Downflow/Horizontal Two-stage Condensing Gas-Fired Furnace XL 90 TDX060,080,100,120R-V Direct Vent with Variable Speed Inducer PUB. NO. 22-1706-01-0400 (EN)

Transcript of Trane TDX Manual - HVAC TECH GROUP

Page 1: Trane TDX Manual - HVAC TECH GROUP

Downflow/HorizontalTwo-stage CondensingGas-Fired Furnace

XL 90TDX060,080,100,120R-VDirect Vent with Variable Speed Inducer

PUB. NO. 22-1706-01-0400 (EN)

Page 2: Trane TDX Manual - HVAC TECH GROUP

©American Standard Inc. 2000 2 22-1706-01-0400 (EN)

GeneralFeatures

Natural Gas ModelsCentral heating furnace designs arecertified by the American Gas Associationfor both natural and L.P. gas. Limit settingand rating data were established andapproved under standard ratingconditions using American NationalStandards Institute standards.

Safe OperationThe Integrated System Control has solidstate devices, which continuously monitorfor presence of flame, when the systemis in the heating mode of operation. Dualsolenoid combination gas valve andregulator provide extra safety.

Quick HeatingDurable, cycle tested, heavy gaugealuminized steel heat exchangerquickly transfers heat to provide warmconditioned air to the structure. Lowenergy power vent blower, to increaseefficiency and provide a positive dis-charge of gas fumes to the outside.

BurnersMulti-port In-shot burners will give yearsof quiet and efficient service. All modelscan be converted to L.P. gas withoutchanging burners.

Integrated System ControlExclusively designed operationalprogram provides total control of furnacelimit sensors, blowers, gas valve, flamecontrol and includes self diagnostics forease of service. Also contains connec-tion points for E.A.C./humidifier.

Condensate DrainBuilt-in trap which can drain from eitherside when the furnace is installed upflow.

Air DeliveryThe variable speed, direct drive blowermotor, has sufficient airflow for mostheating and cooling requirements, willswitch from heating to cooling speeds ondemand from room thermostat. Theblower door safety switch will prevent orterminate furnace operation when theblower door is removed.

Secondary Heat ExchangerThe XL 90 has a special type 29-4C™stainless steel secondary heat ex-changer to reclaim heat from flue gaseswhich would normally be lost outside.

StylingHeavy gauge steel and “wrap-around”cabinet construction is used in thecabinet with baked-on enamel finish forstrength and beauty. The heat exchangersection of the cabinet is completely linedwith foil faced fiberglass insulation. Thisresults in quiet and efficient operationdue to the excellent acoustical andinsulating qualities of fiberglass. Built-inbottom pan and alternate bottom, left orright side return air connection provision.

Features And General OperationThe XL 90 High Efficiency Gas Furnacesemploy an Adaptive Silicon Nitride HotSurface Ignition system, which elimi-nates the waste of a constant burningpilot. The integrated system control lightsthe main burners upon a demand forheat from the room thermostat. Completefront service access.

a. Low energy power venter.b. Vent proving pressure switch.

Page 3: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 3

Contents

Feature Summary 2

Features and Benefits 4Standard Equipment 4Optional Equipment 5

General Data 6TDX060R936V 6TDX080R942V 6TDX100R948V 6TDX120R960V 6

Performance Data 7

Electrical Data 9

Field Wiring 10

Dimensions 14

Page 4: Trane TDX Manual - HVAC TECH GROUP

4 22-1706-01-0400 (EN)

Features andBenefits

• Direct or nondirect vent application

• Convertible to horizontal on left side

• Power supply 115/1/60

• 2-stage gas valve

• Variable speed inducer motor

• Adaptive Silicon Nitride hot surfaceigniter

• Integrated system control

• Heavy gauge aluminized steel heatexchanger

• Blower door safety switch

• Multi-port In-shot burners

• Alternate bottom/left/right return air invertical position

• Slide-out blower assembly

• Direct drive, 4 speed motors

• Adjustable fan off times

• Single pipe venting

• Cleanable high velocity filters

• Heavy gauge reinforced wrap-aroundsteel cabinet

• Super quiet performance

• Complete front service access

• Optional L.P. conversion kit

• Left/right gas connection

• Limited lifetime warranty on primaryand secondary heat exchangers tooriginal owner

• One-year parts warranty

• Three-year warranty on integratedcontrol and hot surface igniter

XL 90 STANDARD EQUIPMENT

Page 5: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 5

Features andBenefits

XL 90 OPTIONAL EQUIPMENTThermostat, Mechanical 2-Stage Heating/1-Stage Cooling .................................................................................... BAYSTAT241 [ ]Thermostat, Mechanical Heating Only With Fan Switch ........................................................................................... BAYSTAT303 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Horizontally) ............................................................................... AY28X092 [ ]Thermostat, Heating/Cooling Single Stage (Mounts Vertically) ............................................................................... BAYSTAT305 [ ]Thermostat, Electronic Programmable 2-Stage Heating/2-Stage Cooling ............................................................BAYSTAT302B [ ]Thermostat, Electronic Programmable 1-Stage Heating/1-Stage Cooling .............................................................. BAYSTAT300 [ ]Propane Conversion Kit ....................................................................................................................................... BAYLPKT210A [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (17-1/2" Wide Gas Furnace) ..................................................... TFE175A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (21" Wide Gas Furnace) ........................................................... TFE210A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Super Efficiency (24-1/2" Wide Gas Furnace) ..................................................... TFE245A9FR0 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (17-1/2" Wide Gas Furnace) ....................................................... TFM175A9FR0 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (21" Wide Gas Furnace) ............................................................. TFM210A9FR0 [ ]Electronic Air Filter, “Perfect Fit” High Efficiency (24-1/2" Wide Gas Furnace) ....................................................... TFM245A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (17-1/2" Wide Gas Furnace) ................................................ TFP175A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (21" Wide Gas Furnace) ...................................................... TFP210A9FR0 [ ]Electronic Air Filter, “Perfect Fit” Standard Efficiency (24-1/2" Wide Gas Furnace) ................................................ TFP245A9FR0 [ ]Coil Enclosure (17-1/2" Wide Cabinets) ................................................................................................................. BAYCLE1700 [ ]Coil Enclosure (21" Wide Cabinets) ....................................................................................................................... BAYCLE2100 [ ]Coil Enclosure (24-1/2" Wide Cabinets) ................................................................................................................. BAYCLE2400 [ ]Downflow Subbase ................................................................................................................................................ BAYBASE205 [ ]High Altitude Switch (060) ...................................................................................................................................... BAYHALT245 [ ]High Altitude Switch (080,100) ............................................................................................................................... BAYHALT246 [ ]High Altitude Switch (120) ...................................................................................................................................... BAYHALT247 [ ]Concentric Vent Termination ................................................................................................................................ BAYVENT100A [ ]Sidewall Vent Termination .................................................................................................................................... BAYVENT200B [ ]Manufactured/Mobile Home Kit ...........................................................................................................................BAYMFGH100A [ ]

Page 6: Trane TDX Manual - HVAC TECH GROUP

6 22-1706-01-0400 (EN)

GeneralData

TDX-R-V PRODUCT SPECIFICATIONS1

1 Central Furnace heating designs are certified by the American Gas Association Inc. Laboratories.2 Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet; Ratings should be reduced at the rate of 4% for each 1000 feet above sea level.3 Based on U.S. Government Standard Tests.4 The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.

MODEL

RATINGS21st Stage Input BTUH

1st Stage Capacity BTUH (ICS)32nd Stage Input BTUH

2nd Stage Capacity BTUH (ICS)3AFUE (ICS)Temp. Rise (Min.-Max.) °F.

BLOWER DRIVEDia.-Width (In.)No. UsedSpeeds (No.)CFM vs. in. w.g.Motor HPR.P.M.Volts/Ph/Hz

COMBUSTION FAN - TYPEDrive - No. SpeedsMotor HP - RPMVolts/Ph/HzFL Amps

FILTER — Furnished?Type RecommendedFilter (No.-Size-Thk.)

VENT — Size (In.)

HEAT EXCHANGERType-Fired

-UnfiredGauge (Fired)

ORIFICES — MainNat. Gas. Qty. — Drill SizeL.P. Gas Qty. — Drill Size

GAS VALVE

DIRECT IGNITION DEVICEType

BURNERS — TypeNumber

POWER CONN. — V/Ph/Hz4Ampacity (In Amps)Fuse Size — Max. (Amps)

PIPE CONN. SIZE (IN.)

DUCT CONN.

DIMENSIONSCrated (In.)Uncrated

WEIGHTShipping (Lbs.)/Net (Lbs.)

TDX060R936V

3900036000600005500092.0

35 - 65

DIRECT10 x 8

14

SEE FAN PERF. TABLE1/3

1075115/1/60

CENTRIFUGALDIRECT - VARIABLE

1/15 - 5000115/1/60

1.1

YESHIGH VELOCITY2 - 14 X 20 X 1

2 ROUND

ALUMINIZED STEEL TYPE 1

20

3 - 453 - 56

REDUNDANT - TWO STAGE

HOT SURFACE IGNITER

IN-SHOT4

115/1/609.115

0.50

SEE OUTLINE DRAWING

H X W X D41-3/4 X 19-1/2 X 30-1/2

SEE OUTLINE DRAWING

155/145

TDX080R942V

5200048000800007400092.5

35 - 65

DIRECT11 x 8

14

SEE FAN PERF. TABLE1/2

1075115/1/60

CENTRIFUGALDIRECT - VARIABLE

1/15 - 5000115/1/60

1.1

YESHIGH VELOCITY2 - 14 X 20 X 1

2 ROUND

ALUMINIZED STEEL TYPE 1

20

4 - 454 - 56

REDUNDANT - TWO STAGE

HOT SURFACE IGNITER

IN-SHOT4

115/1/6011.415

0.50

SEE OUTLINE DRAWING

H X W X D41-3/4 X 19-1/2 X 30-1/2

SEE OUTLINE DRAWING

168/158

TDX100R948V

6500060000

1000009300093.0

45 - 75

DIRECT11 x 10

14

SEE FAN PERF. TABLE1/2

1075115/1/60

CENTRIFUGALDIRECT - VARIABLE

1/15 - 5000115/1/60

1.1

YESHIGH VELOCITY2 - 16 X 20 X 1

2 ROUND

ALUMINIZED STEEL TYPE 1

20

5 - 455 - 56

REDUNDANT - TWO STAGE

HOT SURFACE IGNITER

IN-SHOT5

115/1/6012.515

0.50

SEE OUTLINE DRAWING

H X W X D41-3/4 X 23 X 30-1/2

SEE OUTLINE DRAWING

185/175

TDX120R960V

7800072000

120000111000

92.545 - 75

DIRECT11 x 10

14

SEE FAN PERF. TABLE3/4

1075115/1/60

CENTRIFUGALDIRECT - VARIABLE

1/15 - 5000115/1/60

1.1

YESHIGH VELOCITY2 - 16 X 20 X 1

3 ROUND

ALUMINIZED STEEL TYPE 1

20

6 - 456 - 56

REDUNDANT - TWO STAGE

HOT SURFACE IGNITER

IN-SHOT6

115/1/6012.915

0.50

SEE OUTLINE DRAWING

H X W X D41-3/4 X 26-1/2 X 30-1/2

SEE OUTLINE DRAWING

206/196

Page 7: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 7

PerformanceData

TDX-R-V

FURNACE AIRFLOW (CFM) VS. EXTERNAL STATIC PRESSURE (in. w.c.)

MODEL SPEED TAP 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

TDX060R936V

4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

148713421181877

142512911147863

136212401113849

128611821061820

120911241009791

11251047943739

1040989877686

935869779612

830769681537

TDX080R942V

4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1547148713881263

1498143613481234

1445138213021196

1386132512491150

1323126511911095

1254120211261032

118011371056960

11011069979879

1016998896790

TDX100R948V

4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

1892177916301444

1827172615871416

1762167215441388

1688160514851348

1614153814261308

1531146013621246

1448138112971184

1354129112081108

1260120011191032

TDX120R960V

4 -3 -2 -1 -

HIGH - BlackMED.-HIGH - BlueMED.-LOW - YellowLOW - Red

2213205717651468

2138200017331452

2062194317001435

2001188316521409

1939182216031382

1863175215521336

1786168115001290

1706159514241225

1625150813471159

Page 8: Trane TDX Manual - HVAC TECH GROUP

8 22-1706-01-0400 (EN)

PerformanceData

VENT LENGTH TABLE

ALTITUDEMAXIMUM TOTAL EQUIVALENT LENGTH IN FEET

FOR VENT AND INLET AIR (SEE NOTES)

0-7,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE

TDX060R936V 200 200 200

TDX080R942V 50 120 200

TDX100R948V Not Allowed 60 200

TDX120R960V Not Allowed Not Allowed 200

7,000-9,500 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE

TDX060R936V 100 100 100

TDX080R942V 25 60 100

TDX100R948V Not Allowed 30 100

TDX120R960V Not Allowed Not Allowed 100

9,500-12,000 Feet 2 INCH PIPE 2.5 INCH PIPE 3 INCH PIPE

TDX060R936V 50 50 50

TDX080R942V Not Allowed 30 50

TDX100R948V Not Allowed Not Allowed 50

TDX120R960V Not Allowed Not Allowed 50

NOTES:1. Minimum vent length for all models: 3' horizontal and vertical.2. DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters atthe top of the furnace).3. MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THEMAXIMUM LENGTH OF EACH (Vent or Inlet air pipes).4. One SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One90° elbow is equivalent to 7½' of 2½" pipe or 5' of 2" pipe. Two 45° elbows equal one 90°elbow.5. The termination tee or bend must be included in the total number of elbows. If the BAYVENT100A termination kit is used, theequivalent length of pipe is 5 feet. BAYVENT200A/B equivalent length is 0 feet.6. Pipe adapters are field supplied (except 120).

Page 9: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 9

ElectricalData

SCHEMATIC DIAGRAMS FOR GAS FURNACES

LEGEND

From Dwg. 21D341250 P02

TDX060,080,100,120R-V

Page 10: Trane TDX Manual - HVAC TECH GROUP

10 22-1706-01-0400 (EN)

FieldWiring

From Dwg. 21B341333 Rev. 0

From Dwg. 21B341332 Rev. 0

FIELD WIRING DIAGRAM FOR 2 STAGE HEATING THERMOSTAT

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING

Page 11: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 11

FieldWiring

From Dwg. 21B341335 Rev. 0

From Dwg. 21B341334 Rev. 0

FIELD WIRING DIAGRAM FOR 2 STAGE HEATING SINGLE STAGE COOLING(OUTDOOR SECTION WITHOUT TRANSFORMER)

FIELD WIRING DIAGRAM FOR SINGLE STAGE HEATING/COOLING(OUTDOOR SECTION WITHOUT TRANSFORMER)

Page 12: Trane TDX Manual - HVAC TECH GROUP

12 22-1706-01-0400 (EN)

TwinningField Wiring

From Dwg. 21B341337 Rev. 0

Twinning Connection DiagramFor Twinning UX/DX-R Furnaces - 2 Stage Heat / 2 Stage Cooling Thermostat

From Dwg. 21B341338 Rev. 0

Twinning Connection DiagramFor Twinning UX/DX-R Furnaces - 2 Stage Heat / 1 Stage Cooling Thermostat

Page 13: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 13

Twinning Connection DiagramFor Twinning UX/DX-R Furnaces - 1 Stage Heat / 1 Stage Cooling Thermostat

From Dwg. 21B341336 Rev. 0

TwinningField Wiring

Page 14: Trane TDX Manual - HVAC TECH GROUP

14 22-1706-01-0400 (EN)

Dimensions

TDX-R-V OUTLINE DRAWING(ALL DIMENSIONS ARE IN INCHES)

From Dwg. 21C340762 Rev. 3

Notes:

1. TDX100R960V requires 2-1/2" or 3" and TDX120R960Vrequires a 3" diameter vent pipe.

2. Clearance required at top of plenum is 1"

MODEL A B C D E F

TDX060R936VTDX080R942V

17-1/2" 2-1/4" 16-1/4" 16" 7-1/2" 2"

TDX100R948V 21" 2-1/2" 19-3/4" 19-1/2" 9" 3"

TDX120R960V 24-1/2" 2-15/16" 23-1/4" 23" 10" 3"

Page 15: Trane TDX Manual - HVAC TECH GROUP

22-1706-01-0400 (EN) 15

Notes

Page 16: Trane TDX Manual - HVAC TECH GROUP

The Trane CompanyUnitary Products Group6200 Troup HighwayTyler, TX 75707-9010www.trane.com

An American Standard Company

P.I.

Since The Trane Company has a policy of continuous product and product data improvement, it reserves theright to change design and specifications without notice.