Transformer Oil Test Report

2
® TRANSFORMER SERVICE, INC. ACCEPTABLE IFT ABOVE THIS LINE ACCEPTABLE DIELECTRIC ABOVE THIS LINE ACCEPTABLE NEUT. NO. BELOW THIS LINE ACCEPTABLE MOISTURE BELOW THIS LINE 16 26 36 46 .13 .09 .05 .01 50 40 30 20 10 50 40 30 20 10 IFT (dynes/cm) Neut. No. (mg KOH/g oil) Dielectric (kV) Moisture (ppm) Electrical - Mechanical - Insulating Fluids - PCB Handling - Cleaning & Painting - Engineering Transformer Service, Inc., 74 Regional Dr., PO Box 1077, Concord, NH 03302-1077 (603) 224-4006 FAX (603) 228-2430 DATE OF SAMPLE DATE OF SAMPLE INTERFACIAL TENSION / NEUTRALIZATION NUMBER DIELECTRIC STRENGTH / MOISTURE CONTENT ELECTRICAL EQUIPMENT INSPECTION SERVICE CUSTOMER: E.G. SAMPLE CORPORATION CITY: ANYTOWN STATE: US NAMEPLATE DATA FIELD INSPECTION DATA LIQUID TEST DATA 02/04 02/04 02/03 02/03 02/02 02/02 04/01 04/01 02/01 02/01 PCB CONTENT (Analysis By GC in PPM) METALS-IN-OIL (Analysis by ICP in PPM) RECOMMENDATIONS AND NOTES

Transcript of Transformer Oil Test Report

Page 1: Transformer Oil Test Report

®TRANSFORMER SERVICE, INC.

ACCEPTABLE IFT ABOVE THIS LINE

ACCEPTABLE DIELECTRIC ABOVE THIS LINE

ACCEPTABLE NEUT. NO. BELOW THIS LINE

ACCEPTABLE MOISTURE BELOW THIS LINE

16

26

36

46 .13

.09

.05

.01

50

40

30

20

10

50

40

30

20

10

IFT

(dynes/c

m)

Neut.

No.

(mg

KO

H/g

oil)

Die

lectr

ic(k

V)

Mois

ture

(ppm

)

Electrical - Mechanical - Insulating Fluids - PCB Handling - Cleaning & Painting - Engineering

Transformer Service, Inc., 74 Regional Dr., PO Box 1077, Concord, NH 03302-1077 (603) 224-4006 FAX (603) 228-2430

DATE OF SAMPLE DATE OF SAMPLE

INTERFACIAL TENSION / NEUTRALIZATION NUMBER DIELECTRIC STRENGTH / MOISTURE CONTENT

CUSTOMER ID # : 02688.00 REF #: 001CUSTOMER'S UNIT #: B1137A2

DATE PRINTED : 03/24/04 UNIT LOCATION: SUB W

ELECTRICAL EQUIPMENT INSPECTION SERVICE

CUSTOMER: E.G. SAMPLE CORPORATION CITY: ANYTOWN STATE: US

NAMEPLATE DATA

Make/Rewind : G.E. KVA : 2,500 Phase/Cycle : 3/60 Sample Energ: YESSerial Number : N2844583TEUA High Voltage: 34,500 Fluid Gallons: 500 Filter Energ: NOEquipment Type: TRANSFORMER Low Voltage : 480Y/277 Fluid Type : OIL Hose (1 Way): 100

FIELD INSPECTION DATA

Ambient Eqpt Fluid Temp C Liquid Bushing Paint QualityDate Inspector Temp F Hum % Press Oper High Level Cond Cond Leaks (severity code) Factor

02/05/01 T. SMITH 32 55 -1.0 15 50 S.LOW FAIR FAIR LV BUSHINGS (3) U04/16/01 M. KANE 71 74 +1.0 28 40 GOOD GOOD GOOD NONE S02/09/02 T. SMITH 8 43 +0.5 32 55 GOOD GOOD GOOD NONE S02/18/03 T. SMITH 32 55 +1.0 34 57 GOOD GOOD GOOD NONE S02/10/04 T. SMITH 10 40 0 5 50 GOOD GOOD GOOD HIGH VOLT BUSHINGS (3) U

LIQUID TEST DATA

PCB Neut Moist PF PF Spec Inhib QualityDate Color Visual Content IFT No. Diel Cont @ 25C @ 100C Grav Cont Visc Factor

02/05/01 3.0 PARTICLES 10 21.2 0.070 30 27 0.940 2.675 0.875 .04 8.40 B04/16/01 1.5 CLEAR 9 40.7 0.010 50 8 0.025 0.155 0.880 33 8.90 S02/09/02 1.5 CLEAR 40.0 0.010 50 9 0.055 0.155 0.880 32 8.80 S02/18/03 1.0 CLEAR 39.5 0.010 50 9 0.055 0.155 0.880 32 8.90 S02/10/04 1.5 CLEAR 9 39.0 0.010 48 10 0.055 0.200 0.880 32 8.90 S

02/04 02/0402/03 02/0302/02 02/0204/01 04/0102/01 02/01

PCB CONTENT (Analysis By GC in PPM)

Date 1242 1254 1260 Other Total

02/05/01 4 <2 6 <2 1004/16/01 4 <2 5 <2 902/10/04 4 <2 5 <2 9

METALS-IN-OIL (Analysis by ICP in PPM)

Date Al Cu Fe Pb Ag Sn Zn

02/05/01 <0.05 <0.05 <0.05 <0.05 <0.05 <0.05 <0.0502/09/02 <0.05 <0.05 <0.05 <0.05 <0.05 <0.05 <0.0502/18/03 <0.05 <0.05 <0.05 <0.05 <0.05 <0.05 <0.0502/10/04 <0.05 <0.05 <0.05 <0.05 <0.05 <0.05 <0.05

RECOMMENDATIONS AND NOTES

REGASKET HIGH VOLT BUSHINGS

Page 2: Transformer Oil Test Report

DISSOLVED COMBUSTIBLE GAS CONTENTSHYDROGEN METHANE CARBON MONOXIDE ETHYLENE ETHANE ACETYLENE

( H2 ) ( CH4 ) ( CO ) ( C2H4 ) ( C2H6 ) ( C2H2 )

REFER TO TSI BULLETIN #304 FOR ABBREVIATIONS AND DEFINITIONS

© Copywrite March 1995, By Transformer Service, Inc.

02/05/01

02/05/01

02/05/01

02/05/01

02/05/01

02/05/01

04/16/01

04/16/01

04/16/01

04/16/01

04/16/01

04/16/01

02/09/02

02/09/02

02/09/02

02/09/02

02/09/02

02/09/02

02/18/03

02/18/03

02/18/03

02/18/03

02/18/03

02/18/03

02/10/04

02/10/04

02/10/04

02/10/04

02/10/04

02/10/04

100

MAX

PPM

ACCEPTA

BLE

100

MAX

PPM

ACCEPTA

BLE

500

MAX

PPM

ACCEPTA

BLE

100

MAX

PPM

ACCEPTA

BLE

60

MAX

PPM

ACCEPTA

BLE

5

MAX

PPM

ACCEPTA

BLE

CUSTOMER: E.G. SAMPLE CORPORATION REF #: 001

ANYTOWN, US CUSTOMER’S UNIT #: B1137A2

UNIT LOCATION: SUB W

DISSOLVED GAS-IN-OIL (Analysis by Gas Chromatography in PPM)Carbon Carbon Total TCG Qual

Date Hydrogen Oxygen Nitrogen Methane Monoxide Dioxide Ethylene Ethane Acetylene Content Content Factor

02/05/01 190 7300 89500 <2 710 4400 120 110 6 102336 1136 U04/16/01 <10 1500 38000 <2 10 120 <2 <2 <2 39630 10 S02/09/02 <10 2400 52000 <2 100 800 <2 <2 <2 55300 100 S02/18/03 <10 9300 73000 <2 190 930 <2 2 <2 83422 192 S02/10/04 <10 3900 64000 <2 120 800 <2 2 <2 68822 122 S

ACCESSORY EQUIPMENT AND ADDITIONAL TRANSFORMER INFORMATIONSpecial Cond : PADMOUNT Voltage Config: WYE-WYE High Volt Bushings: 3S Bank : NOAccessory Eqpt: NONE Impedance : 5.43% Low Volt Bushings : 4S Weight: 13,200LTC Type : NONE Color : LT. GRAY No-Load Tap Chnger: 1S Height: 084.0Radiators/Type: 7 FINS X 11 SETS Radiators : WELDED Outside/Inside : OUT Depth : 096.0Radiator Size : 14in WIDE X 5ft HIGH Top Cover : WELDED Ground/Roof : GROUND Width : 084.0Suppl. Cooling: NONE Valves : THREADED Platform/Pole : N/AFilter Valves : 1" BV/BST, 1" TP Headspace : SEALED Cage/Vault : N/A

NO ADDITIONAL INFORMATION ON RECORD

SERVICE HISTORY

04/16/01 PURGED AND PRESSURIZED HEADSPACE; REGASKETED LOW VOLTAGE BUSHINGS; RE-REFINED/DEGASSED FLUID