

• Detection of earth faults on the transformer winding, to which the protection isconnected.

• Detection of earth faults in the power system, to which the protected winding isconnected.

It can be suitable to use a residual overcurrent protection with at least two steps. Step1 shall have a short definite time delay and a relatively high current setting, in orderto detect and clear high current earth faults in the transformer winding or in the powersystem close to the transformer. Step 2 shall have a longer time delay (definite orinverse time delay) and a lower current operation level. Step 2 shall detect and cleartransformer winding earth faults with low earth-fault current, that is, faults close to thetransformer winding neutral point. If the current setting gap between step 1 and step

Section 8 1MRK 504 134-UEN ACurrent protection

160Application manual

Page 167: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2 is large another step can be introduced with a current and time delay setting betweenthe two described steps.

The transformer inrush current will have a large residual current component. Toprevent unwanted function of the earth-fault overcurrent protection, the 2nd harmonicrestrain blocking should be used, at least for the sensitive step 2.

If the protected winding will not feed earth-fault (residual) current to earth faults in theconnected power system the application is as shown in figure 73.

IN>

Three phase CTsummated

Y/Y, Y/D or D/Ytransformer

en05000491.vsd

IEC05000491 V1 EN

Figure 73: Residual overcurrent protection application on an isolatedtransformer winding

In the calculation of the fault current fed to the protection, at different earth faults, arehighly dependent on the positive and zero sequence source impedances, as well as thedivision of residual current in the network. Earth-fault current calculations arenecessary for the setting.

Setting of step 1One requirement is that earth faults at the busbar, where the transformer winding isconnected, shall be detected. Therefore a fault calculation as shown in figure 74 ismade.

1MRK 504 134-UEN A Section 8Current protection

161Application manual

Page 168: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

Single phase-to-earth fault

3I0

IEC05000492-en-2.vsd

IEC05000492 V2 EN

Figure 74: Step 1 fault calculation 1

This calculation gives the current fed to the protection: 3I0fault1.

To assure that step 1, selectivity to other earth-fault protections in the network a shortdelay is selected. Normally, a delay in the range 0.3 – 0.4 s is appropriate. To assureselectivity to line faults, tripped after a delay (typically distance protection zone 2) ofabout 0.5 s the current setting must be set so high so that such faults does not causeunwanted step 1 trip. Therefore, a fault calculation as shown in figure 75 is made.

IN>

alt

Three phase CTsummated

Single CT

YN/D or YN/Ytransformer

Single phase-to-earth fault

3I0

IEC05000493-en-2.vsd

IEC05000493 V2 EN

Figure 75: Step 1 fault calculation 1

Section 8 1MRK 504 134-UEN ACurrent protection

162Application manual

Page 169: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The fault is located at the borderline between instantaneous and delayed operation ofthe line protection, such as Distance protection or line residual overcurrent protection.This calculation gives the current fed to the protection: 3I0fault2

The setting of step 1 can be chosen within the interval shown in equation 79.

0fault 2 step1 0fault13I lowmar I 3I highmar× < < ×

EQUATION1455 V2 EN (Equation 79)

Where:

lowmar is a margin to assure selectivity (typical 1.2) and

highmar is a margin to assure fast fault clearance of busbar fault (typical 1.2).

Setting of step 2The setting of the sensitive step 2 is dependent of the chosen time delay. Often arelatively long definite time delay or inverse time delay is chosen. The current settingcan be chosen very low. As it is required to detect earth faults in the transformerwinding, close to the neutral point, values down to the minimum setting possibilitiescan be chosen. However, one must consider zero-sequence currents that can occurduring normal operation of the power system. Such currents can be due to un-transposed lines.

In case to protection of transformer windings not feeding residual current at externalearth faults a fast lowcurrent step can be acceptable.

8.5 Thermal overload protection, two time constantsTRPTTR

8.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Thermal overload protection, two timeconstants

TRPTTR

SYMBOL-A V1 EN

49

8.5.2 Application

Transformers in the power system are designed for a certain maximum load current(power) level. If the current exceeds this level the losses will be higher than expected.

1MRK 504 134-UEN A Section 8Current protection

163Application manual

Page 170: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

As a consequence the temperature of the transformer will increase. If the temperatureof the transformer reaches too high values the equipment might be damaged:

• The insulation within the transformer will experience forced ageing. As aconsequence of this, the risk of internal phase-to-phase or phase-to-earth faultswill increase.

• There might be hot spots within the transformer, which will degrade the paperinsulation. It might also cause bubbling in the transformer oil.

In stressed situations in the power system it can be required to overload transformersfor a limited time. This should be done without the above mentioned risks. Thethermal overload protection provides information and makes temporary overloadingof transformers possible.

The permissible load level of a power transformer is highly dependent on the coolingsystem of the transformer. There are two main principles:

• OA: The air is naturally circulated to the coolers without fans and the oil isnaturally circulated without pumps.

• FOA: The coolers have fans to force air for cooling and pumps to force thecirculation of the transformer oil.

The protection can have two sets of parameters, one for non-forced cooling and onefor forced cooling. Both the permissive steady state loading level as well as thethermal time constant is influenced by the cooling system of the transformer. The twoparameters sets can be activated by the binary input signal COOLING. This can beused for transformers where forced cooling can be taken out of operation, for exampleat fan or pump faults.

The thermal overload protection estimates the internal heat content of the transformer(temperature) continuously. This estimation is made by using a thermal model of thetransformer, which is based on current measurement.

If the heat content of the protected transformer reaches a set alarm level a signal canbe given to the operator. Two alarm levels are available. This enables preventiveactions in the power system to be taken before dangerous temperatures are reached. Ifthe temperature continues to increase to the trip value, the protection initiates a trip ofthe protected transformer.

After tripping by the thermal overload protection, the transformer will cool down overtime. There will be a time gap before the heat content (temperature) reaches such alevel so that the transformer can be taken into service again. Therefore, the functionwill continue to estimate the heat content using a set cooling time constant. Energizingof the transformer can be blocked until the heat content has reached a set level.

8.5.3 Setting guideline

The parameters for the thermal overload protection, two time constants (TRPTTR) areset via the local HMI or through the Protection and Control Manager (PCM600).

Section 8 1MRK 504 134-UEN ACurrent protection

164Application manual

Page 171: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The following settings can be done for the thermal overload protection:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Sets the mode of operation. Off switches off the complete function.

IRef: Reference level of the current given in % of IBase. When the current is equal toIRef the final (steady state) heat content is equal to 1. It is suggested to give a settingcorresponding to the rated current of the transformer winding. Transformer ratedcurrent / IBase* 100%.

IBase1: Base current for setting given as percentage of IBase. This setting shall berelated to the status with no COOLING input. It is suggested to give a settingcorresponding to the rated current of the transformer with natural cooling (OA).

IBase2: Base current for setting given as percentage of IBase. This setting shall berelated to the status with activated COOLING input. It is suggested to give a settingcorresponding to the rated current of the transformer with forced cooling (FOA). If thetransformer has no forced cooling IBase2 can be set equal to IBase1.

Tau1: The thermal time constant of the protected transformer, related to IBase1 (nocooling) given in minutes.

Tau2: The thermal time constant of the protected transformer, related to IBase2 (withcooling) given in minutes.

The thermal time constant should be obtained from the transformer manufacturersmanuals. The thermal time constant is dependent on the cooling and the amount of oil.Normal time constants for medium and large transformers (according to IEC 60076-7)are about 2.5 hours for naturally cooled transformers and 1.5 hours for forced cooledtransformers.

The time constant can be estimated from measurements of the oil temperature duringa cooling sequence (described in IEC 60076-7). It is assumed that the transformer isoperated at a certain load level with a constant oil temperature (steady state operation).The oil temperature above the ambient temperature is DQo0. Then the transformer isdisconnected from the grid (no load). After a time t of at least 30 minutes thetemperature of the oil is measured again. Now the oil temperature above the ambienttemperature is DQot. The thermal time constant can now be estimated as:

0ln lno ot

tt =DQ - DQ

EQUATION1180 V1 EN (Equation 80)

If the transformer has forced cooling (FOA) the measurement should be made bothwith and without the forced cooling in operation, giving Tau2 and Tau1.

The time constants can be changed if the current is higher than a set value or lower thana set value. If the current is high it is assumed that the forced cooling is activated while

1MRK 504 134-UEN A Section 8Current protection

165Application manual

Page 172: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

it is deactivated at low current. The setting of the parameters below enables automaticadjustment of the time constant.

Tau1High: Multiplication factor to adjust the time constant Tau1 if the current ishigher than the set value IHighTau1. IHighTau1 is set in % of IBase1.

Tau1Low: Multiplication factor to adjust the time constant Tau1 if the current is lowerthan the set value ILowTau1. ILowTau1 is set in % of IBase1.

Tau2High: Multiplication factor to adjust the time constant Tau2 if the current ishigher than the set value IHighTau2. IHighTau2 is set in % of IBase2.

Tau2Low: Multiplication factor to adjust the time constant Tau2 if the current is lowerthan the set value ILowTau2. ILowTau2 is set in % of IBase2.

The possibility to change time constant with the current value as the base can be usefulin different applications. Below some examples are given:

• In case a total interruption (low current) of the protected transformer all coolingpossibilities will be inactive. This can result in a changed value of the timeconstant.

• If other components (motors) are included in the thermal protection, there is a riskof overheating of that equipment in case of very high current. The thermal timeconstant is often smaller for a motor than for the transformer.

ITrip: The steady state current that the transformer can withstand. The setting is givenin % of IBase1 or IBase2.

Alarm1: Heat content level for activation of the signal ALARM1. ALARM1 is set in% of the trip heat content level.

Alarm2: Heat content level for activation of the output signal ALARM2. ALARM2 isset in % of the trip heat content level.

ResLo: Lockout release level of heat content to release the lockout signal. When thethermal overload protection trips a lock-out signal is activated. This signal is intendedto block switching on of the protected circuit transformer as long as the transformertemperature is high. The signal is released when the estimated heat content is belowthe set value. This temperature value should be chosen below the alarm temperature.ResLo is set in % of the trip heat content level.

Warning: If the calculated time to trip factor is below the setting Warning a warningsignal is activated. The setting is given in minutes.

8.6 Breaker failure protection 3-phase activation andoutput CCRBRF

Section 8 1MRK 504 134-UEN ACurrent protection

166Application manual

Page 173: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Breaker failure protection, 3-phaseactivation and output

CCRBRF

3I>BF

SYMBOL-U V1 EN

50BF

8.6.2 Application

In the design of the fault clearance system the N-1 criterion is often used. This meansthat a fault needs to be cleared even if any component in the fault clearance system isfaulty. One necessary component in the fault clearance system is the circuit breaker.It is from practical and economical reason not feasible to duplicate the circuit breakerfor the protected component. Instead a breaker failure protection is used.

Breaker failure protection, 3-phase activation and output (CCRBRF) will issue aback-up trip command to adjacent circuit breakers in case of failure to trip of the“normal” circuit breaker for the protected component. The detection of failure tobreak the current through the breaker is made by means of current measurement or asdetection of remaining trip signal (unconditional).

CCRBRF can also give a re-trip. This means that a second trip signal is sent to theprotected circuit breaker. The re-trip function can be used to increase the probabilityof operation of the breaker, or it can be used to avoid back-up trip of many breakersin case of mistakes during relay maintenance and test.

8.6.3 Setting guidelines

The parameters for Breaker failure protection 3-phase activation and output CCRBRFare set via the local HMI or PCM600.

The following settings can be done for the breaker failure protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On

FunctionMode This parameter can be set Current or Contact. This states the way thedetection of failure of the breaker is performed. In the mode current the currentmeasurement is used for the detection. In the mode Contact the long duration ofbreaker position signal is used as indicator of failure of the breaker. The modeCurrent&Contact means that both ways of detections are activated. Contact mode canbe usable in applications where the fault current through the circuit breaker is small.This can be the case for some generator protection application (for example reversepower protection) or in case of line ends with weak end infeed.

1MRK 504 134-UEN A Section 8Current protection

167Application manual

Page 174: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

RetripMode: This setting states how the re-trip function shall operate. Retrip Offmeans that the re-trip function is not activated. CB Pos Check (circuit breaker positioncheck) and Current means that a phase current must be larger than the operate level toallow re-trip. CB Pos Check (circuit breaker position check) and Contact means re-tripis done when circuit breaker is closed (breaker position is used). No CBPos Checkmeans re-trip is done without check of breaker position.

Table 16: Dependencies between parameters RetripMode and FunctionMode

RetripMode FunctionMode DescriptionRetrip Off N/A the re-trip function is not

activated

CB Pos Check Current a phase current must be largerthan the operate level to allowre-trip

Contact re-trip is done when breakerposition indicates that breaker isstill closed after re-trip time haselapsed

Current&Contact both methods are used

No CBPos Check Current re-trip is done without check ofbreaker position

Contact re-trip is done without check ofbreaker position

Current&Contact both methods are used

BuTripMode: Back-up trip mode is given to state sufficient current criteria to detectfailure to break. For Current operation 2 out of 4 means that at least two currents, ofthe three-phase currents and the residual current, shall be high to indicate breakerfailure. 1 out of 3 means that at least one current of the three-phase currents shall behigh to indicate breaker failure. 1 out of 4 means that at least one current of the three-phase currents or the residual current shall be high to indicate breaker failure. In mostapplications 1 out of 3 is sufficient. For Contact operation means back-up trip is donewhen circuit breaker is closed (breaker position is used).

IP>: Current level for detection of breaker failure, set in % of IBase. This parametershould be set so that faults with small fault current can be detected. The setting can bechosen in accordance with the most sensitive protection function to start the breakerfailure protection. Typical setting is 10% of IBase.

I>BlkCont: If any contact based detection of breaker failure is used this function canbe blocked if any phase current is larger than this setting level. If the FunctionMode isset Current&Contact breaker failure for high current faults are safely detected by thecurrent measurement function. To increase security the contact based function shouldbe disabled for high currents. The setting can be given within the range 5 – 200% ofIBase.

IN>: Residual current level for detection of breaker failure set in % of IBase. In highimpedance earthed systems the residual current at phase- to-earth faults are normallymuch smaller than the short circuit currents. In order to detect breaker failure at single-

Section 8 1MRK 504 134-UEN ACurrent protection

168Application manual

Page 175: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

phase-earth faults in these systems it is necessary to measure the residual currentseparately. Also in effectively earthed systems the setting of the earth-fault currentprotection can be chosen to relatively low current level. The BuTripMode is set 1 outof 4. The current setting should be chosen in accordance to the setting of the sensitiveearth-fault protection. The setting can be given within the range 2 – 200 % of IBase.

t1: Time delay of the re-trip. The setting can be given within the range 0 – 60s in stepsof 0.001 s. Typical setting is 0 – 50ms.

t2: Time delay of the back-up trip. The choice of this setting is made as short aspossible at the same time as unwanted operation must be avoided. Typical setting is 90– 200ms (also dependent of re-trip timer).

The minimum time delay for the re-trip can be estimated as:

_2 1³ + + +cbopen BFP reset margint t t t tEQUATION1430 V1 EN (Equation 81)

where:

tcbopen is the maximum opening time for the circuit breaker

tBFP_reset is the maximum time for breaker failure protection to detect correct breaker function (thecurrent criteria reset)

tmargin is a safety margin

It is often required that the total fault clearance time shall be less than a given criticaltime. This time is often dependent of the ability to maintain transient stability in caseof a fault close to a power plant.

1MRK 504 134-UEN A Section 8Current protection

169Application manual

Page 176: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Time

The fault occurs

Protection operate time

Trip and Start CCRBRF

Normal tcbopen

Margin

Retrip delay t1 tcbopen after re-trip

tBFPreset

Minimum back-up trip delay t2

Critical fault clearance time for stability

IEC05000479_2_en.vsd

IEC05000479 V2 EN

Figure 76: Time sequence

8.7 Pole discordance protection CCRPLD

8.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Pole discordance protection CCRPLD

PD

SYMBOL-S V1 EN

52PD

8.7.2 Application

There is a risk that a circuit breaker will get discordance between the poles at circuitbreaker operation: closing or opening. One pole can be open and the other two closed,or two poles can be open and one closed. Pole discordance of a circuit breaker willcause unsymmetrical currents in the power system. The consequence of this can be:

• Negative sequence currents that will give stress on rotating machines• Zero sequence currents that might give unwanted operation of sensitive earth-

fault protections in the power system.

Section 8 1MRK 504 134-UEN ACurrent protection

170Application manual

Page 177: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

It is therefore important to detect situations with pole discordance of circuit breakers.When this is detected the breaker should be tripped directly.

Pole discordance protection CCRPLD will detect situation with deviating positions ofthe poles of the protected circuit breaker. The protection has two different options tomake this detection:

• By connecting the auxiliary contacts in the circuit breaker so that logic is createdand a signal can be sent to the pole discordance protection, indicating polediscordance.

• Each phase current through the circuit breaker is measured. If the differencebetween the phase currents is larger than a CurrUnsymLevel this is an indicationof pole discordance, and the protection will operate.

8.7.3 Setting guidelines

The parameters for the Pole discordance protection CCRPLD are set via the local HMIor PCM600.

The following settings can be done for the pole discordance protection.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off or On

tTrip: Time delay of the operation.

ContSel: Operation of the contact based pole discordance protection. Can be set:Off/PD signal from CB. If PD signal from CB is chosen the logic to detect polediscordance is made in the vicinity to the breaker auxiliary contacts and only onesignal is connected to the pole discordance function.

CurrSel: Operation of the current based pole discordance protection. Can be set:Off/CB oper monitor/Continuous monitor. In the alternative CB oper monitor thefunction is activated only directly in connection to breaker open or close command(during 200 ms). In the alternative Continuous monitor function is continuouslyactivated.

CurrUnsymLevel: Unsymmetrical magnitude of lowest phase current compared to thehighest, set in % of the highest phase current.

CurrRelLevel: Current magnitude for release of the function in % of IBase.

8.8 Directional over-/under-power protectionGOPPDOP/GUPPDUP

1MRK 504 134-UEN A Section 8Current protection

171Application manual

Page 178: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.8.1 Application

The task of a generator in a power plant is to convert mechanical energy available asa torque on a rotating shaft to electric energy.

Sometimes, the mechanical power from a prime mover may decrease so much that itdoes not cover bearing losses and ventilation losses. Then, the synchronous generatorbecomes a synchronous motor and starts to take electric power from the rest of thepower system. This operating state, where individual synchronous machines operateas motors, implies no risk for the machine itself. If the generator under considerationis very large and if it consumes lots of electric power, it may be desirable to disconnectit to ease the task for the rest of the power system.

Often, the motoring condition may imply that the turbine is in a very dangerous state.The task of the reverse power protection is to protect the turbine and not to protect thegenerator itself.

Steam turbines easily become overheated if the steam flow becomes too low or if thesteam ceases to flow through the turbine. Therefore, turbo-generators should havereverse power protection. There are several contingencies that may cause reversepower: break of a main steam pipe, damage to one or more blades in the steam turbineor inadvertent closing of the main stop valves. In the last case, it is highly desirable tohave a reliable reverse power protection. It may prevent damage to an otherwiseundamaged plant.

During the routine shutdown of many thermal power units, the reverse powerprotection gives the tripping impulse to the generator breaker (the unit breaker). Bydoing so, one prevents the disconnection of the unit before the mechanical power hasbecome zero. Earlier disconnection would cause an acceleration of the turbinegenerator at all routine shutdowns. This should have caused overspeed and highcentrifugal stresses.

When the steam ceases to flow through a turbine, the cooling of the turbine blades willdisappear. Now, it is not possible to remove all heat generated by the windage losses.Instead, the heat will increase the temperature in the steam turbine and especially ofthe blades. When a steam turbine rotates without steam supply, the electric powerconsumption will be about 2% of rated power. Even if the turbine rotates in vacuum,it will soon become overheated and damaged. The turbine overheats within minutes ifthe turbine loses the vacuum.

The critical time to overheating a steam turbine varies from about 0.5 to 30 minutesdepending on the type of turbine. A high-pressure turbine with small and thin bladeswill become overheated more easily than a low-pressure turbine with long and heavyblades. The conditions vary from turbine to turbine and it is necessary to ask theturbine manufacturer in each case.

Power to the power plant auxiliaries may come from a station service transformerconnected to the secondary side of the step-up transformer. Power may also comefrom a start-up service transformer connected to the external network. One has to

Section 8 1MRK 504 134-UEN ACurrent protection

172Application manual

Page 179: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

design the reverse power protection so that it can detect reverse power independent ofthe flow of power to the power plant auxiliaries.

Hydro turbines tolerate reverse power much better than steam turbines do. OnlyKaplan turbine and bulb turbines may suffer from reverse power. There is a risk thatthe turbine runner moves axially and touches stationary parts. They are not alwaysstrong enough to withstand the associated stresses.

Ice and snow may block the intake when the outdoor temperature falls far below zero.Branches and leaves may also block the trash gates. A complete blockage of the intakemay cause cavitations. The risk for damages to hydro turbines can justify reversepower protection in unattended plants.

A hydro turbine that rotates in water with closed wicket gates will draw electric powerfrom the rest of the power system. This power will be about 10% of the rated power.If there is only air in the hydro turbine, the power demand will fall to about 3%.

Diesel engines should have reverse power protection. The generator will take about15% of its rated power or more from the system. A stiff engine may require perhaps25% of the rated power to motor it. An engine that is good run in might need no morethan 5%. It is necessary to obtain information from the engine manufacturer and tomeasure the reverse power during commissioning.

Gas turbines usually do not require reverse power protection.

Figure 77 illustrates the reverse power protection with underpower protection andwith overpower protection. The underpower protection gives a higher margin andshould provide better dependability. On the other hand, the risk for unwantedoperation immediately after synchronization may be higher. One should set theunderpower protection (reference angle set to 0) to trip if the active power from thegenerator is less than about 2%. One should set the overpower protection (referenceangle set to 180) to trip if the power flow from the network to the generator is higherthan 1%.

Underpower protection Overpower protection

Q Q

P P

Operating point without turbine torque

Margin Margin

OperateLine

OperateLine

Operating point without turbine torque

IEC09000019-2-en.vsd

IEC09000019 V2 EN

Figure 77: Reverse power protection with underpower or overpower protection

1MRK 504 134-UEN A Section 8Current protection

173Application manual

Page 180: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.8.2 Directional overpower protection GOPPDOP

8.8.2.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Directional overpower protection GOPPDOPP >

2DOCUMENT172362-IMG158942

V2 EN

32

8.8.2.2 Setting guidelines

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: With the parameter Operation the function can be set On/Off.

Mode: The voltage and current used for the power measurement. The settingpossibilities are shown in table 17.

For reverse power applications PosSeq or Arone modes are strongly recommended.

Table 17: Complex power calculation

Set value Mode Formula used for complex power calculationL1, L2, L3 * * *

1 1 2 2 3 3L L L L L LS U I U I U I= × + × + ×

EQUATION1697 V1 EN (Equation 82)

Arone * *1 2 1 2 3 3L L L L L LS U I U I= × - ×

EQUATION1698 V1 EN (Equation 83)

PosSeq *3 PosSeq PosSeqS U I= × ×

EQUATION1699 V1 EN (Equation 84)

L1L2 * *1 2 1 2( )L L L LS U I I= × -

EQUATION1700 V1 EN (Equation 85)

L2L3 * *2 3 2 3( )L L L LS U I I= × -

EQUATION1701 V1 EN (Equation 86)

L3L1 * *3 1 3 1( )L L L LS U I I= × -

EQUATION1702 V1 EN (Equation 87)

Table continues on next page

Section 8 1MRK 504 134-UEN ACurrent protection

174Application manual

Page 181: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Set value Mode Formula used for complex power calculationL1 *

1 13 L LS U I= × ×

EQUATION1703 V1 EN (Equation 88)

L2 *2 23 L LS U I= × ×

EQUATION1704 V1 EN (Equation 89)

L3 *3 33 L LS U I= × ×

EQUATION1705 V1 EN (Equation 90)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off.

The function gives trip if the power component in the direction defined by the settingAngle1(2) is larger than the set pick up power value Power1(2)

Operate

Angle1(2)

Power1(2)

P

Q

en06000440.vsd

IEC06000440 V1 EN

Figure 78: Overpower mode

The setting Power1(2) gives the power component pick up value in the Angle1(2)direction. The setting is given in p.u. of the generator rated power, see equation 91.

1MRK 504 134-UEN A Section 8Current protection

175Application manual

Page 182: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Minimum recommended setting is 1.0% of SN. Note also that at the same time theminimum IED pickup current shall be at least 9 mA secondary.

3NS UBase IBase= × ×

EQUATION1708 V1 EN (Equation 91)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity of thepower protection function. The setting is given in degrees. For active power the setangle should be 0° or 180°. 180° should be used for generator reverse power protectionin 50Hz network while -179.5° should be used for generator reverse power protectionin 60Hz network. This angle adjustment in 60Hz networks will improve accuracy ofthe power function.

Operate Angle1(2 ) = 180 o

Power1(2)

P

Q

IEC06000557-2-en.vsdIEC06000557 V2 EN

Figure 79: For reverse power the set angle should be 180° in the overpowerfunction

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.

The possibility to have low pass filtering of the measured power can be made as shownin the formula:

Section 8 1MRK 504 134-UEN ACurrent protection

176Application manual

Page 183: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

( )1Old CalculatedS k S k S= × + - ×

EQUATION1893 V1 EN (Equation 92)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter

The value of k=0.98 or even k=0.99 is recommended in generator reverse powerapplications as the trip delay is normally quite long. This filtering will improveaccuracy of the power function.

8.8.3 Directional underpower protection GUPPDUP

8.8.3.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Directional underpower protection GUPPDUPP <

2SYMBOL-LL V2 EN

37

8.8.3.2 Setting guidelines

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: With the parameter Operation the function can be set On/Off.

Mode: The voltage and current used for the power measurement. The settingpossibilities are shown in table 18.

For reverse power applications PosSeq or Arone modes are strongly recommended.

1MRK 504 134-UEN A Section 8Current protection

177Application manual

Page 184: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 18: Complex power calculation

Set value Mode Formula used for complex power calculationL1, L2, L3 * * *

1 1 2 2 3 3L L L L L LS U I U I U I= × + × + ×

EQUATION1697 V1 EN (Equation 93)

Arone * *1 2 1 2 3 3L L L L L LS U I U I= × - ×

EQUATION1698 V1 EN (Equation 94)

PosSeq *3 PosSeq PosSeqS U I= × ×

EQUATION1699 V1 EN (Equation 95)

L1L2 * *1 2 1 2( )L L L LS U I I= × -

EQUATION1700 V1 EN (Equation 96)

L2L3 * *2 3 2 3( )L L L LS U I I= × -

EQUATION1701 V1 EN (Equation 97)

L3L1 * *3 1 3 1( )L L L LS U I I= × -

EQUATION1702 V1 EN (Equation 98)

L1 *1 13 L LS U I= × ×

EQUATION1703 V1 EN (Equation 99)

L2 *2 23 L LS U I= × ×

EQUATION1704 V1 EN (Equation 100)

L3 *3 33 L LS U I= × ×

EQUATION1705 V1 EN (Equation 101)

The function has two stages that can be set independently.

With the parameter OpMode1(2) the function can be set On/Off.

The function gives trip if the power component in the direction defined by the settingAngle1(2) is smaller than the set pick up power value Power1(2)

Section 8 1MRK 504 134-UEN ACurrent protection

178Application manual

Page 185: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Operate

Angle1(2)

Power1(2)

P

Q

en06000441.vsd

IEC06000441 V1 EN

Figure 80: Underpower mode

The setting Power1(2) gives the power component pick up value in the Angle1(2)direction. The setting is given in p.u. of the generator rated power, see equation 102.

Minimum recommended setting is 1.0% of SN. At the same time the minimum IEDpickup current shall be at least 9 mA secondary.

3NS UBase IBase= × ×

EQUATION1708 V1 EN (Equation 102)

The setting Angle1(2) gives the characteristic angle giving maximum sensitivity of thepower protection function. The setting is given in degrees. For active power the setangle should be 0° or 180°. 0° should be used for generator low forward active powerprotection.

1MRK 504 134-UEN A Section 8Current protection

179Application manual

Page 186: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

OperateAngle1(2) = 0°

Power1(2)

P

Q

en06000556.vsdIEC06000556 V1 EN

Figure 81: For low forward power the set angle should be 0° in the underpowerfunction

TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.

The possibility to have low pass filtering of the measured power can be made as shownin the formula:

( )1Old CalculatedS k S k S= × + - ×

EQUATION1893 V1 EN (Equation 103)

Where

S is a new measured value to be used for the protection function

Sold is the measured value given from the function in previous execution cycle

SCalculated is the new calculated value in the present execution cycle

k is settable parameter

The value of k=0.98 or even k=0.99 is recommended in generator low forward powerapplications as the trip delay is normally quite long. This filtering will improveaccuracy of the power function.

Section 8 1MRK 504 134-UEN ACurrent protection

180Application manual

Page 187: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

8.9 Negative sequence based overcurrent functionDNSPTOC

8.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Negative sequence based overcurrentfunction

DNSPTOC

3I2>

IEC09000132 V2 EN

46

8.9.2 Application

Negative sequence based overcurrent function DNSPTOC is typically used assensitive earth-fault protection of power lines, where incorrect zero sequencepolarization may result from mutual induction between two or more parallel lines.

Additionally, it is applied in applications on cables, where zero sequence impedancedepends on the fault current return paths, but the cable negative sequence impedanceis practically constant.

The directional function is current and voltage polarized. The function can be set toforward, reverse or non-directional independently for each step. Both steps areprovided with a settable definite time delay.

DNSPTOC protects against all unbalanced faults including phase-to-phase faults. Theminimum start current of the function must be set to above the normal systemunbalance level in order to avoid unwanted operation.

8.9.3 Setting guidelines

Below is an example of Negative sequence based overcurrent function (DNSPTOC)used as a sensitive earth-fault protection for power lines. The following settings mustbe done in order to ensure proper operation of the protection:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

• setting RCADir to value +65 degrees, that is, the negative sequence currenttypically lags the inverted negative sequence voltage for this angle during thefault

• setting ROADir to value 90 degrees• setting LowVolt_VM to value 2%, that is, the negative sequence voltage level

above which the directional element will be enabled• setting Operation_OC1 to On• setting StartCurr_OC1 to value between 3-10%, (typical values)

1MRK 504 134-UEN A Section 8Current protection

181Application manual

Page 188: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• setting tDef_OC1 to insure proper time coordination with other earth-faultprotections installed in the vicinity of this power line

• setting DirMode_OC1 to Forward• setting DirPrinc_OC1 to IcosPhi&U• setting ActLowVolt1_VM to Block

DNSPTOC is used in directional comparison protection scheme for the power lineprotection, when communication channels to the remote end of this power line areavailable. In that case, two negative sequence overcurrent steps are required - one inforward and another in reverse direction. The OC1 stage is used to detect faults inforward direction and the OC2 stage is used to detect faults in reverse direction.

However, the following must be noted for such application:

• setting RCADir and ROADir are applicable for both steps OC1 and OC2• setting DirMode_OC1 must be set to Forward• setting DirMode_OC2 must be set to Reverse• setting StartCurr_OC2 must be made more sensitive than pickup value of the

forward OC1 element, that is, typically 60% of StartCurr_OC1 set pickup levelin order to insure proper operation of the directional comparison scheme duringcurrent reversal situations

• the start signals STOC1 and STOC2 from OC1 and OC2 elements is used to sendforward and reverse signals to the remote end of the power line

• the available scheme communications function block within IED is used betweenthe protection function and the teleprotection communication equipment, inorder to insure proper conditioning of the above two start signals.

ActLowVolt1 and ActLowVolt2 should not be set to Memory.

Section 8 1MRK 504 134-UEN ACurrent protection

182Application manual

Page 189: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 9 Voltage protection

9.1 Two step undervoltage protection UV2PTUV

9.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step undervoltage protection UV2PTUV

3U<

SYMBOL-R-2U-GREATER-THANV2 EN

27

9.1.2 Application

Two-step undervoltage protection function (UV2PTUV) is applicable in allsituations, where reliable detection of low phase voltages is necessary. It is used alsoas a supervision and fault detection function for other protection functions, to increasethe security of a complete protection system.

UV2PTUV is applied to power system elements, such as generators, transformers,motors and power lines in order to detect low voltage conditions. Low voltageconditions are caused by abnormal operation or fault in the power system. UV2PTUVis used in combination with overcurrent protections, either as restraint or in logic "andgates" of the trip signals issued by the two functions. Other applications are thedetection of "no voltage" condition, for example, before the energization of a HV lineor for automatic breaker trip in case of a blackout. UV2PTUV is also used to initiatevoltage correction measures, like insertion of shunt capacitor banks to compensate forreactive load and thereby increasing the voltage. The function has a high measuringaccuracy to allow applications to control reactive load.

UV2PTUV is used to disconnect apparatuses, like electric motors, which will bedamaged when subject to service under low voltage conditions. UV2PTUV deals withlow voltage conditions at power system frequency, which can be caused by thefollowing reasons:

1. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

2. Overload (symmetrical voltage decrease).3. Short circuits, often as phase-to-earth faults (unsymmetrical voltage decrease).

1MRK 504 134-UEN A Section 9Voltage protection

183Application manual

Page 190: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

UV2PTUV prevents sensitive equipment from running under conditions that couldcause their overheating and thus shorten their life time expectancy. In many cases, itis a useful function in circuits for local or remote automation processes in the powersystem.

9.1.3 Setting guidelines

All the voltage conditions in the system where UV2PTUV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.

There is a very wide application area where general undervoltage functions are used.All voltage related settings are made as a percentage of the global settings base voltageUBase, which normally is set to the primary rated voltage level (phase-to-phase) of thepower system or the high voltage equipment under consideration.

The setting for UV2PTUV is normally not critical, since there must be enough timeavailable for the main protection to clear short circuits and earth faults.

Some applications and related setting guidelines for the voltage level are described inthe following sections.

9.1.3.1 Equipment protection, such as for motors and generators

The setting must be below the lowest occurring "normal" voltage and above the lowestacceptable voltage for the equipment.

9.1.3.2 Disconnected equipment detection

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage, caused by inductive or capacitive coupling, when theequipment is disconnected.

9.1.3.3 Power supply quality

The setting must be below the lowest occurring "normal" voltage and above the lowestacceptable voltage, due to regulation, good practice or other agreements.

9.1.3.4 Voltage instability mitigation

This setting is very much dependent on the power system characteristics, andthorough studies have to be made to find the suitable levels.

9.1.3.5 Backup protection for power system faults

The setting must be below the lowest occurring "normal" voltage and above thehighest occurring voltage during the fault conditions under consideration.

Section 9 1MRK 504 134-UEN AVoltage protection

184Application manual

Page 191: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

9.1.3.6 Settings for Two step undervoltage protection

The following settings can be done for two step undervoltage protection (UV2PTUV).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

ConnType: Sets whether the measurement shall be phase-to-earth fundamental value,phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phaseRMS value.

Operation: Off/On.

UV2PTUV measures selectively phase-to-earth voltages, or phase-to-phase voltagechosen by the setting ConnType.

This means operation for phase-to-earth voltage if:

(%) ( )3

U UBase kV< ×

EQUATION1447 V1 EN (Equation 104)

and operation for phase-to-phase voltage if:

U (%) UBase(kV)< ×EQUATION1990 V1 EN (Equation 105)

Characteristic1: This parameter gives the type of time delay to be used for step 1. Thesetting can be. Definite time/Inverse Curve A/Inverse Curve B. The choice is highlydependent of the protection application.

OpModen: This parameter describes how many of the three measured voltages thatshould be below the set level to give operation for step n (n=step 1 and 2). The settingcan be 1 out of 3, 2 out of 3 or 3 out of 3. It is sufficient that one phase voltage is lowto give operation. If the function shall be insensitive for single phase-to-earth faults 2out of 3 can be chosen.

Un<: Set undervoltage operation value for step n (n=step 1 and 2), given as % of theglobal parameter UBase. This setting is highly dependent of the protectionapplication. Here it is essential to consider the minimum voltage at non-faultedsituations. This voltage is larger than 90% of nominal voltage.

tn: Time delay for step n (n=step 1 and 2), given in s. This setting is highly dependentof the protection application. In many applications the protection function does notdirectly trip where there is short circuit or earth faults in the system. The time delaymust be coordinated to the short circuit protection.

t1Min: Minimum operating time for inverse time characteristic for step 1, given in s.When using inverse time characteristic for the undervoltage function during very lowvoltages can give a short operation time. This might lead to unselective trip. By setting

1MRK 504 134-UEN A Section 9Voltage protection

185Application manual

Page 192: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

t1Min longer than the operation time for other protections such unselective trippingcan be avoided.

k1: Time multiplier for inverse time characteristic. This parameter is used forcoordination between different inverse time delayed undervoltage protections.

The function must be externally blocked when the protected object isdisconnected.

9.2 Two step overvoltage protection OV2PTOV

9.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step overvoltage protection OV2PTOV

3U>

SYMBOL-C-2U-SMALLER-THANV2 EN

59

9.2.2 Application

Two step overvoltage protection OV2PTOV is applicable in all situations, wherereliable detection of high voltage is necessary. OV2PTOV is used for supervision anddetection of abnormal conditions, which, in combination with other protectionfunctions, increase the security of a complete protection system.

High overvoltage conditions are caused by abnormal situations in the power system.OV2PTOV is applied to power system elements, such as generators, transformers,motors and power lines in order to detect high voltage conditions. OV2PTOV is usedin combination with low current signals, to identify a transmission line, open in theremote end. In addition to that, OV2PTOV is also used to initiate voltage correctionmeasures, like insertion of shunt reactors, to compensate for low load, and therebydecreasing the voltage. The function has a high measuring accuracy and hysteresissetting to allow applications to control reactive load.

OV2PTOV is used to disconnect apparatuses, like electric motors, which will bedamaged when subject to service under high voltage conditions. It deals with highvoltage conditions at power system frequency, which can be caused by:

1. Different kinds of faults, where a too high voltage appears in a certain powersystem, like metallic connection to a higher voltage level (broken conductor

Section 9 1MRK 504 134-UEN AVoltage protection

186Application manual

Page 193: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

falling down to a crossing overhead line, transformer flash over fault from thehigh voltage winding to the low voltage winding and so on).

2. Malfunctioning of a voltage regulator or wrong settings under manual control(symmetrical voltage decrease).

3. Low load compared to the reactive power generation (symmetrical voltagedecrease).

4. Earth-faults in high impedance earthed systems causes, beside the high voltage inthe neutral, high voltages in the two non-faulted phases, (unsymmetrical voltageincrease).

OV2PTOV prevents sensitive equipment from running under conditions that couldcause their overheating or stress of insulation material, and, thus, shorten their lifetime expectancy. In many cases, it is a useful function in circuits for local or remoteautomation processes in the power system.

9.2.3 Setting guidelines

The parameters for Two step overvoltage protection (OV2PTOV) are set via the localHMI or PCM600.

All the voltage conditions in the system where OV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.

There is a very wide application area where general overvoltage functions are used.All voltage related settings are made as a percentage of a settable base primaryvoltage, which normally is set to the nominal voltage level (phase-to-phase) of thepower system or the high voltage equipment under consideration.

The time delay for the OV2PTOV can sometimes be critical and related to the size ofthe overvoltage - a power system or a high voltage component can withstand smallerovervoltages for some time, but in case of large overvoltages the related equipmentshould be disconnected more rapidly.

Some applications and related setting guidelines for the voltage level are given below:

Equipment protection, such as for motors, generators, reactors andtransformersHigh voltage can cause overexcitation of the core and deteriorate the windinginsulation. The setting must be above the highest occurring "normal" voltage andbelow the highest acceptable voltage for the equipment.

Equipment protection, capacitorsHigh voltage can deteriorate the dielectricum and the insulation. The setting must beabove the highest occurring "normal" voltage and below the highest acceptablevoltage for the capacitor.

1MRK 504 134-UEN A Section 9Voltage protection

187Application manual

Page 194: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

High impedance earthed systemsIn high impedance earthed systems, earth-faults cause a voltage increase in the non-faulty phases. OV2PTOV can be used to detect such faults. The setting must be abovethe highest occurring "normal" voltage and below the lowest occurring voltage duringfaults. A metallic single-phase earth-fault causes the non-faulted phase voltages toincrease a factor of √3.

The following settings can be done for Two step overvoltage protectionGlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

ConnType: Sets whether the measurement shall be phase-to-earth fundamental value,phase-to-phase fundamental value, phase-to-earth RMS value or phase-to-phaseRMS value.

Operation: Off/On .

OV2PTOV measures the phase-to-earth voltages, or phase-to-phase voltages asselected. The function will operate if the voltage gets higher than the set percentage ofthe global set base voltage UBase. This means operation for phase-to-earth voltageover:

( )(%)3

UBase kVU > ×

IEC09000054 V1 EN (Equation 106)

and operation for phase-to-phase voltage over:

U (%) UBase(kV)> ×EQUATION1993 V1 EN (Equation 107)

Characteristic1: This parameter gives the type of time delay to be used. The settingcan be. Definite time/Inverse Curve A/Inverse Curve B/Inverse Curve C. The choiceis highly dependent of the protection application.

OpModen: This parameter describes how many of the three measured voltages thatshould be above the set level to give operation for step n (n=step 1 and 2). The settingcan be 1 out of 3, 2 out of 3 or 3 out of 3. In most applications it is sufficient that onephase voltage is high to give operation. If the function shall be insensitive for singlephase-to-earth faults 3 out of 3 can be chosen, because the voltage will normally risein the non-faulted phases at single phase-to-earth faults.

Un>: Set overvoltage operating value for step n (n=step 1 and 2), given as % of theglobal parameter UBase. The setting is highly dependent of the protection application.Here it is essential to consider the Maximum voltage at non-faulted situations.Normally this voltage is less than 110% of nominal voltage.

tn: time delay for step n (n=step 1 and 2), given in s. The setting is highly dependentof the protection application. In many applications the protection function has the task

Section 9 1MRK 504 134-UEN AVoltage protection

188Application manual

Page 195: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

to prevent damages to the protected object. The speed might be important for examplein case of protection of transformer that might be overexcited. The time delay must beco-ordinated with other automated actions in the system.

t1Min: Minimum operating time for inverse time characteristic for step 1, given in s.For very high voltages the overvoltage function, using inverse time characteristic, cangive very short operation time. This might lead to unselective trip. By setting t1Minlonger than the operation time for other protections such unselective tripping can beavoided.

k1: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

9.3 Two step residual overvoltage protectionROV2PTOV

9.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Two step residual overvoltageprotection

ROV2PTOV

3U0>

IEC10000168 V1 EN

59N

9.3.2 Application

Two step residual overvoltage protection ROV2PTOV is primarily used in highimpedance earthed distribution networks, mainly as a backup for the primary earth-fault protection of the feeders and the transformer. To increase the security fordifferent earth-fault related functions, the residual overvoltage signal can be used asa release signal. The residual voltage can be measured either at the transformer neutralor from a voltage transformer open delta connection. The residual voltage can also becalculated internally, based on measurement of the three-phase voltages.

In high impedance earthed systems the residual voltage will increase in case of anyfault connected to earth. Depending on the type of fault and fault resistance theresidual voltage will reach different values. The highest residual voltage, equal tothree times the phase-to-earth voltage, is achieved for a single phase-to-earth fault.The residual voltage increases approximately to the same level in the whole systemand does not provide any guidance in finding the faulted component. Therefore,ROV2PTOV is often used as a backup protection or as a release signal for the feederearth-fault protection.

1MRK 504 134-UEN A Section 9Voltage protection

189Application manual

Page 196: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

9.3.3 Setting guidelines

All the voltage conditions in the system where ROV2PTOV performs its functionsshould be considered. The same also applies to the associated equipment, its voltageand time characteristic.

There is a very wide application area where general single input or residualovervoltage functions are used. All voltage related settings are made as a percentageof a settable base voltage, which can be set to the primary nominal voltage (phase-phase) level of the power system or the high voltage equipment under consideration.

The time delay for ROV2PTOV is seldom critical, since residual voltage is related toearth-faults in a high impedance earthed system, and enough time must normally begiven for the primary protection to clear the fault. In some more specific situations,where the single overvoltage protection is used to protect some specific equipment,the time delay is shorter.

Some applications and related setting guidelines for the residual voltage level aregiven below.

9.3.3.1 Equipment protection, such as for motors, generators, reactors andtransformers

High residual voltage indicates earth-fault in the system, perhaps in the component towhich Two step residual overvoltage protection (ROV2PTOV) is connected. Forselectivity reasons to the primary protection for the faulted device ROV2PTOV musttrip the component with some time delay. The setting must be above the highestoccurring "normal" residual voltage and below the highest acceptable residual voltagefor the equipment

9.3.3.2 Power supply quality

The setting must be above the highest occurring "normal" residual voltage and belowthe highest acceptable residual voltage, due to regulation, good practice or otheragreements.

9.3.3.3 High impedance earthed systems

In high impedance earthed systems, earth faults cause a neutral voltage in the feedingtransformer neutral. Two step residual overvoltage protection ROV2PTOV is used totrip the transformer, as a backup protection for the feeder earth-fault protection, andas a backup for the transformer primary earth-fault protection. The setting must beabove the highest occurring "normal" residual voltage, and below the lowestoccurring residual voltage during the faults under consideration. A metallic single-phase earth fault causes a transformer neutral to reach a voltage equal to the nominalphase-to-earth voltage.

Section 9 1MRK 504 134-UEN AVoltage protection

190Application manual

Page 197: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The voltage transformers measuring the phase-to-earth voltages measure zero voltagein the faulty phase. The two healthy phases will measure full phase-to-phase voltage,as the earth is available on the faulty phase and the neutral has a full phase-to-earthvoltage. The residual overvoltage will be three times the phase-to-earth voltage. SeeFigure 82.

IEC07000190 V1 EN

Figure 82: Earth fault in Non-effectively earthed systems

9.3.3.4 Direct earthed system

In direct earthed systems, an earth fault on one phase indicates a voltage collapse inthat phase. The two healthy phases will have normal phase-to-earth voltages. The

1MRK 504 134-UEN A Section 9Voltage protection

191Application manual

Page 198: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

residual sum will have the same value as the remaining phase-to-earth voltage. SeeFigure 83.

IEC07000189 V1 EN

Figure 83: Earth fault in Direct earthed system

9.3.3.5 Settings for Two step residual overvoltage protection

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off or On

UBase is used as voltage reference for the voltage. The voltage can be fed to the IEDin different ways:

1. The IED is fed from a normal voltage transformer group where the residualvoltage is created from the phase-to-earth voltages within the protectionsoftware.

2. The IED is fed from a broken delta connection normal voltage transformer group.In an open delta connection the protection is fed by the voltage 3U0 (single input).The Setting chapter in the application manual explains how the analog inputneeds to be set.

3. The IED is fed from a single voltage transformer connected to the neutral point ofa power transformer in the power system. In this connection the protection is fedby the voltage UN=U0 (single input). The Setting chapter in the applicationmanual explains how the analog input needs to be set. ROV2PTOV will measurethe residual voltage corresponding nominal phase-to-earth voltage for a high

Section 9 1MRK 504 134-UEN AVoltage protection

192Application manual

Page 199: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

impedance earthed system. The measurement will be based on the neutral voltagedisplacement.

Characteristic1: This parameter gives the type of time delay to be used. The settingcan be, Definite time or Inverse curve A or Inverse curve B or Inverse curve C. Thechoice is highly dependent of the protection application.

Un>: Set overvoltage operate value for step n (n=step 1 and 2), given as % of residualvoltage corresponding to global set parameter UBase:

( ) ( )% 3U UBase kV> ×IECEQUATION2290 V1 EN (Equation 108)

The setting is dependent of the required sensitivity of the protection and the systemearthing. In non-effectively earthed systems the residual voltage can be maximum therated phase-to-earth voltage, which should correspond to 100%.

In effectively earthed systems this value is dependent of the ratio Z0/Z1. The requiredsetting to detect high resistive earth-faults must be based on network calculations.

tn: time delay of step n (n=step 1 and 2), given in s. The setting is highly dependent ofthe protection application. In many applications, the protection function has the taskto prevent damages to the protected object. The speed might be important for examplein case of protection of transformer that might be overexcited. The time delay must beco-ordinated with other automated actions in the system.

t1Min: Minimum operate time for inverse time characteristic for step 1, given in s. Forvery high voltages the overvoltage function, using inverse time characteristic, cangive very short operation time. This might lead to unselective trip. By setting t1Minlonger than the operation time for other protections such unselective tripping can beavoided.

k1: Time multiplier for inverse time characteristic. This parameter is used for co-ordination between different inverse time delayed undervoltage protections.

9.4 Overexcitation protection OEXPVPH

9.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Overexcitation protection OEXPVPH

U/f >

SYMBOL-Q V1 EN

24

1MRK 504 134-UEN A Section 9Voltage protection

193Application manual

Page 200: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

9.4.2 Application

The Overexcitation protection (OEXPVPH) has current inputs to allow calculation ofthe load influence on the induced voltage. This gives a more exact measurement of themagnetizing flow. For power transformers with unidirectional load flow, the voltageto OEXPVPH should therefore be taken from the feeder side.

Heat accumulated in critical parts during a period of overexcitation will be reducedgradually when the excitation returns to the normal value. If a new period ofoverexcitation occurs after a short time interval, the heating will start from a higherlevel, therefore, OEXPVPH must have thermal memory. A fixed cooling timeconstant of 20 minutes is used.

The function should preferably be configured to use a three-phase voltage input ifavailable. It then uses the positive sequence quantities of voltages and currents. Whenconfigured to a single phase-to-phase voltage input, a corresponding phase-to-phasecurrent is calculated.

Analog measurements shall not be taken from any winding where aload tap changer is located.

Some different connection alternatives are shown in figure 84.

G

U/f>

24

U/f>

24

U/f>

24

en05000208.vsd

IEC05000208 V1 EN

Figure 84: Alternative connections of an Overexcitation protectionOEXPVPH(Volt/Hertz)

Section 9 1MRK 504 134-UEN AVoltage protection

194Application manual

Page 201: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

9.4.3 Setting guidelines

9.4.3.1 Recommendations for input and output signals

Please refer to the Technical manual for a list of setting parameters.

Binary Input signalsBLOCK: The input will block the operation of the Overexcitation protectionOEXPVPH. The block input can be used to block the operation for a limited timeduring special service conditions.

RESET: OEXPVPH has a thermal memory, which can take a long time to reset.Activation of the RESET input will reset the function instantaneously.

Binary Output signalsSTART: The START output indicates that the setV/Hz>> level has been reached.

TRIP: The TRIP output is activated after the operate time for the U/f level has expired.

ALARM: The output is activated when the alarm level has been reached and the alarmtimer has elapsed.

9.4.3.2 Settings

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: The operation of the Overexcitation protection OEXPVPH can be set toOn/Off.

V/Hz>: Operating level for the inverse characteristic. The operation is based on therelation between rated voltage and rated frequency and set as a percentage factor.Normal setting is around 108-110% depending of the capability curve for thetransformer/generator.

V/Hz>>: Operating level for the tMin definite time delay used at high overvoltages.The operation is based on the relation between rated voltage and rated frequency andset as a percentage factor. Normal setting is around 110-180% depending of thecapability curve of the transformer/generator. Setting should be above the knee-pointwhen the characteristic starts to be straight on the high side.

kForIEEE: The time constant for the IEEE inverse characteristic. Select the onegiving the best match to the transformer capability.

tMin: The operating times at voltages higher than the set V/Hz>>. The setting shallmatch capabilities on these high voltages. Typical setting can be 1-10 second.

AlarmLevel: Setting of the alarm level in percentage of the set trip level. The alarmlevel is normally set at around 98% of the trip level.

1MRK 504 134-UEN A Section 9Voltage protection

195Application manual

Page 202: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

tAlarm: Setting of the time delay to alarm from when the alarm level has been reached.Typical setting is 5 seconds.

Section 9 1MRK 504 134-UEN AVoltage protection

196Application manual

Page 203: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 10 Frequency protection

10.1 Underfrequency protection SAPTUF

10.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Underfrequency protection SAPTUF

f <

SYMBOL-P V1 EN

81

10.1.2 Application

Underfrequency protection SAPTUF is applicable in all situations, where reliabledetection of low fundamental power system frequency is needed. The power systemfrequency, and the rate of change of frequency, is a measure of the unbalance betweenthe actual generation and the load demand. Low fundamental frequency in a powersystem indicates that the available generation is too low to fully supply the powerdemanded by the load connected to the power grid. SAPTUF detects such situationsand provides an output signal, suitable for load shedding, generator boosting, HVDC-set-point change, gas turbine start up and so on. Sometimes shunt reactors areautomatically switched in due to low frequency, in order to reduce the power systemvoltage and hence also reduce the voltage dependent part of the load.

SAPTUF is very sensitive and accurate and is used to alert operators that frequencyhas slightly deviated from the set-point, and that manual actions might be enough. Theunderfrequency signal is also used for overexcitation detection. This is especiallyimportant for generator step-up transformers, which might be connected to thegenerator but disconnected from the grid, during a roll-out sequence. If the generatoris still energized, the system will experience overexcitation, due to the low frequency.

10.1.3 Setting guidelines

All the frequency and voltage magnitude conditions in the system where SAPTUFperforms its functions should be considered. The same also applies to the associatedequipment, its frequency and time characteristic.

There are two specific application areas for SAPTUF:

1MRK 504 134-UEN A Section 10Frequency protection

197Application manual

Page 204: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1. to protect equipment against damage due to low frequency, such as generators,transformers, and motors. Overexcitation is also related to low frequency

2. to protect a power system, or a part of a power system, against breakdown, byshedding load, in generation deficit situations.

The under frequency START value is set in Hz. All voltage magnitude related settingsare made as a percentage of a global base voltage parameter. The UBase value shouldbe set as a primary phase-to-phase value.

Some applications and related setting guidelines for the frequency level are givenbelow:

Equipment protection, such as for motors and generatorsThe setting has to be well below the lowest occurring "normal" frequency and wellabove the lowest acceptable frequency for the equipment.

Power system protection, by load sheddingThe setting has to be below the lowest occurring "normal" frequency and well abovethe lowest acceptable frequency for power stations, or sensitive loads. The settinglevel, the number of levels and the distance between two levels (in time and/or infrequency) depends very much on the characteristics of the power system underconsideration. The size of the "largest loss of production" compared to "the size of thepower system" is a critical parameter. In large systems, the load shedding can be setat a fairly high frequency level, and the time delay is normally not critical. In smallersystems the frequency START level has to be set at a lower value, and the time delaymust be rather short.

10.2 Overfrequency protection SAPTOF

10.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Overfrequency protection SAPTOF

f >

SYMBOL-O V1 EN

81

10.2.2 Application

Overfrequency protection function SAPTOF is applicable in all situations, wherereliable detection of high fundamental power system frequency is needed. The powersystem frequency, and rate of change of frequency, is a measure of the unbalance

Section 10 1MRK 504 134-UEN AFrequency protection

198Application manual

Page 205: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

between the actual generation and the load demand. High fundamental frequency in apower system indicates that the available generation is too large compared to thepower demanded by the load connected to the power grid. SAPTOF detects suchsituations and provides an output signal, suitable for generator shedding, HVDC-set-point change and so on. SAPTOF is very sensitive and accurate and can also be usedto alert operators that frequency has slightly deviated from the set-point, and thatmanual actions might be enough.

10.2.3 Setting guidelines

All the frequency and voltage magnitude conditions in the system where SAPTOFperforms its functions must be considered. The same also applies to the associatedequipment, its frequency and time characteristic.

There are two specific application areas for SAPTOF:

1. to protect equipment against damage due to high frequency, such as generators,and motors

2. to protect a power system, or a part of a power system, against breakdown, byshedding generation, in over production situations.

The overfrequency start value is set in Hz. All voltage magnitude related settings aremade as a percentage of a settable global base voltage parameter UBase. The UBasevalue should be set as a primary phase-to-phase value.

Some applications and related setting guidelines for the frequency level are givenbelow:

Equipment protection, such as for motors and generatorsThe setting has to be well above the highest occurring "normal" frequency and wellbelow the highest acceptable frequency for the equipment.

Power system protection, by generator sheddingThe setting must be above the highest occurring "normal" frequency and below thehighest acceptable frequency for power stations, or sensitive loads. The setting level,the number of levels and the distance between two levels (in time and/or in frequency)depend very much on the characteristics of the power system under consideration. Thesize of the "largest loss of load" compared to "the size of the power system" is a criticalparameter. In large systems, the generator shedding can be set at a fairly low frequencylevel, and the time delay is normally not critical. In smaller systems the frequencySTART level has to be set at a higher value, and the time delay must be rather short.

10.3 Rate-of-change frequency protection SAPFRC

1MRK 504 134-UEN A Section 10Frequency protection

199Application manual

Page 206: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

10.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Rate-of-change frequency protection SAPFRC

df/dt ><

SYMBOL-N V1 EN

81

10.3.2 Application

Rate-of-change frequency protection (SAPFRC), is applicable in all situations, wherereliable detection of change of the fundamental power system voltage frequency isneeded. SAPFRC can be used both for increasing frequency and for decreasingfrequency. SAPFRC provides an output signal, suitable for load shedding or generatorshedding, generator boosting, HVDC-set-point change, gas turbine start up and so on.Very often SAPFRC is used in combination with a low frequency signal, especially insmaller power systems, where loss of a fairly large generator will require quickremedial actions to secure the power system integrity. In such situations load sheddingactions are required at a rather high frequency level, but in combination with a largenegative rate-of-change of frequency the underfrequency protection can be used at arather high setting.

10.3.3 Setting guidelines

The parameters for Rate-of-change frequency protection SAPFRC are set via the localHMI or or through the Protection and Control Manager (PCM600).

All the frequency and voltage magnitude conditions in the system where SAPFRCperforms its functions should be considered. The same also applies to the associatedequipment, its frequency and time characteristic.

There are two specific application areas for SAPFRC:

1. to protect equipment against damage due to high or too low frequency, such asgenerators, transformers, and motors

2. to protect a power system, or a part of a power system, against breakdown byshedding load or generation, in situations where load and generation are not inbalance.

SAPFRC is normally used together with an overfrequency or underfrequencyfunction, in small power systems, where a single event can cause a large imbalancebetween load and generation. In such situations load or generation shedding has totake place very quickly, and there might not be enough time to wait until the frequencysignal has reached an abnormal value. Actions are therefore taken at a frequency levelcloser to the primary nominal level, if the rate-of-change frequency is large (withrespect to sign).

Section 10 1MRK 504 134-UEN AFrequency protection

200Application manual

Page 207: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

SAPFRCSTART value is set in Hz/s. All voltage magnitude related settings are madeas a percentage of a settable base voltage, which normally is set to the primary nominalvoltage level (phase-phase) of the power system or the high voltage equipment underconsideration.

SAPFRC is not instantaneous, since the function needs some time to supply a stablevalue. It is recommended to have a time delay long enough to take care of signal noise.However, the time, rate-of-change frequency and frequency steps between differentactions might be critical, and sometimes a rather short operation time is required, forexample, down to 70 ms.

Smaller industrial systems might experience rate-of-change frequency as large as 5Hz/s, due to a single event. Even large power systems may form small islands with alarge imbalance between load and generation, when severe faults (or combinations offaults) are cleared - up to 3 Hz/s has been experienced when a small island was isolatedfrom a large system. For more "normal" severe disturbances in large power systems,rate-of-change of frequency is much less, most often just a fraction of 1.0 Hz/s.

1MRK 504 134-UEN A Section 10Frequency protection

201Application manual

Page 208: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

202

Page 209: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 11 Secondary system supervision

11.1 Fuse failure supervision SDDRFUF

11.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fuse failure supervision SDDRFUF - -

11.1.2 Application

Different protection functions within the protection IED, operates on the basis of themeasured voltage in the relay point. Examples are:

• impedance protection functions• undervoltage function• energizing check function and voltage check for the weak infeed logic

These functions can operate unintentionally if a fault occurs in the secondary circuitsbetween the voltage instrument transformers and the IED.

It is possible to use different measures to prevent such unwanted operations. Miniaturecircuit breakers in the voltage measuring circuits, located as close as possible to thevoltage instrument transformers, are one of them. Separate fuse-failure monitoringIEDs or elements within the protection and monitoring devices are anotherpossibilities. These solutions are combined to get the best possible effect in the fusefailure supervision function (SDDRFUF).

SDDRFUF function built into the IED products can operate on the basis of externalbinary signals from the miniature circuit breaker or from the line disconnector. Thefirst case influences the operation of all voltage-dependent functions while the secondone does not affect the impedance measuring functions.

The negative sequence detection algorithm, based on the negative-sequencemeasuring quantities, a high value of voltage 3U2 without the presence of thenegative-sequence current 3I2, is recommended for use in isolated or high-impedanceearthed networks.

The zero sequence detection algorithm, based on the zero sequence measuringquantities, a high value of voltage 3U0 without the presence of the residual current3I0, is recommended for use in directly or low impedance earthed networks. In cases

1MRK 504 134-UEN A Section 11Secondary system supervision

203Application manual

Page 210: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

where the line can have a weak-infeed of zero sequence current this function shall beavoided.

A criterion based on delta current and delta voltage measurements can be added to thefuse failure supervision function in order to detect a three phase fuse failure. This isbeneficial for example during three phase transformer switching.

11.1.3 Setting guidelines

11.1.3.1 General

The negative and zero sequence voltages and currents always exist due to differentnon-symmetries in the primary system and differences in the current and voltageinstrument transformers. The minimum value for the operation of the current andvoltage measuring elements must always be set with a safety margin of 10 to 20%,depending on the system operating conditions.

Pay special attention to the dissymmetry of the measuring quantities when thefunction is used on longer untransposed lines, on multicircuit lines and so on.

The settings of negative sequence, zero sequence and delta algorithm are in percent ofthe base voltage and base current for the function, UBase and IBase respectively. SetUBase to the primary rated phase-phase voltage of the potential voltage transformerand IBase to the primary rated current of the current transformer.

11.1.3.2 Setting of common parameters

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

The settings of negative sequence, zero sequence and delta algorithm are in percent ofthe global base voltage and global base current for the function, UBase and IBaserespectively.

The voltage threshold USealIn< is used to identify low voltage condition in thesystem. Set USealIn< below the minimum operating voltage that might occur duringemergency conditions. We propose a setting of approximately 70% of the globalparameter UBase.

The drop off time of 200 ms for dead phase detection makes it recommended to alwaysset SealIn to On since this will secure a fuse failure indication at persistent fuse failwhen closing the local breaker when the line is already energized from the other end.When the remote breaker closes the voltage will return except in the phase that has apersistent fuse fail. Since the local breaker is open there is no current and the deadphase indication will persist in the phase with the blown fuse. When the local breakercloses the current will start to flow and the function detects the fuse failure situation.But due to the 200 ms drop off timer the output BLKZ will not be activated until after200 ms. This means that distance functions are not blocked and due to the “no voltagebut current” situation might issue a trip.

Section 11 1MRK 504 134-UEN ASecondary system supervision

204Application manual

Page 211: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The operation mode selector OpMode has been introduced for better adaptation tosystem requirements. The mode selector makes it possible to select interactionsbetween the negative sequence and zero sequence algorithm. In normal applicationsthe OpMode is set to either UNsINs for selecting negative sequence algorithm orUZsIZs for zero sequence based algorithm. If system studies or field experiencesshows that there is a risk that the fuse failure function will not be activated due to thesystem conditions, the dependability of the fuse failure function can be increased if theOpMode is set to UZsIZs OR UNsINs or OptimZsNs. In mode UZsIZs OR UNsINs boththe negative and zero sequence based algorithm is activated and working in an OR-condition. Also in mode OptimZsNs both the negative and zero sequence algorithmare activated and the one that has the highest magnitude of measured sequence currentwill operate. If there is a requirement to increase the security of the fuse failurefunction OpMode can be selected to UZsIZs AND UNsINs, which gives that bothnegative and zero sequence algorithm is activated working in an AND-condition, thatis, both algorithms must give condition for block in order to activate the output signalsBLKU or BLKZ.

11.1.3.3 Negative sequence based

The relay setting value 3U2> is given in percentage of the base voltage UBase andshould not be set lower than according to equation 109.

3 23 2 100UU

UBase>= ×

EQUATION1519 V3 EN (Equation 109)

where:

3U2 is the maximal negative sequence voltage during normal operation conditions, plus a margin of10...20%

UBase is setting of the global base voltage for all functions in the IED.

The setting of the current limit 3I2< is in percentage of global parameter IBase. Thesetting of 3I2< must be higher than the normal unbalance current that might exist inthe system and can be calculated according to equation 110.

3 23 2 100=< ×II

IBaseEQUATION1520 V3 EN (Equation 110)

where:

3I2 is the maximal negative sequence current during normal operating conditions, plus a margin of10...20%

IBase is the setting of base current for the function

1MRK 504 134-UEN A Section 11Secondary system supervision

205Application manual

Page 212: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

11.1.3.4 Zero sequence based

The relay setting value 3U0> is given in percentage of the global parameter UBase.The setting of 3U0> should not be set lower than according to equation 111.

3 03 0 100

UU

UBase>= ×

EQUATION1521 V2 EN (Equation 111)

where:

3U0 is the maximal zero sequence voltage during normal operation conditions, plus a margin of10...20%

UBase is setting of global base voltage all functions in the IED.

The setting of the current limit 3I0< is done in percentage of the global parameterIBase. The setting of 3I0< must be higher than the normal unbalance current thatmight exist in the system. The setting can be calculated according to equation 112.

3 03 0 100= ×<II

IBaseEQUATION2293 V2 EN (Equation 112)

where:

3I0< is the maximal zero sequence current during normal operating conditions, plus a margin of10...20%

IBase is setting of global base current all functions in the IED.

11.1.3.5 Delta U and delta I

Set the operation mode selector OpDUDI to On if the delta function shall be inoperation.

The setting of DU> should be set high (approximately 60% of UBase) and the currentthreshold DI< low (approximately 10% of IBase) to avoid unwanted operation due tonormal switching conditions in the network. The delta current and delta voltagefunction shall always be used together with either the negative or zero sequencealgorithm. If USetprim is the primary voltage for operation of dU/dt and ISetprim theprimary current for operation of dI/dt, the setting of DU> and DI< will be givenaccording to equation 113 and equation 114.

100primDUUSetUBase

³ ×

EQUATION1523 V2 EN (Equation 113)

Section 11 1MRK 504 134-UEN ASecondary system supervision

206Application manual

Page 213: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

100primDIISetIBase

£ ×

EQUATION1524 V3 EN (Equation 114)

The voltage thresholds UPh> is used to identify low voltage condition in the system.Set UPh> below the minimum operating voltage that might occur during emergencyconditions. A setting of approximately 70% of UBase is recommended.

The current threshold IPh> shall be set lower than the IMinOp for the distanceprotection function. A 5...10% lower value is recommended.

11.1.3.6 Dead line detection

The condition for operation of the dead line detection is set by the parameters IDLD<for the current threshold and UDLD< for the voltage threshold.

Set the IDLD< with a sufficient margin below the minimum expected load current. Asafety margin of at least 15-20% is recommended. The operate value must howeverexceed the maximum charging current of an overhead line, when only one phase isdisconnected (mutual coupling to the other phases).

Set the UDLD< with a sufficient margin below the minimum expected operatingvoltage. A safety margin of at least 15% is recommended.

11.2 Breaker close/trip circuit monitoring TCSSCBR

11.2.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Breaker close/trip circuit monitoring TCSSCBR - -

11.2.2 Application

TCSSCBR detects faults in the electrical control circuit of the circuit breaker. Thefunction can supervise both open and closed coil circuits. This kind of supervision isnecessary to find out the vitality of the control circuits continuously.

Trip circuit supervision generates a current of approximately 1.0 mAthrough the supervised circuit. It must be ensured that this current willnot cause a latch up of the controlled object.

1MRK 504 134-UEN A Section 11Secondary system supervision

207Application manual

Page 214: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

To protect the trip circuit supervision circuits in the IED, the outputcontacts are provided with parallel transient voltage suppressors. Thebreakdown voltage of these suppressors is 400 +/– 20 V DC.

1

PSM

2

RsRext

(+)

(-)

HW

SW

PO1

TCS1

IS

V

IS: Constant current generator. Current level ~ 1,0 mA (Ic)V: Transient Voltage Suppressor Breakdown Voltage 380 to 400 VDC

Ic

TCSSCBRTCS_STATEBLOCK

ALARM

IEC13000025-2-en.vsd

GUID-B056E9DB-E3E5-4300-9150-45916F485CA7 V2 EN

Figure 85: Operating principle of the trip-circuit supervision with an externalresistor. The TCSSCBR blocking switch is not required since theexternal resistor is used.

If TCS is required only in a closed position, the external shunt resistance can beomitted. When the circuit breaker is in the open position, TCS sees the situation as afaulty circuit. One way to avoid TCS operation in this situation would be to block thesupervision function whenever the circuit breaker is open.

Section 11 1MRK 504 134-UEN ASecondary system supervision

208Application manual

Page 215: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

1

PSM

2

Rs

(+)

(-)

HW

S W

PO1

TCS1

IS

V

IS: Constant current generator. Current level ~ 1,0 mA (Ic)V: Transient Voltage Suppressor Breakdown Voltage 380 to 400 VDC

Ic

CBPOS_open

TCSSCBRTCS_STATEBLOCK

ALARM

IEC13000026-2-en.vsd

GUID-6B09F9C7-86D0-4A7A-8E08-8E37CAE53249 V3 EN

Figure 86: Operating principle of the trip-circuit supervision without an externalresistor. The circuit breaker open indication is set to block TCSSCBRwhen the circuit breaker is open.

Trip-circuit supervision and other trip contactsIt is typical that the trip circuit contains more than one trip contact in parallel, forexample in transformer feeders where the trip of a Buchholz relay is connected inparallel with the feeder terminal and other relays involved.

GUID-7264738C-F9D7-48F0-B6FC-F85FD10D5B84 V1 EN

Figure 87: Constant test current flow in parallel trip contacts and trip-circuitsupervision

1MRK 504 134-UEN A Section 11Secondary system supervision

209Application manual

Page 216: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Several trip-circuit supervision functions parallel in circuitNot only the trip circuit often have parallel trip contacts, it is also possible that thecircuit has multiple TCS circuits in parallel. Each TCS circuit causes its ownsupervising current to flow through the monitored coil and the actual coil current is asum of all TCS currents. This must be taken into consideration when determining theresistance of Rext.

Trip-circuit supervision with auxiliary relaysMany retrofit projects are carried out partially, that is, the old electromechanicalrelays are replaced with new ones but the circuit breaker is not replaced. This createsa problem that the coil current of an old type circuit breaker can be too high for theprotection IED trip contact to break.

The circuit breaker coil current is normally cut by an internal contact of the circuitbreaker. In case of a circuit breaker failure, there is a risk that the protection IED tripcontact is destroyed since the contact is obliged to disconnect high level ofelectromagnetic energy accumulated in the trip coil.

An auxiliary relay can be used between the protection IED trip contact and the circuitbreaker coil. This way the breaking capacity question is solved, but the TCS circuit inthe protection IED monitors the healthy auxiliary relay coil, not the circuit breakercoil. The separate trip circuit supervision relay is applicable for this to supervise thetrip coil of the circuit breaker.

Dimensioning of the external resistorUnder normal operating conditions, the applied external voltage is divided betweenthe relay’s internal circuit and the external trip circuit so that at the minimum 20V(3...20 V) remains over the relay’s internal circuit. Should the external circuit’sresistance be too high or the internal circuit’s too low, for example due to welded relaycontacts, the fault is detected.

Mathematically, the operation condition can be expressed as:

( ) 20C ext S CU R R I V DC- + ´ ³IECEQUATION16062 V1 EN (Equation 115)

Uc Operating voltage over the supervised trip circuit

Ic Measuring current through the trip circuit, appr. 1.0 mA (0.85...1.20 mA)

Rext external shunt resistance

Rs trip coil resistance

If the external shunt resistance is used, it has to be calculated not to interfere with thefunctionality of the supervision or the trip coil. Too high a resistance causes too higha voltage drop, jeopardizing the requirement of at least 20 V over the internal circuit,while a resistance too low can enable false operations of the trip coil.

Section 11 1MRK 504 134-UEN ASecondary system supervision

210Application manual

Page 217: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 19: Values recommended for the external resistor Rext

Operating voltage Uc Shunt resistor Rext

48 V DC 10 kΩ, 5 W

60 V DC 22 kΩ, 5 W

110 V DC 33 kΩ, 5 W

220 V DC 68 kΩ, 5 W

Due to the requirement that the voltage over the TCSSCBR contact must be 20V orhigher, the correct operation is not guaranteed with auxiliary operating voltages lowerthan 48V DC because of the voltage drop in Rext and the operating coil or even voltagedrop of the feeding auxiliary voltage system which can cause too low voltage valuesover the TCSSCBR contact. In this case, erroneous alarming can occur.

At lower (<48V DC) auxiliary circuit operating voltages, it is recommended to use thecircuit breaker position to block unintentional operation of TCSSCBR. The use of theposition indication is described earlier in this chapter.

1MRK 504 134-UEN A Section 11Secondary system supervision

211Application manual

Page 218: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

212

Page 219: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 12 Control

12.1 Apparatus control

12.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Bay control QCBAY - -

Local remote LOCREM - -

Local remote control LOCREMCTRL - -

12.1.2 Application

The apparatus control is a function for control and supervising of circuit breakers,disconnectors, and earthing switches within a bay. Permission to operate is given afterevaluation of conditions from other functions such as interlocking, synchrocheck,operator place selection and external or internal blockings.

The complete apparatus control function is not included in thisproduct, and the information below is included for understanding ofthe principle for the use of QCBAY, LOCREM, and LOCREMCTRLfor the selection of the operator place.

Figure 88 gives an overview from what places the apparatus control function receivecommands. Commands to an apparatus can be initiated from the Control Centre (CC),the station HMI or the local HMI on the IED front.

1MRK 504 134-UEN A Section 12Control

213Application manual

Page 220: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Station HMI

GW

cc

Station bus

breakers disconnectors earthing switchesIEC08000227.vsd

ApparatusControl

IED

I/O

Local HMI

ApparatusControl

IED

I/O

ApparatusControl

IED

I/O

Local HMI

Local HMI

IEC08000227 V1 EN

Figure 88: Overview of the apparatus control functions

Features in the apparatus control function:

• Operation of primary apparatuses• Select-Execute principle to give high security• Selection function to prevent simultaneous operation• Selection and supervision of operator place• Command supervision• Block/deblock of operation• Block/deblock of updating of position indications• Substitution of position indications• Overriding of interlocking functions• Overriding of synchrocheck• Operation counter• Suppression of Mid position

The apparatus control function is realized by means of a number of function blocksdesignated:

• Switch controller SCSWI• Circuit breaker SXCBR• Circuit switch SXSWI• Position evaluation POS_EVAL• Select release SELGGIO

Section 12 1MRK 504 134-UEN AControl

214Application manual

Page 221: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Bay control QCBAY• Local remote LOCREM• Local remote control LOCREMCTRL

SCSWI, SXCBR, QCBAY and SXSWI are logical nodes according to IEC 61850.The signal flow between these function blocks appears in figure 89. The functionLogical node Interlocking (SCILO) in the figure 89 is the logical node forinterlocking.

Control operation can be performed from the local IED HMI. If the administrator hasdefined users with the UMT tool, then the local/remote switch is under authoritycontrol. If not, the default (factory) user is the SuperUser that can perform controloperations from the local IED HMI without LogOn. The default position of the local/remote switch is on remote.

IEC09000338-1-en.vsd

SXCBRSCSWI

SCILO

SCSWI

SCILO

SXSWI

-QA1

-QB1

-QB9

IEC 61850

QCBAY

IEC09000338 V1 EN

Figure 89: Signal flow between apparatus control function blocks

The IEC 61850 communication has always priority over binaryinputs, e.g. a block command on binary inputs will not preventcommands over IEC 61850.

1MRK 504 134-UEN A Section 12Control

215Application manual

Page 222: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Accepted originator categories for PSTOIf the requested command is accepted due to the authority allocation control, therespective value will change. Otherwise the attribute blocked-by-switcing-hierarky isset in the cause signal. If the PSTO value is changed under a command, then thecommand is reset.

The accepted originator categories for each PSTO value are shown in Table 20

Table 20: Accepted originator categories for each PSTO

PermittdSourceToOperate Originator

0 = Off 4,5,6

1 = Local 1,4,5,6

2 = Remote 2,3,4,5,6

3 = Faulty 4,5,6

4 = Not in use 1,2,3,4,5,6

5 = All

PSTO = All, then it is no priority between operator places. All operator places areallowed to operate at the same time.

According to IEC61850 standard the orCat attribute in originator category are definedin Table 21

Table 21: orCat attribute according to IEC61850

Value Description

0 not-supported

1 bay-control

2 station-control

3 remote-control

4 automatic-bay

5 automatic-station

6 automatic-remote

7 maintenance

8 process

Switch controller (SCSWI)The Switch controller (SCSWI) initializes and supervises all functions to properlyselect and operate switching primary apparatuses. The Switch controller may handleand operate on one three-phase device.

After the selection of an apparatus and before the execution, the switch controllerperforms the following checks and actions:

Section 12 1MRK 504 134-UEN AControl

216Application manual

Page 223: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• A request initiates to reserve other bays to prevent simultaneous operation.• Actual position inputs for interlocking information are read and evaluated if the

operation is permitted.• The synchrocheck/synchronizing conditions are read and checked, and performs

operation upon positive response.• The blocking conditions are evaluated• The position indications are evaluated according to given command and its

requested direction (open or closed).

The command sequence is supervised regarding the time between:

• Select and execute.• Select and until the reservation is granted.• Execute and the final end position of the apparatus.• Execute and valid close conditions from the synchrocheck.

At error the command sequence is cancelled.

The mid position of apparatuses can be suppressed at SCSWI by setting thetIntermediate at (SXCBR/SXSWI) to an appropriate value.

The switch controller is not dependent on the type of switching device SXCBR orSXSWI. The switch controller represents the content of the SCSWI logical node(according to IEC 61850) with mandatory functionality.

Reservation function (SELGGIO)The purpose of the reservation function is to grant permission to operate only onedevice at a time in a group, like a bay or a station, thereby preventing double operation.

For interlocking evaluation in a substation, the position information from switchingdevices, such as circuit breakers, disconnectors and earthing switches can be requiredfrom the same bay or from several other bays. When information is needed from otherbays, it is exchanged over the serial station bus between the distributed IEDs. Theproblem that arises, even at a high speed of communication, is a time interval duringwhich the information about the position of the switching devices are uncertain. Theinterlocking function uses this information for evaluation, which means that also theinterlocking conditions will be uncertain.

To ensure that the interlocking information is correct at the time of operation, areservation method is available in the IEDs. With this reservation method the reservedsignal can be used for evaluation of permission to select and operate the apparatus.

This functionality is realized over the station bus by means of the function blockSELGGIO.

The SELECTED output signal from the respective SCSWI function block in the ownbay is connected to the inputs of the SELGGIO function block. The output signalRESERVED from SELGGIO is connected to the input RES_EXT of the SCSWIfunction block. If the bay is not currently reserved, the SELGGIO output signalRESERVED is FALSE. Selection for operation on the SCSWI block is now possible.

1MRK 504 134-UEN A Section 12Control

217Application manual

Page 224: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Once any SCSWI block is selected, and if its output SELECTED is connected to theSELGGIO block, then other SCSWI functions as configured are blocked for selection.The RESERVED signal from SELGGIO is also sent to other bay devices.

Due to the design of the plant, some apparatus might need reservation of the own bayas well as reservations from other bays. Received reservation from other bays arehandled by a logical OR together with own bay reservation from the SELGGIOfunction block that checks whether the own bay is currently reserved.

SELGGIOSELECT1SELECT2SELECT3SELECT4SELECT5SELECT6SELECT7SELECT8SELECT9SELECT10SELECT11SELECT12SELECT13SELECT14SELECT15SELECT16

RESERVED

BAY 1

BAY 2

BAY 3

RESERVED

IEC09000258-1.vsd

³1

IEC09000258 V1 EN

Figure 90: Reservations from own and other bays

The reservation can also be realized with external wiring according to the applicationexample in figure 91. This solution is realized with external auxiliary relays and extrabinary inputs and outputs in each IED.

Section 12 1MRK 504 134-UEN AControl

218Application manual

Page 225: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

SCSWI

SELECTED

RES_EXT

IEDIED

OR

Other SCWI in the bay to SELGGIO

SELGGIO

SELECT1

+

BI BOBI BO

IEC09000259_1_en.vsd

IEC09000259 V1 EN

Figure 91: Application principles for reservation with external wiring

The solution in figure 91 can also be realized over the station bus according to theapplication example in figure 92.

SCSWI

SELECTED

RES_EXT

IEDIED

OROther SCSWI in the bay to SELGGIO

Station bus. . .

SELGGIO

SELECT1

RESGRANT

GOOSEINTLKRCV

IEC09000260_2_en.vsd

IEC09000260 V2 EN

Figure 92: Application principle for an alternative reservation solution

Bay control (QCBAY)The Bay control (QCBAY) is used to handle the selection of the operator place for thebay. The function gives permission to operate from two types of locations either fromRemote (for example, control centre or station HMI) or from Local (local HMI on theIED) or from all (Local and Remote). The Local/Remote switch position can also beset to Off, which means no operator place selected that is, operation is not possibleneither from local nor from remote.

QCBAY also provides blocking functions that can be distributed to differentapparatuses within the bay. There are two different blocking alternatives:

1MRK 504 134-UEN A Section 12Control

219Application manual

Page 226: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Blocking of update of positions• Blocking of commands

The function does not have a corresponding functionality defined in the IEC 61850standard, which means that this function is included as a vendor specific logical node.

IEC13000016-1-en.vsd

IEC13000016 V1 EN

Figure 93: APC - Local remote function block

12.1.3 Interaction between modules

A typical bay with apparatus control function consists of a combination of logicalnodes or functions that are described here:

• The Switch controller (SCSWI) initializes all operations for one apparatus andperforms the actual switching and is more or less the interface to the drive of oneapparatus. It includes the position handling as well as the control of the position.

• The Circuit breaker (SXCBR) is the process interface to the circuit breaker for theapparatus control function.

• The Circuit switch (SXSWI) is the process interface to the disconnector or theearthing switch for the apparatus control function.

Section 12 1MRK 504 134-UEN AControl

220Application manual

Page 227: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• The Bay control (QCBAY) fulfils the bay-level functions for the apparatuses,such as operator place selection and blockings for the complete bay.

• The function (SELGGIO), deals with reservation of the bay.• The Four step overcurrent protection (OC4PTOC) trips the breaker.• The Protection trip logic (SMPPTRC) connects the "trip" outputs of one or more

protection functions to a common "trip" to be transmitted to SXCBR.• The Autorecloser (SMBRREC) consists of the facilities to automatically close a

tripped breaker with respect to a number of configurable conditions.• The logical node Interlocking (SCILO) provides the information to SCSWI

whether it is permitted to operate due to the switchyard topology. Theinterlocking conditions are evaluated with separate logic and connected toSCILO .

• The Synchrocheck, energizing check, and synchronizing (SESRSYN) calculatesand compares the voltage phasor difference from both sides of an open breakerwith predefined switching conditions (synchrocheck). Also the case that one sideis dead (energizing-check) is included.

• The logical node Generic Automatic Process Control, GAPC, is an automaticfunction that reduces the interaction between the operator and the system. Withone command, the operator can start a sequence that will end with a connectionof a process object (for example a line) to one of the possible busbars.

The overview of the interaction between these functions is shown in figure 94 below.

1MRK 504 134-UEN A Section 12Control

221Application manual

Page 228: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000207_1_en.vsd

OC4PTOC (Overcurrent)

SXCBR(Circuit breaker)

Interlockingfunctionblock

(Not a LN)

SCSWI(Switching control)

QCBAY(Bay control)

SMBRREC

(Auto-recloser)

I/O

Trip

Close rel.

Selected

Star

t SM

BRR

EC

Close CB

Position

Reserved

Operator placeselection

SCSWI(Switching control)

SXSWI(Disconnector)

Open cmd

Close cmd

Position

SESRSYN(Synchrocheck)

SCILO

SCILO

Synchrocheck OK

SELGGIO(Reservation) Selected

Reserved

Enable close

Enable open

Open rel.

Close rel.Open rel.

SMPPTRC(Trip logic)

Position

Enab

leop

en

Enab

lecl

ose

Pos.

from

ot

her b

ays

I/O

Open cmdClose cmd

(Interlocking)

(Interlocking)

IEC09000207 V1 EN

Figure 94: Example overview of the interactions between functions in a typicalbay

12.1.4 Setting guidelines

The setting parameters for the apparatus control function are set via the local HMI orPCM600.

Section 12 1MRK 504 134-UEN AControl

222Application manual

Page 229: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.1.4.1 Switch controller (SCSWI)

The parameter CtlModel specifies the type of control model according to IEC 61850.For normal control of circuit breakers, disconnectors and earthing switches the controlmodel is set to SBO Enh (Select-Before-Operate) with enhanced security.

When the operation shall be performed in one step, the model direct control withnormal security is used.

At control with enhanced security there is an additional supervision of the status valueby the control object, which means that each command sequence must be terminatedby a termination command.

The parameter PosDependent gives permission to operate depending on the positionindication, that is, at Always permitted it is always permitted to operate independentof the value of the position. At Not perm at 00/11 it is not permitted to operate if theposition is in bad or intermediate state.

tSelect is the maximum time between the select and the execute command signal, thatis, the time the operator has to perform the command execution after the selection ofthe object to operate. When the time has expired, the selected output signal is set tofalse and a cause-code is given over IEC 61850.

tSynchrocheck is the allowed time for the synchrocheck function to fulfill the closeconditions. When the time has expired, the control function is reset.

The timer tSynchronizing supervises that the signal synchronizing in progress isobtained in SCSWI after start of the synchronizing function. The start signal for thesynchronizing is obtained if the synchrocheck conditions are not fulfilled. When thetime has expired, the control function is reset. If no synchronizing function isincluded, the time is set to 0, which means no start of the synchronizing function.

tExecutionFB is the maximum time between the execute command signal and thecommand termination. When the time has expired, the control function is reset.

12.1.4.2 Bay control (QCBAY)

If the parameter AllPSTOValid is set to No priority, all originators from local andremote are accepted without any priority.

1MRK 504 134-UEN A Section 12Control

223Application manual

Page 230: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.2 Interlocking

12.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logical node for interlocking SCILO - 3

Interlocking for busbar earthing switch BB_ES - 3

Interlocking for bus-section breaker A1A2_BS - 3

Interlocking for bus-sectiondisconnector

A1A2_DC - 3

Interlocking for bus-coupler bay ABC_BC - 3

Interlocking for 1 1/2 breaker diameter BH_CONN - 3

Interlocking for 1 1/2 breaker diameter BH_LINE_A - 3

Interlocking for 1 1/2 breaker diameter BH_LINE_B - 3

Interlocking for double CB bay DB_BUS_A - 3

Interlocking for double CB bay DB_BUS_B - 3

Interlocking for double CB bay DB_LINE - 3

Interlocking for line bay ABC_LINE - 3

Interlocking for transformer bay AB_TRAFO - 3

12.2.2 Application

The main purpose of switchgear interlocking is:

• To avoid the dangerous or damaging operation of switchgear• To enforce restrictions on the operation of the substation for other reasons for

example, load configuration. Examples of the latter are to limit the number ofparallel transformers to a maximum of two or to ensure that energizing is alwaysfrom one side, for example, the high voltage side of a transformer.

This section only deals with the first point, and only with restrictions caused byswitching devices other than the one to be controlled. This means that switchinterlock, because of device alarms, is not included in this section.

Disconnectors and earthing switches have a limited switching capacity.Disconnectors may therefore only operate:

• With basically zero current. The circuit is open on one side and has a smallextension. The capacitive current is small (for example, < 5A) and powertransformers with inrush current are not allowed.

• To connect or disconnect a parallel circuit carrying load current. The switchingvoltage across the open contacts is thus virtually zero, thanks to the parallel circuit(for example, < 1% of rated voltage). Paralleling of power transformers is notallowed.

Section 12 1MRK 504 134-UEN AControl

224Application manual

Page 231: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Earthing switches are allowed to connect and disconnect earthing of isolated points.Due to capacitive or inductive coupling there may be some voltage (for example <40% of rated voltage) before earthing and some current (for example < 100A) afterearthing of a line.

Circuit breakers are usually not interlocked. Closing is only interlocked againstrunning disconnectors in the same bay, and the bus-coupler opening is interlockedduring a busbar transfer.

The positions of all switching devices in a bay and from some other bays determine theconditions for operational interlocking. Conditions from other stations are usually notavailable. Therefore, a line earthing switch is usually not fully interlocked. Theoperator must be convinced that the line is not energized from the other side beforeclosing the earthing switch. As an option, a voltage indication can be used forinterlocking. Take care to avoid a dangerous enable condition at the loss of a VTsecondary voltage, for example, because of a blown fuse.

The switch positions used by the operational interlocking logic are obtained fromauxiliary contacts or position sensors. For each end position (open or closed) a trueindication is needed - thus forming a double indication. The apparatus control functioncontinuously checks its consistency. If neither condition is high (1 or TRUE), theswitch may be in an intermediate position, for example, moving. This dynamic statemay continue for some time, which in the case of disconnectors may be up to 10seconds. Should both indications stay low for a longer period, the position indicationwill be interpreted as unknown. If both indications stay high, something is wrong, andthe state is again treated as unknown.

In both cases an alarm is sent to the operator. Indications from position sensors shallbe self-checked and system faults indicated by a fault signal. In the interlocking logic,the signals are used to avoid dangerous enable or release conditions. When theswitching state of a switching device cannot be determined operation is not permitted.

12.2.3 Configuration guidelines

The following sections describe how the interlocking for a certain switchgearconfiguration can be realized in the IED by using standard interlocking modules andtheir interconnections. They also describe the configuration settings. The inputs fordelivery specific conditions (Qx_EXy) are set to 1=TRUE if they are not used, exceptin the following cases:

• QB9_EX2 and QB9_EX4 in modules BH_LINE_A and BH_LINE_B• QA1_EX3 in module AB_TRAFO

when they are set to 0=FALSE.

12.2.4 Interlocking for busbar earthing switch BB_ES

1MRK 504 134-UEN A Section 12Control

225Application manual

Page 232: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.2.4.1 Application

The interlocking for busbar earthing switch (BB_ES) function is used for one busbarearthing switch on any busbar parts according to figure 95.

QC

en04000504.vsd

IEC04000504 V1 EN

Figure 95: Switchyard layout BB_ES

The signals from other bays connected to the module BB_ES are described below.

12.2.4.2 Signals in single breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_LINEBB_ES

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000505.vsd

BB_ESABC_BC

IEC04000505 V1 EN

Figure 96: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle the transferbus (WA7)C.

To derive the signals:

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnector on this part of the busbar is valid.

EXDU_BB No transmission error from any bay containing the above information.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:

Section 12 1MRK 504 134-UEN AControl

226Application manual

Page 233: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE)

QB220OTR QB2 and QB20 are open (ABC_BC)

QB7OPTR QB7 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2and QB20 is valid.

VPQB7TR The switch status of QB7 is valid.

EXDU_BB No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If no bus-section disconnector exists, the signal DCOPTR, VPDCTR and EXDU_DCare set to 1 (TRUE).

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS) rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a busbar earthing switch, these conditions from the A1 busbar section are valid:

1MRK 504 134-UEN A Section 12Control

227Application manual

Page 234: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB1OPTR (bay 1/sect.A1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000506.vsd

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A1)

EXDU_DC (A1/A2)

IEC04000506 V1 EN

Figure 97: Signals from any bays in section A1 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000507.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A1/A2)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A1/A2)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A1/A2)

IEC04000507 V1 EN

Figure 98: Signals from any bays in section A2 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the B1 busbar section are valid:

Section 12 1MRK 504 134-UEN AControl

228Application manual

Page 235: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB2OPTR(QB220OTR)(bay 1/sect.B1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000508.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B1)

VPQB2TR(VQB220TR) (bay n/sect.B1)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B1)

EXDU_DC (B1/B2)

IEC04000508 V1 EN

Figure 99: Signals from any bays in section B1 to a busbar earthing switch in thesame section

For a busbar earthing switch, these conditions from the B2 busbar section are valid:

QB2OPTR(QB220OTR) (bay 1/sect.B2) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000509.vsd

QB2OPTR(QB220OTR) (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B1/B2)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B1/B2)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B1/B2)

IEC04000509 V1 EN

Figure 100: Signals from any bays in section B2 to a busbar earthing switch in thesame section

For a busbar earthing switch on bypass busbar C, these conditions are valid:

1MRK 504 134-UEN A Section 12Control

229Application manual

Page 236: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB7OPTR (bay 1) BB_DC_OP

VP_BB_DC

EXDU_BB

en04000510.vsd

&

&

&

QB7OPTR (bay n)

. . .

. . .

. . .

VPQB7TR (bay 1)

VPQB7TR (bay n)

EXDU_BB (bay 1)

EXDU_BB (bay n)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000510 V1 EN

Figure 101: Signals from bypass busbar to busbar earthing switch

12.2.4.3 Signals in double-breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bussection are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000511.vsd

DB_BUS

IEC04000511 V1 EN

Figure 102: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal BB_DC_OP All disconnectors of this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar are valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

Section 12 1MRK 504 134-UEN AControl

230Application manual

Page 237: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnectors A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration described in section “Signalsin single breaker arrangement”.

12.2.4.4 Signals in 1 1/2 breaker arrangement

The busbar earthing switch is only allowed to operate if all disconnectors of the bus-section are open.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS) BB_ESBB_ES

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000512.vsdBH_LINE

IEC04000512 V1 EN

Figure 103: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic are the same as for the logic for the double busbarconfiguration described in section “Signals in single breaker arrangement”.

Signal BB_DC_OP All disconnectors on this part of the busbar are open.

VP_BB_DC The switch status of all disconnectors on this part of the busbar is valid.

EXDU_BB No transmission error from any bay that contains the above information.

12.2.5 Interlocking for bus-section breaker A1A2_BS

12.2.5.1 Application

The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-section circuit breaker between section 1 and 2 according to figure 104. The functioncan be used for different busbars, which includes a bus-section circuit breaker.

1MRK 504 134-UEN A Section 12Control

231Application manual

Page 238: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QA1

WA1 (A1)

QB2

QC4

QB1

QC3

WA2 (A2)

en04000516.vsd

QC2QC1

A1A2_BS

IEC04000516 V1 EN

Figure 104: Switchyard layout A1A2_BS

The signals from other bays connected to the module A1A2_BS are described below.

12.2.5.2 Signals from all feeders

If the busbar is divided by bus-section circuit breakers into bus-sections and bothcircuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-coupler connection exists between busbars on one bus-section side and if on the otherbus-section side a busbar transfer is in progress:

Section 1 Section 2

A1A2_BSB1B2_BS

ABC_LINEABC_BC

ABC_LINEABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000489.vsd

AB_TRAFOAB_TRAFO

IEC04000489 V1 EN

Figure 105: Busbars divided by bus-section circuit breakers

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-section.

VP_BBTR The switch status of BBTR is valid.

EXDU_12 No transmission error from any bay connected to busbar 1(A) and 2(B).

Section 12 1MRK 504 134-UEN AControl

232Application manual

Page 239: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC) are needed:

Signal QB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 and

WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from the bus-section circuit breaker bay (A1A2_BS, B1B2_BS) areneeded.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-section circuit breaker between A1 and A2 section busbars, these conditionsare valid:

1MRK 504 134-UEN A Section 12Control

233Application manual

Page 240: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

S1S2OPTR (B1B2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (B1B2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000490.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (B1B2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12 (bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12(bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (B1B2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000490 V1 EN

Figure 106: Signals from any bays for a bus-section circuit breaker betweensections A1 and A2

For a bus-section circuit breaker between B1 and B2 section busbars, these conditionsare valid:

Section 12 1MRK 504 134-UEN AControl

234Application manual

Page 241: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

S1S2OPTR (A1A2)BC12OPTR (sect.1)

QB12OPTR (bay 1/sect.2)

QB12OPTR (bay n/sect.2)

S1S2OPTR (A1A2)BC12OPTR (sect.2)

QB12OPTR (bay 1/sect.1)

QB12OPTR (bay n /sect.1)

BBTR_OP

VP_BBTR

EXDU_12

en04000491.vsd

>1&

>1&

. . .

. . .

. . .

. . .

&

&

VPS1S2TR (A1A2)VPBC12TR (sect.1)

VPQB12TR (bay 1/sect.2)

VPQB12TR (bay n/sect.1). . .. . .

VPBC12TR (sect.2)VPQB12TR (bay 1/sect.1)

VPQB12TR (bay n/sect.1)

. . .

. . .

&

EXDU_12(bay 1/sect.2)

EXDU_12 (bay n /sect.2)

EXDU_12 (bay 1/sect.1)

EXDU_12 (bay n /sect.1)

EXDU_BS (A1A2)EXDU_BC (sect.1)

EXDU_BC (sect.2)

. . .

. . .

. . .

. . .

IEC04000491 V1 EN

Figure 107: Signals from any bays for a bus-section circuit breaker betweensections B1 and B2

12.2.5.3 Configuration setting

If there is no other busbar via the busbar loops that are possible, then either theinterlocking for the QA1 open circuit breaker is not used or the state for BBTR is setto open. That is, no busbar transfer is in progress in this bus-section:

• BBTR_OP = 1• VP_BBTR = 1

1MRK 504 134-UEN A Section 12Control

235Application manual

Page 242: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.2.6 Interlocking for bus-section disconnector A1A2_DC

12.2.6.1 Application

The interlocking for bus-section disconnector (A1A2_DC) function is used for onebus-section disconnector between section 1 and 2 according to figure 108. A1A2_DCfunction can be used for different busbars, which includes a bus-section disconnector.

WA1 (A1) WA2 (A2)

QB

QC1 QC2

A1A2_DC en04000492.vsd

IEC04000492 V1 EN

Figure 108: Switchyard layout A1A2_DC

The signals from other bays connected to the module A1A2_DC are described below.

12.2.6.2 Signals in single breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition no otherdisconnector connected to the bus-section must be made by a project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE

(WA1)A1(WA2)B1(WA7)C C

B3A3

en04000493.vsd

AB_TRAFOAB_TRAFO

A2B2

IEC04000493 V1 EN

Figure 109: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

Section 12 1MRK 504 134-UEN AControl

236Application manual

Page 243: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

To derive the signals:

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from any bay that contains the above information.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and each bus-coupler bay (ABC_BC) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open (AB_TRAFO, ABC_LINE).

QB220OTR QB2 and QB20 are open (ABC_BC).

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

VQB220TR The switch status of QB2 and QB20 are valid.

EXDU_BB No transmission error from the bay that contains the above information.

If there is an additional bus-section disconnector, the signal from the bus-sectiondisconnector bay (A1A2_DC) must be used:

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If there is an additional bus-section circuit breaker rather than an additional bus-section disconnector the signals from the bus-section, circuit-breaker bay (A1A2_BS)rather than the bus-section disconnector bay (A1A2_DC) must be used:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_BS No transmission error from the bay BS (bus-section coupler bay) that contains theabove information.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

1MRK 504 134-UEN A Section 12Control

237Application manual

Page 244: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000494.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_BB (bay 1/sect.A1)

EXDU_BB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000494 V1 EN

Figure 110: Signals from any bays in section A1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000495.vsd

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)VPDCTR (A2/A3)

EXDU_BB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (A2/A3)

EXDU_BB (bay 1/sect.A2)

EXDU_DC (A2/A3)IEC04000495 V1 EN

Figure 111: Signals from any bays in section A2 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

Section 12 1MRK 504 134-UEN AControl

238Application manual

Page 245: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB2OPTR (QB220OTR)(bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000496.vsd

QB2OPTR (QB220OTR)(bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (VQB220TR)(bay 1/sect.B1)

VPQB2TR (VQB220TR)(bay n/sect.B1)

EXDU_BB (bay 1/sect.B1)

EXDU_BB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

IEC04000496 V1 EN

Figure 112: Signals from any bays in section B1 to a bus-section disconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (QB220OTR)(bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000497.vsd

QB2OPTR (QB220OTR)(bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR(VQB220TR) (bay 1/sect.B2)

VPQB2TR(VQB220TR) (bay n/sect.B2)VPDCTR (B2/B3)

EXDU_BB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

&

&

&

DCOPTR (B2/B3)

EXDU_BB (bay 1/sect.B2)

EXDU_DC (B2/B3)IEC04000497 V1 EN

Figure 113: Signals from any bays in section B2 to a bus-section disconnector

12.2.6.3 Signals in double-breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

1MRK 504 134-UEN A Section 12Control

239Application manual

Page 246: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

DB_BUS DB_BUSDB_BUS DB_BUS

(WA1)A1(WA2)B1 B2

A2

en04000498.vsd

IEC04000498 V1 EN

Figure 114: Busbars divided by bus-section disconnectors (circuit breakers)

To derive the signals:

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of all disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of all disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from double-breaker bay (DB) that contains the aboveinformation.

These signals from each double-breaker bay (DB_BUS) are needed:

Signal QB1OPTR QB1 is open.

QB2OPTR QB2 is open.

VPQB1TR The switch status of QB1 is valid.

VPQB2TR The switch status of QB2 is valid.

EXDU_DB No transmission error from the bay that contains the above information.

The logic is identical to the double busbar configuration “Signals in single breakerarrangement”.

For a bus-section disconnector, these conditions from the A1 busbar section are valid:

Section 12 1MRK 504 134-UEN AControl

240Application manual

Page 247: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB1OPTR (bay 1/sect.A1) S1DC_OP

VPS1_DC

EXDU_BB

en04000499.vsd

&

&

&

QB1OPTR (bay n/sect.A1)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A1)

VPQB1TR (bay n/sect.A1)

EXDU_DB (bay 1/sect.A1)

EXDU_DB (bay n/sect.A1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000499 V1 EN

Figure 115: Signals from double-breaker bays in section A1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the A2 busbar section are valid:

QB1OPTR (bay 1/sect.A2) S2DC_OP

VPS2_DC

EXDU_BB

en04000500.vsd

&

&

&

QB1OPTR (bay n/sect.A2)

. . .

. . .

. . .

VPQB1TR (bay 1/sect.A2)

VPQB1TR (bay n/sect.A2)

EXDU_DB (bay 1/sect.A2)

EXDU_DB (bay n/sect.A2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000500 V1 EN

Figure 116: Signals from double-breaker bays in section A2 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B1 busbar section are valid:

1MRK 504 134-UEN A Section 12Control

241Application manual

Page 248: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB2OPTR (bay 1/sect.B1) S1DC_OP

VPS1_DC

EXDU_BB

en04000501.vsd

&

&

&

QB2OPTR (bay n/sect.B1)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B1)

VPQB2TR (bay n/sect.B1)

EXDU_DB (bay 1/sect.B1)

EXDU_DB (bay n/sect.B1)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000501 V1 EN

Figure 117: Signals from double-breaker bays in section B1 to a bus-sectiondisconnector

For a bus-section disconnector, these conditions from the B2 busbar section are valid:

QB2OPTR (bay 1/sect.B2) S2DC_OP

VPS2_DC

EXDU_BB

en04000502.vsd

&

&

&

QB2OPTR (bay n/sect.B2)

. . .

. . .

. . .

VPQB2TR (bay 1/sect.B2)

VPQB2TR (bay n/sect.B2)

EXDU_DB (bay 1/sect.B2)

EXDU_DB (bay n/sect.B2)

. . .

. . .

. . .

. . .

. . .

. . .

IEC04000502 V1 EN

Figure 118: Signals from double-breaker bays in section B2 to a bus-sectiondisconnector

12.2.6.4 Signals in 1 1/2 breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbardisconnector bay no other disconnector connected to the bus-section must be made bya project-specific logic.

The same type of module (A1A2_DC) is used for different busbars, that is, for bothbus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,corresponding signals from busbar B are used.

Section 12 1MRK 504 134-UEN AControl

242Application manual

Page 249: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

BH_LINE

(WA1)A1(WA2)B1 B2

A2

en04000503.vsd

BH_LINE BH_LINE BH_LINE

IEC04000503 V1 EN

Figure 119: Busbars divided by bus-section disconnectors (circuit breakers)

The project-specific logic is the same as for the logic for the double-breakerconfiguration.

Signal S1DC_OP All disconnectors on bus-section 1 are open.

S2DC_OP All disconnectors on bus-section 2 are open.

VPS1_DC The switch status of disconnectors on bus-section 1 is valid.

VPS2_DC The switch status of disconnectors on bus-section 2 is valid.

EXDU_BB No transmission error from breaker and a half (BH) that contains the aboveinformation.

12.2.7 Interlocking for bus-coupler bay ABC_BC

12.2.7.1 Application

The interlocking for bus-coupler bay (ABC_BC) function is used for a bus-couplerbay connected to a double busbar arrangement according to figure 120. The functioncan also be used for a single busbar arrangement with transfer busbar or double busbararrangement without transfer busbar.

1MRK 504 134-UEN A Section 12Control

243Application manual

Page 250: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB1 QB2

QC1

QA1

WA1 (A)

WA2 (B)

WA7 (C)

QB7QB20

QC2

en04000514.vsdIEC04000514 V1 EN

Figure 120: Switchyard layout ABC_BC

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

12.2.7.2 Configuration

The signals from the other bays connected to the bus-coupler module ABC_BC aredescribed below.

12.2.7.3 Signals from all feeders

To derive the signals:

Signal BBTR_OP No busbar transfer is in progress concerning this bus-coupler.

VP_BBTR The switch status is valid for all apparatuses involved in the busbar transfer.

EXDU_12 No transmission error from any bay connected to the WA1/WA2 busbars.

These signals from each line bay (ABC_LINE), each transformer bay (AB_TRAFO),and bus-coupler bay (ABC_BC), except the own bus-coupler bay are needed:

Signal QQB12OPTR QB1 or QB2 or both are open.

VPQB12TR The switch status of QB1 and QB2 are valid.

EXDU_12 No transmission error from the bay that contains the above information.

For bus-coupler bay n, these conditions are valid:

Section 12 1MRK 504 134-UEN AControl

244Application manual

Page 251: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB12OPTR (bay 1)QB12OPTR (bay 2)

. . .

. . .QB12OPTR (bay n-1)

& BBTR_OP

VPQB12TR (bay 1)VPQB12TR (bay 2)

. . .

. . .VPQB12TR (bay n-1)

& VP_BBTR

EXDU_12 (bay 1)EXDU_12 (bay 2)

. . .

. . .EXDU_12 (bay n-1)

& EXDU_12

en04000481.vsd

IEC04000481 V1 EN

Figure 121: Signals from any bays in bus-coupler bay n

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBBTR are connected in parallel - if both bus-section disconnectors are closed. So forthe basic project-specific logic for BBTR above, add this logic:

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINEABC_BC

ABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000482.vsd

AB_TRAFO

IEC04000482 V1 EN

Figure 122: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle the transferbus (WA7)C.

The following signals from each bus-section disconnector bay (A1A2_DC) areneeded. For B1B2_DC, corresponding signals from busbar B are used. The same typeof module (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

1MRK 504 134-UEN A Section 12Control

245Application manual

Page 252: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), have to be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a bus-coupler bay in section 1, these conditions are valid:

BBTR_OP (sect.1)

DCOPTR (A1A2)DCOPTR (B1B2)

BBTR_OP (sect.2)

&VP_BBTR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VP_BBTR (sect.2)

EXDU_12 (sect.1)

EXDU_DC (B1B2)EXDU_12 (sect.2)

VP_BBTR

EXDU_12

en04000483.vsd

&EXDU_DC (A1A2)

BBTR_OP

>1&

IEC04000483 V1 EN

Figure 123: Signals to a bus-coupler bay in section 1 from any bays in eachsection

For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

12.2.7.4 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the signalsBC_12 from the busbar coupler of the other busbar section must be transmitted to theown busbar coupler if both disconnectors are closed.

Section 12 1MRK 504 134-UEN AControl

246Application manual

Page 253: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_BCABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000484.vsd

IEC04000484 V1 EN

Figure 124: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

To derive the signals:

Signal BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

VPBC12TR The switch status of BC_12 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC), must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

1MRK 504 134-UEN A Section 12Control

247Application manual

Page 254: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Signal S1S2CLTR A bus-section coupler connection exists between bus sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay containing the above information.

For a bus-coupler bay in section 1, these conditions are valid:

DCCLTR (A1A2)DCCLTR (B1B2)

BC12CLTR (sect.2)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

& BC_12_CL

VP_BC_12

EXDU_BC

en04000485.vsd

&

&

IEC04000485 V1 EN

Figure 125: Signals to a bus-coupler bay in section 1 from a bus-coupler bay inanother section

For a bus-coupler bay in section 2, the same conditions as above are valid by changingsection 1 to section 2 and vice versa.

12.2.7.5 Configuration setting

If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then theinterlocking for QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then theinterlocking for QB2 and QB20 are not used. The states for QB2, QB20, QC21,BC_12, BBTR are set to open by setting the appropriate module inputs as follows. Inthe functional block diagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

Section 12 1MRK 504 134-UEN AControl

248Application manual

Page 255: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• QB2_OP = 1• QB2_CL = 0

• QB20_OP = 1• QB20_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

• BBTR_OP = 1• VP_BBTR = 1

12.2.8 Interlocking for 1 1/2 CB BH

12.2.8.1 Application

The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A,BH_LINE_B) functions are used for lines connected to a 1 1/2 breaker diameteraccording to figure 126.

1MRK 504 134-UEN A Section 12Control

249Application manual

Page 256: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB6

QB9

QB2QC1

QA1

QC2

QC3

QB6

QC3

QB62QB61 QA1

QC1 QC2QC9

QB9

BH_LINE_A BH_LINE_B

BH_CONNen04000513.vsd

IEC04000513 V1 EN

Figure 126: Switchyard layout 1 1/2 breaker

Three types of interlocking modules per diameter are defined. BH_LINE_A andBH_LINE_B are the connections from a line to a busbar. BH_CONN is theconnection between the two lines of the diameter in the 1 1/2 breaker switchyardlayout.

For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN andBH_LINE_B must be used.

12.2.8.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:

Section 12 1MRK 504 134-UEN AControl

250Application manual

Page 257: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

12.2.9 Interlocking for double CB bay DB

12.2.9.1 Application

The interlocking for a double busbar double circuit breaker bay includingDB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to adouble busbar arrangement according to figure 127.

WA1 (A)

WA2 (B)

QB1QC1

QA1

QC2

QC9

QB61

QB9

QB2QC4

QA2

QC5

QC3

QB62

DB_BUS_B

DB_LINE

DB_BUS_A

en04000518.vsdIEC04000518 V1 EN

Figure 127: Switchyard layout double circuit breaker

Three types of interlocking modules per double circuit breaker bay are defined.DB_BUS_A handles the circuit breaker QA1 that is connected to busbar WA1 and thedisconnectors and earthing switches of this section. DB_BUS_B handles the circuitbreaker QA2 that is connected to busbar WA2 and the disconnectors and earthingswitches of this section.

1MRK 504 134-UEN A Section 12Control

251Application manual

Page 258: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE andDB_BUS_B must be used.

12.2.9.2 Configuration setting

For application without QB9 and QC9, just set the appropriate inputs to open state anddisregard the outputs. In the functional block diagram, 0 and 1 are designated0=FALSE and 1=TRUE:

• QB9_OP = 1• QB9_CL = 0

• QC9_OP = 1• QC9_CL = 0

If, in this case, line voltage supervision is added, then rather than setting QB9 to openstate, specify the state of the voltage supervision:

• QB9_OP = VOLT_OFF• QB9_CL = VOLT_ON

If there is no voltage supervision, then set the corresponding inputs as follows:

• VOLT_OFF = 1• VOLT_ON = 0

12.2.10 Interlocking for line bay ABC_LINE

12.2.10.1 Application

The interlocking for line bay (ABC_LINE) function is used for a line connected to adouble busbar arrangement with a transfer busbar according to figure 128. Thefunction can also be used for a double busbar arrangement without transfer busbar ora single busbar arrangement with/without transfer busbar.

Section 12 1MRK 504 134-UEN AControl

252Application manual

Page 259: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB1 QB2QC1

QA1

QC2

QB9QC9

WA1 (A)

WA2 (B)

WA7 (C)

QB7

en04000478.vsdIEC04000478 V1 EN

Figure 128: Switchyard layout ABC_LINE

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

The signals from other bays connected to the module ABC_LINE are describedbelow.

12.2.10.2 Signals from bypass busbar

To derive the signals:

Signal BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.

VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.

EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7

These signals from each line bay (ABC_LINE) except that of the own bay are needed:

Signal QB7OPTR Q7 is open

VPQB7TR The switch status for QB7 is valid.

EXDU_BPB No transmission error from the bay that contains the above information.

For bay n, these conditions are valid:

1MRK 504 134-UEN A Section 12Control

253Application manual

Page 260: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

QB7OPTR (bay 1)QB7OPTR (bay 2)

. . .

. . .QB7OPTR (bay n-1)

& BB7_D_OP

VPQB7TR (bay 1)VPQB7TR (bay 2)

. . .

. . .VPQB7TR (bay n-1)

& VP_BB7_D

EXDU_BPB (bay 1)EXDU_BPB (bay 2)

. . .

. . .EXDU_BPB (bay n-1)

& EXDU_BPB

en04000477.vsd

IEC04000477 V1 EN

Figure 129: Signals from bypass busbar in line bay n

12.2.10.3 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus section.

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

ABC_LINE ABC_BCABC_LINE ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000479.vsd

IEC04000479 V1 EN

Figure 130: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series can not handle the transferbus (WA7)C.

To derive the signals:

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

BC_17_OP No bus-coupler connection between busbar WA1 and WA7.

BC_17_CL A bus-coupler connection exists between busbar WA1and WA7.

BC_27_OP No bus-coupler connection between busbar WA2 and WA7.

Table continues on next page

Section 12 1MRK 504 134-UEN AControl

254Application manual

Page 261: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Signal BC_27_CL A bus-coupler connection exists between busbar WA2 and WA7.

VP_BC_12 The switch status of BC_12 is valid.

VP_BC_17 The switch status of BC_17 is valid.

VP_BC_27 The switch status of BC_27 is valid.

EXDU_BC No transmission error from any bus-coupler bay (BC).

These signals from each bus-coupler bay (ABC_BC) are needed:

Signal BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1

and WA2.

BC17OPTR No bus-coupler connection through the own bus-coupler between busbar WA1 andWA7.

BC17CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA1and WA7.

BC27OPTR No bus-coupler connection through the own bus-coupler between busbar WA2 andWA7.

BC27CLTR A bus-coupler connection through the own bus-coupler exists between busbar WA2and WA7.

VPBC12TR The switch status of BC_12 is valid.

VPBC17TR The switch status of BC_17 is valid.

VPBC27TR The switch status of BC_27 is valid.

EXDU_BC No transmission error from the bay that contains the above information.

These signals from each bus-section disconnector bay (A1A2_DC) are also needed.For B1B2_DC, corresponding signals from busbar B are used. The same type ofmodule (A1A2_DC) is used for different busbars, that is, for both bus-sectiondisconnector A1A2_DC and B1B2_DC.

Signal DCOPTR The bus-section disconnector is open.

DCCLTR The bus-section disconnector is closed.

VPDCTR The switch status of bus-section disconnector DC is valid.

EXDU_DC No transmission error from the bay that contains the above information.

If the busbar is divided by bus-section circuit breakers, the signals from the bus-section coupler bay (A1A2_BS), rather than the bus-section disconnector bay(A1A2_DC) must be used. For B1B2_BS, corresponding signals from busbar B areused. The same type of module (A1A2_BS) is used for different busbars, that is, forboth bus-section circuit breakers A1A2_BS and B1B2_BS.

1MRK 504 134-UEN A Section 12Control

255Application manual

Page 262: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Signal S1S2OPTR No bus-section coupler connection between bus-sections 1 and 2.

S1S2CLTR A bus-section coupler connection exists between bus-sections 1 and 2.

VPS1S2TR The switch status of bus-section coupler BS is valid.

EXDU_BS No transmission error from the bay that contains the above information.

For a line bay in section 1, these conditions are valid:

BC12CLTR (sect.1)

DCCLTR (A1A2)DCCLTR (B1B2)

>1&

BC12CLTR (sect.2)

&VPBC12TR (sect.1)

VPDCTR (A1A2)VPDCTR (B1B2)

VPBC12TR (sect.2)

>1&

BC17OPTR (sect.1)

DCOPTR (A1A2)BC17OPTR (sect.2)

>1&

BC17CLTR (sect.1)

DCCLTR (A1A2)BC17CLTR (sect.2)

&VPBC17TR (sect.1)

VPDCTR (A1A2)VPBC17TR (sect.2)

>1&

>1&

&

&

BC27OPTR (sect.1)

DCOPTR (B1B2)BC27OPTR (sect.2)

BC27CLTR (sect.1)

DCCLTR (B1B2)BC27CLTR (sect.2)

VPBC27TR (sect.1)VPDCTR (B1B2)

VPBC27TR (sect.2)

EXDU_BC (sect.1)EXDU_DC (A1A2)EXDU_DC (B1B2)EXDU_BC (sect.2)

BC_12_CL

VP_BC_12

BC_17_OP

BC_17_CL

VP_BC_17

BC_27_OP

BC_27_CL

VP_BC_27

EXDU_BC

en04000480.vsd

IEC04000480 V1 EN

Figure 131: Signals to a line bay in section 1 from the bus-coupler bays in eachsection

Section 12 1MRK 504 134-UEN AControl

256Application manual

Page 263: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

For a line bay in section 2, the same conditions as above are valid by changing section1 to section 2 and vice versa.

12.2.10.4 Configuration setting

If there is no bypass busbar and therefore no QB7 disconnector, then the interlockingfor QB7 is not used. The states for QB7, QC71, BB7_D, BC_17, BC_27 are set to openby setting the appropriate module inputs as follows. In the functional block diagram,0 and 1 are designated 0=FALSE and 1=TRUE:

• QB7_OP = 1• QB7_CL = 0

• QC71_OP = 1• QC71_CL = 0

• BB7_D_OP = 1

• BC_17_OP = 1• BC_17_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• EXDU_BPB = 1

• VP_BB7_D = 1• VP_BC_17 = 1• VP_BC_27 = 1

If there is no second busbar WA2 and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12, BC_27 are set toopen by setting the appropriate module inputs as follows. In the functional blockdiagram, 0 and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• BC_27_OP = 1• BC_27_CL = 0

• VP_BC_12 = 1

1MRK 504 134-UEN A Section 12Control

257Application manual

Page 264: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.2.11 Interlocking for transformer bay AB_TRAFO

12.2.11.1 Application

The interlocking for transformer bay (AB_TRAFO) function is used for a transformerbay connected to a double busbar arrangement according to figure 132. The functionis used when there is no disconnector between circuit breaker and transformer.Otherwise, the interlocking for line bay (ABC_LINE) function can be used. Thisfunction can also be used in single busbar arrangements.

QB1 QB2QC1

QA1

QC2

WA1 (A)

WA2 (B)

QA2

QC3

T

QC4

QB4QB3

QA2 and QC4 are notused in this interlocking

AB_TRAFO

en04000515.vsdIEC04000515 V1 EN

Figure 132: Switchyard layout AB_TRAFO

The signals from other bays connected to the module AB_TRAFO are describedbelow.

12.2.11.2 Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus-sections, the busbar-busbar connection could exist via the bus-section disconnector and bus-coupler withinthe other bus-section.

Section 12 1MRK 504 134-UEN AControl

258Application manual

Page 265: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 1 Section 2

A1A2_DC(BS)B1B2_DC(BS)

AB_TRAFO ABC_BCAB_TRAFO ABC_BC

(WA1)A1(WA2)B1(WA7)C C

B2A2

en04000487.vsd

IEC04000487 V1 EN

Figure 133: Busbars divided by bus-section disconnectors (circuit breakers)

The interlocking functionality in 650 series cannot handle the transferbus (WA7)C.

The project-specific logic for input signals concerning bus-coupler are the same as thespecific logic for the line bay (ABC_LINE):

Signal BC_12_CL A bus-coupler connection exists between busbar WA1 and WA2.

VP_BC_12 The switch status of BC_12 is valid.

EXDU_BC No transmission error from bus-coupler bay (BC).

The logic is identical to the double busbar configuration “Signals from bus-coupler“.

12.2.11.3 Configuration setting

If there are no second busbar B and therefore no QB2 disconnector, then theinterlocking for QB2 is not used. The state for QB2, QC21, BC_12 are set to open bysetting the appropriate module inputs as follows. In the functional block diagram, 0and 1 are designated 0=FALSE and 1=TRUE:

• QB2_OP = 1• QB2QB2_CL = 0

• QC21_OP = 1• QC21_CL = 0

• BC_12_CL = 0• VP_BC_12 = 1

If there is no second busbar B at the other side of the transformer and therefore no QB4disconnector, then the state for QB4 is set to open by setting the appropriate moduleinputs as follows:

1MRK 504 134-UEN A Section 12Control

259Application manual

Page 266: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• QB4_OP = 1• QB4_CL = 0

12.3 Voltage control

12.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Automatic voltage control for tapchanger

TR8ATCC

U

IEC10000166 V1 EN

90

Tap changer control and supervision, 6binary inputs

TCMYLTC

IEC10000167 V1 EN

84

12.3.2 Application

When the load in a power network is increased the voltage will decrease and viceversa. To maintain the network voltage at a constant level, power transformers areusually equipped with an load tap changer. This alters the power transformer ratio ina number of predefined steps and in that way changes the voltage. Each step usuallyrepresents a change in voltage of approximately 0.5-1.7%.

The voltage control function is intended for control of power transformers with amotor driven load tap changer. The function is designed to regulate the voltage at thesecondary side of the power transformer. The control method is based on a step-by-step principle which means that a control pulse, one at a time, will be issued to the tapchanger mechanism to move it one position up or down. The length of the controlpulse can be set within a wide range to accommodate different types of tap changermechanisms. The pulse is generated whenever the measured voltage, for a given time,deviates from the set reference value by more than the preset deadband (degree ofinsensitivity).

The voltage can be controlled at the point of voltage measurement, as well as a loadpoint located out in the network. In the latter case, the load point voltage is calculatedbased on the measured load current and the known impedance from the voltagemeasuring point to the load point.

The automatic voltage control can be either for a single transformer, or for paralleltransformers. Parallel control of power transformers with an IED can be made in threealternative ways:

Section 12 1MRK 504 134-UEN AControl

260Application manual

Page 267: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• With the master-follower method• With the reverse reactance method• With the circulating current method

Of these alternatives, the first and the last require communication between thefunction control blocks of the different transformers, whereas the middle alternativedoes not require any communication.

The voltage control includes many extra features such as possibility to avoidsimultaneous tapping of parallel transformers, extensive tap changer monitoringincluding contact wear and hunting detection, monitoring of the power flow in thetransformer so that for example, the voltage control can be blocked if the powerreverses and so on.

The voltage control function is built up by two function blocks which both are logicalnodes in IEC 61850-8-1:

• Automatic voltage control for tap changer, TR8ATCC for parallel control.• Tap changer control and supervision, 6 binary inputs, TCMYLTC

Automatic voltage control for tap changer, TR8ATCC is a function designed toautomatically maintain the voltage at the LV-side side of a power transformer withingiven limits around a set target voltage. A raise or lower command is generatedwhenever the measured voltage, for a given period of time, deviates from the set targetvalue by more than the preset deadband value (degree of insensitivity). A time delay(inverse or definite time) is set to avoid unnecessary operation during shorter voltagedeviations from the target value, and in order to coordinate with other automaticvoltage controllers in the system.

TCMYLTCis an interface between the Automatic voltage control for tap changer,TR8ATCC and the transformer load tap changer itself. More specifically this meansthat it gives command-pulses to a power transformer motor driven load tap changerand that it receives information from the load tap changer regarding tap position,progress of given commands, and so on.

TCMYLTC also serves the purpose of giving information about tap position to thetransformer differential protection.

Control location local/remoteThe tap changer can be operated from the front of the IED or from a remote placealternatively. On the IED front there is a local remote switch that can be used to selectthe operator place. For this functionality the Apparatus control function blocks Baycontrol (QCBAY), Local remote (LOCREM) and Local remote control(LOCREMCTRL) are used.

Information about the control location is given to TR8ATCC function throughconnection of the Permitted Source to Operate (PSTO) output of the QCBAY functionblock to the input PSTO of the TR8ATCC function block.

1MRK 504 134-UEN A Section 12Control

261Application manual

Page 268: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Control ModeThe control mode of the automatic voltage control for tap changer function,TR8ATCC for parallel control can be:

• Manual• Automatic

The control mode can be changed from the local location via the command menu onthe local HMI under Main menu/ Control/Commands/TR8ATCC (90)/1:TR8ATCC, or changed from a remote location via binary signals connected to theMANCTRL, AUTOCTRL inputs on TR8ATCC function block.

Measured QuantitiesIn normal applications, the LV side of the transformer is used as the voltage measuringpoint. If necessary, the LV side current is used as load current to calculate the line-voltage drop to the regulation point.

Automatic voltage control for tap changer, TR8ATCC function block has three inputsI3P1, I3P2 and U3P2 corresponding to HV-current, LV-current and LV-voltagerespectively. These analog quantities are fed to the IED via the transformer inputmodule, the Analog to Digital Converter and thereafter a Pre-Processing Block. In thePre-Processing Block, a great number of quantities for example, phase-to-phaseanalog values, sequence values, max value in a three phase group etc., are derived. Thedifferent function blocks in the IED are then “subscribing” on selected quantities fromthe pre-processing blocks. In case of TR8ATCC, there are the following possibilities:

• I3P1 represents a three-phase group of phase current with the highest current inany of the three phases considered. As only the highest of the phase current isconsidered, it is also possible to use one single-phase current as well as two-phasecurrents. In these cases, the currents that are not used will be zero.

• For I3P2 and U3P2 the setting alternatives are: any individual phase current/voltage, as well as any combination of phase-phase current/voltage or the positivesequence current/voltage. Thus, single-phase as well as, phase-phase or three-phase feeding on the LV-side is possible but it is commonly selected for currentand voltage.

Section 12 1MRK 504 134-UEN AControl

262Application manual

Page 269: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

OLT

C

raise,lowersignals/alarms

positionBIO

AIM

IED

IL1,IL2,IL3

TRMIL1,IL2,IL3 or ILi,ILj or ILi

UL1,UL2,UL3 or ULi,ULj or ULi

High Voltage Side

(Load Current) IL

Low Voltage Side

Line Impedance R+jX

UB (Busbar Voltage)

Load Center UL (Load Point Voltage)

IEC11000064-1-en.vsdIEC11000064 V1 EN

Figure 134: Signal flow for a single transformer with voltage control

On the HV side, the three-phase current is normally required in order to feed the three-phase over current protection that blocks the load tap changer in case of over-currentabove harmful levels.

The voltage measurement on the LV-side can be made single phase-earth. However,it shall be remembered that this can only be used in solidly earthed systems, as themeasured phase-earth voltage can increase with as much as a factor √3 in case of earthfaults in a non-solidly earthed system.

The analog input signals are normally common with other functions in the IED forexample, protection functions.

The LV-busbar voltage is designated UB, the load current IL and loadpoint voltage UL.

Automatic voltage control for a single transformerAutomatic voltage control for tap changer, parallel control TR8ATCC measures themagnitude of the busbar voltage UB. If no other additional features are enabled (linevoltage drop compensation), this voltage is further used for voltage regulation.

1MRK 504 134-UEN A Section 12Control

263Application manual

Page 270: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

TR8ATCC then compares this voltage with the set voltage, USet and decides whichaction should be taken. To avoid unnecessary switching around the setpoint, adeadband (degree of insensitivity) is introduced. The deadband is symmetrical aroundUSet, see figure 135, and it is arranged in such a way that there is an outer and an innerdeadband. Measured voltages outside the outer deadband start the timer to initiate tapcommands, whilst the sequence resets when the measured voltage is once again backinside the inner deadband. One half of the outer deadband is denoted ΔU. The settingof ΔU, setting Udeadband should be set to a value near to the power transformer’s tapchanger voltage step (typically 75–125% of the tap changer step).

Voltage MagnitudeUmaxU2UsetU1UminUblock0

Raise Cmd

*) Action in accordance with setting

Security Range

Lower Cmd

IEC06000489_2_en.vsd

DD U UDUin DUin

*) *) *)

IEC06000489 V2 EN

Figure 135: Control actions on a voltage scale

During normal operating conditions the busbar voltage UB, stays within the outerdeadband (interval between U1 and U2 in figure 135). In that case no actions will betaken by TR8ATCC. However, if UB becomes smaller than U1, or greater than U2, anappropriate lower or raise timer will start. The timer will run as long as the measuredvoltage stays outside the inner deadband. If this condition persists longer than thepreset time delay, TR8ATCC will initiate that the appropriate ULOWER or URAISEcommand will be sent from Tap changer control and supervision, 6 binary inputsTCMYLTC to the transformer load tap changer. If necessary, the procedure will berepeated until the magnitude of the busbar voltage again falls within the innerdeadband. One half of the inner deadband is denoted ΔUin. The inner deadband ΔUin,setting UDeadbandInner should be set to a value smaller than ΔU. It is recommendedto set the inner deadband to 25-70% of the ΔU value.

This way of working is used by TR8ATCC while the busbar voltage is within thesecurity range defined by settings Umin and Umax.

A situation where UB falls outside this range will be regarded as an abnormalsituation.

When UB falls below setting Ublock, or alternatively, falls below setting Umin but stillabove Ublock, or rises above Umax, actions will be taken in accordance with settingsfor blocking conditions (refer to table 25).

If the busbar voltage rises above Umax, TR8ATCC can initiate one or more fast stepdown commands (ULOWER commands) in order to bring the voltage back into thesecurity range (settings Umin, and Umax). The fast step down function operation canbe set in one of the following three ways: off /auto/auto and manual, according to the

Section 12 1MRK 504 134-UEN AControl

264Application manual

Page 271: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

setting FSDMode. The ULOWER command, in fast step down mode, is issued withthe settable time delay tFSD.

The measured RMS magnitude of the busbar voltage UB is shown on the local HMI asvalue BUSVOLT under Main menu/Tests/Function status/Control/TR8ATCC(90)/1:TR8ATCC/Outputs.

Time characteristicThe time characteristic defines the time that elapses between the moment whenmeasured voltage exceeds the deadband interval until the appropriate URAISE orULOWER command is initiated.

The purpose of the time delay is to prevent unnecessary load tap changer operationscaused by temporary voltage fluctuations and to coordinate load tap changeroperations in radial networks in order to limit the number of load tap changeroperations. This can be done by setting a longer time delay closer to the consumer andshorter time delays higher up in the system.

The first time delay, t1, is used as a time delay (usually long delay) for the firstcommand in one direction. It can have a definite or inverse time characteristic,according to the setting t1Use (Constant/Inverse). For inverse time characteristicslarger voltage deviations from the USet value will result in shorter time delays, limitedby the shortest time delay equal to the tMin setting. This setting should be coordinatedwith the tap changer mechanism operation time.

Constant (definite) time delay is independent of the voltage deviation.

The inverse time characteristic for the first time delay follows the formulas:

DA UB USet= -

IECEQUATION2294 V1 EN (Equation 116)

DADU

=D

EQUATION1986 V1 EN (Equation 117)

t1tMin D=

EQUATION1848 V2 EN (Equation 118)

Where:

DA absolute voltage deviation from the set point

D relative voltage deviation in respect to set deadband value

For the last equation, the condition t1 > tMin shall also be fulfilled. This practicallymeans that tMin will be equal to the set t1 value when absolute voltage deviation DA

1MRK 504 134-UEN A Section 12Control

265Application manual

Page 272: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

is equal to ΔU ( relative voltage deviation D is equal to 1). For other values seefigure 136. It should be noted that operating times, shown in the figure 136 are for 30,60, 90, 120, 150 & 180 seconds settings for t1 and 10 seconds for tMin.

t1=180

t1=150

t1=120

t1=90

t1=60

t1=30

IEC06000488_2_en.vsd

IEC06000488 V2 EN

Figure 136: Inverse time characteristic for TR8ATCC

The second time delay, t2, will be used for consecutive commands (commands in thesame direction as the first command). It can have a definite or inverse timecharacteristic according to the setting t2Use (Constant/Inverse). Inverse timecharacteristic for the second time delay follows the similar formulas as for the firsttime delay, but the t2 setting is used instead of t1.

Line voltage dropThe purpose with the line voltage drop compensation is to control the voltage, not atthe power transformer low voltage side, but at a point closer to the load point.

Figure 137 shows the vector diagram for a line modelled as a series impedance withthe voltage UB at the LV busbar and voltage UL at the load center. The load current onthe line is IL, the line resistance and reactance from the station busbar to the load pointare RL and XL. The angle between the busbar voltage and the current, is j. If all theseparameters are known UL can be obtained by simple vector calculation.

Values for RL and XL are given as settings in primary system ohms. If more than oneline is connected to the LV busbar, an equivalent impedance should be calculated andgiven as a parameter setting.

The line voltage drop compensation function can be turned On/Off by the settingparameter OperationLDC. When it is enabled, the voltage UL will be used by theAutomatic voltage control for tap changer function, TR8ATCC for parallel control for

Section 12 1MRK 504 134-UEN AControl

266Application manual

Page 273: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

voltage regulation instead of UB. However, TR8ATCC will still perform thefollowing two checks:

1. The magnitude of the measured busbar voltage UB, shall be within the securityrange, (setting Umin and Umax). If the busbar voltage falls-out of this range theline voltage drop compensation calculations will be temporarily stopped until thevoltage UB comes back within the range.

2. The magnitude of the calculated voltage UL at the load point, can be limited suchthat it is only allowed to be equal to or smaller than the magnitude of UB,otherwise UB will be used. However, a situation where UL>UB can be caused bya capacitive load condition, and if the wish is to allow for a situation like that, thelimitation can be removed by setting the parameter OperCapaLDC to On.

~ Load

RL XL

UB

UL

UB

RLIL

jXLIL Re

en06000487.vsd

IEC06000487 V1 EN

Figure 137: Vector diagram for line voltage drop compensation

The calculated load voltage UL is shown on the local HMI as value ULOAD underMain menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

Load voltage adjustmentDue to the fact that most loads are proportional to the square of the voltage, it ispossible to provide a way to shed part of the load by decreasing the supply voltage acouple of percent.

It is possible to do this voltage adjustment in two different ways in Automatic voltagecontrol for tap changer, parallel control TR8ATCC:

1. Automatic load voltage adjustment, proportional to the load current.2. Constant load voltage adjustment with four different preset values.

In the first case the voltage adjustment is dependent on the load and maximum voltageadjustment should be obtained at rated load of the transformer.

In the second case, a voltage adjustment of the set point voltage can be made in fourdiscrete steps (positive or negative) activated with binary signals connected toTR8ATCC function block inputs LVA1, LVA2, LVA3 and LVA4. Thecorresponding voltage adjustment factors are given as setting parameters LVAConst1,LVAConst2, LVAConst3 and LVAConst4. The inputs are activated with a pulse, and

1MRK 504 134-UEN A Section 12Control

267Application manual

Page 274: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

the latest activation of anyone of the four inputs is valid. Activation of the inputLVARESET in TR8ATCC block, brings the voltage setpoint back to USet.

With these factors, TR8ATCC adjusts the value of the set voltage USet according tothe following formula:

Usetadjust = Uset + Sa × IL + Sci

IBaseEQUATION1865 V2 EN (Equation 119)

Uset, adjust Adjusted set voltage in per unit

USet Original set voltage: Base quality is Un2

Sa Automatic load voltage adjustment factor, setting VRAuto

IL Load current

IBase Rated current, LV winding (for winding 2, which is defined in a global base function,selected with setting GlobalBaseSel2 for TR8ATCC)

Sci Constant load voltage adjust. factor for active input i (corresponding to LVAConst1,LVAConst2, LVAConst3 and LVAConst4)

It shall be noted that the adjustment factor is negative in order to decrease the loadvoltage and positive in order to increase the load voltage. After this calculation Uset,

adjust will be used by TR8ATCC for voltage regulation instead of the original valueUSet. The calculated set point voltage USet, adjust is shown on the local HMI as a servicevalue USETOUT under and Main menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

Automatic control of parallel transformersParallel control of power transformers means control of two or more powertransformers connected to the same busbar on the LV side and in most cases also onthe HV side. Special measures must be taken in order to avoid a runaway situationwhere the tap changers on the parallel transformers gradually diverge and end up inopposite end positions.

Three alternative methods can be used in an IED for parallel control with theAutomatic voltage control for tap changer, TR8ATCC:

• master-follower method• reverse reactance method• circulating current method

In order to realize the need for special measures to be taken when controllingtransformers in parallel, consider first two parallel transformers which are supposedto be equal with similar tap changers. If they would each be in automatic voltagecontrol for single transformer that is, each of them regulating the voltage on the LVbusbar individually without any further measures taken, then the following couldhappen. Assuming for instance that they start out on the same tap position and that the

Section 12 1MRK 504 134-UEN AControl

268Application manual

Page 275: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

LV busbar voltage UB is within USet ± DU, then a gradual increase or decrease in theload would at some stage make UB fall outside USet ± DU and a lower or raisecommand would be initiated. However, the rate of change of voltage would normallybe slow, which would make one tap changer act before the other. This is unavoidableand is due to small inequalities in measurement and so on. The one tap changer thatresponds first on a low voltage condition with a raise command will be prone to alwaysdo so, and vice versa. The situation could thus develop such that, for example T1responds first to a low busbar voltage with a raise command and thereby restores thevoltage. When the busbar voltage thereafter at a later stage gets high, T2 could respondwith a lower command and thereby again restore the busbar voltage to be within theinner deadband. However, this has now caused the load tap changer for the twotransformers to be 2 tap positions apart, which in turn causes an increasing circulatingcurrent. This course of events will then repeat with T1 initiating raise commands andT2 initiating lower commands in order to keep the busbar voltage within USet ± DU,but at the same time it will drive the two tap changers to its opposite end positions.High circulating currents and loss of control would be the result of this runaway tapsituation.

Parallel control with the master-follower methodIn the master-follower method, one of the transformers is selected to be master, andwill regulate the voltage in accordance with the principles for Automatic voltagecontrol. Selection of the master is made by activating the binary input FORCMASTin TR8ATCC function block for one of the transformers in the group.

The followers can act in two alternative ways depending on the setting of theparameter MFMode. When this setting is Follow Cmd, raise and lower commands(URAISE and ULOWER) generated by the master, will initiate the correspondingcommand in all follower TR8ATCCs simultaneously, and consequently they willblindly follow the master irrespective of their individual tap positions. Effectively thismeans that if the tap positions of the followers were harmonized with the master fromthe beginning, they would stay like that as long as all transformers in the parallel groupcontinue to participate in the parallel control. On the other hand for example, onetransformer is disconnected from the group and misses a one tap step operation, andthereafter is reconnected to the group again, it will thereafter participate in theregulation but with a one tap position offset.

If the parameter MFMode is set to Follow Tap, then the followers will read the tapposition of the master and adopt to the same tap position or to a tap position with anoffset relative to the master, and given by setting parameter TapPosOffs (positive ornegative integer value). The setting parameter tAutoMSF introduces a time delay onURAISE/ULOWER commands individually for each follower when setting MFModehas the value Follow Tap.

Selecting a master is made by activating the input FORCMAST in TR8ATCCfunction block. Deselecting a master is made by activating the input RSTMAST.These two inputs are pulse activated, and the most recent activation is valid that is, anactivation of any of these two inputs overrides previous activations. If none of theseinputs has been activated, the default is that the transformer acts as a follower (givenof course that the settings are parallel control with the master follower method).

1MRK 504 134-UEN A Section 12Control

269Application manual

Page 276: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

When the selection of master or follower in parallel control, or automatic control insingle mode, is made with a three position switch in the substation, an arrangement asin figure 138 below is arranged with ACT tool.

M

F

I SNGLMODE

FORCMAST

RSTMAST

TR8ATCC

IEC09000333-1-en.vsd

BIO

IEC09000333 V1 EN

Figure 138: Principle for a three-position switch Master/Follower/Single

Parallel control with the reverse reactance methodConsider figure 139 with two parallel transformers with equal rated data and similartap changers. The tap positions will diverge and finally end up in a runaway tapsituation if no measures to avoid this are taken.

Section 12 1MRK 504 134-UEN AControl

270Application manual

Page 277: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Load

T1

I L

T2

UB

UL

IT1 IT2

en06000486.vsd

IEC06000486 V1 EN

Figure 139: Parallel transformers with equal rated data.

In the reverse reactance method, the line voltage drop compensation is used. Thepurpose is to control the voltage at a load point further out in the network. The verysame function can also be used here but with a completely different objective.

Figure 140, shows a vector diagram where the principle of reverse reactance has beenintroduced for the transformers in figure 139. The transformers are here supposed tobe on the same tap position, and the busbar voltage is supposed to give a calculatedcompensated value UL that coincides with the target voltage USet.

IEC06000485_2_en.vsd

UB

RLIT1=RLIT2

jXLIT1=jXLIT2

IT1=IT2=(IT1+IT2)/2

UL1=UL2=USet

IEC06000485 V2 EN

Figure 140: Vector diagram for two transformers regulated exactly on targetvoltage.

A comparison with figure 137 gives that the line voltage drop compensation for thepurpose of reverse reactance control is made with a value with opposite sign on XL,hence the designation “reverse reactance” or “negative reactance”. Effectively this

1MRK 504 134-UEN A Section 12Control

271Application manual

Page 278: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

means that, whereas the line voltage drop compensation in figure 137 gave a voltagedrop along a line from the busbar voltage UB to a load point voltage UL, the linevoltage drop compensation in figure 140 gives a voltage increase (actually, byadjusting the ratio XL/RL with respect to the power factor, the length of the vector ULwill be approximately equal to the length of UB) from UB up towards the transformeritself. Thus in principal the difference between the vector diagrams in figure 137 andfigure 140 is the sign of the setting parameter XL.

If now the tap position between the transformers will differ, a circulating current willappear, and the transformer with the highest tap (highest no load voltage) will be thesource of this circulating current. Figure 141 below shows this situation with T1 beingon a higher tap than T2.

Load

T1 T2

UB

UL

IT1 IT2

UB

UL1 RIT1

jXLIT1

Icc

-Icc

(IT1+IT2)/2IT1

IT2

UL2

RLIT2

jXLIT2

IEC06000491-2-en.vsd

ICC...T2

ICC...T1

IL

IEC06000491 V2 EN

Figure 141: Circulating current caused by T1 on a higher tap than T2.

The circulating current Icc is predominantly reactive due to the reactive nature of thetransformers. The impact of Icc on the individual transformer currents is that itincreases the current in T1 (the transformer that is driving Icc) and decreases it in T2at the same time as it introduces contradictive phase shifts, as can be seen infigure 141. The result is thus, that the line voltage drop compensation calculatedvoltage UL for T1 will be higher than the line voltage drop compensation calculatedvoltage UL for T2, or in other words, the transformer with the higher tap position willhave the higher UL value and the transformer with the lower tap position will have thelower UL value. Consequently, when the busbar voltage increases, T1 will be the oneto tap down, and when the busbar voltage decreases, T2 will be the one to tap up. Theoverall performance will then be that the runaway tap situation will be avoided andthat the circulating current will be minimized.

Section 12 1MRK 504 134-UEN AControl

272Application manual

Page 279: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Parallel control with the circulating current methodTwo transformers with different turns ratio, connected to the same busbar on the HV-side, will apparently show different LV-side voltage. If they are now connected to thesame LV busbar but remain unloaded, this difference in no-load voltage will cause acirculating current to flow through the transformers. When load is put on thetransformers, the circulating current will remain the same, but now it will besuperimposed on the load current in each transformer. Voltage control of paralleltransformers with the circulating current method means minimizing of the circulatingcurrent at a given voltage target value, thereby achieving:

1. that the busbar or load voltage is regulated to a preset target value2. that the load is shared between parallel transformers in proportion to their ohmic

short circuit reactance

If the transformers have equal percentage impedance given in the respectivetransformer MVA base, the load will be divided in direct proportion to the rated powerof the transformers when the circulating current is minimized.

This method requires extensive exchange of data between the TR8ATCC functionblocks (one TR8ATCC function for each transformer in the parallel group).TR8ATCC function block can either be located in the same IED, where they areconfigured in PCM600 to co-operate, or in different IEDs. If the functions are locatedin different IEDs they must communicate via GOOSE interbay communication on theIEC 61850 communication protocol. .

The busbar voltage UB is measured individually for each transformer in the parallelgroup by its associated TR8ATCC function. These measured values will then beexchanged between the transformers, and in each TR8ATCC block, the mean value ofall UB values will be calculated. The resulting value UBmean will then be used in eachIED instead of UB for the voltage regulation, thus assuring that the same value is usedby all TR8ATCC functions, and thereby avoiding that one erroneous measurement inone transformer could upset the voltage regulation. At the same time, supervision ofthe VT mismatch is also performed. This works such that, if a measured voltage UB,differs from UBmean with more than a preset value (setting parameter VTmismatch)and for more than a pre set time (setting parameter tVTmismatch) an alarm signalVTALARM will be generated.

The calculated mean busbar voltage UBmean is shown on the local HMI as a servicevalue BusVolt under Main menu/Tests/Function status/Control/TR8ATCC (90)/1:TR8ATCC/Outputs.

Measured current values for the individual transformers must be communicatedbetween the participating TR8ATCC functions, in order to calculate the circulatingcurrent.

The calculated circulating current Icc_i for transformer “i” is shown on the HMI as aservice value ICIRCUL under Main menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

1MRK 504 134-UEN A Section 12Control

273Application manual

Page 280: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

When the circulating current is known, it is possible to calculate a no-load voltage foreach transformer in the parallel group. To do that the magnitude of the circulatingcurrent in each bay, is first converted to a voltage deviation, Udi, with equation 120:

_di i cc i iU C I X= ´ ´

EQUATION1869 V1 EN (Equation 120)

where Xi is the short-circuit reactance for transformer i and Ci, is a setting parameternamed Comp which serves the purpose of alternatively increasing or decreasing theimpact of the circulating current in TR8ATCC control calculations. It should be notedthat Udi will have positive values for transformers that produce circulating currentsand negative values for transformers that receive circulating currents.

Now the magnitude of the no-load voltage for each transformer can be approximatedwith:

i Bmean diU U U= +

EQUATION1870 V1 EN (Equation 121)

This value for the no-load voltage is then simply put into the voltage control functionfor single transformer. There it is treated as the measured busbar voltage, and furthercontrol actions are taken as described previously in section "Automatic voltagecontrol for a single transformer". By doing this, the overall control strategy can besummarized as follows.

For the transformer producing/receiving the circulating current, the calculated no-load voltage will be greater/smaller than the measured voltage UBmean. The calculatedno-load voltage will then be compared with the set voltage USet. A steady deviationwhich is outside the outer deadband will result in ULOWER or URAISE beinginitiated alternatively. In this way the overall control action will always be correctsince the position of a tap changer is directly proportional to the transformer no-loadvoltage. The sequence resets when UBmean is inside the inner deadband at the sametime as the calculated no-load voltages for all transformers in the parallel group areinside the outer deadband.

In parallel operation with the circulating current method, different USet values forindividual transformers can cause the voltage regulation to be unstable. For thisreason, the mean value of USet for parallel operating transformers can beautomatically calculated and used for the voltage regulation. This is set On/Off bysetting parameter OperUsetPar. The calculated mean USet value is shown on the localHMI as a service value USETPAR under Main menu/Control/Commands/TR8ATCC (90)/X:TR8ATCC.

The use of mean USet is recommended for parallel operation with the circulatingcurrent method, especially in cases when Load Voltage Adjustment is also used.

Section 12 1MRK 504 134-UEN AControl

274Application manual

Page 281: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Line voltage drop compensation for parallel controlThe line voltage drop compensation for a single transformer is described in section"Line voltage drop". The same principle is used for parallel control with thecirculating current method and with the master – follower method, except that the totalload current, IL, is used in the calculation instead of the individual transformer current.(See figure 137 for details). The same values for the parameters Rline and Xline shallbe set in all IEDs in the same parallel group. There is no automatic change of theseparameters due to changes in the substation topology, thus they should be changedmanually if needed.

Adapt mode, manual control of a parallel group

Adapt mode (operation with the circulating current method)When the circulating current method is used, it is also possible to manually control thetransformers as a group. To achieve this, the setting OperationAdapt must be set On,then the control mode for one TR8ATCC shall be set to “Manual” via the binary inputMANCTRL or the local HMI under Main menu/Control/Commands/TR8ATCC(90)/1:TR8ATCC whereas the other TR8ATCCs are left in “Automatic”.TR8ATCCs in automatic mode will then observe that one transformer in the parallelgroup is in manual mode and will then automatically be set in adapt mode. As the nameindicates they will adapt to the manual tapping of the transformer that has been put inmanual mode.

TR8ATCC in adapt mode will continue the calculation of Udi, but instead of addingUdi to the measured busbar voltage, it will compare it with the deadband DU. Thefollowing control rules are used:

1. If Udi is positive and its modulus is greater thanDU, then initiate an ULOWERcommand. Tapping will then take place after appropriate t1/t2 timing.

2. If Udi is negative and its modulus is greater than DU, then initiate an URAISEcommand. Tapping will then take place after appropriate t1/t2 timing.

3. If Udi modulus is smaller thanDU, then do nothing.

The binary output signal ADAPT on the TR8ATCC function block will be activatedto indicate that this TR8ATCC is adapting to another TR8ATCC in the parallel group.

It shall be noted that control with adapt mode works as described under the conditionthat only one transformer in the parallel group is set to manual mode via the binaryinput MANCTRL or, the local HMI Main menu/Control/Commands/TR8ATCC(90)/1:TR8ATCC.

In order to operate each tap changer individually when the circulating current methodis used, the operator must set each TR8ATCC in the parallel group, in manual.

Adapt mode (operation with the master follower method)When in master follower mode, the adapt situation occurs when the settingOperationAdapt is On, and the master is put in manual control with the followers stillin parallel master-follower control. In this situation the followers will continue tofollow the master the same way as when it is automatic control.

1MRK 504 134-UEN A Section 12Control

275Application manual

Page 282: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

If one follower in a master follower parallel group is put in manual mode, still with thesetting OperationAdaptOn, the rest of the group will continue in automatic masterfollower control. The follower in manual mode will of course disregard any possibletapping of the master. However, as one transformer in the parallel group is nowexempted from the parallel control, the binary output signal ADAPT on TR8ATCCfunction block will be activated for the rest of the parallel group.

Power monitoringThe level (with sign) of active and reactive power flow through the transformer, canbe monitored. This function can be utilized for different purposes for example, toblock the voltage control function when active power is flowing from the LV side tothe HV side or to initiate switching of reactive power compensation plant, and so on.

There are four setting parameters P>, P<, Q> and Q< with associated outputs inTR8ATCC function blocks PGTFWD, PLTREV, QGTFWD and QLTREV. Whenpassing the pre-set value, the associated output will be activated after the commontime delay setting tPower.

The definition of direction of the power is such that the active power P is forward whenpower flows from the HV-side to the LV-side as shown in figure 142. The reactivepower Q is forward when the total load on the LV side is inductive ( reactance) asshown in figure 142.

ATCC

IED

HV-side

Pforward

LV-sideIEC06000536_1_en.vsd

Qforward (inductive)

IEC06000536 V2 EN

Figure 142: Power direction references

With the four outputs in the function block available, it is possible to do more than justsupervise a level of power flow in one direction. By combining the outputs withlogical elements in ACT tool, it is also possible to cover for example, intervals as wellas areas in the P-Q plane.

Busbar topology logicInformation of the busbar topology that is, position of circuit breakers and isolators,yielding which transformers that are connected to which busbar and which busbarsthat are connected to each other, is vital for the Automatic voltage control for tapchanger, parallel control function TR8ATCC when the circulating current or the

Section 12 1MRK 504 134-UEN AControl

276Application manual

Page 283: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

master-follower method is used. This information tells each TR8ATCC, whichtransformers that it has to consider in the parallel control.

In a simple case, when only the switchgear in the transformer bays needs to beconsidered, there is a built-in function in TR8ATCC block that can provideinformation on whether a transformer is connected to the parallel group or not. This ismade by connecting the transformer CB auxiliary contact status to TR8ATCCfunction block input DISC, which can be made via a binary input, or via GOOSE fromanother IED in the substation. When the transformer CB is open, this activates thatinput which in turn will make a corresponding signal DISC=1 in TR8ATCC data set.This data set is the same data package as the package that contains all TR8ATCC datatransmitted to the other transformers in the parallel group (see section "Exchange ofinformation between TR8ATCC functions" for more details). Figure 143 shows anexample where T3 is disconnected which will lead to T3 sending the DISC=1 signalto the other two parallel TR8ATCC modules (T1 and T2) in the group. Also see table24.

T1 T2 T3

99000952.VSD

U1 U2 U3

Z1 Z2 Z3I1 I2 I3=0

IL=I1+I2

IEC99000952 V1 EN

Figure 143: Disconnection of one transformer in a parallel group

When the busbar arrangement is more complicated with more buses and bus couplers/bus sections, it is necessary to engineer a specific station topology logic. This logic canbe built in the ACT tool in PCM600 and will keep record on which transformers thatare in parallel (in one or more parallel groups). In each TR8ATCC function blockthere are four binary inputs (T1INCLD,..., T4INCLD) that will be activated from thelogic depending on which transformers that are in parallel with the transformer towhom the TR8ATCC function block belongs.

TR8ATCC function block is also fitted with four outputs (T1PG,..., T4PG) forindication of the actual composition of the parallel group that it itself is part of. Ifparallel operation mode has been selected in the IED with setting TrfId = Tx, then theTxPG signal will always be set to 1. The parallel function will considercommunication messages only from the voltage control functions working in parallel(according to the current station configuration). When the parallel voltage controlfunction detects that no other transformers work in parallel it will behave as a singlevoltage control function in automatic mode.

1MRK 504 134-UEN A Section 12Control

277Application manual

Page 284: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Exchange of information between TR8ATCC functionsEach transformer in a parallel group needs an Automatic voltage control for tapchanger, parallel control TR8ATCC function block of its own for the parallel voltagecontrol. Communication between these TR8ATCCs is made either on the GOOSEinterbay communication on the IEC 61850 protocol if TR8ATCC functions reside indifferent IEDs, or alternatively configured internally in one IED if multiple instancesof TR8ATCC reside in the same IED. Complete exchange of TR8ATCC data, analogas well as binary, on GOOSE is made cyclically every 300 ms.

TR8ATCC function block has an output ATCCOUT. This output contains two sets ofsignals. One is the data set that needs to be transmitted to other TR8ATCC blocks inthe same parallel group, and the other is the data set that is transferred to theTCMYLTC function block for the same transformer as TR8ATCC block belongs to.

There are 10 binary signals and 6 analog signals in the data set that is transmitted fromone TR8ATCC block to the other TR8ATCC blocks in the same parallel group:

Table 22: Binary signals

Signal ExplanationTimerOn This signal is activated by the transformer that has started its timer and is going

to tap when the set time has expired.

automaticCTRL Activated when the transformer is set in automatic control

mutualBlock Activated when the automatic control is blocked

disc Activated when the transformer is disconnected from the busbar

receiveStat Signal used for the horizontal communication

TermIsForcedMaster Activated when the transformer is selected Master in the master-followerparallel control mode

TermIsMaster Activated for the transformer that is master in the master-follower parallelcontrol mode

termReadyForMSF Activated when the transformer is ready for master-follower parallel controlmode

raiseVoltageOut Order from the master to the followers to tap up

lowerVoltageOut Order from the master to the followers to tap down

Table 23: Analog signals

Signal ExplanationvoltageBusbar Measured busbar voltage for this transformer

ownLoadCurrim Measured load current imaginary part for this transformer

ownLoadCurrre Measured load current real part for this transformer

reacSec Transformer reactance in primary ohms referred to the LV side

relativePosition The transformer's actual tap position

voltage Setpoint The transformer's set voltage (USet) for automatic control

Section 12 1MRK 504 134-UEN AControl

278Application manual

Page 285: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Manual configuration of VCTR GOOSE data set is required. Note thatboth data value attributes and quality attributes have to be mapped.The following data objects must be configured:

• BusV• LodAIm• LodARe• PosRel• SetV• VCTRStatus• X2

The transformers controlled in parallel with the circulating current method or themaster-follower method must be assigned unique identities. These identities areentered as a setting in each TR8ATCC, and they are predefined as T1, T2, T3,T4( transformers 1 to 4). In figure 143 there are three transformers with the parameterTrfId set to T1, T2 and T3, respectively.

For parallel control with the circulating current method or the master-follower methodalternatively, the same type of data set as described above, must be exchangedbetween two TR8ATCC. To achieve this, each TR8ATCC is transmitting its own dataset on the output ATCCOUT as previously mentioned. To receive data from the othertransformers in the parallel group, the output ATCCOUT from each transformer mustbe connected (via GOOSE or internally in the application configuration) to the inputsHORIZx (x = identifier for the other transformers in the parallel group) on TR8ATCCfunction block. Apart from this, there is also a setting in each TR8ATCCT1RXOP=Off/On,..., T4RXOP=Off/On. This setting determines from which of theother transformer individuals that data shall be received. Settings in the threeTR8ATCC blocks for the transformers in figure 143, would then be according to thetable 24:

Table 24: Setting of TxRXOP

TrfId=T1 T1RXOP=Off T2RXOP=On T3RXOP=On T4RXOP=Off

TrfId=T2 T1RXOP=On T2RXOP=Off T3RXOP=On T4RXOP=Off

TrfId=T3 T1RXOP=On T2RXOP=On T3RXOP=Off T4RXOP=Off

Observe that this parameter must be set to Off for the “own” transformer. (fortransformer with identity T1 parameter T1RXOP must be set to Off, and so on.

Blocking

Blocking conditionsThe purpose of blocking is to prevent the tap changer from operating under conditionsthat can damage it, or otherwise when the conditions are such that power systemrelated limits would be exceeded or when, for example the conditions for automaticcontrol are not met.

1MRK 504 134-UEN A Section 12Control

279Application manual

Page 286: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

For the Automatic voltage control for tap changer function, TR8ATCC for parallelcontrol, three types of blocking are used:

Partial Block: Prevents operation of the tap changer only in one direction (onlyURAISE or ULOWER command is blocked) in manual and automatic control mode.

Auto Block: Prevents automatic voltage regulation, but the tap changer can still becontrolled manually.

Total Block: Prevents any tap changer operation independently of the control mode(automatic as well as manual).

Setting parameters for blocking that can be set in TR8ATCC under general settings inlocal HMI are listed in table 25.

Table 25: Blocking settings

Setting Values (Range) DescriptionOCBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

When any one of the three HV currents exceeds the presetvalue IBlock, TR8ATCC will be temporarily totally blocked.The outputs IBLK and TOTBLK or AUTOBLK will beactivated depending on the actual parameter setting.

OVPartBk(automaticallyreset)

AlarmAuto&Man Block

If the busbar voltage UB (not the compensated load pointvoltage UL) exceeds Umax (see figure 135, further URAISEcommands will be blocked if the value Auto&Man Block isselected. If permitted by setting, a fast step down action willbe initiated in order to re-enter into the range Umin < UB <Umax. The Fast Step down function can be set active forautomatic control or automatic as well as manual controland it is blocked when the lowest voltage tap position isreached. The time delay for the fast step down function isseparately set. The output UHIGH will be activated as longas the voltage is above Umax.

UVPartBk(automaticallyreset)

AlarmAuto&Man Block

If the busbar voltage UB (not the calculated load pointvoltage UL) is between Ublock and Umin (see figure 135),further ULOWER commands will be blocked independentlyof the control mode when the value Auto&Man Block isselected. The output ULOW will be set.

UVBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

If the busbar voltage UB falls below Ublock this blockingcondition is active. It is recommended to block automaticcontrol in this situation and allow manual control. This isbecause the situation normally would correspond to adisconnected transformer and then it should be allowed tooperate the tap changer before reconnecting thetransformer. The outputs UBLK and TOTBLK or AUTOBLKwill be activated depending on the actual parameter setting.

Table continues on next page

Section 12 1MRK 504 134-UEN AControl

280Application manual

Page 287: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Setting Values (Range) DescriptionCmdErrBk(manually reset)

AlarmAuto BlockAuto&Man Block

Typical operating time for a tap changer mechanism isaround 3-8 seconds. Therefore, the function should wait fora position change before a new command is issued. Thecommand error signal, CMDERRAL on the TCMYLTCfunction block, will be set if the tap changer position doesnot change one step in the correct direction within the timegiven by the setting tTCTimeout in TCMYLTC functionblock. The tap changer module TCMYLTC will then indicatethe error until a successful command has been carried outor it has been reset by changing control mode of TR8ATCCfunction to Manual and then back to Automatic. The outputsCMDERRAL on TCMYLTC and TOTBLK or AUTOBLK onTR8ATCC will be activated depending on the actualparameter setting.This error condition can be reset by the input RESETERRon TCMYLTC function block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

TapChgBk(manually reset

AlarmAuto BlockAuto&Man Block

If the input TCINPROG of TCMYLTC function block isconnected to the tap changer mechanism, then thisblocking condition will be active if the TCINPROG input hasnot reset when the tTCTimeout timer has timed out. Theoutput TCERRAL will be activated depending on the actualparameter setting. In correct operation the TCINPROGshall appear during the URAISE/ULOWER output pulseand disappear before the tTCTimeout time has elapsed.This error condition can be reset by the input RESETERRon TCMYLTC function block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

Table continues on next page

1MRK 504 134-UEN A Section 12Control

281Application manual

Page 288: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Setting Values (Range) DescriptionTapPosBk(automaticallyreset/manuallyreset)

AlarmAuto BlockAuto&Man Block

This blocking/alarm is activated by either:

1. The tap changer reaching an end position i.e. one ofthe extreme positions according to the settingparameters LowVoltTapand HighVoltTap. When thetap changer reaches one of these two positionsfurther commands in the corresponding direction willbe blocked. Effectively this will then be a partial blockif Auto Block or Auto&Man Blockis set. The outputsPOSERRAL and LOPOSAL or HIPOSAL will beactivated.

2. Tap Position Error which in turn can be caused by oneof the following conditions:

• Tap position is out of range that is, the indicatedposition is above or below the end positions.

• The tap changer indicates that it has changed morethan one position on a single raise or lower command.

• The tap position reading shows a BCD code error(unaccepted combination) or a parity fault.

• Indication of hardware fault on BIO or AIM module.Supervision of the input hardware module is providedby connecting the corresponding error signal to theINERR input (input module error) or BIERR onTCMYLTC function block.

• Interruption of communication with the tap changer.

The outputs POSERRAL and AUTOBLK or TOTBLK will beset.This error condition can be reset by the input RESETERRon TCMYLTCfunction block, or alternatively by changingcontrol mode of TR8ATCC function to Manual and thenback to Automatic.

CircCurrBk(automaticallyreset)

AlarmAuto BlockAuto&Man Block

When the magnitude of the circulating current exceeds thepreset value (setting parameter CircCurrLimit) for longertime than the set time delay (setting parameter tCircCurr) itwill cause this blocking condition to be fulfilled provided thatthe setting parameter OperCCBlock is On. The signalresets automatically when the circulating current decreasesbelow the preset value. Usually this can be achieved bymanual control of the tap changers. TR8ATCC outputsICIRC and TOTBLK or AUTOBLK will be activateddepending on the actual parameter setting.

MFPosDiffBk(manually reset)

AlarmAuto Block

In the master-follower mode, if the tap difference between afollower and the master is greater than the set value (settingparameter MFPosDiffLim) then this blocking condition isfulfilled and the outputs OUTOFPOS and AUTOBLK(alternatively an alarm) will be set.

Setting parameters for blocking that can be set in TR8ATCC under setting group Nxin local HMI are listed in table 26.

Section 12 1MRK 504 134-UEN AControl

282Application manual

Page 289: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 26: Blocking settings

Setting Value (Range) DescriptionTotalBlock (manually reset) On/Off TR8ATCC function can be totally

blocked via the setting parameterTotalBlock, which can be setOn/Off from the local HMI . Theoutput TOTBLK will be activated.

AutoBlock (manually reset) On/Off TR8ATCC function can beblocked for automatic control viathe setting parameter AutoBlock,which can be set On/Off from thelocal HMI . The output AUTOBLKwill be set.

TR8ATCC blockings that can be made via input signals in the function block are listedin table 27.

Table 27: Blocking via binary inputs

Input name Activation DescriptionBLOCK (manually reset) On/Off(via binary input) The voltage control function can

be totally blocked via the binaryinput BLOCK on TR8ATCCfunction block. The outputTOTBLK will be activated.

EAUTOBLK (manually reset) On/Off(via binary input) The voltage control function canbe blocked for automatic controlvia the binary input EAUTOBLKon TR8ATCC function block. Theoutput AUTOBLK will beactivated. Deblocking is made viathe input DEBLKAUT.

Blockings activated by the operating conditions and there are no setting or separateexternal activation possibilities are listed in table 28.

1MRK 504 134-UEN A Section 12Control

283Application manual

Page 290: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 28: Blockings without setting possibilities

Activation Type of blocking DescriptionDisconnectedtransformer(automatically reset)

Auto Block Automatic control is blocked for a transformer whenparallel control with the circulating current method isused, and that transformer is disconnected from theLV-busbar. . The binary input signal DISC in TR8ATCCfunction shall be used to supervise if the transformerLV circuit breaker is closed or not. The outputsTRFDISC and AUTOBLK will be activated . Blockingwill be removed when the transformer is reconnected(input signal DISC set back to zero).

No Master/More than oneMaster (automaticallyreset)

Auto Block Automatic control is blocked when parallel control withthe master-follower method is used, and the master isdisconnected from the LV-busbar. Also if there forsome reason should be a situation with more than onemaster in the system, the same blocking will occur. Thebinary input signal DISC in TR8ATCC function shall beused to supervise if the transformer LV circuit breakeris closed or not. The outputs TRFDISC, MFERR andAUTOBLK will be activated. The followers will also beblocked by mutual blocking in this situation. Blockingwill be removed when the transformer is reconnected(input signal DISC set back to zero).

One transformer in aparallel group switched tomanual control(automatically reset)

Auto Block When the setting OperationAdapt is “Off”, automaticcontrol will be blocked when parallel control with themaster-follower or the circulating current method isused, and one of the transformers in the group isswitched from auto to manual. The output AUTOBLKwill be activated.

Communication error(COMMERR) (automaticdeblocking)

Auto block If the horizontal communication (GOOSE) for any oneof TR8ATCCs in the group fails it will cause blocking ofautomatic control in all TR8ATCC functions, whichbelong to that parallel group. This error condition will bereset automatically when the communication is re-established. The outputs COMMERR and AUTOBLKwill be set.

Circulating current method

Mutual blockingWhen one parallel instance of voltage control TR8ATCC blocks its operation, allother TR8ATCCs working in parallel with that module, shall block their operation aswell. To achieve this, the affected TR8ATCC function broadcasts a mutual block tothe other group members. When mutual block is received from any of the groupmembers, automatic operation is blocked in the receiving TR8ATCCs that is, all unitsof the parallel group.

The following conditions in any one of TR8ATCCs in the group will cause mutualblocking when the circulating current method is used:

• Over-Current• Total block via settings• Total block via configuration• Analog input error• Automatic block via settings• Automatic block via configuration

Section 12 1MRK 504 134-UEN AControl

284Application manual

Page 291: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Under-Voltage• Command error• Position indication error• Tap changer error• Circulating current• Communication error

Master-follower methodWhen the master is blocked, the followers will not tap by themselves and there isconsequently no need for further mutual blocking. On the other hand, when a followeris blocked there is a need to send a mutual blocking signal to the master. This willprevent a situation where the rest of the group otherwise would be able to tap awayfrom the blocked individual, and that way cause high circulating currents.

Thus, when a follower is blocked, it broadcasts a mutual block on the horizontalcommunication. The master picks up this message, and blocks its automatic operationas well.

Besides the conditions listed above for mutual blocking with the circulating currentmethod, the following blocking conditions in any of the followers will also causemutual blocking:

• Master-follower out of position• Master-follower error (No master/More than one master)

GeneralIt should be noted that partial blocking will not cause mutual blocking.

TR8ATCC, which is the “source” of the mutual blocking will set its AUTOBLKoutput as well as the output which corresponds to the actual blocking condition forexample, IBLK for over-current blocking. The other TR8ATCCs that receive amutual block signal will only set its AUTOBLK output.

The mutual blocking remains until TR8ATCC that dispatched the mutual block signalis de-blocked. Another way to release the mutual blocking is to force TR8ATCC,which caused mutual blocking to Single mode operation. This is done by activatingthe binary input SNGLMODE on TR8ATCC function block or by setting theparameter OperationPAR to Off from the built-in local HMI .

TR8ATCC function can be forced to single mode at any time. It will then behaveexactly the same way as described in section "Automatic voltage control for a singletransformer", except that horizontal communication messages are still sent andreceived, but the received messages are ignored. TR8ATCC is at the same time alsoautomatically excluded from the parallel group.

Disabling of blockings in special situationsWhen the Automatic voltage control for tap changer TR8ATCC for parallel control,function block is connected to read back information (tap position value and tap

1MRK 504 134-UEN A Section 12Control

285Application manual

Page 292: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

changer in progress signal) it may sometimes be difficult to find timing data to be setin TR8ATCC for proper operation. Especially at commissioning of for example, oldertransformers the sensors can be worn and the contacts maybe bouncing etc. Before theright timing data is set it may then happen that TR8ATCC becomes totally blocked orblocked in auto mode because of incorrect settings. In this situation, it isrecommended to temporarily set these types of blockings to alarm instead until thecommissioning of all main items are working as expected.

Hunting detectionHunting detection is provided in order to generate an alarm when the voltage controlgives an abnormal number of commands or abnormal sequence of commands withina pre-defined period of time.

There are three hunting functions:

1. The Automatic voltage control for tap changer function, TR8ATCC for parallelcontrol will activate the output signal DAYHUNT when the number of tapchanger operations exceed the number given by the setting DayHuntDetectduring the last 24 hours (sliding window). Active as well in manual as inautomatic mode.

2. TR8ATCC function will activate the output signal HOURHUNT when thenumber of tap changer operations exceed the number given by the settingHourHuntDetect during the last hour (sliding window). Active as well in manualas in automatic mode.

3. TR8ATCC function will activate the output signal HUNTING when the totalnumber of contradictory tap changer operations (RAISE, LOWER, RAISE,LOWER, and so on) exceeds the pre-set value given by the setting NoOpWindowwithin the time sliding window specified via the setting parametertWindowHunt. Only active in automatic mode.

Hunting can be the result of a narrow deadband setting or some other abnormalities inthe control system.

Wearing of the tap changer contactsTwo counters, ContactLife and NoOfOperations are available within the Tap changercontrol and supervision function, 6 binary inputs TCMYLTC. They can be used as aguide for maintenance of the tap changer mechanism. The ContactLife counterrepresents the remaining number of operations (decremental counter) at rated load.

ContactLife ContactLifen+1 n Irated

Iloada

æ ö= - ç ÷ç ÷

è øEQUATION1873 V2 EN (Equation 122)

where n is the number of operations and α is an adjustable setting parameter,CLFactor, with default value is set to 2. With this default setting an operation at ratedload (current measured on HV-side) decrements the ContactLife counter with 1.

Section 12 1MRK 504 134-UEN AControl

286Application manual

Page 293: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The NoOfOperations counter simply counts the total number of operations(incremental counter).

Both counters are stored in a non-volatile memory as well as, the times and dates oftheir last reset. These dates are stored automatically when the command to reset thecounter is issued. It is therefore necessary to check that the IED internal time is correctbefore these counters are reset. The counter value can be reset on the local HMI underMain menu/Clear/Clear counters/TCMLYTC (84)/n:TCMYLTC/ContLifeCounter

Both counters and their last reset dates are shown on the local HMI as service valuesCLCNT_VAL and CNT_VAL under Main menu/Tests/Function status/Control/TCMYLTC (84)/n:TCMYLTC/Outputs/CLCNT_VAL and Main menu/Tests/Function status/Control/TCMYLTC (84)/n:TCMYLTC/Outputs/CNT_VAL

12.3.3 Setting guidelines

12.3.3.1 TR8ATCC general settings

Base IED values for primary current (setting IBase), primary voltage (setting UBase)and primary power (setting SBase) for a particular winding are set in a Global basevalues for settings function GBASVAL. Settings GlobalBaseSel1 andGlobalBaseSel2 are used to select the corresponding GBASVAL function forreference of base values.

TrfId: The transformer identity is used to identify transformer individuals in a parallelgroup. Thus, transformers that can be part of the same parallel group must have uniqueidentities. Moreover, all transformers that communicate over the same horizontalcommunication (GOOSE) must have unique identities.

Xr2: The reactance of the transformer in primary ohms referred to the LV side.

tAutoMSF: Time delay set in a follower for execution of a raise or lower commandgiven from a master. This feature can be used when a parallel group is controlled in themaster-follower mode, follow tap, and it is individually set for each follower, whichmeans that different time delays can be used in the different followers in order to avoidsimultaneous tapping if this is wanted. It shall be observed that it is not applicable inthe follow command mode.

OperationAdapt: This setting enables or disables adapt mode for parallel control withthe circulating current method or the master-follower method.

MFMode: Selection of Follow Command or Follow Tap in the master-follower mode.

CircCurrBk: Selection of action to be taken in case the circulating current exceedsCircCurrLimit.

CmdErrBk: Selection of action to be taken in case the feedback from the tap changerhas resulted in command error.

1MRK 504 134-UEN A Section 12Control

287Application manual

Page 294: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

OCBk: Selection of action to be taken in case any of the three phase currents on theHV-side has exceeded Iblock.

MFPosDiffBk: Selection of action to be taken in case the tap difference between afollower and the master is greater than MFPosDiffLim.

OVPartBk: Selection of action to be taken in case the busbar voltage UB exceedsUmax.

TapChgBk: Selection of action to be taken in case a Tap Changer Error has beenidentified.

TapPosBk: Selection of action to be taken in case of Tap Position Error, or if the tapchanger has reached an end position.

UVBk: Selection of action to be taken in case the busbar voltage UB falls belowUblock.

UVPartBk: Selection of action to be taken in case the busbar voltage UB is betweenUblock and Umin.

12.3.3.2 TR8ATCC Setting group

GeneralOperation: Switching automatic voltage control for tap changer, TR8ATCC functionOn/Off.

MeasMode: Selection of single phase, or phase-phase, or positive sequence quantityto be used for voltage and current measurement on the LV-side. The involved phasesare also selected. Thus, single phase as well as phase-phase or three-phase feeding onthe LV-side is possible but it is commonly selected for current and voltage.

TotalBlock: When this setting is On, TR8ATCC function that is, the voltage control istotally blocked for manual as well as automatic control.

AutoBlock: When this setting is On, TR8ATCC function that is, the voltage control isblocked for automatic control.

OperationFSDMode: This setting enables/disables the fast step down function. Enabling can befor automatic and manual control, or for only automatic control alternatively.

tFSD: Time delay to be used for the fast step down tapping.

VoltageUSet: Setting value for the target voltage, to be set in per cent of UBase.

UDeadband: Setting value for one half of the outer deadband, to be set in per cent ofUBase. The deadband is symmetrical around USet, see section "Automatic voltage

Section 12 1MRK 504 134-UEN AControl

288Application manual

Page 295: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

control for a single transformer", figure 135. In that figure UDeadband is equal to DU.The setting is normally selected to a value near the power transformer’s tap changervoltage step (typically 75 - 125% of the tap changer step).

UDeadbandInner: Setting value for one half of the inner deadband, to be set in per centof UBase. The inner deadband is symmetrical around USet, see section "Automaticvoltage control for a single transformer",figure 135. In that figure UDeadbandInner isequal to DUin. The setting shall be smaller than UDeadband. Typically the innerdeadband can be set to 25-70% of the UDeadband value.

Umax: This setting gives the upper limit of permitted busbar voltage (see section"Automatic voltage control for a single transformer", figure 135). It is set in per cent ofUBase. If OVPartBk is set to Auto&ManBlock, then busbar voltages above Umax willresult in a partial blocking such that only lower commands are permitted.

Umin This setting gives the lower limit of permitted busbar voltage (see section"Automatic voltage control for a single transformer", figure 135). It is set in per cent ofUBase. If UVPartBk is set to Auto&ManBlock, then busbar voltages below Umin willresult in a partial blocking such that only raise commands are permitted.

Ublock: Voltages below Ublock normally correspond to a disconnected transformerand therefore it is recommended to block automatic control for this condition (settingUVBk). Ublock is set in per cent of UBase.

Timet1Use: Selection of time characteristic (definite or inverse) for t1.

t1: Time delay for the initial (first) raise/lower command.

t2Use: Selection of time characteristic (definite or inverse) for t2.

t2: Time delay for consecutive raise/lower commands. In the circulating currentmethod, the second, third, etc. commands are all executed with time delay t2independently of which transformer in the parallel group that is tapping. In the master-follower method with the follow tap option, the master is executing the second, third,etc. commands with time delay t2. The followers on the other hand read the master’stap position, and adapt to that with the additional time delay given by the settingtAutoMSF and set individually for each follower.

tMin: The minimum operate time when inverse time characteristic is used (see section"Time characteristic", figure 136).

Line voltage drop compensation (LDC)OpertionLDC: Sets the line voltage drop compensation function On/Off.

OperCapaLDC: This setting, if set On, will permit the load point voltage to be greaterthan the busbar voltage when line voltage drop compensation is used. That situationcan be caused by a capacitive load. When the line voltage drop compensation functionis used for parallel control with the reverse reactance method, then OperCapaLDCmust always be set On.

1MRK 504 134-UEN A Section 12Control

289Application manual

Page 296: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Rline and Xline: For line voltage drop compensation, these settings give the lineresistance and reactance from the station busbar to the load point. The settings forRline and Xline are given in primary system ohms. If more than one line is connectedto the LV busbar, equivalent Rline and Xline values should be calculated and given assettings.

When the line voltage drop compensation function is used for parallel control with thereverse reactance method, then the compensated voltage which is designated “loadpoint voltage” UL is effectively an increase in voltage up into the transformer. Toachieve this voltage increase, Xline must be negative. The sensitivity of the parallelvoltage regulation is given by the magnitude of Rline and Xline settings, with Rlinebeing important in order to get a correct control of the busbar voltage. This can berealized in the following way. Figure 137 shows the vector diagram for a transformercontrolled in a parallel group with the reverse reactance method and with nocirculation (for example, assume two equal transformers on the same tap position).The load current lags the busbar voltage UB with the power factor j and the argumentof the impedance Rline and Xline is designated j1.

Load voltage adjustment (LVA)LVAConst1: Setting of the first load voltage adjustment value. This adjustment of thetarget value USet is given in percent of UBase.

LVAConst2: Setting of the second load voltage adjustment value. This adjustment ofthe target value USet is given in percent ofUBase.

LVAConst3: Setting of the third load voltage adjustment value. This adjustment of thetarget value USet is given in percent of UBase.

LVAConst4: Setting of the fourth load voltage adjustment value. This adjustment ofthe target value USet is given in percent of UBase.

VRAuto: Setting of the automatic load voltage adjustment. This adjustment of thetarget valueUSet is given in percent of UBase, and it is proportional to the load currentwith the set value reached at the nominal current IBase (for winding 2 which is definedin a global base function, selected with setting GlobalBaseSel2 forTR8ATCC).

Tap changer control (TCCtrl)Iblock: Current setting of the over current blocking function. In case, the transformeris carrying a current exceeding the rated current of the tap changer for example,because of an external fault. The tap changer operations shall be temporarily blocked.This function typically monitors the three phase currents on the HV side of thetransformer.

DayHuntDetect: Setting of the number of tap changer operations required during thelast 24 hours (sliding window) to activate the signal DAYHUNT

HourHuntDetect: Setting of the number of tap changer operations required during thelast hour (sliding window) to activate the signal HOURHUNT

Section 12 1MRK 504 134-UEN AControl

290Application manual

Page 297: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

tWindowHunt: Setting of the time window for the window hunting function. Thisfunction is activated when the number of contradictory commands to the tap changerexceeds the specified number given by NoOpWindow within the time tWindowHunt.

NoOpWindow: Setting of the number of contradictory tap changer operations(RAISE, LOWER, RAISE, LOWER etc.) required during the time windowtWindowHunt to activate the signal HUNTING.

PowerP>: When the active power exceeds the value given by this setting, the outputPGTFWD will be activated after the time delay tPower. It shall be noticed that thesetting is given with sign, which effectively means that a negative value of P> meansan active power greater than a value in the reverse direction. This is shown in figure144 where a negative value of P> means pickup for all values to the right of the setting.Reference is made to figure 142 for definition of forward and reverse direction ofpower through the transformer.

en06000634_2_en.vsd

PP>

IEC06000634 V2 EN

Figure 144: Setting of a negative value for P>

P<: When the active power falls below the value given by this setting, the outputPLTREV will be activated after the time delay tPower. It shall be noticed that thesetting is given with sign, which effectively means that, for example a positive valueof P< means an active power less than a value in the forward direction. This is shownin figure 145 where a positive value of P< means pickup for all values to the left of thesetting. Reference is made to figure 142 for definition of forward and reverse directionof power through the transformer.

en06000635_2_en.vsd

PP<

IEC06000635 V2 EN

Figure 145: Setting of a positive value for P<

Q>: When the reactive power exceeds the value given by this setting, the outputQGTFWD will be activated after the time delay tPower. It shall be noticed that the

1MRK 504 134-UEN A Section 12Control

291Application manual

Page 298: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

setting is given with sign, which effectively means that the function picks up for allvalues of reactive power greater than the set value, similar to the functionality for P>.

Q<: When the reactive power in reverse direction falls below the value given by thissetting, the output QLTREV will be activated after the time delay tPower. It shall benoticed that the setting is given with sign, which effectively means that the functionpicks up for all values of reactive power less than the set value, similar to thefunctionality for P<.

tPower: Time delay for activation of the power monitoring output signals (PGTFWD,PLTREV, QGTFWD and QLTREV).

Parallel control (ParCtrl)OperationPAR: Setting of the method for parallel operation.

OperCCBlock: This setting enables/disables blocking if the circulating currentexceeds CircCurrLimit.

CircCurrLimit: Pick up value for the circulating current blocking function. Thesetting is made in percent of IBase (for winding 2 which is defined in a global basefunction, selected with setting GlobalBaseSel2 for TR8ATCC).

tCircCurr: Time delay for the circulating current blocking function.

Comp: When parallel operation with the circulating current method is used, thissetting increases or decreases the influence of the circulating current on the regulation.

If the transformers are connected to the same bus on the HV- as well as the LV-side,Comp can be calculated with the following formula which is valid for any number oftwo-winding transformers in parallel, irrespective if the transformers are of differentsize and short circuit impedance.

2 UComp a 100%n p´D

= ´ ´´

EQUATION1941 V1 EN (Equation 123)

where:

• DU is the deadband setting in percent.

• n denotes the desired number of difference in tap position between thetransformers, that shall give a voltage deviation Udi which corresponds to thedead-band setting.

• p is the tap step (in % of transformer nominal voltage).

• a is a safety margin that shall cover component tolerances and other non-linearmeasurements at different tap positions (for example, transformer reactances

Section 12 1MRK 504 134-UEN AControl

292Application manual

Page 299: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

changes from rated value at the ends of the regulation range). In most cases avalue of a = 1.25 serves well.

This calculation gives a setting of Comp that will always initiate an action (start timer)when the transformers have n tap positions difference.

OperSimTap: Enabling/disabling the functionality to allow only one transformer at atime to execute a Lower/Raise command. This setting is applicable only to thecirculating current method, and when enabled, consecutive tap changes of the nexttransformer (if required) will be separated with the time delay t2.

OperUsetPar: Enables/disables the use of a common setting for the target voltageUSet. This setting is applicable only to the circulating current method, and whenenabled, a mean value of the USet values for the transformers in the same parallelgroup will be calculated and used.

VTmismatch: Setting of the level for activation of the output VTALARM in case thevoltage measurement in one transformer bay deviates to the mean value of all voltagemeasurements in the parallel group.

tVTmismatch: Time delay for activation of the output VTALARM.

T1RXOP.......T4RXOP: This setting is set On for every transformer that canparticipate in a parallel group with the transformer in case. For this transformer (owntransformer), the setting must always be Off.

TapPosOffs: This setting gives the tap position offset in relation to the master so thatthe follower can follow the master’s tap position including this offset. Applicablewhen regulating in the follow tap command mode.

MFPosDiffLim: When the difference (including a possible offset according toTapPosOffs) between a follower and the master reaches the value in this setting, thenthe output OUTOFPOS in the Automatic voltage control for tap changer, parallelcontrol TR8ATCC function block of the follower will be activated after the time delaytMFPosDiff.

tMFPosDiff: Time delay for activation of the output OUTOFPOS.

Transformer nameINSTNAME: This setting can be used for indicating in tools and the local HMI towhich transformer a certain instance of the function belongs.

12.3.3.3 TCMYLTC general settings

Base IED values for primary current (setting IBase), primary voltage (setting UBase)and primary power (setting SBase) for a particular winding are set in a Global basevalues for settings function GBASVAL. Settings GlobalBaseSel1 andGlobalBaseSel2 are used to select the corresponding GBASVAL function forreference of base values.

1MRK 504 134-UEN A Section 12Control

293Application manual

Page 300: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

LowVoltTap: This gives the tap position for the lowest LV-voltage.

HighVoltTap: This gives the tap position for the highest LV-voltage.

CodeType: This setting gives the method of tap position reading.

UseParity: Sets the parity check On/Off for tap position reading when this is made byBinary, BCD, or Gray code.

tStable: This is the time that needs to elapse after a new tap position has been reportedto TCMYLTC until it is accepted.

CLFactor: This is the factor designated “a” in equation 123. When a tap changeroperates at nominal load current(current measured on the HV-side), the ContactLifecounter decrements with 1, irrespective of the setting of CLFactor. The setting of thisfactor gives the weighting of the deviation with respect to the load current.

InitCLCounter: The ContactLife counter monitors the remaining number ofoperations (decremental counter). The setting InitCLCounter then gives the startvalue for the counter that is, the total number of operations at rated load that the tapchanger is designed for.

EnabTapCmd: This setting enables/disables the lower and raise commands to the tapchanger. It shall be On for voltage control, and Off for tap position feedback to thetransformer differential protection T2WPDIF or T3WPDIF.

TCMYLTC Setting group

GeneralOperation: Switching the TCMYLTC function On/Off.

tTCTimeout: This setting gives the maximum time interval for a raise or lowercommand to be completed.

tPulseDur: Length of the command pulse (URAISE/ULOWER) to the tap changer. Itshall be noticed that this pulse has a fixed extension of 4 seconds that adds to thesetting value of tPulseDur.

12.4 Logic rotating switch for function selection and LHMIpresentation SLGGIO

12.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Logic rotating switch for functionselection and LHMI presentation

SLGGIO - -

Section 12 1MRK 504 134-UEN AControl

294Application manual

Page 301: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.4.2 Application

The logic rotating switch for function selection and LHMI presentation function(SLGGIO) (or the selector switch function block, as it is also known) is used to get aselector switch functionality similar with the one provided by a hardware multi-position selector switch. Hardware selector switches are used extensively by utilities,in order to have different functions operating on pre-set values. Hardware switches arehowever sources for maintenance issues, lower system reliability and extendedpurchase portfolio. The virtual selector switches eliminate all these problems.

SLGGIO function block has two operating inputs (UP and DOWN), one blockinginput (BLOCK) and one operator position input (PSTO).

SLGGIO can be activated both from the local HMI and from external sources(switches), via the IED binary inputs. It also allows the operation from remote (like thestation computer). SWPOSN is an integer value output, giving the actual outputnumber. Since the number of positions of the switch can be established by settings (seebelow), one must be careful in coordinating the settings with the configuration (if onesets the number of positions to x in settings – for example, there will be only the firstx outputs available from the block in the configuration). Also the frequency of the (UPor DOWN) pulses should be lower than the setting tPulse.

The operation from local HMI is from select or indication buttons (32 positions).Typical applications are: Select operating modes for e.g. Auto reclose, Energizingcheck, Earth-fault protection (IN,UN). The output integer can be connected to anInteger to Binary function block to give the position as a boolean for use in theconfiguration.

12.4.3 Setting guidelines

The following settings are available for the Logic rotating switch for functionselection and LHMI presentation (SLGGIO) function:

Operation: Sets the operation of the function On or Off.

NrPos: Sets the number of positions in the switch (max. 32). This setting influence thebehavior of the switch when changes from the last to the first position.

OutType: Steady or Pulsed.

tPulse: In case of a pulsed output, it gives the length of the pulse (in seconds).

tDelay: The delay between the UP or DOWN activation signal positive front and theoutput activation.

StopAtExtremes: Sets the behavior of the switch at the end positions – if set toDisabled, when pressing UP while on first position, the switch will jump to the lastposition; when pressing DOWN at the last position, the switch will jump to the firstposition; when set to Enabled, no jump will be allowed.

1MRK 504 134-UEN A Section 12Control

295Application manual

Page 302: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.5 Selector mini switch VSGGIO

12.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Selector mini switch VSGGIO - -

12.5.2 Application

Selector mini switch (VSGGIO) function is a multipurpose function used in theconfiguration tool in PCM600 for a variety of applications, as a general purposeswitch. VSGGIO can be used for both acquiring an external switch position (throughthe IPOS1 and the IPOS2 inputs) and represent it through the single line diagramsymbols (or use it in the configuration through the outputs POS1 and POS2) as wellas, a command function (controlled by the PSTO input), giving switching commandsthrough the CMDPOS12 and CMDPOS21 outputs.

The output POSITION is an integer output, showing the actual position as an integernumber 0 – 3.

An example where VSGGIO is configured to switch Autorecloser on–off from abutton symbol on the local HMI is shown in figure 146. The I and O buttons on thelocal HMI are normally used for on–off operations of the circuit breaker.

IEC07000112-2-en.vsd

PSTO

CMDPOS12

IPOS1

NAM_POS1NAM_POS2

IPOS2

CMDPOS21OFFON

VSGGIO

SMBRRECONOFF

SETON

INTONE

INVERTERINPUT OUT

IEC07000112 V2 EN

Figure 146: Control of Autorecloser from local HMI through Selector mini switch

12.5.3 Setting guidelines

Selector mini switch (VSGGIO) function can generate pulsed or steady commands(by setting the Mode parameter). When pulsed commands are generated, the length ofthe pulse can be set using the tPulse parameter. Also, being accessible on the single

Section 12 1MRK 504 134-UEN AControl

296Application manual

Page 303: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

line diagram (SLD), this function block has two control modes (settable throughCtlModel): Dir Norm and SBO Enh.

12.6 IEC61850 generic communication I/O functionsDPGGIO

12.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions

DPGGIO - -

12.6.2 Application

The IEC61850 generic communication I/O functions (DPGGIO) function block isused to send three logical outputs to other systems or equipment in the substation. Thethree inputs are named OPEN, CLOSE and VALID, since this function block isintended to be used as a position indicator block in interlocking and reservationstation-wide logics.

12.6.3 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

12.7 Single point generic control 8 signals SPC8GGIO

12.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Single point generic control 8 signals SPC8GGIO - -

12.7.2 Application

The Single point generic control 8 signals (SPC8GGIO) function block is a collectionof 8 single point commands, designed to bring in commands from REMOTE(SCADA) to those parts of the logic configuration that do not need complicatedfunction blocks that have the capability to receive commands (for example SCSWI).In this way, simple commands can be sent directly to the IED outputs, withoutconfirmation. Confirmation (status) of the result of the commands is supposed to beachieved by other means, such as binary inputs and SPGGIO function blocks.

1MRK 504 134-UEN A Section 12Control

297Application manual

Page 304: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

PSTO is the universal operator place selector for all control functions.Even if PSTO can be configured to allow LOCAL or ALL operatorpositions, the only functional position usable with the SPC8GGIOfunction block is REMOTE.

12.7.3 Setting guidelines

The parameters for the single point generic control 8 signals (SPC8GGIO) functionare set via the local HMI or PCM600.

Operation: turning the function operation On/Off.

There are two settings for every command output (totally 8):

Latchedx: decides if the command signal for output x is Latched (steady) or Pulsed.

tPulsex: if Latchedx is set to Pulsed, then tPulsex will set the length of the pulse (inseconds).

12.8 Automation bits AUTOBITS

12.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

AutomationBits, command function forDNP3 AUTOBITS - -

12.8.2 Application

The AUTOBITS function block (or the automation bits function block) is used withinPCM600 in order to get into the configuration the commands coming through theDNP3 protocol.AUTOBITS function block have 32 individual outputs which eachcan be mapped as a Binary Output point in DNP3. The output is operated by a "Object12" in DNP3. This object contains parameters for control-code, count, on-time andoff-time. To operate an AUTOBITS output point, send a control-code of latch-On,latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining parameters are regardedas appropriate. For example, pulse-On, on-time=100, off-time=300, count=5 wouldgive 5 positive 100 ms pulses, 300 ms apart.

See the communication protocol manual for a detailed description of the DNP3protocol

Section 12 1MRK 504 134-UEN AControl

298Application manual

Page 305: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

12.8.3 Setting guidelines

AUTOBITS function block has one setting, (Operation: On/Off) enabling or disablingthe function. These names will be seen in the DNP communication configuration toolin PCM600.

1MRK 504 134-UEN A Section 12Control

299Application manual

Page 306: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

300

Page 307: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 13 Logic

13.1 Tripping logic common 3-phase output SMPPTRC

13.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Tripping logic common 3-phase output SMPPTRC

I->O

SYMBOL-K V1 EN

94

13.1.2 Application

All trip signals from the different protection functions shall be routed through the triplogic. In its simplest alternative the logic will only link the internal TRIP signals to abinary output and make sure that the pulse length is long enough.

The tripping logic common 3-phase output (SMPPTRC) offers only three-phasetripping. A three-phase trip for all faults offers a simple solution and is often sufficientin well meshed transmission systems and in High Voltage (HV) systems.

One SMPPTRC function block should be used for each breaker, if the object isconnected to the system via more than one breaker.

To prevent closing of a circuit breaker after a trip the function can block the closingof the circuit breaker (trip lock-out).

13.1.2.1 Three-phase tripping

A simple application with three-phase tripping from the tripping logic common 3-phase output SMPPTRC utilizes part of the function block. Connect the inputs fromthe protection function blocks to the input TRIN. If necessary (normally the case) usethe trip matrix logic TMAGGIO to combine the different function outputs to thisinput. Connect the output TRIP to the required binary outputs.

A typical connection is shown below in figure 147.

1MRK 504 134-UEN A Section 13Logic

301Application manual

Page 308: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC11000054-1-en.vsd

IEC11000054 V1 EN

Figure 147: Tripping logic common 3-phase output SMPPTRC is used for asimple three-phase tripping application

13.1.2.2 Lock-out

This function block is provided with possibilities to initiate lock-out. The lock-out canbe set to only activate the block closing output CLLKOUT or initiate the block closingoutput and also maintain the trip signal (latched trip).

The lock-out can then be manually reset after checking the primary fault by activatingthe input reset Lock-Out RSTLKOUT or via the HMI.

If external conditions are required to initiate Lock-out but not initiate trip this can beachieved by activating input SETLKOUT. The setting AutoLock = Off means that theinternal trip will not activate lock-out so only initiation of the input SETLKOUT willresult in lock-out. This is normally the case for overhead line protection where mostfaults are transient. Unsuccessful autoreclose and back-up zone tripping can in suchcases be connected to initiate Lock-out by activating the input SETLKOUT.

13.1.2.3 Blocking of the function block

Blocking can be initiated internally by logic, or by the operator using acommunication channel. Total blockage of Tripping logic (SMPPTRC) function isdone by activating the input BLOCK and can be used to block the output ofSMPPTRC in the event of internal failures.

13.1.3 Setting guidelines

The parameters for Tripping logic common 3-phase output SMPPTRC are set via thelocal HMI or through the Protection and Control Manager (PCM600).

The following trip parameters can be set to regulate tripping.

Section 13 1MRK 504 134-UEN ALogic

302Application manual

Page 309: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Operation: Sets the mode of operation. Off switches the function off. The normalselection is On.

TripLockout: Sets the scheme for lock-out. Off only activates the lock-out output. Onactivates the lock-out output and latches the output TRIP. The normal selection isOff.

AutoLock: Sets the scheme for lock-out. Off only activates lock-out through the inputSETLKOUT. On additonally allows activation through the trip function itself. Thenormal selection is Off.

tTripMin: Sets the required minimum duration of the trip pulse. It should be set toensure that the breaker is tripped correctly. Normal setting is 0.150s.

13.2 Trip matrix logic TMAGGIO

13.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Trip matrix logic TMAGGIO - -

13.2.2 Application

The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to routetrip signals and other logical output signals to the tripping logics SMPPTRC andSPTPTRC or to different output contacts on the IED.

TMAGGIO 3 output signals and the physical outputs allows the user to adapt thesignals to the physical tripping outputs according to the specific application needs forsettable pulse or steady output.

13.2.3 Setting guidelines

Operation: Turns the operation of the function On/Off.

PulseTime: Defines the pulse time duration. When used for direct tripping of circuitbreaker(s) the pulse time duration shall be set to approximately 0.150 seconds in orderto obtain satisfactory minimum duration of the trip pulse to the circuit breaker tripcoils. Used only for ModeOutputx: Pulsed.

OnDelay: Used to prevent output signals to be given for spurious inputs. Normally setto 0 or a low value. Used only for ModeOutputx: Steady.

OffDelay: Defines a minimum on time for the outputs. When used for direct trippingof circuit breaker(s) the off delay time shall be set to approximately 0.150 seconds in

1MRK 504 134-UEN A Section 13Logic

303Application manual

Page 310: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

order to obtain a satisfactory minimum duration of the trip pulse to the circuit breakertrip coils. Used only for ModeOutputx: Steady.

ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed.A steady signal follows the status of the input signals, with respect to OnDelay andOffDelay. A pulsed signal will give a pulse once, when the Outputx rises from 0 to1.

13.3 Configurable logic blocks

13.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

OR Function block OR - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Inverter function block INVERTER - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

PULSETIMER function block PULSETIMER - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Controllable gate function block GATE - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Exclusive OR function block XOR - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Logic loop delay function block LOOPDELAY - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Timer function block TIMERSET - -

Section 13 1MRK 504 134-UEN ALogic

304Application manual

Page 311: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

AND function block AND - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Set-reset memory function block SRMEMORY - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Reset-set with memory function block RSMEMORY - -

13.3.2 Application

A set of standard logic blocks, like AND, OR etc, and timers are available for adaptingthe IED configuration to the specific application needs.

There are no settings for AND gates, OR gates, inverters or XOR gates.

For normal On/Off delay and pulse timers the time delays and pulse lengths are setfrom the local HMI or via the PST tool.

Both timers in the same logic block (the one delayed on pick-up and the one delayedon drop-out) always have a common setting value.

For controllable gates, settable timers and SR flip-flops with memory, the settingparameters are accessible via the local HMI or via the PST tool.

13.3.3.1 Configuration

Logic is configured using the ACT configuration tool in PCM600.

Execution of functions as defined by the configurable logic blocks runs according toa fixed sequence with different cycle times.

For each cycle time, the function block is given an serial execution number. This isshown when using the ACT configuration tool with the designation of the functionblock and the cycle time, see example below.

1MRK 504 134-UEN A Section 13Logic

305Application manual

Page 312: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC09000695_2_en.vsd

IEC09000695 V2 EN

Figure 148: Example designation, serial execution number and cycle time forlogic function

The execution of different function blocks within the same cycle is determined by theorder of their serial execution numbers. Always remember this when connecting twoor more logical function blocks in series.

Always be careful when connecting function blocks with a fast cycletime to function blocks with a slow cycle time.Remember to design the logic circuits carefully and always check theexecution sequence for different functions. In other cases, additionaltime delays must be introduced into the logic schemes to preventerrors, for example, race between functions.Default value on all four inputs of the AND gate are logical 1 whichmakes it possible for the user to just use the required number of inputsand leave the rest un-connected. The output OUT has a default value0 initially, which will suppress one cycle pulse if the function has beenput in the wrong execution order.

13.4 Fixed signals FXDSIGN

13.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Fixed signals FXDSIGN - -

13.4.2 Application

The Fixed signals function FXDSIGN generates nine pre-set (fixed) signals that canbe used in the configuration of an IED, either for forcing the unused inputs in otherfunction blocks to a certain level/value, or for creating certain logic. Boolean, integer,floating point, string types of signals are available.

Section 13 1MRK 504 134-UEN ALogic

306Application manual

Page 313: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Example for use of GRP_OFF signal in FXDSIGNThe Restricted earth fault function REFPDIF can be used both for auto-transformersand normal transformers.

When used for auto-transformers, information from both windings parts, togetherwith the neutral point current, needs to be available to the function. This means thatthree inputs are needed.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

IEC09000619_3_en.vsd

IEC09000619 V3 EN

Figure 149: REFPDIF function inputs for autotransformer application

For normal transformers only one winding and the neutral point is available. Thismeans that only two inputs are used. Since all group connections are mandatory to beconnected, the third input needs to be connected to something, which is the GRP_OFFsignal in FXDSIGN function block.

I3PW1CT1I3PW2CT1 I3P

REFPDIF

GRP_OFFFXDSIGN

IEC09000620_3_en.vsd

IEC09000620 V3 EN

Figure 150: REFPDIF function inputs for normal transformer application

13.5 Boolean 16 to integer conversion B16I

13.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean 16 to integer conversion B16I - -

1MRK 504 134-UEN A Section 13Logic

307Application manual

Page 314: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

13.5.2 Application

Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary(logical) signals into an integer. It can be used – for example, to connect logical outputsignals from a function (like distance protection) to integer inputs from anotherfunction (like line differential protection). B16I does not have a logical node mapping.

13.5.3 Setting guidelines

The function does not have any parameters available in Local HMI or Protection andControl IED Manager (PCM600).

13.6 Boolean 16 to integer conversion with logic noderepresentation B16IFCVI

13.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Boolean 16 to integer conversion withlogic node representation

B16IFCVI - -

13.6.2 Application

Boolean 16 to integer conversion with logic node representation function B16IFCVIis used to transform a set of 16 binary (logical) signals into an integer. B16IFCVI canreceive an integer from a station computer – for example, over IEC 61850–8–1. Thesefunctions are very useful when you want to generate logical commands (for selectorswitches or voltage controllers) by inputting an integer number. B16IFCVI has alogical node mapping in IEC 61850.

13.6.3 Setting guidelines

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

13.7 Integer to boolean 16 conversion IB16A

13.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion IB16A - -

Section 13 1MRK 504 134-UEN ALogic

308Application manual

Page 315: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

13.7.2 Application

Integer to boolean 16 conversion function (IB16A) is used to transform an integer intoa set of 16 binary (logical) signals. It can be used – for example, to connect integeroutput signals from one function to binary (logical) inputs to another function. IB16Afunction does not have a logical node mapping.

13.7.3 Setting guidelines

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600).

13.8 Integer to boolean 16 conversion with logic noderepresentation IB16FCVB

13.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Integer to boolean 16 conversion withlogic node representation

IB16FCVB - -

13.8.2 Application

Integer to boolean 16 conversion with logic node representation function(IB16FCVB) is used to transform an integer into a set of 16 binary (logical) signals.IB16FCVB function can receive an integer from a station computer – for example,over IEC 61850–8–1. These functions are very useful when the user wants to generatelogical commands (for selector switches or voltage controllers) by inputting an integernumber. IB16FCVB function has a logical node mapping in IEC 61850.

13.8.3 Settings

The function does not have any parameters available in the local HMI or Protectionand Control IED Manager (PCM600)

1MRK 504 134-UEN A Section 13Logic

309Application manual

Page 316: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

13.9 Elapsed time integrator with limit transgression andoverflow supervision TEIGGIO

13.9.1 IdentificationFunction Description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2 devicenumber

Elapsed time integrator TEIGGIO - -

13.9.2 Application

The function TEIGGIO is used for user defined logics and it can also be used fordifferent purposes internally in the IED . An application example is the integration ofelapsed time during the measurement of neutral point voltage or neutral current atearth fault conditions.

Settable time limits for warning and alarm are provided. The time limit for overflowindication is fixed.

13.9.3 Setting guidelines

The settings tAlarm and tWarning are user settable limits defined in seconds. Theachievable resolution of the settings depends on the level of the values defined.

A resolution of 10 ms can be achieved when the settings are defined within the range

1.00 second ≤ tAlarm ≤ 99 999.99 seconds

1.00 second ≤ tWarning ≤ 99 999.99 seconds.

If the values are above this range the resolution becomes lower

99 999.99 seconds ≤ tAlarm ≤ 999 999.9 seconds

99 999.99 seconds≤ tWarning ≤ 999 999.9 seconds

Note that tAlarm and tWarning are independent settings, that is, thereis no check if tAlarm > tWarning.

tOverflow is for overflow supervision with a default value tOverflow = 999 999.9seconds. The outputs freeze if an overflow occurs.

Section 13 1MRK 504 134-UEN ALogic

310Application manual

Page 317: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 14 Monitoring

14.1 IEC61850 generic communication I/O functionsSPGGIO

14.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions

SPGGIO - -

14.1.2 Application

IEC 61850–8–1 generic communication I/O functions (SPGGIO) function is used tosend one single logical output to other systems or equipment in the substation. It hasone visible input, that should be connected in ACT tool.

14.1.3 Setting guidelines

The function does not have any parameters available in Local HMI or Protection andControl IED Manager (PCM600).

14.2 IEC61850 generic communication I/O functions 16inputs SP16GGIO

14.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850 generic communication I/Ofunctions 16 inputs

SP16GGIO - -

14.2.2 Application

SP16GGIO function block is used to send up to 16 logical signals to other systems orequipment in the substation. Inputs should be connected in ACT tool.

1MRK 504 134-UEN A Section 14Monitoring

311Application manual

Page 318: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.2.3 Setting guidelines

The function does not have any parameters available in Local HMI or Protection andControl IED Manager (PCM600).

14.3 IEC61850 generic communication I/O functionsMVGGIO

14.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC61850 generic communication I/Ofunctions

MVGGIO - -

14.3.2 Application

IEC61850 generic communication I/O functions (MVGGIO) function is used to sendthe instantaneous value of an analog signal to other systems or equipment in thesubstation. It can also be used inside the same IED, to attach a RANGE aspect to ananalog value and to permit measurement supervision on that value.

14.3.3 Setting guidelines

The settings available for IEC61850 generic communication I/O functions(MVGGIO) function allows the user to choose a deadband and a zero deadband for themonitored signal. Values within the zero deadband are considered as zero.

The high and low limit settings provides limits for the high-high-, high, normal, lowand low-low ranges of the measured value. The actual range of the measured value isshown on the range output of MVGGIO function block. When a Measured valueexpander block (MVEXP) is connected to the range output, the logical outputs of theMVEXP are changed accordingly.

Section 14 1MRK 504 134-UEN AMonitoring

312Application manual

Page 319: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.4 Measurements

14.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measurements CVMMXN

P, Q, S, I, U, f

SYMBOL-RR V1 EN

-

Phase current measurement CMMXU

I

SYMBOL-SS V1 EN

-

Phase-phase voltage measurement VMMXU

U

SYMBOL-UU V1 EN

-

Current sequence componentmeasurement

CMSQI

I1, I2, I0

SYMBOL-VV V1 EN

-

Voltage sequence measurement VMSQI

U1, U2, U0

SYMBOL-TT V1 EN

-

Phase-neutral voltage measurement VNMMXU

U

SYMBOL-UU V1 EN

-

14.4.2 Application

Measurement functions is used for power system measurement, supervision andreporting to the local HMI, monitoring tool within PCM600 or to station level forexample, via IEC 61850. The possibility to continuously monitor measured values ofactive power, reactive power, currents, voltages, frequency, power factor etc. is vitalfor efficient production, transmission and distribution of electrical energy. It providesto the system operator fast and easy overview of the present status of the powersystem. Additionally, it can be used during testing and commissioning of protectionand control IEDs in order to verify proper operation and connection of instrumenttransformers (CTs and VTs). During normal service by periodic comparison of themeasured value from the IED with other independent meters the proper operation ofthe IED analog measurement chain can be verified. Finally, it can be used to verify

1MRK 504 134-UEN A Section 14Monitoring

313Application manual

Page 320: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

proper direction orientation for distance or directional overcurrent protectionfunction.

The available measured values of an IED are depending on the actualhardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-low limit,low limit, high limit and high-high limit. A zero clamping reduction is also supported,that is, the measured value below a settable limit is forced to zero which reduces theimpact of noise in the inputs. There are no interconnections regarding any settings orparameters, neither between functions nor between signals within each function.

Zero clampings are handled by ZeroDb for each signal separately for each of thefunctions. For example, the zero clamping of U12 is handled by ULZeroDb inVMMXU, zero clamping of I1 is handled by ILZeroDb in CMMXU.

Dead-band supervision can be used to report measured signal value to station levelwhen change in measured value is above set threshold limit or time integral of allchanges since the last time value updating exceeds the threshold limit. Measure valuecan also be based on periodic reporting.

The measurement function, CVMMXN, provides the following power systemquantities:

• P, Q and S: three phase active, reactive and apparent power• PF: power factor• U: phase-to-phase voltage amplitude• I: phase current amplitude• F: power system frequency

The output values are displayed in the local HMI under Main menu/Tests/Functionstatus/Monitoring/CVMMXN/Outputs

The measuring functions CMMXU, VNMMXU and VMMXU provide physicalquantities:

• I: phase currents (amplitude and angle) (CMMXU)• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle)

(VMMXU, VNMMXU)

It is possible to calibrate the measuring function above to get better then class 0.5presentation. This is accomplished by angle and amplitude compensation at 5, 30 and100% of rated current and at 100% of rated voltage.

The power system quantities provided, depends on the actualhardware, (TRM) and the logic configuration made in PCM600.

Section 14 1MRK 504 134-UEN AMonitoring

314Application manual

Page 321: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The measuring functions CMSQI and VMSQI provide sequence componentquantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)• U: sequence voltages (positive, zero and negative sequence, amplitude and

angle).

The CVMMXN function calculates three-phase power quantities by usingfundamental frequency phasors (DFT values) of the measured current respectivelyvoltage signals. The measured power quantities are available either, asinstantaneously calculated quantities or, averaged values over a period of time (lowpass filtered) depending on the selected settings.

14.4.3 Setting guidelines

The available setting parameters of the measurement function CVMMXN, CMMXU,VMMXU, CMSQI, VMSQI, VNMMXU are depending on the actual hardware(TRM) and the logic configuration made in PCM600.

The parameters for the Measurement functions CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU are set via the local HMI or PCM600.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On. Every function instance (CVMMXN, CMMXU, VMMXU,CMSQI, VMSQI, VNMMXU) can be taken in operation (On) or out of operation(Off).

The following general settings can be set for the Measurement function(CVMMXN).

PowAmpFact: Amplitude factor to scale power calculations.

PowAngComp: Angle compensation for phase shift between measured I & U.

Mode: Selection of measured current and voltage. There are 9 different ways ofcalculating monitored three-phase values depending on the available VT inputsconnected to the IED. See parameter group setting table.

k: Low pass filter coefficient for power measurement, U and I.

UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% ofUr, where Y is equal to 5, 30 or 100.

IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.

IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, whereY is equal to 5, 30 or 100.

1MRK 504 134-UEN A Section 14Monitoring

315Application manual

Page 322: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Parameters IBase, Ubase and SBase have been implemented as asettings instead of a parameters, which means that if the values of theparameters are changed there will be no restart of the application. Asrestart is required to activate new parameters values, the IED must berestarted in some way. Either manually or by changing some otherparameter at the same time.

The following general settings can be set for the Phase-phase current measurement(CMMXU).

IAmpCompY: Amplitude compensation to calibrate current measurements at Y% ofIr, where Y is equal to 5, 30 or 100.

IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, whereY is equal to 5, 30 or 100.

The following general settings can be set for the Phase-phase voltage measurement(VMMXU).

UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% ofUr, where Y is equal to 5, 30 or 100.

UAngCompY: Angle compensation to calibrate angle measurements at Y% of Ur,where Y is equal to 5, 30 or 100.

The following general settings can be set for all monitored quantities included in thefunctions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X insetting names below equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2, 3I0, U1,U2 or 3U0.

Xmin: Minimum value for analog signal X.

Xmax: Maximum value for analog signal X.

Xmin and Xmax values are directly set in applicable measuring unit, V,A, and so on, for all measurement functions, except CVMMXN whereXmin and Xmax values are set in % of the base quantity.

XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.

XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) orintegral deadband (Int deadband). The reporting interval is controlled by theparameter XDbRepInt.

XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and isreporting interval in seconds. Amplitude deadband is the setting value in % ofmeasuring range. Integral deadband setting is the integral area, that is, measured valuein % of measuring range multiplied by the time between two measured values.

Section 14 1MRK 504 134-UEN AMonitoring

316Application manual

Page 323: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Limits are directly set in applicable measuring unit, V, A , and so on,for all measureing functions, except CVMMXN where limits are setin % of the base quantity.

XHiHiLim: High-high limit.

XHiLim: High limit.

XLowLim: Low limit.

XLowLowLim: Low-low limit.

XLimHyst: Hysteresis value in % of range and is common for all limits.

All phase angles are presented in relation to defined reference channel. The parameterPhaseAngleRef defines the reference, see settings for analog input modules inPCM600.

Calibration curvesIt is possible to calibrate the functions (CVMMXN, CMMXU, VNMMXU andVMMXU) to get class 0.5 presentations of currents, voltages and powers. This isaccomplished by amplitude and angle compensation at 5, 30 and 100% of ratedcurrent and voltage. The compensation curve will have the characteristic foramplitude and angle compensation of currents as shown in figure 151 (example). Thefirst phase will be used as reference channel and compared with the curve forcalculation of factors. The factors will then be used for all related channels.

1MRK 504 134-UEN A Section 14Monitoring

317Application manual

Page 324: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC05000652 V2 EN

Figure 151: Calibration curves

14.4.4 Setting examples

Three setting examples, in connection to Measurement function (CVMMXN), areprovided:

• Measurement function (CVMMXN) application for a 110kV OHL• Measurement function (CVMMXN) application on the secondary side of a

transformer• Measurement function (CVMMXN) application for a generator

For each of them detail explanation and final list of selected setting parameters valueswill be provided.

The available measured values of an IED are depending on the actualhardware (TRM) and the logic configuration made in PCM600.

14.4.4.1 Measurement function application for a 110kV OHL

Single line diagram for this application is given in figure 152:

Section 14 1MRK 504 134-UEN AMonitoring

318Application manual

Page 325: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

110kV Busbar

110kV OHL

P Q

600/1 A110 0,1/

3 3kV

IEC09000039-2-en.vsd

IED

IEC09000039-1-EN V2 EN

Figure 152: Single line diagram for 110kV OHL application

In order to monitor, supervise and calibrate the active and reactive power as indicatedin figure 152 it is necessary to do the following:

1. Set correctly CT and VT data and phase angle reference channel PhaseAngleRef(see settings for analog input modules in PCM600) using PCM600 for analoginput channels

2. Connect, in PCM600, measurement function to three-phase CT and VT inputs3. Set under General settings parameters for the Measurement function:

• general settings as shown in table 29.• level supervision of active power as shown in table 30.• calibration parameters as shown in table 31.

Table 29: General settings parameters for the Measurement function

Setting Short Description Selectedvalue

Comments

Operation Operation Off/On On Function must be On

PowAmpFact Amplitude factor to scale powercalculations

1.000 It can be used duringcommissioning to achieve highermeasurement accuracy. Typicallyno scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

0.0 It can be used duringcommissioning to achieve highermeasurement accuracy. Typicallyno angle compensation isrequired. As well here requireddirection of P & Q measurement istowards protected object (as perIED internal default direction)

Mode Selection of measured currentand voltage

L1, L2, L3 All three phase-to-earth VT inputsare available

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

1MRK 504 134-UEN A Section 14Monitoring

319Application manual

Page 326: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 30: Settings parameters for level supervision

Setting Short Description Selectedvalue

Comments

PMin Minimum value -100 Minimum expected load

PMax Minimum value 100 Maximum expected load

PZeroDb Zero point clamping in 0.001% ofrange

3000 Set zero point clamping to 45 MWthat is, 3% of 200 MW

PRepTyp Reporting type db Select amplitude deadbandsupervision

PDbRepInt Cycl: Report interval (s), Db: In %of range, Int Db: In %s

2 Set ±Δdb=30 MW that is, 2%(larger changes than 30 MW willbe reported)

PHiHiLim High High limit (physical value) 60 High alarm limit that is, extremeoverload alarm

PHiLim High limit (physical value) 50 High warning limit that is, overloadwarning

PLowLim Low limit (physical value) -50 Low warning limit. Not active

PLowLowlLim Low Low limit (physical value) -60 Low alarm limit. Not active

PLimHyst Hysteresis value in % of range(common for all limits)

2 Set ±Δ Hysteresis MW that is, 2%

Table 31: Settings for calibration parameters

Setting Short Description Selectedvalue

Comments

IAmpComp5 Amplitude factor to calibratecurrent at 5% of Ir

0.00

IAmpComp30 Amplitude factor to calibratecurrent at 30% of Ir

0.00

IAmpComp100 Amplitude factor to calibratecurrent at 100% of Ir

0.00

UAmpComp5 Amplitude factor to calibratevoltage at 5% of Ur

0.00

UAmpComp30 Amplitude factor to calibratevoltage at 30% of Ur

0.00

UAmpComp100 Amplitude factor to calibratevoltage at 100% of Ur

0.00

IAngComp5 Angle calibration for current at 5%of Ir

0.00

IAngComp30 Angle pre-calibration for currentat 30% of Ir

0.00

IAngComp100 Angle pre-calibration for currentat 100% of Ir

0.00

14.4.4.2 Measurement function application for a power transformer

Single line diagram for this application is given in figure 153.

Section 14 1MRK 504 134-UEN AMonitoring

320Application manual

Page 327: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

110kV Busbar

200/1

35 / 0,1kV

35kV Busbar

500/5

P Q

31,5 MVA110/36,75/(10,5) kV

Yy0(d5)

UL1L2

IEC09000040-1-en.vsd

IED

IEC09000040-1-EN V1 EN

Figure 153: Single line diagram for transformer application

In order to measure the active and reactive power as indicated in figure 153, it isnecessary to do the following:

1. Set correctly all CT and VT and phase angle reference channel PhaseAngleRef(see settings for analog input modules in PCM600) data using PCM600 foranalog input channels

2. Connect, in PCM600, measurement function to LV side CT & VT inputs3. Set the setting parameters for relevant Measurement function as shown in the

following table 32:

1MRK 504 134-UEN A Section 14Monitoring

321Application manual

Page 328: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Table 32: General settings parameters for the Measurement function

Setting Short description Selectedvalue

Comment

Operation Operation Off/On On Function must be On

PowAmpFact Amplitude factor to scale powercalculations

1.000 Typically no scaling is required

PowAngComp Angle compensation for phaseshift between measured I & U

180.0 Typically no angle compensationis required. However here therequired direction of P & Qmeasurement is towards busbar(Not per IED internal defaultdirection). Therefore anglecompensation have to be used inorder to get measurements inaliment with the requireddirection.

Mode Selection of measured currentand voltage

L1L2 Only UL1L2 phase-to-phasevoltage is available

k Low pass filter coefficient forpower measurement, U and I

0.00 Typically no additional filtering isrequired

14.5 Event counter CNTGGIO

14.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Event counter CNTGGIO

S00946 V1 EN

-

14.5.2 Application

Event counter (CNTGGIO) has six counters which are used for storing the number oftimes each counter has been activated. CNTGGIO can be used to count how manytimes a specific function, for example the tripping logic, has issued a trip signal. Allsix counters have a common blocking and resetting feature.

14.5.3 Setting guidelines

Operation: Sets the operation of Event counter (CNTGGIO) On or Off.

14.6 Limit counter L4UFCNT

Section 14 1MRK 504 134-UEN AMonitoring

322Application manual

Page 329: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.6.1 Function descriptionFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Limit counter L4UFCNT -

14.6.2 Application

Limit counter (L4UFCNT) is intended for applications where positive and/or negativeflanks on a binary signal need to be counted.

The limit counter provides four independent limits to be checked against theaccumulated counted value. The four limit reach indication outputs can be utilized toinitiate proceeding actions. The output indicators remain high until the reset of thefunction.

It is also possible to initiate the counter from a non-zero value by resetting the functionto the wanted initial value provided as a setting.

If applicable, the counter can be set to stop or rollover to zero and continue countingafter reaching the maximum count value. The steady overflow output flag indicatesthe next count after reaching the maximum count value. It is also possible to set thecounter to rollover and indicate the overflow as a pulse, which lasts up to the first countafter rolling over to zero. In this case, periodic pulses will be generated at multipleoverflow of the function.

14.6.2.1 Setting guidelines

The parameters for Limit counter L4UFCNT are set in the local HMI or PCM600.

14.7 Disturbance report

14.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Disturbance report DRPRDRE - -

Analog input signals A1RADR - -

Analog input signals A2RADR - -

Analog input signals A3RADR - -

Analog input signals A4RADR - -

Binary input signals B1RBDR - -

Binary input signals B2RBDR - -

Binary input signals B3RBDR - -

Table continues on next page

1MRK 504 134-UEN A Section 14Monitoring

323Application manual

Page 330: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Binary input signals B4RBDR - -

Binary input signals B5RBDR - -

Binary input signals B6RBDR - -

14.7.2 Application

To get fast, complete and reliable information about disturbances in the primary and/or in the secondary system it is very important to gather information on fault currents,voltages and events. It is also important having a continuous event-logging to be ableto monitor in an overview perspective. These tasks are accomplished by thedisturbance report function DRPRDRE and facilitate a better understanding of thepower system behavior and related primary and secondary equipment during and aftera disturbance. An analysis of the recorded data provides valuable information that canbe used to explain a disturbance, basis for change of IED setting plan, improveexisting equipment, and so on. This information can also be used in a longerperspective when planning for and designing new installations, that is, a disturbancerecording could be a part of Functional Analysis (FA).

Disturbance report DRPRDRE, always included in the IED, acquires sampled data ofall selected analog and binary signals connected to the function blocks that is,

• maximum 30 external analog signals,• 10 internal derived analog signals, and• 96 binary signals.

Disturbance report function is a common name for several functions that is,Indications, Event recorder, Event list, Trip value recorder, Disturbance recorder.

Disturbance report function is characterized by great flexibility as far asconfiguration, starting conditions, recording times, and large storage capacity areconcerned. Thus, disturbance report is not dependent on the operation of protectivefunctions, and it can record disturbances that were not discovered by protectivefunctions for one reason or another. Disturbance report can be used as an advancedstand-alone disturbance recorder.

Every disturbance report recording is saved in the IED. The same applies to all events,which are continuously saved in a ring-buffer. Local HMI can be used to getinformation about the recordings, and the disturbance report files may be uploaded inthe PCM600 using the Disturbance handling tool, for report reading or further analysis(using WaveWin, that can be found on the PCM600 installation CD). The user canalso upload disturbance report files using FTP or MMS (over 61850–8–1) clients.

If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder(record made and fault number) and the fault locator information are available asGOOSE or Report Control data.

Section 14 1MRK 504 134-UEN AMonitoring

324Application manual

Page 331: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.7.3 Setting guidelines

The setting parameters for the Disturbance report function DRPRDRE are set via thelocal HMI or PCM600.

It is possible to handle up to 40 analog and 96 binary signals, either internal signals orsignals coming from external inputs. The binary signals are identical in all functionsthat is, Disturbance recorder, Event recorder, Indication, Trip value recorder andEvent list function.

User-defined names of binary and analog input signals is set using PCM600. Theanalog and binary signals appear with their user-defined names. The name is used inall related functions (Disturbance recorder, Event recorder, Indication, Trip valuerecorder and Event list).

Figure 154 shows the relations between Disturbance report, included functions andfunction blocks. Event list, Event recorder and Indication uses information from thebinary input function blocks (BxRBDR). Trip value recorder uses analog informationfrom the analog input function blocks (AxRADR),. Disturbance report functionacquires information from both AxRADR and BxRBDR.

Trip value rec

Event list

Event recorder

Indications

Disturbancerecorder

A1-4RADR

B1-6RBDR

Disturbance Report

Binary signals

Analog signalsA4RADR

B6RBDR

DRPRDRE

IEC09000337-2-en.vsdIEC09000337 V2 EN

Figure 154: Disturbance report functions and related function blocks

For Disturbance report function there are a number of settings which also influencesthe sub-functions.

Three LED indications placed above the LCD screen makes it possible to get quickstatus information about the IED.

1MRK 504 134-UEN A Section 14Monitoring

325Application manual

Page 332: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Green LED: Steady light In Service

Flashing light Internal failure

Dark No power supply

Yellow LED: Function controlled by SetLEDnsetting in Disturbance report function.

Red LED: Function controlled by SetLEDnsetting in Disturbance report function.

OperationThe operation of Disturbance report function DRPRDRE has to be set On or Off. If Offis selected, note that no disturbance report is registered, and none sub-function willoperate (the only general parameter that influences Event list).

Operation = Off:

• Disturbance reports are not stored.• LED information (yellow - start, red - trip) is not stored or changed.

Operation = On:

• Disturbance reports are stored, disturbance data can be read from the local HMIand from a PC using PCM600.

• LED information (yellow - start, red - trip) is stored.

Every recording will get a number (0 to 999) which is used as identifier (local HMI,disturbance handling tool and IEC 61850). An alternative recording identification isdate, time and sequence number. The sequence number is automatically increased byone for each new recording and is reset to zero at midnight. The maximum number ofrecordings stored in the IED is 100. The oldest recording will be overwritten when anew recording arrives (FIFO).

To be able to delete disturbance records, Operation parameter has tobe On.

The maximum number of recordings depend on each recordings totalrecording time. Long recording time will reduce the number ofrecordings to less than 100.

Section 14 1MRK 504 134-UEN AMonitoring

326Application manual

Page 333: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The IED flash disk should NOT be used to store any user files. Thismight cause disturbance recordings to be deleted due to lack of diskspace.

Recording timesThe different recording times for Disturbance report are set (the pre-fault time, post-fault time, and limit time). These recording times affect all sub-functions more or lessbut not the Event list function.

Prefault recording time (PreFaultRecT) is the recording time before the starting pointof the disturbance. The setting should be at least 0.1 s to ensure enough samples for theestimation of pre-fault values in the Trip value recorder function.

Postfault recording time (PostFaultRecT) is the maximum recording time after thedisappearance of the trig-signal (does not influence the Trip value recorder function).

Recording time limit (TimeLimit) is the maximum recording time after trig. Theparameter limits the recording time if some trigging condition (fault-time) is very longor permanently set (does not influence the Trip value recorder function).

Post retrigger (PostRetrig) can be set to On or Off. Makes it possible to chooseperformance of Disturbance report function if a new trig signal appears in the post-fault window.

PostRetrig = Off

The function is insensitive for new trig signals during post fault time.

PostRetrig = On

The function completes current report and starts a new complete report that is, thelatter will include:

• new pre-fault- and fault-time (which will overlap previous report)• events and indications might be saved in the previous report too, due to overlap• new trip value calculations if installed, in operation and started

Operation in test modeIf the IED is in test mode and OpModeTest = Off. Disturbance report function does notsave any recordings and no LED information is displayed.

If the IED is in test mode and OpModeTest = On. Disturbance report function worksin normal mode and the status is indicated in the saved recording.

14.7.3.1 Binary input signals

Up to 96 binary signals can be selected among internal logical and binary inputsignals. The configuration tool is used to configure the signals.

1MRK 504 134-UEN A Section 14Monitoring

327Application manual

Page 334: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

For each of the 96 signals, it is also possible to select if the signal is to be used as atrigger for the start of the Disturbance report and if the trigger should be activated onpositive (1) or negative (0) slope.

OperationN: Disturbance report may trig for binary input N (On) or not (Off).

TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary inputN.

14.7.3.2 Analog input signals

Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.

The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).

If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

NomValueM: Nominal value for input M.

OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).

OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relativenominal value for analog input M in percent of nominal value.

14.7.3.3 Sub-function parameters

All functions are in operation as long as Disturbance report is in operation.

IndicationsIndicationMaN: Indication mask for binary input N. If set (Show), a status change ofthat particular input, will be fetched and shown in the disturbance summary on localHMI. If not set (Hide), status change will not be indicated.

SetLEDN: Set yellow Start and red Trip LED on local HMI in front of the IED if binaryinput N changes status.

Disturbance recorderOperationM: Analog channel M is to be recorded by the disturbance recorder (On) ornot (Off).

If OperationM = Off, no waveform (samples) will be recorded and reported in graph.However, Trip value, pre-fault and fault value will be recorded and reported. Theinput channel can still be used to trig the disturbance recorder.

Section 14 1MRK 504 134-UEN AMonitoring

328Application manual

Page 335: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

If OperationM = On, waveform (samples) will also be recorded and reported in graph.

Event recorderEvent recorder function has no dedicated parameters.

Trip value recorderZeroAngleRef: The parameter defines which analog signal that will be used as phaseangle reference for all other analog input signals. This signal will also be used forfrequency measurement and the measured frequency is used when calculating tripvalues. It is suggested to point out a sampled voltage input signal, for example, a lineor busbar phase voltage (channel 1-30).

Event listEvent list function has no dedicated parameters.

14.7.3.4 Consideration

The density of recording equipment in power systems is increasing, since the numberof modern IEDs, where recorders are included, is increasing. This leads to a vastnumber of recordings at every single disturbance and a lot of information has to behandled if the recording functions do not have proper settings. The goal is to optimizethe settings in each IED to be able to capture just valuable disturbances and tomaximize the number that is possible to save in the IED.

The recording time should not be longer than necessary (PostFaultrecT andTimeLimit).

• Should the function record faults only for the protected object or cover more?• How long is the longest expected fault clearing time?• Is it necessary to include reclosure in the recording or should a persistent fault

generate a second recording (PostRetrig)?

Minimize the number of recordings:

• Binary signals: Use only relevant signals to start the recording that is, protectiontrip, carrier receive and/or start signals.

• Analog signals: The level triggering should be used with great care, sinceunfortunate settings will cause enormously number of recordings. If neverthelessanalog input triggering is used, chose settings by a sufficient margin from normaloperation values. Phase voltages are not recommended for trigging.

Remember that values of parameters set elsewhere are linked to the information on areport. Such parameters are, for example, station and object identifiers, CT and VTratios.

1MRK 504 134-UEN A Section 14Monitoring

329Application manual

Page 336: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.8 Measured value expander block MVEXP

14.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Measured value expander block MVEXP - -

14.8.2 Application

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXUand VNMMXU), current and voltage sequence measurement functions (CMSQI andVMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) areprovided with measurement supervision functionality. All measured values can besupervised with four settable limits, that is low-low limit, low limit, high limit andhigh-high limit. The measure value expander block (MVEXP) has been introduced tobe able to translate the integer output signal from the measuring functions to 5 binarysignals, that is below low-low limit, below low limit, normal, above high-high limit orabove high limit. The output signals can be used as conditions in the configurablelogic.

14.8.3 Setting guidelines

The function does not have any parameters available in Local HMI or Protection andControl IED Manager (PCM600).

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

14.9 Station battery supervision SPVNZBAT

14.9.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Station battery supervision function SPVNZBAT U<> -

14.9.2 Application

Usually, the load on the DC system is a constant resistance load, for example, lamps,LEDs, electronic instruments and electromagnetic contactors in a steady statecondition. A transient RL load exists when breakers are tripped or closed.

Section 14 1MRK 504 134-UEN AMonitoring

330Application manual

Page 337: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The battery voltage has to be continuously monitored as the batteries can withstandmoderate overvoltage and undervoltage only for a short period of time.

• If the battery is subjected to a prolonged or frequent overvoltage, it leads to theageing of the battery, which may lead to the earlier failure of the battery. The otheroccurrences may be the thermal runaway, generation of heat or increased amountof hydrogen gas and the depletion of fluid in case of valve regulated batteries.

• If the value of the charging voltage drops below the minimum recommended floatvoltage of the battery, the battery does not receive sufficient charging current tooffset internal losses, resulting in a gradual loss of capacity.• If a lead acid battery is subjected to a continuous undervoltage, heavy

sulfation occurs on the plates, which leads to the loss of the battery capacity.

14.10 Insulation gas monitoring function SSIMG

14.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation gas monitoring function SSIMG - 63

14.10.2 Application

Insulation gas monitoring function (SSIMG) is used for monitoring the circuit breakercondition. Proper arc extinction by the compressed gas in the circuit breaker is veryimportant. When the pressure becomes too low compared to the required value, thecircuit breaker operation gets blocked to minimize the risk of internal failure. Binaryinformation based on the gas pressure in the circuit breaker is used as input signals tothe function. In addition to that, the function generates alarms based on receivedinformation.

14.11 Insulation liquid monitoring function SSIML

14.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Insulation liquid monitoring function SSIML - 71

1MRK 504 134-UEN A Section 14Monitoring

331Application manual

Page 338: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

14.11.2 Application

Insulation liquid monitoring function (SSIML) is used for monitoring the circuitbreaker condition. Proper arc extinction by the compressed oil in the circuit breaker isvery important. When the level becomes too low, compared to the required value, thecircuit breaker operation is blocked to minimize the risk of internal failures. Binaryinformation based on the oil level in the circuit breaker is used as input signals to thefunction. In addition to that, the function generates alarms based on receivedinformation.

14.12 Circuit breaker condition monitoring SSCBR

14.12.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Circuit breaker condition monitoring SSCBR - -

14.12.2 Application

SSCBR includes different metering and monitoring subfunctions.

Circuit breaker statusCircuit breaker status monitors the position of the circuit breaker, that is, whether thebreaker is in an open, closed or intermediate position.

Circuit breaker operation monitoringThe purpose of the circuit breaker operation monitoring is to indicate that the circuitbreaker has not been operated for a long time. The function calculates the number ofdays the circuit breaker has remained inactive, that is, has stayed in the same open orclosed state. There is also the possibility to set an initial inactive day.

Breaker contact travel timeHigh travelling times indicate the need for maintenance of the circuit breakermechanism. Therefore, detecting excessive travelling time is needed. During theopening cycle operation, the main contact starts opening. The auxiliary contact Aopens, the auxiliary contact B closes, and the main contact reaches its openingposition. During the closing cycle, the first main contact starts closing. The auxiliarycontact B opens, the auxiliary contact A closes, and the main contact reaches its closeposition. The travel times are calculated based on the state changes of the auxiliarycontacts and the adding correction factor to consider the time difference of the maincontact's and the auxiliary contact's position change.

Section 14 1MRK 504 134-UEN AMonitoring

332Application manual

Page 339: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Operation counterRoutine maintenance of the breaker like the lubricating breaker mechanism, isgenerally based on a number of operations. A suitable threshold setting, to raise analarm when the number of operation cycle exceeds the set limit, helps preventivemaintenance. This can also be used to indicate the requirement for oil sampling fordielectric testing in case of an oil circuit breaker.

The change of state can be detected from the binary input of the auxiliary contact.There is a possibility to set an initial value for the counter which can be used toinitialize this functionality after a period of operation or in case of refurbished primaryequipment.

Accumulation of Iyt

Accumulation of Iyt calculates the accumulated energy ΣIyt where the factor y isknown as the current exponent. The factor y depends on the type of the circuit breaker.For oil circuit breakers the factor y is normally 2. In case of a high-voltage system, thefactor y can be 1.4...1.5.

Remaining life of the breakerEvery time the breaker operates, the life of the circuit breaker reduces due to wearing.The wearing in the breaker depends on the tripping current, and the remaining life ofthe breaker is estimated from the circuit breaker trip curve provided by themanufacturer.

Example for estimating the remaining life of a circuit breaker

1MRK 504 134-UEN A Section 14Monitoring

333Application manual

Page 340: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

A071114 V3 EN

Figure 155: Trip Curves for a typical 12 kV, 630 A, 16 kA vacuum interrupter

Nr the number of closing-opening operations allowed for the circuit breaker

Ia the current at the time of tripping of the circuit breaker

Calculation of Directional Coefficient

The directional coefficient is calculated according to the formula:

Section 14 1MRK 504 134-UEN AMonitoring

334Application manual

Page 341: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Directional Coef

B

A

I

I

f

r

=

= −log

log

.2 2609

A070794 V2 EN (Equation 124)

Ir Rated operating current = 630 A

If Rated fault current = 16 kA

A Op number rated = 30000

B Op number fault = 20

Calculation for estimating the remaining life

The equation shows that there are 30,000 possible operations at the rated operatingcurrent of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if thetripping current is 10 kA, one operation at 10 kA is equivalent to 30,000/500=60operations at the rated current. It is also assumed that prior to this tripping, theremaining life of the circuit breaker is 15,000 operations. Therefore, after oneoperation of 10 kA, the remaining life of the circuit breaker is 15,000-60=14,940 at therated operating current.

Spring charging time indicationFor normal circuit breaker operation, the circuit breaker spring should be chargedwithin a specified time. Therefore, detecting long spring charging time indicates thetime for circuit breaker maintenance. The last value of the spring charging time can begiven as a service value.

Gas pressure supervisionThe gas pressure supervision monitors the gas pressure inside the arc chamber. Whenthe pressure becomes too low compared to the required value, the circuit breakeroperations are locked. A binary input is available based on the pressure levels in thefunction, and alarms are generated based on these inputs.

1MRK 504 134-UEN A Section 14Monitoring

335Application manual

Page 342: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

336

Page 343: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 15 Metering

15.1 Pulse counter PCGGIO

15.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Pulse counter PCGGIO

S00947 V1 EN

-

15.1.2 Application

Pulse counter (PCGGIO) function counts externally generated binary pulses, forinstance pulses coming from an external energy meter, for calculation of energyconsumption values. The pulses are captured by the binary input module (BIO), andread by the PCGGIO function. The number of pulses in the counter is then reported viathe station bus to the substation automation system or read via the station monitoringsystem as a service value. When using IEC 61850–8–1, a scaled service value isavailable over the station bus.

The normal use for this function is the counting of energy pulses from external energymeters. An optional number of inputs from the binary input module in IED can be usedfor this purpose with a frequency of up to 10 Hz. PCGGIO can also be used as a generalpurpose counter.

15.1.3 Setting guidelines

From PCM600, these parameters can be set individually for each pulse counter:

• Operation: Off/On• tReporting: 0-3600s• EventMask: NoEvents/ReportEvents

The configuration of the inputs and outputs of PCGGIO function block is made withPCM600.

On the binary input output module (BIO), the debounce filter default time is set to 5ms, that is, the counter suppresses pulses with a pulse length less than 5 ms. The binary

1MRK 504 134-UEN A Section 15Metering

337Application manual

Page 344: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

input channels on the binary input output module (BIO) have individual settings fordebounce time, oscillation count and oscillation time. The values can be changed inthe local HMI and PCM600 under Main menu/Configuration/I/O modules

The debunce time should be set to the same value for all channels onthe board

The setting isindividual for all input channels on the binary inputoutput module (BIO), that is, if changes of the limits are made forinputs not connected to the pulse counter, it will not influence theinputs used for pulse counting.

15.2 Energy calculation and demand handling EPTMMTR

15.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Energy calculation and demandhandling

ETPMMTR

Wh

IEC10000169 V1 EN

-

15.2.2 Application

Energy calculation and demand handling function ETPMMTR is intended forstatistics of the forward and reverse active and reactive energy. It has a high accuracybasically given by the measurements function (CVMMXN). This function has a sitecalibration possibility to further increase the total accuracy.

The function is connected to the instantaneous outputs of (CVMMXN) as shown infigure 156.

PQ

STACCRSTACCRSTDMD

TRUEFALSEFALSE

CVMMXN

IEC09000106.vsd

ETPMMTRP_INSTQ_INST

IEC09000106 V1 EN

Figure 156: Connection of energy calculation and demand handling functionETPMMTR to the measurements function (CVMMXN)

Section 15 1MRK 504 134-UEN AMetering

338Application manual

Page 345: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The energy values can be read through communication in MWh and MVarh inmonitoring tool of PCM600 and/or alternatively the values can be presented on thelocal HMI. The local HMI graphical display is configured with PCM600 Graphicaldisplay editor tool (GDE) with a measuring value which is selected to the active andreactive component as preferred. All four values can also be presented.

Maximum demand values are presented in MWh or MVarh in the same way.

Alternatively, the values can be presented with use of the pulse counters function(PCGGIO). The output values are scaled with the pulse output setting valuesEAFAccPlsQty, EARAccPlsQty, ERFAccPlsQty and ERRAccPlsQty of the energymetering function and then the pulse counter can be set-up to present the correct valuesby scaling in this function. Pulse counter values can then be presented on the localHMI in the same way and/or sent to the SA system through communication where thetotal energy then is calculated by summation of the energy pulses. This principle isgood for very high values of energy as the saturation of numbers else will limit energyintegration to about one year with 50 kV and 3000 A. After that the accumulation willstart on zero again.

15.2.3 Setting guidelines

The parameters are set via the local HMI or PCM600.

The following settings can be done for the energy calculation and demand handlingfunction ETPMMTR:

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

Operation: Off/On

tEnergy: Time interval when energy is measured.

StartAcc: Off/On is used to switch the accumulation of energy on and off.

The input signal STACC is used to start accumulation. Input signalSTACC cannot be used to halt accumulation. The energy content isreset every time STACC is activated. STACC can for example, beused when an external clock is used to switch two active energymeasuring function blocks on and off to have indication of two tariffs.

tEnergyOnPls: gives the pulse length ON time of the pulse. It should be at least 100ms when connected to the Pulse counter function block. Typical value can be 100 ms.

tEnergyOffPls: gives the OFF time between pulses. Typical value can be 100 ms.

EAFAccPlsQty and EARAccPlsQty: gives the MWh value in each pulse. It should beselected together with the setting of the Pulse counter (PCGGIO) settings to give thecorrect total pulse value.

1MRK 504 134-UEN A Section 15Metering

339Application manual

Page 346: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

ERFAccPlsQty and ERRAccPlsQty: gives the MVarh value in each pulse. It should beselected together with the setting of the Pulse counter (PCGGIO) settings to give thecorrect total pulse value.

For the advanced user there are a number of settings for direction, zero clamping, maxlimit, and so on. Normally, the default values are suitable for these parameters.

Section 15 1MRK 504 134-UEN AMetering

340Application manual

Page 347: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 16 Station communication

16.1 IEC61850-8-1 communication protocol

16.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IEC 61850-8-1 communication protocol IEC 61850-8-1 - -

16.1.2 Application

IEC 61850-8-1 communication protocol allows vertical communication to HSIclients and allows horizontal communication between two or more intelligentelectronic devices (IEDs) from one or several vendors to exchange information and touse it in the performance of their functions and for correct co-operation.

GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard, allows the IEDs to communicate state and control information amongstthemselves, using a publish-subscribe mechanism. That is, upon detecting an event,the IED(s) use a multi-cast transmission to notify those devices that have registered toreceive the data. An IED can, by publishing a GOOSE message, report its status. It canalso request a control action to be directed at any device in the network.

Figure 157 shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1specifies only the interface to the substation LAN. The LAN itself is left to the systemintegrator.

1MRK 504 134-UEN A Section 16Station communication

341Application manual

Page 348: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

KIOSK 2 KIOSK 3

Station HSIBase System

EngineeringWorkstation

SMSGateway

Printer

CC

IEC09000135_en.vsd

KIOSK 1

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IED 1

IED 2

IED 3

IEC09000135 V1 EN

Figure 157: Example of a communication system with IEC 61850–8–1

Figure 158 shows the GOOSE peer-to-peer communication.

Control Protection Control ProtectionControl and protection

GOOSE

en05000734.vsd

Station HSIMicroSCADA

Gateway

IEDA

IEDA

IEDA

IEDA

IEDA

IEC05000734 V1 EN

Figure 158: Example of a broadcasted GOOSE message

Section 16 1MRK 504 134-UEN AStation communication

342Application manual

Page 349: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

16.1.2.1 Horizontal communication via GOOSE

GOOSE messages are sent in horizontal communication between the IEDs. Theinformation, which is exchanged, is used for station wide interlocking, breaker failureprotection, busbar voltage selection and so on.

The simplified principle is shown in Figure 159 and can be described as follows.When IED1 has decided to transmit the data set it forces a transmission via the stationbus. All other IEDs receive the data set, but only those who have this data set in theiraddress list will take it and keep it in an input container. It is defined, that the receivingIED will take the content of the received data set and makes it available for theapplication configuration.

IEC08000145.vsd

IED1 IED3IED2

DO1/DA1DO1/DA2DO2/DA1DO2/DA2DO3/DA1DO3/DA2

IED1IED1IED1IED1IED1IED1

SMT

Receive-FB

DA1DA2DO1

DA1DA2DA1DA2DO3

DA1DA2DO2

Stationbus

DO1/DA1DO1/DA2DO2/DA1DO2/DA2DO3/DA1DO3/DA2

IED1IED1IED1IED1IED1IED1

PLC Program

FBa FBb FBc

IEC08000145 V1 EN

Figure 159: SMT: GOOSE principle and signal routing with SMT

Special function blocks take the data set and present it via the function block as outputsignals for application functions in the application configuration. Different GOOSEreceive function blocks are available for the specific tasks.

SMT links the different data object attributes (for example stVal or magnitude) to theoutput signal to make it available for functions in the application configuration. Whena matrix cell array is marked red the IEC 61850–8–1 data attribute type does not fittogether, even if the GOOSE receive function block is the partner. SMT checks this onthe content of the received data set. See Figure 160

1MRK 504 134-UEN A Section 16Station communication

343Application manual

Page 350: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC08000174.vsd

IEC08000174 V1 EN

Figure 160: SMT: GOOSE marshalling with SMT

GOOSE receive function blocks extract process information, received by the data set,into single attribute information that can be used within the application configuration.Crosses in the SMT matrix connect received values to the respective function blocksignal in SMT, see Figure 161

The corresponding quality attribute is automatically connected bySMT. This quality attribute is available in ACT, through the outputsof the available GOOSE function blocks.

Section 16 1MRK 504 134-UEN AStation communication

344Application manual

Page 351: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC11000056-1-en.vsd

IEC11000056 V1 EN

Figure 161: SMT: GOOSE receive function block with converted signals

GOOSEVCTRCONF function is used to control the rate (in seconds) at which voltagecontrol information from TR8ATCC is transmitted/received to/from other IEDs viaGOOSE communication. GOOSEVCTRCONF function is visible in PST.

The following voltage control information can be sent from TR8ATCC via GOOSEcommunication:

• BusV• LoadAIm• LoadARe• PosRel• SetV• VCTRStatus• X2

GOOSEVCTRRCV component receives the voltage control data from GOOSEnetwork at the user defined rate.

This component also checks the received data validity, communication validity andtest mode. Communication validity will be checked upon the rate of data reception.Data validity also depends upon the communication. If communication is invalid thendata validity will also be invalid. IEC 61850 also checks for data validity usinginternal parameters which will also be passed to the DATAVALID output.

1MRK 504 134-UEN A Section 16Station communication

345Application manual

Page 352: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

16.1.3 Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:

Operation User can set IEC 61850 communication to On or Off.

GOOSE has to be set to the Ethernet link where GOOSE traffic shall be send andreceived.

IEC 61850–8–1 specific data (logical nodes etc.) per includedfunction in an IED can be found in the communication protocolmanual for IEC 61850–8–1.

The setting parameters for GOOSEVCTRCONF are described below:

SendOperation: This setting sets the send functionality ON or OFF.

ReceiveOperation: This setting sets the receive functionality ON or OFF.

SendInterval: This parameter sets the rate at which VCTR Send component need totransmit the GOOSE message over network. Default value of the send interval is 0.3s.Minimum value of the send interval can be set to 0.1s and maximum as 5.0s.

ReceiveInterval: This parameter sets the rate at which VCTR receive component needto receive the GOOSE message from the network. Default value of the receive intervalis 0.8s. Minimum value of the send interval can be set to 0.1s and maximum as 10.0s

Receive interval should be greater than the send interval. With thisconfiguration receiving component shall always have the updatedvalue. For example ReceiveInterval > 2•SendInterval.

16.2 DNP3 protocol

DNP3 (Distributed Network Protocol) is a set of communications protocols used tocommunicate data between components in process automation systems. For a detaileddescription of the DNP3 protocol, see the DNP3 Communication protocol manual.

16.3 IEC 60870-5-103 communication protocol

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serialcommunication exchanging information with a control system, and with a datatransfer rate up to 19200 bit/s. In IEC terminology, a primary station is a master anda secondary station is a slave. The communication is based on a point-to-point

Section 16 1MRK 504 134-UEN AStation communication

346Application manual

Page 353: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

principle. The master must have software that can interpret IEC 60870-5-103communication messages.

The Communication protocol manual for IEC 60870-5-103 includes the 650 seriesvendor specific IEC 60870-5-103 implementation.

IEC 60870-5-103 protocol can be configured to use either the optical serial or RS485serial communication interface on the COM03 or the COM05 communicationmodule. The functions Operation selection for optical serial OPTICALPROT andOperation selection for RS485 RS485PROT are used to select the communicationinterface.

See the Engineering manual for IEC103 60870-5-103 engineeringprocedures in PCM600.

The function IEC60870-5-103 Optical serial communication, OPTICAL103, is usedto configure the communication parameters for the optical serial communicationinterface. The function IEC60870-5-103 serial communication for RS485,RS485103, is used to configure the communication parameters for the RS485 serialcommunication interface.

16.4 IEC 61850-8-1 redundant station bus communication

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

System component for parallelredundancy protocol

PRPSTATUS - -

16.5 Application

Parallel redundancy protocol status (PRPSTATUS) is used to supervise and assureredundant Ethernet communication over two channels. This will secure data transfereven though one communication channel might not be available for some reason.PRPSTATUS provides redundant communication over the station bus running IEC61850-8-1 protocol. The redundant communication uses port L1_A and L1_B on theCOM3 module.

1MRK 504 134-UEN A Section 16Station communication

347Application manual

Page 354: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Switch A Switch B1 2

DataData

DataData

IEC13000003-1-en.vsd

IED

PRPSTATUS

1 2

COM03

A B

Duo

Redundancy Supervision

Station Control System

IEC13000003 V1 EN

Figure 162: Redundant station bus

16.6 Setting guidelines

The redundant station bus communication is configured using the local HMI, MainMenu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB

The settings can be viewed and OperationMode can be set in the Parameter Settingtool in PCM600 under IED Configuration/Communication/TCP-IPconfiguration/ETHLAN1_AB where

OperationMode can be set to Off, NonRedundant(A) or PRP(A+B). The redundantcommunication will be activated when this parameter is set to PRP(A+B).

Section 16 1MRK 504 134-UEN AStation communication

348Application manual

Page 355: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The ETHLAN1_AB in the Parameter Setting tool is relevant only when the COM03module is present.

IEC13000009-1-en.vsd

IEC13000009 V1 EN

Figure 163: PRP1 Configured in the Parameter Setting tool

IEC13000010-1-en.vsd

IEC13000010 V1 EN

Figure 164: Lock/Unlock parameter

1MRK 504 134-UEN A Section 16Station communication

349Application manual

Page 356: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC13000008-1-en.vsd

IEC13000008 V1 EN

Figure 165: PST screen: OperationMode is set to PRP(A+B)

Section 16 1MRK 504 134-UEN AStation communication

350Application manual

Page 357: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 17 Basic IED functions

17.1 Self supervision with internal event list

17.1.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Internal error signal INTERRSIG - -

Internal event list SELFSUPEVLST - -

17.1.2 Application

The protection and control IEDs have many functions included . Self supervision withinternal event list (SELFSUPEVLST) and internal error signals (INTERRSIG)function provide supervision of the IED. The fault signals make it easier to analyzeand locate a fault.

Both hardware and software supervision is included and it is also possible to indicatepossible faults through a hardware contact on the power supply module and/orthrough the software communication.

Internal events are generated by the built-in supervisory functions. The supervisoryfunctions supervise the status of the various modules in the IED and, in case of failure,a corresponding event is generated. Similarly, when the failure is corrected, acorresponding event is generated.

The event list is updated every 10s hence, an event will not be visiblein the event list as soon as it is created.

Apart from the built-in supervision of the various modules, events are also generatedwhen the status changes for the:

• built-in real time clock (in operation/out of order).• external time synchronization (in operation/out of order).• Change lock (on/off)

Events are also generated:

• whenever any setting in the IED is changed.

1MRK 504 134-UEN A Section 17Basic IED functions

351Application manual

Page 358: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The internal events are time tagged with a resolution of 1 ms and stored in a list. Thelist can store up to 40 events. The list is based on the FIFO principle, that is, when itis full, the oldest event is overwritten. The list can be cleared via the local HMI .

The list of internal events provides valuable information, which can be used duringcommissioning and fault tracing.

17.2 Time synchronization

17.2.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization TIMESYNCHGEN

- -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time system, summer time begins DSTBEGIN - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time system, summer time ends DSTEND - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization via IRIG-B IRIG-B - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time synchronization via SNTP SNTP - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Time zone from UTC TIMEZONE - -

17.2.2 Application

Use a common global source for example GPS time synchronization inside eachsubstation as well as inside the area of the utility responsibility to achieve a common

Section 17 1MRK 504 134-UEN ABasic IED functions

352Application manual

Page 359: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

time base for the IEDs in a protection and control system. This makes comparison andanalysis of events and disturbance data between all IEDs in the power system possible.

Time-tagging of internal events and disturbances are an excellent help whenevaluating faults. Without time synchronization, only the events within the IED canbe compared to one another. With time synchronization, events and disturbanceswithin the entire station, and even between line ends, can be compared duringevaluation.

In the IED, the internal time can be synchronized from a number of sources:

• SNTP• IRIG-B• DNP• IEC60870-5-103

Micro SCADA OPC server should not be used as a timesynchronization source.

17.2.3 Setting guidelines

System timeThe time is only possible to set inside the IED via the local HMI by navigating toConfiguration/Time/SYSTEMTIME with year, month, day, hour, minute andsecond.

SynchronizationWith external time synchronization the setting how to synchronize for the real-timeclock (TIME) are set via local HMI or PCM600.

TimeSynchThe setting TIMESYNCGEN is used to set the source of the time synchronization. Thesetting alternatives are:

CoarseSyncSrc which can have the following values:

• Off• SNTP• DNP• IEC60870-5-103

FineSyncSource which can have the following values:

1MRK 504 134-UEN A Section 17Basic IED functions

353Application manual

Page 360: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

• Off• SNTP• IRIG-B

The parameter SyncMaster defines if the IED is a master, or not a master for timesynchronization in a system of IEDs connected in a communication network(IEC61850-8-1). The SyncMaster can have the following values:

• Off• SNTP -Server

The time synchronization fine tunes the clock.

IEC 60870-5-103 time synchronizationAn IED with IEC 60870-5-103 protocol can be used for time synchronization, but foraccuracy reasons, it is not recommended. In some cases, however, this kind ofsynchronization is needed, for example, when no other synchronization is available.

First, set the IED to be synchronized via IEC 60870-5-103 either from IEDConfiguration/Time/Synchronization/TIMESYNCHGEN:1 in PST or from thelocal HMI.

GUID-68284E7B-A24D-4E78-B5BA-736B29F50E9A V1 EN

Figure 166: Settings under TIMESYNCHGEN:1 in PST

Only CoarseSyncSrc can be set to IEC 60870-5-103, not FineSyncSource.

After setting up the time synchronization source, the user must check and modify theIEC 60870-5-103 time synchronization specific settings, under Main menu/Configuration/Communication/Station communication/IEC60870-5-103.

• MasterTimeDomain specifies the format of the time sent by the master. Formatcan be:• Coordinated Universal Time (UTC)• Local time set in the master (Local)• Local time set in the master adjusted according to daylight saving time

(Local with DST)• TimeSyncMode specifies the time sent by the IED. The time synchronisation is

done using the following ways:• IEDTime: The IED sends the messages with its own time.• LinMasTime: The IED measures the offset between its own time and the

master time, and applies the same offset for the messages sent as in the

Section 17 1MRK 504 134-UEN ABasic IED functions

354Application manual

Page 361: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEDTimeSkew. But in LinMasTime it applies the time changes occurredbetween two synchronised messages.

• IEDTimeSkew: The IED measures the offset in between its own time andthe master time and applies the same offset for the messages sent.

• EvalTimeAccuracy evaluates time accuracy for invalid time. Specifies theaccuracy of the synchronization (5, 10, 20 or 40 ms). If the accuracy is less thanthe specified value, the “Bad Time” flag is raised. To accommodate those mastersthat are really bad in time sync, the EvalTimeAccuracy can be set to Off.

According to the standard, the “Bad Time” flag is reported when synchronization hasbeen omitted in the protection for >23 h.

17.3 Parameter setting group handling

17.3.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Setting group handling SETGRPS - -

Parameter setting groups ACTVGRP - -

17.3.2 Application

Four different groups of settings are available to optimize IED operation for differentpower system conditions. By creating and switching between fine tuned setting sets,either from the local HMI or configurable binary inputs, results in a highly adaptableIED that can cope with a variety of power system scenarios.

Different conditions in networks with different voltage levels require highly adaptableprotection and control IEDs to best provide for dependability, security and selectivityrequirements. Protection IEDs operate with a higher degree of availability, especially,if the setting values of their parameters are continuously optimized according to theconditions in the power system.

Operational departments can plan for different operating conditions in the primarypower system equipment. The protection engineer can prepare the necessaryoptimized and pre-tested settings in advance for different protection functions.different groups of setting parameters are available in the IED. Any of them can beactivated through the different programmable binary inputs by means of external orinternal control signals.

The four different groups of setting parameters are available in the IED. Any of themcan be activated through different inputs by means of external programmable binaryor internal control signals.

1MRK 504 134-UEN A Section 17Basic IED functions

355Application manual

Page 362: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.3.3 Setting guidelines

The setting ActiveSetGrp, is used to select which parameter group to be active. Theactive group can also be selected with configured input to the function blockACTVGRP.

The parameter MaxNoSetGrp defines the maximum number of setting groups in useto switch between. Only the selected number of setting groups will be available in theParameter Setting tool (PST) for activation with the ACTVGRP function block.

17.4 Test mode functionality TESTMODE

17.4.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Test mode functionality TESTMODE - -

17.4.2 Application

The protection and control IEDs may have a complex configuration with manyincluded functions. To make the testing procedure easier, the IEDs include the featurethat allows individual blocking of all functions except the function(s) the shall betested.

This means that it is possible to see when a function is activated or trips. It also enablesthe user to follow the operation of several related functions to check correctfunctionality and to check parts of the configuration, and so on.

17.4.3 Setting guidelines

There are two possible ways to place the IED in the TestMode= On” state. This meansthat if the IED is set to normal operation (TestMode = Off), but the functions are stillshown being in the test mode, the input signal INPUT on the TESTMODE functionblock must be activated in the configuration.

Forcing of binary output signals is only possible when the IED is in test mode.

Section 17 1MRK 504 134-UEN ABasic IED functions

356Application manual

Page 363: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.5 Change lock CHNGLCK

17.5.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Change lock function CHNGLCK - -

17.5.2 Application

Change lock function CHNGLCK is used to block further changes to the IEDconfiguration once the commissioning is complete. The purpose is to make itimpossible to perform inadvertent IED configuration and setting changes.

However, when activated, CHNGLCK will still allow the following actions that doesnot involve reconfiguring of the IED:

• Monitoring• Reading events• Resetting events• Reading disturbance data• Clear disturbances• Reset LEDs• Reset counters and other runtime component states• Control operations• Set system time• Enter and exit from test mode• Change of active setting group

The binary input controlling the function is defined in ACT or SMT. The CHNGLCKfunction is configured using ACT.

LOCK Binary input signal that will activate/deactivate the function, defined in ACT orSMT.

ACTIVE Output status signal

OVERRIDE Set if function is overridden

When CHNGLCK has a logical one on its input, then all attempts to modify the IEDconfiguration and setting will be denied and the message "Error: Changes blocked"will be displayed on the local HMI; in PCM600 the message will be "Operation deniedby active ChangeLock". The CHNGLCK function should be configured so that it iscontrolled by a signal from a binary input card. This guarantees that by setting thatsignal to a logical zero, CHNGLCK is deactivated. If any logic is included in the signalpath to the CHNGLCK input, that logic must be designed so that it cannot

1MRK 504 134-UEN A Section 17Basic IED functions

357Application manual

Page 364: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

permanently issue a logical one to the CHNGLCK input. If such a situation wouldoccur in spite of these precautions, then please contact the local ABB representativefor remedial action.

17.5.3 Setting guidelines

The Change lock function CHNGLCK does not have any parameters available in thelocal HMI or PCM600.

17.6 IED identifiers TERMINALID

17.6.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

IED identifiers TERMINALID - -

17.6.2 Application

17.6.2.1 Customer specific settings

The customer specific settings are used to give the IED a unique name and address.The settings are used by a central control system to communicate with the IED. Thecustomer specific identifiers are found in the local HMI under Configuration/Powersystem/Identifiers/TERMINALID

The settings can also be made from PCM600. For more information about theavailable identifiers, see the technical manual.

Use only characters A - Z, a - z and 0 - 9 in station, unit and objectnames.

17.7 Product information PRODINF

17.7.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Product information PRODINF - -

Section 17 1MRK 504 134-UEN ABasic IED functions

358Application manual

Page 365: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.7.2 Application

17.7.2.1 Factory defined settings

The factory defined settings are very useful for identifying a specific version and veryhelpful in the case of maintenance, repair, interchanging IEDs between differentSubstation Automation Systems and upgrading. The factory made settings can not bechanged by the customer. They can only be viewed. The settings are found in the localHMI under Main menu/Diagnostics/IED status/Product identifiers

The following identifiers are available:

• IEDProdType• Describes the type of the IED (like REL, REC or RET). Example: REL650

• ProductVer• Describes the product version. Example: 1.2.3

1 is the Major version of the manufactured product this means, new platform of theproduct

2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product

3 is the Major revision of the manufactured product this means, functions or hardware iseither changed or enhanced in the product

• ProductDef• Describes the release number, from the production. Example: 1.2.3.4

where;

1 is the Major version of the manufactured product this means, new platform of theproduct

2 is the Minor version of the manufactured product this means, new functions or newhardware added to the product

3 is the Major revision of the manufactured product this means, functions or hardware iseither changed or enhanced in the product

4 is the Minor revision of the manufactured product this means, code is corrected in theproduct

• SerialNo: the structure of the SerialNo is as follows, for example, T0123456where

01 is the last two digits in the year when the IED was manufactured that is, 2001

23 is the week number when the IED was manufactured

456 is the sequential number of the IEDs produced during the production week

• OrderingNo: the structure of the OrderingNo is as follows, for example,1MRK008526-BA. This alphanumeric string has no specific meaning except,that it is used for internal identification purposes within ABB.

• ProductionDate: states the production date in the “YYYY-MM_DD” format.

1MRK 504 134-UEN A Section 17Basic IED functions

359Application manual

Page 366: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.8 Primary system values PRIMVAL

17.8.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Primary system values PRIMVAL - -

17.8.2 Application

The rated system frequency and phasor rotation are set under Main menu/Configuration/ Power system/ Primary values/PRIMVAL in the local HMI andPCM600 parameter setting tree.

17.9 Signal matrix for analog inputs SMAI

17.9.1 Identification

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Signal matrix for analog inputs SMAI_20_x - -

17.9.2 Application

Signal matrix for analog inputs function (SMAI), also known as the preprocessorfunction, processes the analog signals connected to it and gives information about allaspects of the analog signals connected, like the RMS value, phase angle, frequency,harmonic content, sequence components and so on. This information is then used bythe respective functions in ACT (for example protection, measurement ormonitoring).

The SMAI function is used within PCM600 in direct relation with the Signal Matrixtool or the Application Configuration tool.

The SMAI function blocks for the 650 series of products are possibleto set for two cycle times either 5 or 20ms. The function blocksconnected to a SMAI function block shall always have the same cycletime as the SMAI block.

Section 17 1MRK 504 134-UEN ABasic IED functions

360Application manual

Page 367: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.9.3 Setting guidelines

The parameters for the signal matrix for analog inputs (SMAI) functions are set via thelocal HMI or via the PCM600.

Every SMAI function block can receive four analog signals (three phases and oneneutral value), either voltage or current. SMAI outputs give information about everyaspect of the 3ph analog signals acquired (phase angle, RMS value, frequency andfrequency derivates, and so on – 244 values in total). Besides the block “group name”,the analog inputs type (voltage or current) and the analog input names that can be setdirectly in ACT.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

DFTRefExtOut: Parameter valid only for function block SMAI_20_1:1 andSMAI_20_1:2 .

These 2 SMAI blocks can be used as reference blocks for other SMAI blocks; thesetting is related to the output signal SPFCOUT, and it defines the source for thisoutput, when the adaptive frequency tracking is used. The possible options are:InternalDFTRef (i.e. fixed DFT reference based on set system frequency): it is notused when the adaptive frequency tracking is needed. DFTRefGrpn (where n is anumber from 1 to 12): it define the SMAI block numbered n, within its task, that is thereference for the adaptive frequency tracking. That reference SMAI shall be voltagetype, and shall be connected to a 3-phase voltage transformer which supply voltage inall the needed operating conditions. ExternalDFTRef : the reference is based on whatis connected to input DFTSPFC.

DFTReference: Reference DFT for the SMAI block.

These DFT reference block settings decide DFT reference for DFT calculations. Thesettings InternalDFTRef will use fixed DFT reference based on set system frequency.The setting DFTRefGrpn (where n is a number from 1 to 12) will use the SMAI blocknumbered n, within its task, as reference for the adaptive frequency tracking. Thesetting ExternalDFTRef will use reference based on what is connected to inputDFTSPFC.

The setting ConnectionType: Connection type for that specific instance (n) of theSMAI (if it is Ph-N or Ph-Ph). Depending on connection type setting the notconnected Ph-N or Ph-Ph outputs will be calculated.

Negation: Negation means rotation with 1800 of the vectors. If the user wants to negatethe 3ph signal, it is possible to choose to negate only the phase signals Negate3Ph,only the neutral signal NegateN or both Negate3Ph+N.

MinValFreqMeas: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of the voltage in the selected Global Base voltagegroup (n) (for each instance 1<n<6).

1MRK 504 134-UEN A Section 17Basic IED functions

361Application manual

Page 368: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Settings DFTRefExtOut and DFTReference shall be set to defaultvalue InternalDFTRef if no VT inputs are available.

Even if the user sets the AnalogInputType of a SMAI block to“Current”, the MinValFreqMeas is still visible. However, using thecurrent channel values as base for frequency measurement is notrecommendable for a number of reasons, not last among them beingthe low level of currents that one can have in normal operatingconditions.

Example of adaptive frequency tracking

IEC09000029_1_en.vsd

SMAI instance 3 phase groupSMAI_20_1:1 1SMAI_20_2:1 2SMAI_20_3:1 3SMAI_20_4:1 4SMAI_20_5:1 5SMAI_20_6:1 6SMAI_20_7:1 7SMAI_20_8:1 8SMAI_20_9:1 9SMAI_20_10:1 10SMAI_20_11:1 11SMAI_20_12:1 12

Task time group 1

SMAI instance 3 phase groupSMAI_20_1:2 1SMAI_20_2:2 2SMAI_20_3:2 3SMAI_20_4:2 4SMAI_20_5:2 5SMAI_20_6:2 6SMAI_20_7:2 7SMAI_20_8:2 8SMAI_20_9:2 9SMAI_20_10:2 10SMAI_20_11:2 11SMAI_20_12:2 12

Task time group 2

DFTRefGrp7

IEC09000029 V1 EN

Figure 167: SMAI instances as organized in different task time groups and thecorresponding parameter numbers

The example shows a situation with adaptive frequency tracking with one referenceselected for all instances. In practice each instance can be adapted to the needs of theactual application. The adaptive frequency tracking is needed in IEDs that belong tothe protection system of synchronous machines and that are active during run-up andshout-down of the machine. In other application the usual setting of the parameterDFTReference of SMAI is InternalDFTRef.

Section 17 1MRK 504 134-UEN ABasic IED functions

362Application manual

Page 369: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Example 1

SMAI_20_7:1BLOCKDFTSPFCREVROT^GRP1L1^GRP1L2^GRP1L3^GRP1N

SPFCOUTAI3P

AI1AI2AI3AI4AIN

SMAI_20_1-12:2BLOCKDFTSPFCREVROT^GRP1L1^GRP1L2^GRP1L3^GRP1N

SPFCOUTAI3P

AI1AI2AI3AI4AIN

IEC09000028-2-en.vsd

IEC09000028 V2 EN

Figure 168: Configuration for using an instance in task time group 1 as DFTreference

Assume instance SMAI_20_7:1 in task time group 1 has been selected in theconfiguration to control the frequency tracking (For the SMAI_20_x of task timegroup 1). Observe that the selected reference instance (i.e. frequency tracking master)must be a voltage type. Observe that positive sequence voltage is used for thefrequency tracking feature.

For task time group 1 this gives the following settings (see Figure 167 for numbering):

SMAI_20_1:1 DFTRefExtOut = DFTRefGrp7 to route SMAI_20_7:1 reference to theSPFCOUT output, DFTReference = DFTRefGrp7 for SMAI_20_7:1 to useSMAI_20_7:1 as reference (see Figure 168). .

SMAI_20_2:1 - SMAI_20_12:1 DFTReference = DFTRefGrp7 for SMAI_20_2:1 -SMAI_20_12:1 to use SMAI_20_7:1 as reference.

For task time group 2 this gives the following settings:

SMAI_20_2:2: DFTReference = ExternalDFTRef to use DFTSPFC input asreference (SMAI_20_7:1); DFTRefExtOut = ExternalDFTRef (even if the outputSPCFOUT is not wired in AC).

SMAI_20_2:2 - SMAI_20_12:2 DFTReference = ExternalDFTRef to use DFTSPFCinput as reference (SMAI_20_7:1)

17.10 Summation block 3 phase 3PHSUM

17.10.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Summation block 3 phase 3PHSUM - -

1MRK 504 134-UEN A Section 17Basic IED functions

363Application manual

Page 370: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.10.2 Application

Summation block 3 phase function 3PHSUM is used to get the sum of two sets ofthree-phase analog signals (of the same type) for those IED functions that might needit.

17.10.3 Setting guidelines

The summation block receives the three-phase signals from SMAI blocks. Thesummation block has several settings.

GlobalBaseSel: Selects the global base value group used by the function to define(IBase), (UBase) and (SBase).

SummationType: Summation type (Group 1 + Group 2, Group 1 - Group 2, Group 2- Group 1 or –(Group 1 + Group 2)).

DFTReference: The reference DFT block (InternalDFT Ref,DFTRefGrp1 or ExternalDFT ref) .

FreqMeasMinVal: The minimum value of the voltage for which the frequency iscalculated, expressed as percent of UBase (for each instance x).

17.11 Global base values GBASVAL

17.11.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Global base values GBASVAL - -

17.11.2 Application

Global base values function (GBASVAL) is used to provide global values, commonfor all applicable functions within the IED. One set of global values consists of valuesfor current, voltage and apparent power and it is possible to have six different sets.

This is an advantage since all applicable functions in the IED use a single source ofbase values. This facilitates consistency throughout the IED and also facilitates asingle point for updating values when necessary.

Each applicable function in the IED has a parameter, GlobalBaseSel, defining one outof the six sets of GBASVAL functions.

Section 17 1MRK 504 134-UEN ABasic IED functions

364Application manual

Page 371: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.11.3 Setting guidelines

UBase: Phase-to-phase voltage value to be used as a base value for applicablefunctions throughout the IED.

IBase: Phase current value to be used as a base value for applicable functionsthroughout the IED.

SBase: Standard apparent power value to be used as a base value for applicablefunctions throughout the IED, typically SBase=√3·UBase·IBase.

17.12 Authority check ATHCHCK

17.12.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Authority check ATHCHCK - -

17.12.2 Application

To safeguard the interests of our customers, both the IED and the tools that areaccessing the IED are protected, by means of authorization handling. Theauthorization handling of the IED and the PCM600 is implemented at both accesspoints to the IED:

• local, through the local HMI• remote, through the communication ports

The IED users can be created, deleted and edited only with PCM600 IED usermanagement tool.

1MRK 504 134-UEN A Section 17Basic IED functions

365Application manual

Page 372: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

IEC12000202-1-en.vsd

IEC12000202 V1 EN

Figure 169: PCM600 user management tool

17.12.2.1 Authorization handling in the IED

At delivery the default user is the SuperUser. No Log on is required to operate the IEDuntil a user has been created with the IED User Management..

Once a user is created and written to the IED, that user can perform a Log on, using thepassword assigned in the tool. Then the default user will be Guest.

If there is no user created, an attempt to log on will display a message box: “No userdefined!”

If one user leaves the IED without logging off, then after the timeout (set in Mainmenu/Configuration/HMI/Screen/SCREEN:1) elapses, the IED returns to Gueststate, when only reading is possible. By factory default, the display timeout is set to 60minutes.

If one or more users are created with the IED User Management and written to theIED, then, when a user attempts a Log on by pressing the key or when the userattempts to perform an operation that is password protected, the Log on windowopens.

Section 17 1MRK 504 134-UEN ABasic IED functions

366Application manual

Page 373: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The cursor is focused on the User identity field, so upon pressing the key, one canchange the user name, by browsing the list of users, with the “up” and “down” arrows.After choosing the right user name, the user must press the key again. When it

comes to password, upon pressing the key, the following characters will show up:“”. The user must scroll for every letter in the password. After all theletters are introduced (passwords are case sensitive) choose OK and press the keyagain.

At successful Log on, the local HMI shows the new user name in the status bar at thebottom of the LCD. If the Log on is OK, when required to change for example apassword protected setting, the local HMI returns to the actual setting folder. If theLog on has failed, an "Error Access Denied" message opens. If a user enters anincorrect password three times, that user will be blocked for ten minutes before a newattempt to log in can be performed. The user will be blocked from logging in, bothfrom the local HMI and PCM600. However, other users are to log in during thisperiod.

17.13 Authority status ATHSTAT

17.13.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Authority status ATHSTAT - -

17.13.2 Application

Authority status (ATHSTAT) function is an indication function block, which informsabout two events related to the IED and the user authorization:

• the fact that at least one user has tried to log on wrongly into the IED and it wasblocked (the output USRBLKED)

• the fact that at least one user is logged on (the output LOGGEDON)

The two outputs of ATHSTAT function can be used in the configuration for differentindication and alarming reasons, or can be sent to the station control for the samepurpose.

1MRK 504 134-UEN A Section 17Basic IED functions

367Application manual

Page 374: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

17.14 Denial of service

17.14.1 IdentificationFunction description IEC 61850

identificationIEC 60617identification

ANSI/IEEE C37.2device number

Denial of service, frame rate control forfront port

DOSFRNT - -

Function description IEC 61850identification

IEC 60617identification

ANSI/IEEE C37.2device number

Denial of service, frame rate control forLAN1 port

DOSLAN1 - -

17.14.2 Application

The denial of service functions (DOSFRNT,DOSLAN1 and DOSSCKT) aredesigned to limit the CPU load that can be produced by Ethernet network traffic on theIED. The communication facilities must not be allowed to compromise the primaryfunctionality of the device. All inbound network traffic will be quota controlled so thattoo heavy network loads can be controlled. Heavy network load might for instance bethe result of malfunctioning equipment connected to the network.

DOSFRNT, DOSLAN1 and DOSSCKT measures the IED load from communicationand, if necessary, limit it for not jeopardizing the IEDs control and protectionfunctionality due to high CPU load. The function has the following outputs:

• LINKUP indicates the Ethernet link status• WARNING indicates that communication (frame rate) is higher than normal• ALARM indicates that the IED limits communication

17.14.3 Setting guidelines

The function does not have any parameters available in the local HMI or PCM600.

Section 17 1MRK 504 134-UEN ABasic IED functions

368Application manual

Page 375: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 18 Requirements

18.1 Current transformer requirements

The performance of a protection function will depend on the quality of the measuredcurrent signal. Saturation of the current transformer (CT) will cause distortion of thecurrent signal and can result in a failure to operate or cause unwanted operations ofsome functions. Consequently CT saturation can have an influence on both thedependability and the security of the protection. This protection IED has beendesigned to permit heavy CT saturation with maintained correct operation.

18.1.1 Current transformer classification

To guarantee correct operation, the current transformers (CTs) must be able tocorrectly reproduce the current for a minimum time before the CT will begin tosaturate. To fulfill the requirement on a specified time to saturation the CTs mustfulfill the requirements of a minimum secondary e.m.f. that is specified below.

There are several different ways to specify CTs. Conventional magnetic core CTs areusually specified and manufactured according to some international or nationalstandards, which specify different protection classes as well. There are many differentstandards and a lot of classes but fundamentally there are three different types of CTs:

• High remanence type CT• Low remanence type CT• Non remanence type CT

The high remanence type has no limit for the remanent flux. This CT has a magneticcore without any airgaps and a remanent flux might remain almost infinite time. In thistype of transformers the remanence can be up to around 80% of the saturation flux.Typical examples of high remanence type CT are class P, PX, TPX according to IEC,class P, X according to BS (old British Standard) and non gapped class C, K accordingto ANSI/IEEE.

The low remanence type has a specified limit for the remanent flux. This CT is madewith a small air gap to reduce the remanence to a level that does not exceed 10% of thesaturation flux. The small air gap has only very limited influences on the otherproperties of the CT. Class PXR, TPY according to IEC are low remanence type CTs.

The non remanence type CT has practically negligible level of remanent flux. Thistype of CT has relatively big air gaps in order to reduce the remanence to practicallyzero level. In the same time, these air gaps reduce the influence of the DC-componentfrom the primary fault current. The air gaps will also decrease the measuring accuracy

1MRK 504 134-UEN A Section 18Requirements

369Application manual

Page 376: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

in the non-saturated region of operation. Class TPZ according to IEC is a nonremanence type CT.

Different standards and classes specify the saturation e.m.f. in different ways but it ispossible to approximately compare values from different classes. The rated equivalentlimiting secondary e.m.f. Eal according to the IEC 61869–2 standard is used to specifythe CT requirements for the IED. The requirements are also specified according toother standards.

18.1.2 Conditions

The requirements are a result of investigations performed in our network simulator.The current transformer models are representative for current transformers of highremanence and low remanence type. The results may not always be valid for nonremanence type CTs (TPZ).

The performances of the protection functions have been checked in the range fromsymmetrical to fully asymmetrical fault currents. Primary time constants of at least120 ms have been considered at the tests. The current requirements below are thusapplicable both for symmetrical and asymmetrical fault currents.

Depending on the protection function phase-to-earth, phase-to-phase and three-phasefaults have been tested for different relevant fault positions for example, close inforward and reverse faults, zone 1 reach faults, internal and external faults. Thedependability and security of the protection was verified by checking for example,time delays, unwanted operations, directionality, overreach and stability.

The remanence in the current transformer core can cause unwanted operations orminor additional time delays for some protection functions. As unwanted operationsare not acceptable at all maximum remanence has been considered for fault casescritical for the security, for example, faults in reverse direction and external faults.Because of the almost negligible risk of additional time delays and the non-existentrisk of failure to operate the remanence have not been considered for the dependabilitycases. The requirements below are therefore fully valid for all normal applications.

It is difficult to give general recommendations for additional margins for remanenceto avoid the minor risk of an additional time delay. They depend on the performanceand economy requirements. When current transformers of low remanence type (forexample, TPY, PR) are used, normally no additional margin is needed. For currenttransformers of high remanence type (for example, P, PX, TPS, TPX) the smallprobability of fully asymmetrical faults, together with high remanence in the samedirection as the flux generated by the fault, has to be kept in mind at the decision of anadditional margin. Fully asymmetrical fault current will be achieved when the faultoccurs at approximately zero voltage (0°). Investigations have shown that 95% of thefaults in the network will occur when the voltage is between 40° and 90°. In additionfully asymmetrical fault current will not exist in all phases at the same time.

18.1.3 Fault current

Section 18 1MRK 504 134-UEN ARequirements

370Application manual

Page 377: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

The current transformer requirements are based on the maximum fault current forfaults in different positions. Maximum fault current will occur for three-phase faultsor single phase-to-earth faults. The current for a single phase-to-earth fault will exceedthe current for a three-phase fault when the zero sequence impedance in the total faultloop is less than the positive sequence impedance.

When calculating the current transformer requirements, maximum fault current forthe relevant fault position should be used and therefore both fault types have to beconsidered.

18.1.4 Secondary wire resistance and additional load

The voltage at the current transformer secondary terminals directly affects the currenttransformer saturation. This voltage is developed in a loop containing the secondarywires and the burden of all relays in the circuit. For earth faults the loop includes thephase and neutral wire, normally twice the resistance of the single secondary wire. Forthree-phase faults the neutral current is zero and it is just necessary to consider theresistance up to the point where the phase wires are connected to the common neutralwire. The most common practice is to use four wires secondary cables so it normallyis sufficient to consider just a single secondary wire for the three-phase case.

The conclusion is that the loop resistance, twice the resistance of the single secondarywire, must be used in the calculation for phase-to-earth faults and the phase resistance,the resistance of a single secondary wire, may normally be used in the calculation forthree-phase faults.

As the burden can be considerable different for three-phase faults and phase-to-earthfaults it is important to consider both cases. Even in a case where the phase-to-earthfault current is smaller than the three-phase fault current the phase-to-earth fault canbe dimensioning for the CT depending on the higher burden.

In isolated or high impedance earthed systems the phase-to-earth fault is not thedimensioning case and therefore the resistance of the single secondary wire alwayscan be used in the calculation, for this case.

18.1.5 General current transformer requirements

The current transformer ratio is mainly selected based on power system data forexample, maximum load. However, it should be verified that the current to theprotection is higher than the minimum operating value for all faults that are to bedetected with the selected CT ratio. The minimum operating current is different fordifferent functions and normally settable so each function should be checked.

The current error of the current transformer can limit the possibility to use a verysensitive setting of a sensitive residual overcurrent protection. If a very sensitivesetting of this function will be used it is recommended that the current transformershould have an accuracy class which have an current error at rated primary current thatis less than ±1% (for example, 5P). If current transformers with less accuracy are used

1MRK 504 134-UEN A Section 18Requirements

371Application manual

Page 378: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

it is advisable to check the actual unwanted residual current during thecommissioning.

18.1.6 Rated equivalent secondary e.m.f. requirements

With regard to saturation of the current transformer all current transformers of highremanence and low remanence type that fulfill the requirements on the ratedequivalent limiting secondary e.m.f. Eal below can be used. The characteristic of thenon remanence type CT (TPZ) is not well defined as far as the phase angle error isconcerned. If no explicit recommendation is given for a specific function we thereforerecommend contacting ABB to confirm that the non remanence type can be used.

The CT requirements for the different functions below are specified as a ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard.Requirements for CTs specified according to other classes and standards are given atthe end of this section.

18.1.6.1 Transformer differential protection

The current transformers must have a rated equivalent secondary e.m.f. Eal that islarger than the maximum of the required secondary e.m.f. Ealreq below:

sn Ral alreq nt CT L 2

pn r

I SE E 30 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1412 V1 EN (Equation 125)

sn Ral alreq tf CT L 2

pn r

I SE E 2 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1413 V1 EN (Equation 126)

where:

Int The rated primary current of the power transformer (A)

Itf Maximum primary fundamental frequency current that passes two main CTs andthe power transformer (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary wire and additional load (W). The loop resistancecontaining the phase and neutral wires must be used for faults in solidly earthedsystems. The resistance of a single secondary wire should be used for faults in highimpedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 Aand Sr=0.250 VA/channel for Ir=5 A

Section 18 1MRK 504 134-UEN ARequirements

372Application manual

Page 379: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

In substations with breaker-and-a-half or double-busbar double-breaker arrangement,the fault current may pass two main CTs for the transformer differential protectionwithout passing the power transformer. In such cases and if both main CTs have equalratios and magnetization characteristics the CTs must satisfy equation 125 andequation 127.

sn Ral alreq f CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1414 V1 EN (Equation 127)

where:

If Maximum primary fundamental frequency current that passes two main CTs without passingthe power transformer (A)

18.1.6.2 1 Ph high impedance differential protection

The CTs connected to the IED must have a rated equivalent secondary e.m.f. Eal thatis larger than or equal to the required equivalent secondary e.m.f. Ealreq below:

snal alreq s tmax CT L

pn

IE E 2 U 2 I (R R )

I³ = × = × × × +

where:

Us Set operate value to the voltage relay (V)

Ikmax Maximum primary fundamental frequency fault current for through fault current for externalfaults (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

RCT The secondary resistance of the CT (Ω)

RL The resistance of the secondary cable from the CT up to a common junction point (Ω). The loopresistance containing the phase and neutral wires, must be used for faults in solidly earthedsystems and the resistance of a single-phase wire should be used for faults in high impedanceearthed systems.

All CTs to the same protection should have identical turn ratios. Consequentlyauxiliary CTs cannot normally be used. The IED must be provided with separatecores.

1MRK 504 134-UEN A Section 18Requirements

373Application manual

Page 380: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

18.1.6.3 Breaker failure protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equalto the required secondary e.m.f. Ealreq below:

sn Ral alreq op CT L 2

pn r

I SE E 5 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1380 V1 EN (Equation 129)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistance containingthe phase and neutral wires, must be used for faults in solidly earthed systems. The resistanceof a single secondary wire should be used for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A and SR=0.250VA/channel for Ir=5 A

18.1.6.4 Non-directional instantaneous and definitive time, phase and residualovercurrent protection

The CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equalto the required secondary e.m.f. Ealreq below:

sn Ral alreq op CT L 2

pn r

I SE E 1,5 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1381 V1 EN (Equation 130)

where:

Iop The primary operate value (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistance containingthe phase and neutral wires, must be used for faults in solidly earthed systems. The resistanceof a single secondary wire should be used for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 A and SR=0.250VA/channel for Ir=5 A

Section 18 1MRK 504 134-UEN ARequirements

374Application manual

Page 381: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

18.1.6.5 Non-directional inverse time delayed phase and residual overcurrentprotection

The requirement according to Equation 131 and Equation 132 does not need to befulfilled if the high set instantaneous or definitive time stage is used. In this caseEquation 130 is the only necessary requirement.

If the inverse time delayed function is the only used overcurrent protection functionthe CTs must have a rated equivalent secondary e.m.f. Eal that is larger than or equalto the required secondary e.m.f. Ealreq below:

sn Ral alreq op CT L 2

pn r

I SE E 20 I R RI I

æ ö³ = × × × + +ç ÷

è øEQUATION1076 V1 EN (Equation 131)

where

Iop The primary current set value of the inverse time function (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistancecontaining the phase and neutral wires, must be used for faults in solidly earthedsystems. The resistance of a single secondary wire should be used for faults in highimpedance earthed systems.

SR The burden of an IED current input channel (VA). SR=0.010 VA/channel for Ir=1 Aand SR=0.250 VA/channel for Ir=5 A

Independent of the value of Iop the maximum required Eal is specified according to thefollowing:

sn Ral alreq max k max CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1077 V1 EN (Equation 132)

where

Ikmax Maximum primary fundamental frequency current for close-in faults (A)

1MRK 504 134-UEN A Section 18Requirements

375Application manual

Page 382: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

18.1.6.6 Directional phase and residual overcurrent protection

If the directional overcurrent function is used the CTs must have a rated equivalentsecondary e.m.f. Eal that is larger than or equal to the required equivalent secondarye.m.f. Ealreq below:

sn Ral alreq k max CT L 2

pn r

I SE E I R RI I

æ ö³ = × × + +ç ÷

è øEQUATION1078 V1 EN (Equation 133)

where:

Ikmax Maximum primary fundamental frequency current for close-in forward and reverse faults (A)

Ipn The rated primary CT current (A)

Isn The rated secondary CT current (A)

Ir The rated current of the protection IED (A)

RCT The secondary resistance of the CT (W)

RL The resistance of the secondary cable and additional load (W). The loop resistance containingthe phase and neutral wires, must be used for faults in solidly earthed systems. The resistanceof a single secondary wire should be used for faults in high impedance earthed systems.

SR The burden of an IED current input channel (VA). Sr=0.010 VA/channel for Ir=1 A and Sr=0.250VA/channel for Ir=5 A

18.1.7 Current transformer requirements for CTs according to otherstandards

All kinds of conventional magnetic core CTs are possible to use with the IEDs if theyfulfill the requirements corresponding to the above specified expressed as the ratedequivalent limiting secondary e.m.f. Eal according to the IEC 61869-2 standard. Fromdifferent standards and available data for relaying applications it is possible toapproximately calculate a secondary e.m.f. of the CT comparable with Eal. Bycomparing this with the required rated equivalent limiting secondary e.m.f. Ealreq it ispossible to judge if the CT fulfills the requirements. The requirements according tosome other standards are specified below.

18.1.7.1 Current transformers according to IEC 61869-2, class P, PR

A CT according to IEC 61869-2 is specified by the secondary limiting e.m.f. Ealf. Thevalue of the Ealf is approximately equal to the corresponding Eal. Therefore, the CTsaccording to class P and PR must have a secondary limiting e.m.f. Ealf that fulfills thefollowing:

Section 18 1MRK 504 134-UEN ARequirements

376Application manual

Page 383: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

2 max max alreqE E>

EQUATION1383 V2 EN (Equation 134)

18.1.7.2 Current transformers according to IEC 61869-2, class PX, PXR (andold IEC 60044-6, class TPS and old British Standard, class X)

CTs according to these classes are specified approximately in the same way by a ratedknee point e.m.f. Eknee (Ek for class PX and PXR, EkneeBS for class X and the limitingsecondary voltage Ual for TPS). The value of the Eknee is lower than the correspondingEal according to IEC 61869-2. It is not possible to give a general relation between theEknee and the Eal but normally the Eknee is approximately 80 % of the Eal. Therefore,the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f.Eknee that fulfills the following:

Eknee » Ek » EkneeBS » Ual > 0.8 · (maximum of Ealreq)EQUATION2100 V1 EN (Equation 135)

18.1.7.3 Current transformers according to ANSI/IEEE

Current transformers according to ANSI/IEEE are partly specified in different ways.A rated secondary terminal voltage UANSI is specified for a CT of class C. UANSI is thesecondary terminal voltage the CT will deliver to a standard burden at 20 times ratedsecondary current without exceeding 10 % ratio correction. There are a number ofstandardized UANSI values for example, UANSI is 400 V for a C400 CT. Acorresponding rated equivalent limiting secondary e.m.f. EalANSI can be estimated asfollows:

Ea lANSI 20 Isn RCT UA NSI+× × 20 Isn RC T× × 20 Isn ZbANSI× ×+= =

EQUATION971 V1 EN (Equation 136)

where:

ZbANSI The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific Cclass (W)

UANSI The secondary terminal voltage for the specific C class (V)

The CTs according to class C must have a calculated rated equivalent limitingsecondary e.m.f. EalANSI that fulfils the following:

1MRK 504 134-UEN A Section 18Requirements

377Application manual

Page 384: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

alANSI alreqE max imum of E>

EQUATION1384 V1 EN (Equation 137)

A CT according to ANSI/IEEE is also specified by the knee point voltage UkneeANSIthat is graphically defined from an excitation curve. The knee point voltage UkneeANSInormally has a lower value than the knee-point e.m.f. according to IEC and BS.UkneeANSI can approximately be estimated to 75 % of the corresponding Eal accordingto IEC 61869-2. Therefore, the CTs according to ANSI/IEEE must have a knee pointvoltage UkneeANSI that fulfills the following:

EkneeANSI > 0.75 · (maximum of Ealreq)EQUATION2101 V1 EN (Equation 138)

18.2 Voltage transformer requirements

The performance of a protection function will depend on the quality of the measuredinput signal. Transients caused by capacitive voltage transformers (CVTs) can affectsome protection functions.

Magnetic or capacitive voltage transformers can be used.

The capacitive voltage transformers (CVTs) should fulfill the requirements accordingto the IEC 61869-5 standard regarding ferro-resonance and transients. The ferro-resonance requirements of the CVTs are specified in chapter 6.502 of the standard.

The transient responses for three different standard transient response classes, T1, T2and T3 are specified in chapter 6.503 of the standard. CVTs according to all classescan be used.

The protection IED has effective filters for these transients, which gives secure andcorrect operation with CVTs.

18.3 SNTP server requirements

18.3.1 SNTP server requirements

The SNTP server to be used is connected to the local network, that is not more than 4-5switches or routers away from the IED. The SNTP server is dedicated for its task, orat least equipped with a real-time operating system, that is not a PC with SNTP serversoftware. The SNTP server should be stable, that is, either synchronized from a stablesource like GPS, or local without synchronization. Using a local SNTP server withoutsynchronization as primary or secondary server in a redundant configuration is notrecommended.

Section 18 1MRK 504 134-UEN ARequirements

378Application manual

Page 385: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Section 19 Glossary

AC Alternating current

ACC Actual channel

ACT Application configuration tool within PCM600

A/D converter Analog-to-digital converter

ADBS Amplitude deadband supervision

AI Analog input

ANSI American National Standards Institute

AR Autoreclosing

ASCT Auxiliary summation current transformer

ASD Adaptive signal detection

ASDU Application service data unit

AWG American Wire Gauge standard

BBP Busbar protection

BFOC/2,5 Bayonet fibre optic connector

BFP Breaker failure protection

BI Binary input

BOS Binary outputs status

BR External bistable relay

BS British Standards

CB Circuit breaker

CCITT Consultative Committee for International Telegraph andTelephony. A United Nations-sponsored standards bodywithin the International Telecommunications Union.

CCVT Capacitive Coupled Voltage Transformer

Class C Protection Current Transformer class as per IEEE/ ANSI

CMPPS Combined megapulses per second

CMT Communication Management tool in PCM600

CO cycle Close-open cycle

COMTRADE Standard format according to IEC 60255-24

COT Cause of transmission

CPU Central processing unit

1MRK 504 134-UEN A Section 19Glossary

379Application manual

Page 386: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

CR Carrier receive

CRC Cyclic redundancy check

CROB Control relay output block

CS Carrier send

CT Current transformer

CU Communication unit

CVT Capacitive voltage transformer

DAR Delayed autoreclosing

DARPA Defense Advanced Research Projects Agency (The USdeveloper of the TCP/IP protocol etc.)

DBDL Dead bus dead line

DBLL Dead bus live line

DC Direct current

DFC Data flow control

DFT Discrete Fourier transform

DHCP Dynamic Host Configuration Protocol

DI Digital input

DLLB Dead line live bus

DNP Distributed Network Protocol as per IEEE Std 1815-2012

DR Disturbance recorder

DRAM Dynamic random access memory

DRH Disturbance report handler

DTT Direct transfer trip scheme

EHV network Extra high voltage network

EIA Electronic Industries Association

EMC Electromagnetic compatibility

EMF Electromotive force

EMI Electromagnetic interference

EnFP End fault protection

EPA Enhanced performance architecture

ESD Electrostatic discharge

F-SMA Type of optical fibre connector

FAN Fault number

FCB Flow control bit; Frame count bit

Section 19 1MRK 504 134-UEN AGlossary

380Application manual

Page 387: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

FOX 20 Modular 20 channel telecommunication system for speech,data and protection signals

FOX 512/515 Access multiplexer

FOX 6Plus Compact time-division multiplexer for the transmission ofup to seven duplex channels of digital data over opticalfibers

FTP File Transfer Protocal

FUN Function type

GCM Communication interface module with carrier of GPSreceiver module

GDE Graphical display editor within PCM600

GI General interrogation command

GIS Gas-insulated switchgear

GOOSE Generic object-oriented substation event

GPS Global positioning system

GSAL Generic security application

GSE Generic substation event

HDLC protocol High-level data link control, protocol based on the HDLCstandard

HFBR connector type Plastic fiber connector

HMI Human-machine interface

HSAR High speed autoreclosing

HV High-voltage

HVDC High-voltage direct current

IDBS Integrating deadband supervision

IEC International Electrical Committee

IEC 61869-2 IEC Standard, Instrument transformers

IEC 60870-5-103 Communication standard for protective equipment. A serialmaster/slave protocol for point-to-point communication

IEC 61850 Substation automation communication standard

IEC 61850–8–1 Communication protocol standard

IEEE Institute of Electrical and Electronics Engineers

IEEE 802.12 A network technology standard that provides 100 Mbits/s ontwisted-pair or optical fiber cable

IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules.References the CMC (IEEE P1386, also known as CommonMezzanine Card) standard for the mechanics and the PCI

1MRK 504 134-UEN A Section 19Glossary

381Application manual

Page 388: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

specifications from the PCI SIG (Special Interest Group) forthe electrical EMF (Electromotive force).

IEEE 1686 Standard for Substation Intelligent Electronic Devices(IEDs) Cyber Security Capabilities

IED Intelligent electronic device

I-GIS Intelligent gas-insulated switchgear

Instance When several occurrences of the same function are availablein the IED, they are referred to as instances of that function.One instance of a function is identical to another of the samekind but has a different number in the IED user interfaces.The word "instance" is sometimes defined as an item ofinformation that is representative of a type. In the same wayan instance of a function in the IED is representative of atype of function.

IP 1. Internet protocol. The network layer for the TCP/IPprotocol suite widely used on Ethernet networks. IP is aconnectionless, best-effort packet-switching protocol. Itprovides packet routing, fragmentation and reassemblythrough the data link layer.2. Ingression protection, according to IEC standard

IP 20 Ingression protection, according to IEC standard, level 20

IP 40 Ingression protection, according to IEC standard, level 40

IP 54 Ingression protection, according to IEC standard, level 54

IRF Internal failure signal

IRIG-B: InterRange Instrumentation Group Time code format B,standard 200

ITU International Telecommunications Union

LAN Local area network

LCD Liquid crystal display

LDD Local detection device

LED Light-emitting diode

LNT LON network tool

MCB Miniature circuit breaker

MVAL Value of measurement

NCC National Control Centre

NOF Number of grid faults

NUM Numerical module

OCO cycle Open-close-open cycle

OCP Overcurrent protection

Section 19 1MRK 504 134-UEN AGlossary

382Application manual

Page 389: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

OLTC On-load tap changer

OTEV Disturbance data recording initiated by other event thanstart/pick-up

OV Over-voltage

Overreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is overreachingwhen the impedance presented to it is smaller than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay “sees” the fault but perhaps itshould not have seen it.

PCI Peripheral component interconnect, a local data bus

PCM600 Protection and control IED manager

PC-MIP Mezzanine card standard

POR Permissive overreach

POTT Permissive overreach transfer trip

Process bus Bus or LAN used at the process level, that is, in nearproximity to the measured and/or controlled components

PSM Power supply module

PST Parameter setting tool within PCM600

PT ratio Potential transformer or voltage transformer ratio

PUTT Permissive underreach transfer trip

RCA Relay characteristic angle

RISC Reduced instruction set computer

RMS value Root mean square value

RS422 A balanced serial interface for the transmission of digitaldata in point-to-point connections

RS485 Serial link according to EIA standard RS485

RTC Real-time clock

RTU Remote terminal unit

SA Substation Automation

SBO Select-before-operate

SC Switch or push button to close

SCL Short circuit location

SCS Station control system

SCADA Supervision, control and data acquisition

SCT System configuration tool according to standard IEC 61850

SDU Service data unit

1MRK 504 134-UEN A Section 19Glossary

383Application manual

Page 390: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

SMA connector Subminiature version A, A threaded connector withconstant impedance.

SMT Signal matrix tool within PCM600

SMS Station monitoring system

SNTP Simple network time protocol – is used to synchronizecomputer clocks on local area networks. This reduces therequirement to have accurate hardware clocks in everyembedded system in a network. Each embedded node caninstead synchronize with a remote clock, providing therequired accuracy.

SOF Status of fault

SPA Strömberg protection acquisition, a serial master/slaveprotocol for point-to-point communication

SRY Switch for CB ready condition

ST Switch or push button to trip

Starpoint Neutral point of transformer or generator

SVC Static VAr compensation

TC Trip coil

TCS Trip circuit supervision

TCP Transmission control protocol. The most common transportlayer protocol used on Ethernet and the Internet.

TCP/IP Transmission control protocol over Internet Protocol. Thede facto standard Ethernet protocols incorporated into4.2BSD Unix. TCP/IP was developed by DARPA forInternet working and encompasses both network layer andtransport layer protocols. While TCP and IP specify twoprotocols at specific protocol layers, TCP/IP is often used torefer to the entire US Department of Defense protocol suitebased upon these, including Telnet, FTP, UDP and RDP.

TEF Time delayed earth-fault protection function

TLS Transport Layer Security

TM Transmit (disturbance data)

TNC connector Threaded Neill-Concelman, a threaded constant impedanceversion of a BNC connector

TP Trip (recorded fault)

TPZ, TPY, TPX, TPS Current transformer class according to IEC

TRM Transformer Module. This module transforms currents andvoltages taken from the process into levels suitable forfurther signal processing.

TYP Type identification

Section 19 1MRK 504 134-UEN AGlossary

384Application manual

Page 391: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

UMT User management tool

Underreach A term used to describe how the relay behaves during a faultcondition. For example, a distance relay is underreachingwhen the impedance presented to it is greater than theapparent impedance to the fault applied to the balance point,that is, the set reach. The relay does not “see” the fault butperhaps it should have seen it. See also Overreach.

UTC Coordinated Universal Time. A coordinated time scale,maintained by the Bureau International des Poids et Mesures(BIPM), which forms the basis of a coordinateddissemination of standard frequencies and time signals.UTC is derived from International Atomic Time (TAI) bythe addition of a whole number of "leap seconds" tosynchronize it with Universal Time 1 (UT1), thus allowingfor the eccentricity of the Earth's orbit, the rotational axis tilt(23.5 degrees), but still showing the Earth's irregularrotation, on which UT1 is based. The Coordinated UniversalTime is expressed using a 24-hour clock, and uses theGregorian calendar. It is used for aeroplane and shipnavigation, where it is also sometimes known by the militaryname, "Zulu time." "Zulu" in the phonetic alphabet standsfor "Z", which stands for longitude zero.

UV Undervoltage

WEI Weak end infeed logic

VT Voltage transformer

3IO Three times zero-sequence current. Often referred to as theresidual or the earth-fault current

3UO Three times the zero sequence voltage. Often referred to asthe residual voltage or the neutral point voltage

1MRK 504 134-UEN A Section 19Glossary

385Application manual

Page 392: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

386

Page 393: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

387

Page 394: Transformer protection RET650 Application manual · Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not

Contact us

For more information please contact:

ABB ABGrid Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00

www.abb.com/protection-control

Note:We reserve the right to make technical changes or modifythe contents of this document without prior notice. ABB ABdoes not accept any responsibility whatsoever for potentialerrors or possible lack of information in this document.We reserve all rights in this document and in the subjectmatter and illustrations contained herein. Any reproduction,disclosure to third parties or utilization of its contents – inwhole or in part – is forbidden without prior written consent ofABB AB.

© Copyright 2013 ABB.

All rights reserved.

Scan this QR code to visit our website

1MR

K 5

04 1

34-U

EN