TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division Electricity Generating Authority of Thailand

Transcript of TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION...

Page 1: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

TRANSFORMER PROTECTIONPHILOSOPHY, SETTING & PERFORMANCE

ANUCHIT SOMJUNTR

Control and Protection System Division

Electricity Generating Authority of Thailand

Page 2: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

TYPE OF TRANSFORMER IN EGAT

TRANSMISSION SYSTEM

1. LOADING TRANSFORMER

(115kV/22kV, 33kV)

DY1, YYd1

2. TIE TRANSFORMER

(500kV/230kV, 230kV/115kV, 69kV)

YYd1

Page 3: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

Fault Type Protection Used

Primary winding Phase-phase fault Differential; Overcurrent

Primary winding Phase-earth fault Differential; Overcurrent

Secondary winding Phase-phase fault Differential

Secondary winding Phase-earth fault Differential; Restricted Earth Fault

Interturn Fault Differential; Buchholz

Core Fault Differential; Buchholz

Tank Fault Differential; Buchholz; Tank-Earth

Overfluxing Overfluxing

Overheating Thermal

TRANSFORMER FAULT / PROTECTION

Page 4: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

87K

51T

51G

51

87K = Transformer Differential relay

51T = High Side Phase OC relay

51 = Low Side Phase OC relay

51G = Low Side Ground OC relay

PROTECTION FOR LOADING TRANSFORMER

Page 5: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

87B = Bus Differential relay

87K51G

51

87K = Transformer Differential relay

51T = High Side Phase OC relay

51 = Low Side Phase OC relay 51G = Low Side Ground OC relay

51GB1

51GB2

51GB1,2 = Ground Backup OC relay

51T

51TG

51TG = High Side Ground OC relay

PROTECTION FOR 230/115 KV TIE TRANSFORMER

Page 6: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

87B = Bus Differential relay 87K-P = Pri. Transformer Diff. relay

51T = High Side Phase OC relay

51 = Low Side Phase OC relay

51G = Low Side Ground OC relay 51GB1,2 = Ground Backup OC relay

51G

5151GB1

51GB2

51TG = High Side Ground OC relay

87K-S

87K-P

87K-S = Sec. Transformer Diff. relay

24T

24T = Overfluxing Relay

PROTECTION FOR 500/230 KV TIE TRANSFORMER

51T

51TG

Page 7: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Considerations - Phase correction

- Filtering of zero sequence currents

- Ratio correction

- The effect of magnetizing inrush during initial energization

RELAY SETTING CRITERIA

Page 8: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• CT. Ratio

- Main CT ratio = 150% FOA rating of transformer

- 20 times of primary current of the selected CT ratio must

higher than maximum busbar fault current

- Secondary current must lower than relay rating current

RELAY SETTING CRITERIA

Page 9: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Check CT performance

- CT must not be saturated when a maximum external fault

occurs

RELAY SETTING CRITERIA

Vk = IF max x (RCT + 2 RL+RT) /N

Where :

Vk = Required CT Knee point voltage (volts)

IF max = Maximum value of fault current (A)

RCT = CT secondary winding resistance (Ohms)

RL = Single lead resistance from CT to relay (Ohms)

RT = Effective impedance of interposing CT

N = CT turn ratio

Page 10: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction Without interposing CT

- Use star connected CT on delta windings of the transformer

- Use appropriated delta connected CT on star windings of the

transformer to ensure that the transformer primary and

secondary currents, as measured by the relay, are in phase

RELAY SETTING CRITERIA

Page 11: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

Without interposing CT

RELAY SETTING CRITERIA

D Y

87K

Y D

Page 12: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

Without interposing CT

RELAY SETTING CRITERIA

Y D

87K

D Y

Page 13: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

Without interposing CT

RELAY SETTING CRITERIA

Y Y

87K

D D

D

Page 14: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction With interposing CT

- Use star connected CT on all windings of the transformer

- Compensate for the winding phase shift by interposing CT

- Use star/star connected interposing CT on delta windings of the transformer

- Use star/delta connected interposing CT on star windings of the transformer

RELAY SETTING CRITERIA

Page 15: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

With interposing CT

RELAY SETTING CRITERIA

Y D

87K

Y Y

Y D Y Y

Page 16: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

With interposing CT

RELAY SETTING CRITERIA

D Y

87K

Y Y

Y Y D Y

Page 17: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

With interposing CT

RELAY SETTING CRITERIA

Y Y

87K

Y Y

Y D D YD

Page 18: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction Numerical and Digital relay

- Use star connected CT on all windings of the transformer

- Compensate for the winding phase shift by software

RELAY SETTING CRITERIA

Page 19: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Phase correction

Numerical and Digital relay

RELAY SETTING CRITERIA

D YY Y

Numerical Transformer Differential relay

Page 20: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Ratio correction

- Calculate interposing CT ratio at normal tap of transformer

- Percent mismatch of CT must be lower than 5 %

- Percent mismatch of CT can be calculated from

Percent mismatch =

RELAY SETTING CRITERIA

[ I to relay (HS) – I to relay (LS) ] x 100 %[ I to relay (HS) + I to relay (LS) ] / 2

Page 21: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• Differential current setting ( I diff > )

- I diff > must be greater than

CT mismatch + CT error + % Tap change

• Percent slope setting

- Set as the relay manufacturer’s recommendation

- Consider that relay will not operate when a maximum external fault occurs

- Generally lower slope = 20-30% , upper slope = 70-80%

RELAY SETTING CRITERIA

Page 22: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

• High-Set Differential current setting ( I diff >> )

- I diff >> must be greater than maximum inrush current

(about 15 time transformer rating current)

• Harmonic stabilization

- Inrush restraint ratio (2nd harmonic) = 12% I2fN/IfN

- Activate cross-block function

RELAY SETTING CRITERIA

Page 23: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

1. Transformer Differential Relay

RELAY SETTING CRITERIA

0 1 2 3 4 5 6

2

3

1

Operate

Restrain

Effective bias (*In)

Diff

eren

tial c

urre

nt (*

Id)

Setting range

(0.1-0.5Id)

Tripping characteristic of Transformer differential relay

Page 24: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• CT. Ratio

- Main CT ratio = 150% FOA rating of transformer

• Minimum Pick up Current

- Phase overcurrent relay = 150% FOA rating of transformer

- Ground overcurrent relay = 30% FOA rating of transformer

RELAY SETTING CRITERIA

Page 25: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• Time Characteristic Curve

- 115/22KV Loading transformer = Normal inverse

- 230/115kV Tie transformer = Normal inverse

- 500/230kV Tie transformer = Very inverse

• Operating Time

- Co-ordination time interval between low side and high side

overcurrent = 0.5 sec at maximum fault

RELAY SETTING CRITERIA

Page 26: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• Operating Time

115/22kv Loading and 230/115kV Tie Transformer

- High side phase overcurrent (51T) = 2.0 sec at Maximum 3 Ph.

Fault Current Contributed to Low Side Busbar

- High side ground overcurrent* (51TG) = 2.0 sec at Maximum

SLG Fault Current Contributed to Low Side Busbar

Note * High side ground overcurrent for Tie Transformer only

RELAY SETTING CRITERIA

Page 27: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• Operating Time

115/22kv Loading and 230/115kV Tie Transformer

- Low side phase overcurrent (51) = 1.5 sec at Maximum 3 Ph.

Fault Current Contributed to Low Side Busbar

- Low side ground overcurrent (51G) = 1.5 sec at Maximum

SLG Fault Current Contributed to Low Side Busbar

RELAY SETTING CRITERIA

Page 28: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• Operating Time

500/230kV Tie Transformer

- High side phase overcurrent (51T) = 1.5 sec at Maximum 3 Ph.

Fault Current Contributed to Low Side Busbar

- High side ground overcurrent (51TG) = 1.5 sec at Maximum

SLG Fault Current Contributed to Low Side Busbar

RELAY SETTING CRITERIA

Page 29: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

2. Phase and Ground Overcurrent Relay

• Operating Time

500/230kV Tie Transformer

- Low side phase overcurrent (51) = 1.0 sec at Maximum 3 Ph.

Fault Current Contributed to Low Side Busbar

- Low side ground overcurrent (51G) = 1.0 sec at Maximum

SLG Fault Current Contributed to Low Side Busbar

• Instantaneous Unit

- Block

RELAY SETTING CRITERIA

Page 30: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS 2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

1

1. KT2A_51T MCGG-SI CTR=400/5 Tap=4.75A TD=0.400 No inst.

2

2. KT2A_51 MCGG-SI CTR=1800/5 Tap=5.5A TD=0.300 No inst.

3

3. KT2A_51G MCGG-SI CTR=1800/5 Tap=1.1A TD=0.700 No inst.

3PH FAULT

SLG FAULT

51T51G

51115 / 22KV

KT2A

Overcurrent Relay Time Curve

Page 31: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

3. Overcurrent Ground Back-up Relay (Tertiary winding)

• CT. Ratio

- CT ratio = Use maximum ratio in tertiary winding

- Connect all 3 phases in parallel to relay

RELAY SETTING CRITERIA

51GB1

51GB2

IOT

iOT 2iOT 3iOT

Page 32: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

3. Overcurrent Ground Back-up Relay (Tertiary winding)

• Minimum Pick up Current

- Overcurrent Ground Back-up Relay No.1 = 100% OA rating of

tertiary winding

- Overcurrent Ground Back-up Relay No.2 = 200-300% OA

rating of tertiary winding

Note – The value will be multiply by 3 because of the three CT in

tertiary winding connected in parallel

RELAY SETTING CRITERIA

Page 33: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

3. Overcurrent Ground Back-up Relay (Tertiary winding)

• Time Characteristic Curve

- Overcurrent Ground Back-up Relay No.1 = Long time inverse

- Overcurrent Ground Back-up Relay No.2 = Very inverse

RELAY SETTING CRITERIA

Page 34: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

3. Overcurrent Ground Back-up Relay (Tertiary winding)

• Operating Time

- Time characteristic curves of both relay must be lower than

transformer thermal damage curve

- Operating Time = 1.5 sec. at maximum circulating current

(3IOT) in tertiary winding when SLG fault occurs at low voltage

side of the transformer

• Instantaneous Unit

- Block

RELAY SETTING CRITERIA

Page 35: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

3. Overcurrent Ground Back-up Relay (Tertiary winding)

RELAY SETTING CRITERIA

Overcurrent Ground Back-up Relay Time Characteristic Curve

51GB1LI

51GB2VI

Damage Curve2

4

6

8

3IOT Current (A)

Time (sec.)

Page 36: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

4. Overfluxing Relay for 500/230kV Tie Transformer

- Set time characteristic curves of overfluxing relay so that

relays always operate before transformers reach the overfluxing

limit

- Time margin = 1-2 sec.

RELAY SETTING CRITERIA

Page 37: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

4. Overfluxing Relay for 500/230kV Tie Transformer

RELAY SETTING CRITERIA

10

40

50

70

Overfluxing in PU.

Time (sec.)

20

30

60

1.2 1.25 1.3 1.35 1.4

Transformer Overfluxing limit Curve

Overfluxing Relay

Time Curve

Overfluxing Relay Time Curve

Page 38: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

PERFORMANCE OF DIFFERENTIAL RELAY

Correct / Unnecessary Operation Of Transformer Differential Relay

YEAR CORRECT OPERATION UNNECESSARY OPERATION

Tie Loading Total Tie Loading Total

2001 4 43 47 0 0 0

2002 4 44 48 0 1 1

2003 6 37 43 0 0 0

2004 6 36 42 1 2 3

2005 6 34 40 2 1 3

Total Number of Transformer = 588 Units (Tie = 36% , Loading = 64%)

Old relays (age > 15 years)New relay maloperation

Page 39: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

PERFORMANCE OF DIFFERENTIAL RELAY

230/69kV Transformer KT6A at NB sub. Date 19/06/2004

B-C fault (Short turn) Clearing time = 96 ms. Relay type MBCH (GEC)

Page 40: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

PERFORMANCE OF DIFFERENTIAL RELAY

230/115kV Transformer KT3A at SR2 sub. Date 14/09/2005

C-G fault (Low side bushing explode) Clearing time = 90 ms. Relay type HU (ABB)

Page 41: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

PERFORMANCE OF DIFFERENTIAL RELAY

230/115kV Transformer KT2A at LPR sub. Date 16/09/2005

A-B-C-G fault (Flash over at LA 22kV) Clearing time = 108 ms. Relay type D202 (BBC)

Page 42: TRANSFORMER PROTECTION - EGAT Services protection for power... · TRANSFORMER PROTECTION PHILOSOPHY, SETTING & PERFORMANCE ANUCHIT SOMJUNTR Control and Protection System Division

PERFORMANCE OF DIFFERENTIAL RELAY

230/115kV Transformer KT4A at HY2 sub. Date 10/11/2005

B-G fault (High side bushing flashover) Clearing time = 64 ms. Relay type MBCH (GEC)