Tornados of the South - Wood Works Engineering,...
Transcript of Tornados of the South - Wood Works Engineering,...
A p r i l 2 0 1 1
Tornados of the South
By
Bryan T. Readling, P.E. – APA Field Services Division
StructurAl performAnce of newly conStructed HomeS in nortH cArolinA, AlAbAmA, And GeorGiA
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
2
bAckGround
Damage observations were conducted by APA after the April 16, 2011 tornados in Eastern North Carolina and
the subsequent events scattered across the South on April 27, 2011 including Tuscaloosa, Alabama and Griffin,
Georgia. Even in these powerful storms, investigations found that structural failure was often due to a lack of ade-
quate connections.
Building scientists and engineers use the term “load path” to describe how forces flow through a structure and connec-
tions and how the structure can be designed to resist wind loads. Many homes failed as a result of an interruption in
continuity along the load-path to the foundation. If poorly made, critical connections along the uplift load-path are lost
when the dead weight of the building is overcome by the wind force. A continuous load-path from the roofing and siding
(cladding), to the framing, and to the foundation must be provided for reliable building performance.
This study focused on the performance of homes constructed approximately within the last 10 years. There were
many similarities in observations with past APA Damage Assessments but the EF-4 and EF-5 tornados of April 27, 2011
were exceptional in their size, severity and impact on populations.
obServAtionS
Structural failure along the critical load-path was often located at the roof-to-wall connection. Most of these con-
nections were made using toe-nails through the roof framing and into the top plate of the exterior walls. Toe-nail
connections are weak because they rely upon the withdrawal capacity of nails, which is limited. Light-gauge metal
connectors provide good performance in wood framing because load is applied perpendicular to the nail shank,
instead of pulling the nail straight out. Toe-nail rafter connections are still prescriptively allowed in most non-
hurricane areas by modern building codes. It is generally recognized that these connections may not provide the
capacity to resist some high wind pressure requirements of the International Building Code.
Metal roof-to-wall connectors should be installed in-line with the load-path. Failure was observed when metal roof
framing connectors were installed on the inside face of the wall top plate instead of on the exterior of the wall and in-
line with the load-path in the structural wall sheathing.
A common observation, especially in hardest hit areas, was the loss of the exterior walls due to poor attachment of the
wall framing to the foundation. In many cases hand-driven cut masonry nails were used to attach the bottom of sup-
port walls to the concrete or masonry foundations, but in a few locations the nails were observed to be pneumatically
driven framing nails. Modern building codes generally require anchor-bolts to be embedded into concrete or grouted
concrete masonry unit foundations.
Breaches or openings in the building envelope, and the resulting pressurization of the building interior, caused cata-
strophic failure of homes in many examples. Openings in walls due to failure of doors, windows, and non-structural
cladding systems were common. These often resulted in heavy damage to home interiors due to rainwater infiltration
and flying debris penetration. Larger breaches from loss of weak garage doors and exterior cladding systems often
acted to initiate catastrophic failure and exacerbated deficiencies along the aforementioned load-path.
In homes with gable roofs, failures were most notable at the bottom of the gable-end roof and ceiling framing where
they are connected to the top of the gable-end wall below. This joint is often not well connected laterally to the rest of
the building and is weak to resist negative pressure on the exterior gable-end surfaces.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
3
The gable-end is also a vulnerable location for non-structural cladding systems because the walls within the roof
cavity are not backed by drywall like the exterior walls within the living space. Material failure was commonly
observed when foam wall sheathing was used in conjunction with low-strength siding. Besides being vulnerable to
wind pressure, these products provide little resistance to the flying debris.
In most observations where buildings were at least partially intact, wood wall and roof sheathing loss could be
attributed to improper attachment. When nails were used as prescribed in the building codes good performance was
observed. Staples performed poorly since they generally offer less resistance to pull-out than nails and must be used
in greater quantity. Greater structural failure often resulted from poor roof sheathing attachment to the last rafter or
gable-end truss.
buildinG for GreAter tornAdo or HurricAne reSiStAnce
Tracking tornado paths in North Carolina, Alabama, and Georgia, APA focused on the performance of homes con-
structed within the last ten years. In many cases engineers can point to one of several common weak links as the
cause of catastrophic failure in homes that were on the periphery of these powerful tornados. It is possible to do a far
better job of protecting a home’s occupants and their possessions. Already commonplace in hurricane prone areas,
wind-resistant shell designs are simple and represent a relatively small increase in construction cost over houses built
to code minimums. The following APA recommendations, some of which exceed the minimum requirements of the
current codes, address the common weak links and provide tips for building a wind-resistant shell:
1. Nail wall sheathing with 8d common (0.131 in. x 2-1/2 in.) nails at 4 inches on center at end and edges of wood
structural panels and 6 inches on center in the intermediate framing. This enhanced nailing will improve the resis-
tance of the wall sheathing panels to negative wind pressure. The use of deformed shank nails will even further
improve the performance of the sheathing at a minimal cost. Staples offer less resistance to blow-off than nails and
so a greater number of them are required to achieve the same level of resistance.
2. Sheath gable end walls with wood structural panels, such as plywood or oriented strand board (OSB). In the 2011
tornados, gable end wall failures were frequently observed when non-structural sheathing was used.
3. Tie gable end walls back to the structure. One of the weakest links in residential structures during high wind
events is the lateral connection between the bottom of the gable-end and the top of the wall below.
4. For the roof framing to wall connection, use an H1 or equivalent connector attached on the exterior (sheathing
side) of the exterior walls. The roof to wall connection under high wind loads is subject to both uplift and shear
due to positive or negative wind pressure on the walls below.
5. Nail roof sheathing with 8d ring shank or deformed shank (0.131 in. x 2-1/2 in.) nails at 4 inches on center along
the edges of the wood structural panel wall sheathing and 6 inches on center along the intermediate framing.
6. Nail upper story sheathing and lower story sheathing into common wood structural panel Rim Board®. The most
effective way to provide lateral and in some cases uplift load continuity is to attach adjacent wall sheathing panels
to one another over common framing.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
4
7. Continuously sheath all walls with wood structural panels including areas around openings for windows and doors.
8. Extend wood structural panel sheathing to lap the sill plate. The connection of the wall sheathing panel to the
sill plate is important because this is where uplift forces are transferred into the sill plate and into the foundation
through the anchor bolts.
9. Space ½ in. anchor bolts 32 inches to 48 inches on center with 0.229 in. x 3 in. x 3 in. square plate washers with
slotted holes.
More information and illustrations of these construction details can be found in the APA guide: Simplified Tips for
Improving Tornado or Hurricane Resistance of Light-Frame Wood Construction, Form M310, available for download at
www.apawood.org.
SummAry
The concept of building a storm-resistant shell or building envelope is nothing new but the concept has seen greater
interest since recent severe weather. In the past, misperceptions about tornados were often used to justify a lack of
attention to structural details. A common myth remains that all tornados are so strong that structural failure is immi-
nent no matter how well a building is constructed. This rationale results in homes that lack adequate attention to a
few important details.
Weaker tornados rated as EF-0, EF-1 and EF-2 by the National Weather Service statistically comprise 95 percent of all
tornados. These smaller less-violent tornados produce winds which a carefully constructed home can be expected to
withstand.
Stronger tornados rated EF-3, EF-4 and EF-5 are statistically much rarer. They are harder for homes to survive but
improvements in design can still help. This might be the case when a building is located along the outer reaches of
the area influenced by a strong vortex.
Individual components (exterior walls, roofs, floors) are often strongly built. This is especially true when framing is
sheathed with wood structural panels, but the assemblies must still be tied together to complete the load path. A few
thoughtfully constructed connections can mean the difference between homes that survive the more common and
less powerful tornados, and those that don’t.
Homeowners deserve better, and by following a few simple guidelines, the chances of a home surviving a tornado
intact improve dramatically. First, securely attach OSB or plywood sheathing to integrate the framing. Thoughtful
joint location and blocking of horizontal joints in the wall sheathing can eliminate common discontinuities in wall
framing and at the Rim Board. Next, connect roof framing to the walls using metal connectors instead of just toenails.
Lastly, to complete the load-path, use anchor bolts into the foundation using large plate washers atop the bottom plate
of the wall. This type of construction is already commonplace in earthquake and hurricane prone areas and can be
used to improve peace-of-mind and safety for occupants in areas susceptible to tornados.
About the author:
Bryan Readling is a registered professional engineer. He received a master’s degree in Civil Engineering from Clemson
University, where his graduate research included wind tunnel studies of low-rise structures. Before joining APA in
1990, Bryan worked as a consulting structural engineer in Atlanta.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
5
FigurE 1:
Extensive damage to the mostly brick homes
in a subdivision in Fayetteville, NC, included
this home where damage likely initiated from
the failure of garage doors. A subsequent pres-
surization of the garage portion of the home
caused walls on the gable-end and rear of the
garage to be pushed out.
FigurE 2:
The gable-end of the home in Figure 1 is
shown here. A hinge has formed at the second
floor level in the gable-end wall. Minimal fas-
tening was observed at the connection of the
ceiling and second floor sheathing to the top of
the gable-end wall and the bottom of the gable-
end truss.
FigurE 3:
The interior side of the gable-end truss is
shown here. The truss was fabricated using
a standard attic truss as was used over the
garage to frame the bonus room. Minimal fas-
tening was observed at the 2x10 bottom chord
member to the drywall ceiling and OSB floor
sheathing.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
6
FigurE 6:
Poorly attached brick veneer was lost on the
rear of this home in the Fayetteville subdivi-
sion. Despite this, the OSB wall sheathing has
remained intact.
FigurE 5:
Another home within the Fayetteville subdi-
vision exhibited weakness at the gable ends.
This home lost gable-end attic trusses at two
locations on the roof. Garage doors on the
left side of this home were observed to be
breached and the front gable end wall above
the garage has failed.
FigurE 4:
This is the rear of the home shown in Figure
1. Numerous examples of isolated roof sheath-
ing loss at step-down trusses on hip roofs were
observed. It is likely that the complexity of the
connection between the roof sheathing and the
step-down trusses has resulted in poor resis-
tance to negative pressure in these cases.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
7
FigurE 9:
Almost complete collapse of this home in the
Fayetteville subdivision was observed. Garage
walls were pushed out of the left side and rear
of the home, suggesting that the failure of this
home was likely initiated due to internal pres-
sure after the envelope was breached at the
garage doors.
FigurE 8:
A section of roof that was blown off within the
Fayetteville subdivision was connected to the
top plate of the wall using metal connectors.
The connectors were installed on the inside
face of the wall which may have resulted in
weakness due to misalignment with the load-
path within the exterior wall sheathing.
FigurE 7:
These two homes within the Fayetteville sub-
division lost significant amounts of the fiber-
cement lap-siding. Despite this, no breaches
were observed in the OSB wall sheathing.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
8
FigurE 12:
Another home with near total collapse of
above-grade wood walls was fully sheathed
with OSB wall sheathing. The wall sheathing
lapped the rim board and sill plate but was
fastened to the rim board only with 16d nails
at approximately 16" on center. No nails were
observed from the bottom of the sheathing
into the sill plate.
FigurE 11:
Roof trusses from the home in Figure 9 con-
tained two 16d toe-nails used for the connec-
tion to the top of the wall.
FigurE 10:
Detail from Figure 9 of the bottom of the
left-side garage wall shows that the OSB wall
sheathing was poorly attached to the bottom
plate using 8d nails at approximately 16" on
center. The minimum fastening recommenda-
tion for this application is 6" on center along
panel ends and edges.
Anchor bolts with minimally-sized round
washers were observed in this location at 48"
on center.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
9
FigurE 15:
Built between 2004 and 2009, these homes
are in Wilson, NC. The author observes tor-
nado damage at the end of a cul-de-sac. The
tornados in this location were not nearly as
strong as those observed the following week
in Alabama.
FigurE 14:
This image shows the tornados that struck
the Eastern part of North Carolina on
April 16, 2011.
FigurE 13:
This home in the Fayetteville subdivision was
partially stripped of the fiber-cement siding
fastened to the framing at 16" on center. Most
of the siding nails remained embedded in the
wall sheathing with small pieces of the sid-
ing retained below the head of the fastener in
most cases.
Source: National Weather Service
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
10
FigurE 18:
Shown here is a detail of the end wall in Figure
17. Non-structural foam panels did little to
strengthen this wall. Note the separation
between the foam wall panels and the top
plate.
FigurE 17:
This Wilson, NC home was almost completely
destroyed. Shown here is the left end-wall
that was braced at the corners using OSB.
Extruded polystyrene foam panels were used
to infill between the OSB corner bracing.
FigurE 16:
This figure shows two of the homes in Wilson,
NC that were almost completely destroyed.
Others in the vicinity lost substantial amounts
of wall coverings.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
11
FigurE 21:
A close up of this left gable end wall shows
that the foam wall panels were likely rein-
forced by the presence of the interior drywall.
Where no drywall existed at the gable-end
framing, the siding and foam wall sheathing
were almost completely stripped.
FigurE 20:
Several homes in Wilson, NC lost the vinyl
siding and extruded polystyrene foam panels
covering both gable ends.
FigurE 19:
This photo shows the foam insulation panel
connection to the bottom plate of the wall.
Note the small bits of the wall sheathing still
attached to the bottom plate. Structural panel
wall sheathing lapped over this joint can be
used to add significant strength to the connec-
tion between the wall studs and the bottom
plate.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
12
FigurE 24:
The right rear portion of the home in Figure
23 is still supported by the section of the wall
reinforced by the OSB corner bracing. The
corner bracing from the right front corner of
the home is still intact and lying in the yard,
visible in the left-most portion of this photo.
FigurE 23:
The exterior walls of this Wilson, NC home
were mostly destroyed. Despite this, the roof
remained in place over the foundation, a testa-
ment to the relatively light tornado forces and
the weakness of the foam wall panels in pro-
tecting the building envelope.
FigurE 22:
The right side gable end wall of the home
shown in Figure 21 shows a similar failure
of the foam and vinyl materials covering the
gable-end framing.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
13
FigurE 27:
Foam panels at the gable-end are almost com-
pletely stripped from the framing. The rel-
atively weak foam sheathed portion of the
end wall contained a window that was lost
between the OSB corner bracing and the util-
ity closet due to pressurization.
FigurE 26:
This photo shows the rear of the home in
Figure 23. Most of the rear wall is severely
damaged with the exception of the OSB cor-
ner bracing at the left-rear corner. A mirror
still hangs on the interior wall of the bath-
room at the left-rear corner of the home.
FigurE 25:
A close-up of the corner bracing seen in Figure
24 shows that the bottom plate remained
attached to the slab foundation along the side-
wall but the connection of the bottom plate
along the front wall failed.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
14
FigurE 30:
This two-story fiberboard-sheathed home col-
lapsed after racking failure of the first floor
walls occurred.
FigurE 29:
The left-front portion of the home shown in
Figure 28 shows loss of vinyl siding at the
gable ends and instability at the top of the
gable-end wall.
FigurE 28:
Homes in this part of suburban Northeast
Raleigh, NC were heavily damaged. Inter me-
diate fiberboard wall sheathing with vinyl
siding covered the exterior of most of these
homes. Homes in this area were constructed
between 2001 and 2004.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
15
FigurE 33:
A close-up of the foundation shows negligible
connection of the sill plate to the foundation.
The builder attempted to use nails to connect
the sill plate to the foundation. These nails
were mostly bent at the tip and did not sig-
nificantly penetrate the masonry foundation
walls.
FigurE 32:
This home also shown in Figure 31 was
sheathed primarily with fiberboard and used
OSB corner bracing.
FigurE 31:
This home was moved off of its foundation
and displaced approximately 6 feet toward the
rear. The attached garage totally collapsed.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
16
FigurE 36:
This failure in Alberta City combines two
vulnerabilities, the gable end and the garage.
Loss of the garage door likely resulted in pres-
surization of the garage and failure of the
gable-end wall.
FigurE 35:
These homes were in the same area and built
during the same time period as those in
Figure 34. Similar failures of roof coverings
and wall claddings and good performance of
OSB sheathing were observed.
FigurE 34:
These homes in Alberta City in Northeast
Tuscaloosa were built in 1999 and 2000.
Although stripped of much of their roof and
wall coverings, the OSB sheathing was well
attached and largely remained intact.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
17
FigurE 39:
The right side of the homes shown in Figure 38
show gable-end failures likely associated with
breaches in the front walls.
FigurE 38:
Although gable-ends were a vulnerability in
these two heavily impacted homes in Alberta
City, these OSB sheathed homes remain
standing and offered some protection to
inhabitants.
FigurE 37:
As seen in much of the homes destroyed in
this area, nails were used to attach the bot-
tom plate of the gable-end wall of the home in
Figure 36 to the foundation.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
18
FigurE 42:
A gable end failure occurred on the front and
right side of this home in Coaling, AL and
the garage door was lost on the left side of
the home. The front wall of the garage was
pushed-in apparently by wind pressure
as there are no indications that an impact
occurred in this location.
FigurE 41:
Although many of the homes in this Coaling,
AL subdivision were equipped with storm
shelters, according to residents, none of them
were occupied during the severe weather
event, partly because an alarm system
that had operated in the past did not wake
residents. This storm shelter was part of a
detached garage that was totally destroyed.
The main portion of the home remained intact
with moderate structural damage.
FigurE 40:
Homes in this subdivision in Coaling, AL were
built between 1999 and 2004. Most of the
homes within the subdivision were heavily
damaged by the tornado that passed through
this neighborhood at 5:27 a.m. All of the homes
were fully sheathed with OSB but connection
continuity and lateral support for gable-end-
walls were found to be lacking.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
19
FigurE 45:
The safe-room on the front of the home in
Figure 42 was formerly accessed through the
garage and may have acted to strengthen the
home against the tornado forces.
FigurE 44:
This photo shows the roof truss connection to
the top plate using four toenails. The toenails
were placed in opposing pairs and resulted in
splitting of the truss material.
FigurE 43:
The right rear of the home in Figure 42 shows
the loss of the gable end and adjacent roof area
over the children’s bedrooms. This home is
fully sheathed with OSB with pink housewrap
under vinyl siding.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
20
FigurE 48:
The right side of the home in Figure 47.
FigurE 47:
This home in Coaling, AL lost all of its exterior
walls.
FigurE 46:
This photo shows the edge of the slab where
the garage wall was blown-in on the home in
Figure 42. Non-galvanized spiral shank nails
were used to attach the bottom plate to the
foundation. This photo shows very little pen-
etration of the nail into the concrete slab and
also the gouge made by the nail as the wall
moved inwards.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
21
FigurE 51:
This home in Coaling, AL was completely
swept from the foundation. Remarkably the
family members inside the home were swept
away from the building footprint by the
tornado but were not seriously injured.
FigurE 50:
Non-galvanized spiral shank nails 24" – 48"
on center were observed within the piece of
bottom plate material. Most of the nail tips
were bent and did not significantly penetrate
the slab foundation.
FigurE 49:
Close-up of a bottom plate nail that remained
embedded in the slab of the home in Figure
47 after the exterior wall was demolished.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
22
FigurE 54:
Attachment of the gable-end for the home in
Figure 53 used 16d toenails 29" on center from
the bottom of the gable-end truss into top plate
of end- wall.
FigurE 53:
This home located on the periphery of the
tornado in Coaling, AL lost the gable-end
framing.
FigurE 52:
This piece of bottom plate material was the
only piece of the exterior walls that remained
of the home in Figure 51. Cut-nails with a rect-
angular cross-section were used to attach the
bottom plate to the slab.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
23
FigurE 57:
The condition of the left rear of the home
in Figure 56 shows that an impact occurred
between the two windows. Soffits were blown
away from most of the home’s perimeter,
which likely led to loss of roof sheathing along
the eaves.
FigurE 56:
This home in Coaling, AL was heavily
impacted by the tornado, but fared better than
adjacent homes. This is possibly due to superior
structural performance inherent in hip roof
construction as compared to the gable roofs
more typically found in this neighborhood.
FigurE 55:
For the home in Figure 53, nails into the top
chord were measured to be 48" on center
with staples located 12" on center between the
nails. The nails were placed at the top of roof
sheathing panels apparently in an effort to
hold the panels in place until the staples could
be placed within the field of the panels.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
24
FigurE 60:
The same location shown in Figure 59 shows
roof sheathing loss corresponding to loss
of lightweight vinyl soffit and porch ceiling
materials.
FigurE 59:
This photo of the left front portion of the
home in Figure 56 shows loss of soffit material
and porch ceiling materials.
FigurE 58:
Inside the home shown in Figure 56, where
the impact occurred, shows that the wall
studs separated from the top plate. OSB wall
sheathing likely saved this wall from complete
failure at the impact location.
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
25
FigurE 63:
The rear of the home in Figure 62 is shown
in this photo. Based on the failure of a few
small trees in the backyard of this home, the
winds were mostly straight-line at this loca-
tion. The homeowner was dismayed that the
home suffered such severe damage despite the
fact that 2 of the 3 geese decoys in the back-
yard remained in-place.
FigurE 62:
This newly constructed home in Griffin, GA
lost vinyl siding and foam wall sheathing at
the gable-end trusses on both the front and
rear of the home. Despite this, no damage was
observed to a nearby detached lightweight
metal carport that is anchored with metal
stakes.
FigurE 61:
This image shows the tornados impacting
the state of Alabama on April 27, 2011. The
Alabama images contained in this list of
photos all came from the tornado marked in
blue and were taken between Tuscaloosa and
Birmingham, AL.
Source: National Weather Service
Tornadoes of the South – April, 2011
Form No. SP-1154 ■ © 2011 APA – The Engineered Wood Association ■ www.apawood.org
26
FigurE 65:
This is the damage to the foam wall sheathing at
the rear gable-end of the home in Figures 62, 63
and 64 before the blue tarps were installed.
This photo was supplied by the homeowner.
FigurE 64:
This is the damage to the foam wall sheathing
at the front gable-end of the home in Figures 62
and 63 before the blue tarps were installed.
This photo was supplied by the homeowner.
Tornados of the SouthWe have field representatives in many major u.S. cities and in Canada who can help answer questions involving APA trademarked products.
For additional assistance in specifying engineered wood products, contact us:
APA – The engineered Wood AssociATion
Headquarters7011 So. 19th St. ■ Tacoma, Washington 98466 ■ (253) 565-6600 ■ Fax: (253) 565-7265
Product suPPort HeLP desk(253) 620-7400 ■ E-mail Address: [email protected]
discLaimerThe information contained herein is based on APA – The Engineered Wood Association’s continu-ing programs of laboratory testing, product research, and comprehensive field experience. Neither APA, nor its members make any warranty, expressed or implied, or assume any legal liability or responsibility for the use, application of, and/or reference to opinions, findings, conclusions, or recommendations included in this publication. Consult your local jurisdiction or design professional to assure compliance with code, construction, and performance requirements. Because APA has no control over quality of workmanship or the conditions under which engineered wood products are used, it cannot accept responsibility for product performance or designs as actually constructed.
Form No. SP-1154/issued August 2011