Installation Instructions
PanelView Plus, VersaView CE Terminalsand Display Modules
2711P and 6182H
Inside...
English....................................................... 3Français................................................... 19
Deutsch ................................................... 35
Español.................................................... 51Italiano .................................................... 67
Português................................................ 83
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 2/18
2 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
Important User Information
Because of the variety of uses for the products described in this publication, those responsible for the
application and use of these products must satisfy themselves that all necessary steps have been taken to
assure that each application and use meets all performance and safety requirements, including any applicable
laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for
indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely
for purposes of example. Since there are many variables and requirements associated with any particular
installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property
liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of
Solid-State Control (available from your local Rockwell Automation office), describes some important
differences between solid-state equipment and electromechanical devices that should be taken into
consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of
Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following
annotations and their accompanying statements help you to identify a potential hazard, avoid a potential
hazard, and recognize the consequences of a potential hazard:
!
WARNINGIdentifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage,
or economic loss.
ATTENTION
!Identifies information about practices or circumstances that can lead to personal injuryor death, property damage, or economic loss.
IMPORTANTIdentifies information that is critical for successful application and understanding of the
product.
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 3/18
Publication 2711P-IN001C-MU-P
Installation Instructions
PanelView Plus, VersaView CE Terminalsand Display Modules2711P and 6182H
English
Inside:
Overview ..............................................................................................................................4
For More Information...........................................................................................................4
Modular Components ..........................................................................................................4Wiring and Safety Guidelines..............................................................................................5
Hazardous Locations............................................................................................................6
USB Ports .............................................................................................................................6
Environmental Considerations .............................................................................................8
Enclosures............................................................................................................................8
Clearances ...........................................................................................................................8
Required Tools......................................................................................................................8
Mounting Dimensions..........................................................................................................9
Cutout Dimensions.............................................................................................................11Installing Terminal in a Panel.............................................................................................11
Connecting DC Power ........................................................................................................13
European Communities (EC) Directive Compliance ...........................................................15
Product Specifications .......................................................................................................16
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 4/18
4 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
Overview
This document provides instructions on how to install the following devices in apanel or enclosure.
• factory assembled PanelView Plus or VersaView CE terminal
• PanelView Plus or VersaView CE Display Module
Refer to the installation instructions shipped with the Logic Module andCommunication Module for field installation of these components.
For More InformationTo obtain electronic versions of the PanelView Plus or VersaView CE User Manual, visit the following website:
www.rockwellautomation.com/literature
Modular Components
The PanelView Plus and VersaView CE terminals have the following modularcomponents:
• Display Module (700/700H, 1000/1000H, 1250/1250H, 1500/1500H)
• Logic Module (DC Power, CF Card Slot, Ethernet Port, Serial Port, USB Ports)
• Internal Compact Flash card with firmware or operating system, RAMMemory (SO-DIMM)
• Communication Module (for specific communication protocols)
These items can be ordered as separate components for field installation or factory assembled per your configuration. The base configured unit includes the Display Module and the Logic Module (with Internal Compact Flash and RAM).
Communication Module
Logic Module
Display Module
DC Power Input
Ethernet Port
Serial PortUSB PortsCompact Flash Card Slot
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 5/18
PanelView Plus, VersaView CE Terminals and Display Modules 5
Publication 2711P-IN001C-MU-P
If the modules are ordered separately, attach the Logic Module and CommunicationModule) to the Display Module before panel installation. See instructions shipped
with each module.The Logic Module for both the PanelView Plus and VersaView CE is available withor without RAM and Compact Flash pre-installed. If ordered as separatecomponents, you must install the memory in the Logic Module before attaching theLogic Module to the Display Module. Refer to the installation instructions shipped with the Logic Module (2711P-IN004).
Wiring and Safety GuidelinesUse publication NFPA 70E, "Electrical Safety Requirements for Employee Workplaces", IEC 60364 "Electrical Installations in Buildings" or other applicable wiring safety requirements for the country of installation when wiring the VersaView CE terminals. In addition to the NFPA guidelines:
• connect the terminal and other similar electronic equipment to its ownbranch circuit
• protect the input power by a fuse or circuit breaker rated at no more than 15
Amps.• route incoming power to the terminal by a separate path from the
communication lines.
• where power and communication lines must cross, they should cross at rightangles. Communication lines can be installed in the same conduit as lowlevel DC I/O lines (less than 10 volts).
• grounding minimizes noise from Electromagnetic Interference (EMI) and is asafety measure in electrical installations. To avoid EMI, shield and groundcables appropriately.
A source for grounding recommendations is the National Electrical Code publishedby the National Fire Protection Association of Boston.
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 6/18
6 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
Hazardous Locations
This equipment is suitable for:• Class I, Division 2 Groups A, B, C, D• Class II, Division 2 Groups F, G• Class III• or (ordinary) non-hazardous locations only
The following statement applies to use in hazardous locations.
The PanelView Plus and VersaView CE terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum ambient temperature. Do not installthe terminals in environments where atmospheric gases have ignition temperaturesless than 135 °C (275 °F).
USB Ports
The PanelView Plus/VersaView CE terminals contain USB (Universal Serial Bus)ports which comply with hazardous location environments. This section details thefield wiring compliance requirements and is provided in accordance with theNational Electrical Code, article 500.
The USB peripheral device must be rated for use in the hazardous locationenvironment in which it is used and also comply with the circuit parameters inTable 2.
!
WARNING Explosion Hazard
• Substitution of components may impair suitability for
hazardous locations.
• Do not disconnect equipment unless power has beenswitched off and area is known to be non-hazardous.
• Do not connect or disconnect components unless powerhas been switched off.
• All wiring must comply with N.E.C. articles 501-4(b),502-4(b), 503-3(b) as appropriate.
• Peripheral equipment must be suitable for the location it is
used in.
USB
Peripheral
Device
Associated Nonincendive FieldWiring Apparatus
USB Port
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 7/18
PanelView Plus, VersaView CE Terminals and Display Modules 7
Publication 2711P-IN001C-MU-P
The circuit parameters in Table 1 define the maximum voltage and current of thePanelView Plus/VersaView CE USB ports.
The circuit parameters in Table 2 define the maximum voltage, current, capacitance,
and inductance values for any peripheral device connected to a PanelViewPlus/VersaView CE USB port in a hazardous location environment.
Application Information
Per the National Electrical Code, the circuit parameters of associated field wiredapparatus for use in hazardous locations shall be coordinated with the host productsuch that their combination remains nonincendive. The PanelView Plus/VersaViewCE terminal and the USB peripheral device shall be treated in this manner.
The circuit parameters of the PanelView Plus/VersaView CE USB ports are given in
Table 1. The USB peripheral device and its associated cabling shall have circuitparameters with the limits given in Table 2 for them to remain nonincendive whenused with the PanelView Plus/VersaView CE USB ports. If cable compliance andinductance are not known, use the following values from UL 913:
Ccable = 60 pF/ft
Lcable = 0.20 µH/ft
Table 1 PanelView Plus/VersaView CE USB Port Circuit Parameters
Parameter Value Parameter Definition
V oc 5.25V dc Open circuit voltage of the host USB port.
I sc 1.68 A Maximum output current of the host USB port.
Table 2 Required Circuit Parameters for the USB Peripheral Device
Parameter Value Parameter Definition and Application Requirement
V max 5.25V dc Maximum applied voltage rating of the USB peripheral device.Vmax shall be greater than or equal to Voc in Table 2.1. (Vmax ≥ Voc )
I max 1.68 A Maximum current to which the USB peripheral device can be subjected.
I max shall be greater than or equal to Isc in Table 2.1.(Imax ≥ Isc)
C a 10 µF Maximum allowed capacitance of the USB peripheral device and itsassociated cable. The sum of Cint of the USB peripheral device andCcable of the associated cable shall be less than or equal to Ca.(Cint + Ccable ≤ Ca)
L a 15 µH Maximum allowed inductance of the USB peripheral device and itsassociated cable. The sum of Lint of the USB peripheral device andLcable of the associated cable shall be less than or equal to La.
(Lint + Lcable ≤ La)
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 8/18
8 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
Environmental Considerations
The terminals are suitable for use in an industrial environment when installed inaccordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution Degree 2(1) and with circuits not exceeding
Over Voltage Category II (2) (IEC 60664-1).(3)
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally atemporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages arecontrolled and do not exceed the impulse voltage capability of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Enclosures
The terminals must be mounted in a panel or enclosure to protect the internal
circuitry. The terminals meet NEMA Type 12/13 and 4X ratings only when mountedin a panel or enclosure with the equivalent rating.
When the terminal is not mounted in a panel, it is not secure or safe for operation. You must comply with the NEMA Type 4 requirements for environmentalspecifications.
Clearances
Allow adequate clearances around the terminal, inside the enclosure, for adequate ventilation. Consider heat produced by other devices in the enclosure. The ambient
temperature around the terminals must be between 0…55 °C (32…131 °F).Minimum clearances for ventilation are:
• top and bottom clearance: 51 mm (2 in)
• side clearances: 25 mm (1 in)
Maximum side clearance for insertion of memory card is 102 mm (4 in).
Required ToolsBesides the tools required for the panel or enclosure cutouts, you will need thefollowing for installation:
• small slotted screw driver
• torque wrench (in-lb)
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 9/18
PanelView Plus, VersaView CE Terminals and Display Modules 9
Publication 2711P-IN001C-MU-P
Mounting Dimensions
This section provides mounting dimensions for the PanelView Plus and VersaViewCE terminals. The depth dimensions are shown for the:
• base configured unit (Display Module and Logic Module)
• base configured unit with Communication Module
All measurements are in mm (inches).
To provide a frame of reference, the illustration following the table showsdimensions for the 1000/1000H terminals.
Terminal Type Height Width Depth
PanelView Plus 700/VersaView CE 700H
Keypad or Keypad & Touch193 (7.58) 290 (11.40)
55 (2.18)
Display to Logic Module
83 (3.27)Display to Comm Module
PanelView Plus 700/VersaView CE 700H
Touch Screen179 (7.04) 246 (9.68)
PanelView Plus 1000/VersaView CE 1000H
Keypad or Keypad & Touch248 (9.77) 399 (15.72)
PanelView Plus 1000/VersaView CE 1000HTouch Screen
248 (9.77) 329 (12.97)
PanelView Plus 1250/VersaView CE 1250H
Keypad or Keypad & Touch282 (11.12) 416 (16.36)
PanelView Plus 1250/VersaView CE 1250H
Touch Screen282 (11.12) 363 (14.30)
PanelView Plus 1500/VersaView CE 1500H
Keypad or Keypad & Touch330 (12.97) 469 (18.46) 65 (2.55)
Display to Logic Module
93 (3.65)Display to Comm Module
PanelView Plus 1500/VersaView CE 1500HTouch Screen
330 (12.97) 416 (16.36)
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 10/18
10 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
PanelView Plus 1000 and VersaView CE 1000H
All measurements are in mm (inches).
Keypad or
Keypad & Touch
Touch Screen
a 55 (2.18) Display to Logic Module
b 83 (3.27) Display to Comm Module
a 55 (2.18) Display to Logic Module
b 83 (3.27) Display to Comm Module
248
(9.77)
399
(15.72)
ba
b
a
329
(12.97)
248
(9.77)
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 11/18
PanelView Plus, VersaView CE Terminals and Display Modules 11
Publication 2711P-IN001C-MU-P
Cutout Dimensions
The table below shows the overall cutout dimensions for each PanelView Plus and VersaView CE terminal. Dimensions are in mm (inches).
Use the full size template shipped with your terminal to mark the cutoutdimensions.
Installing Terminal in a Panel
All of the PanelView Plus and VersaView CE terminals are installed in the samemanner using clips for mounting. The number of clips used (4, 6 or 8) varies by terminal type. The mounting clips are shipped with each terminal.
To install terminal in a panel:1. Cut an opening in the panel using the panel cutout provided with the
terminal. Remove any sharp edges or burrs.
2. Make sure the terminal sealing gasket is properly positioned on the terminalas shown. This gasket forms a compression type seal. Do not use sealingcompounds.
PanelView Plus /VersaView CE Terminal Height Width
700/700H Keypad or Keypad & Touch 167 (6.57) 264 (10.39)
700/700H Touch 154 (6.08) 220 (8.67)
1000/1000H Keypad or Keypad & Touch 224 (8.8) 375 (14.75)
1000/1000H Touch 224 (8.8) 305 (12.00)
1250/1250H Keypad or Keypad & Touch 257 (10.11) 390 (15.35)
1250/1250H Touch 257 (10.11) 338 (13.29)
1500/1500H Keypad or Keypad & Touch 305 (12.00) 419 (16.50)
1500/1500H Touch 305 (12.00) 391 (15.40)
ATTENTION
!
• Disconnect all electrical power from the panel beforemaking the panel cutout.
• Make sure the area around the panel cutout is clear.
• Do not allow metal cuttings to enter any componentsalready installed in the panel.
• Failure to follow these instructions may result in personalinjury or damage to panel components.
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 12/18
12 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
3. If using keypad legend strips on keypad terminals, we recommend that youinstall the strips before installing the terminal. Be careful not to pinch legendstrip during installation.
4. Place the terminal in the panel cutout.
5. Install the mounting clips. The ends of the clips slide into the slots on theterminal.
6. Tighten the mounting clip screws by hand until the gasket seal contacts themounting surface uniformly.
Sealing Gasket
Mounting Clip Slot
Mounting Clip
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 13/18
PanelView Plus, VersaView CE Terminals and Display Modules 13
Publication 2711P-IN001C-MU-P
7. Alternately tighten the mounting clips screws to a torque of .90 - 1.1 N•m (8- 10 in-lb). Do not over-tighten. Below are recommended torque sequences.
Connecting DC Power
The PanelView Plus and VersaView CE terminals have an integrated power supply that operates on 24V dc. The electrical input ratings of the power supply are:
• 24V dc nominal (18…32V dc)
• 70 Watts maximum (2.9A @24V dc)
The power supply is internally protected against reverse polarity.
The input power, terminal block on the power supply is removable and supportsthe following wire sizes:
ATTENTION
!
Tighten the mounting clip screws to a torque of .90 - 1.1N•m (8 - 10 in-lb) to provide a proper seal and to preventpotential damage to the terminal. Allen-Bradley assumes noresponsibility for water or chemical damage to the terminalor other equipment within the enclosure because of improper installation.
Wire Type Wire Size Terminal Block Screw Torque
Stranded #16 to #22 AWG.23 - .45 N•m (2 - 4 in-lbs)
Solid #18 to #22 AWG
8 Clips
1
2
3
4
5
6
7
86 Clips
24 6
51 3
4 Clips
1 4
3 2
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 14/18
14 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
The terminals using 24V dc power are EN 61131-2 Equipment Class II devices.
To connect DC power:
1. Secure the DC power wires to the terminal block screws.
2. Secure the Functional Earth (FE) ground wire to the terminal blockscrew.
3. Apply 24V dc power to the terminal.
ATTENTION
!
Use a Class 2/SELV (Safety Extra-Low Voltage), isolated andungrounded power supply as input power to the terminals.This power source provides protection so that under nominaland single fault conditions, the voltage between conductorsand between conductors and Functional Earth/Protective Earthdoes not exceed a safe value.
Functional Earth Ground
- DC Negative
Logic Module with
DC Power Input
+ DC Positive
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 15/18
PanelView Plus, VersaView CE Terminals and Display Modules 15
Publication 2711P-IN001C-MU-P
European Communities (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the EuropeanUnion and EEA regions. It has been designed and tested to meet the followingdirectives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC ElectromagneticCompatibility (EMC) by applying the following standards, in whole or in part,documented in a technical construction file:
• EN 50081-2 EMC - Generic Emission Standard, Part 2 - IndustrialEnvironment
• EN 61000-6-2 EMC - Generic Immunity Standard, Part 2 - IndustrialEnvironment
This product is intended for use in an industrial environment.
Low Voltage DirectiveThis product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 -Equipment Requirements and Tests. For specific information required by EN61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley publication Industrial Automation Wiring and Grounding GuidelinesFor Noise Immunity, publication 1770-4.1.
Open style devices must be provided with environmental and safety protection by
proper mounting in enclosures designed for specific application conditions. SeeNEMA Standards publication 250 and IEC publication 529, as applicable, forexplanations of the degrees of protection provided by different types of enclosure.
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 16/18
16 PanelView Plus, VersaView CE Terminals and Display Modules
Publication 2711P-IN001C-MU-P
Product Specifications
Electrical
DC Power
Input Voltage DC
Power Consumption DC
24V dc nominal (18…32V dc)
70 Watts maximum (2.9 A @24V dc)
Display
Display Type Color Active Matrix, Thin FilmTransistor (TFT), with
Liquid Crystal Display (LCD)
Display Size
700/700H
1000/1000H
1250/1250H
1500/1500H
6.5 in
10.4 in
12.1 in
15 in
Display Area (W x H)
700/700H
1000/1000H
1250/1250H1500/1500H
132 x 99 mm (5.2 x 3.9 in)
211 x 158 mm (8.3 x 6.2 in)
246 x 184 mm (9.7 in x 7.2 in)304 x 228 mm (12.0 x 9.0 in)
Display Resolution
700/700H
1000/1000H
1250/1250H
1500/1500H
640 x 480
640 x 480
800 x 600
1024 x 768
Touch Screen Analog Resistive
Environmental
Operating Temperature 0…55 °C (32…131 °F)
Storage Temperature -20…70 °C (-13…158 °F)
Vibration 10…57 Hz, 0.012 pk-pk displacement
57…500 Hz 2.0 g pk acceleration
Shock Operating 15 g at 11 ms
Shock Non-Operating 30 g at 11 ms
Relative Humidity 5…95% without condensation
Ratings NEMA Type 12, 13, 4X (indoor use only), IP54, IP65
8/3/2019 Touch Screen Installation Manual
http://slidepdf.com/reader/full/touch-screen-installation-manual 17/18
PanelView Plus, VersaView CE Terminals and Display Modules 17
Publication 2711P-IN001C-MU-P
Mechanical
Dimensions H x W x D (for base configured unit without communication module)
700/700H Keypad or Keypad & Touch 193 x 290 x 55 mm (7.58 x 11.40 x 2.18 in)
700/700H Touch 179 x 246 x 55 mm (7.04 x 9.68 x 2.18 in)
1000/1000H Keypad or Keypad & Touch 248 x 399 x 55 mm (9.77 x 15.72 x 2.18 in)
1000/1000H Touch 248 x 329 x 55 mm (9.77 x 12.97 x 2.18 in)
1250/1250H Keypad or Keypad & Touch 282 x 416 x 55 mm (11.12 x 16.36 x 2.18 in)
1250/1250H Touch 282 x 363 x 55 mm (11.12 x 14.30 x 2.18 in)1500/1500H Keypad or Keypad & Touch 330 x 469 x 65 mm (12.97 x 18.46 x 2.55 in)
1500/1500H Touch 330 x 416 x 65 mm (12.97 x 16.36 x 2.55 in)
Weight (for base configured unit without communication module)
700/700H Keypad or Keypad & Touch 1.9 kg (4.2 lb)
700/700H Touch 1.7 kg (3.8 lb)
1000/1000H Keypad or Keypad & Touch 2.9 kg (6.3 lb)
1000/1000H Touch 2.6 kg (5.7 lb)
1250/1250H Keypad or Keypad & Touch 3.4 kg (7.6 lb)
1250/1250H Touch 3.2 kg (7.1 lb)
1500/1500H Keypad or Keypad & Touch 4.6 kg (10.0 lb)
1500/1500H Touch 4.2 kg (9.3 lb)
Agency Certifications
When product is marked:
N223
Marked for all applicable directives
Marked for all applicable acts
UL Listed Industrial Control EquipmentUL Listed Industrial Control Equipment for use inCanadaUL Listed Industrial Control Equipment for use in• Class I, Div 2, Group A, B, C, D
• Class II, Div 2 Groups F, G
• Class III Hazardous Locations