Topic I - Paper - 6
Transcript of Topic I - Paper - 6
-
8/2/2019 Topic I - Paper - 6
1/7
DEVELOPMENT OF PHASE SHIFTING TRANSFORMERS
FOR SCOTTISH AND SOUTHERN ENERGY plc
Krishnamurthy Vijayan, Waldemar Ziomek, Juan Carlos Garcia Willi Felber
Pauwels Canada Inc., Winnipeg, Canada Felber Engineering, Austria
INTRODUCTION
Reliability of power systems are strengthened by large
interconnected networks. Effective control of power flow
in these networks is essential for improving stability,
enhancing reliability and optimizing capabilities of such
large interconnected systems. The voltage variation
provided by load tap changers in transformers can help to
control only reactive power flow where as Phase Shifting
Transformers (PSTs) are proven solution for control of real
power flow in interconnected systems.
In 2004, Pauwels Canada Inc. successfully developed 240
MVA and 150 MVA PSTs for Scottish and Southern Energy
plc, Scotland. This paper describes briefly the general
principle and basic types of PSTs. It also describes specific
details on the design, manufacture and testing process of
the PSTs delivered to Scottish and Southern Energy plc.
PRINCIPLE OF PSTs
Purpose
PSTs are primarily used to control flow of real power inparallel lines or interconnected systems by introducing a
phase angle shift between the Primary (Source) and
Secondary (Load) terminals. This is achieved by providing
a boost voltage in quadrature (perpendicular) to line
voltage.
Application
Consider the current distribution between two parallel lines
as shown below
When power flows between these two systems, Individual
line loading depends on the impedance of the lines. More
power flows through the path with lower impedance. This
may cause individual line overloading and is usually
contrary to efficient system operation. If it is desired to
balance the current by increasing i1
by Di, and therefore
decreasing the current in line 2 to i2-Di, it is necessary to
introduce a circulating current Di in the system. This can
be done with the introduction of a PST in series with one
of the lines (see Fig. 2). An expression for the circulatingcurrent is
(1)
Where DV is the quadrature boost voltage provided by the
PST. This voltage needs to be almost perpendicular to the
line voltage so that control of real power flow can be
achieved. By using on load tap changers in PSTs DV can
be varied or even reversed so that a full range of power
flow control is possible between parallel lines.
Another important application of PSTs is the control of
power flow between two large independent grids. The flow
of active power between two interconnected systems is
given by (2).
VS
i1 Z1
i2Z2 iTOTAL
VL
Fig. 1 Current distribution in parallel lines
Fig. 2 Current distribution in parallel lines with PST
i1+i Z1
i2-i Z2 iTOTAL
VS VL
VLVPSTPST
1 2
Vi
Z Z
=
+
V1 V2
P
System 1 System 2
Fig. 3 Two independent grids
( )1 2 sinVVP Z
= (2)Therefore, the flow of real power between two systems
can be effectively controlled by varying the phase angle
difference (j).
Equivalent circuit and phasor diagram
Before understanding the phasor diagram it is essential to
understand the following terminologies
Advance phase angle : The phase angle that results when
Session I Paper 6
I-28
-
8/2/2019 Topic I - Paper - 6
2/7
the PST's Load terminal voltage leads the Source voltage
terminal. This condition produces an increase in the line's
source to load power flow. Fig. 4 shows the vector diagram
for this case.
Retard phase angle: The phase angles those results when
the Load terminal voltage lags the Source terminal voltage.
This condition produces a decrease of the line's source toload power flow.
Like any transformer, PSTs have inherent impedance which
varies with the phase angle. Generally, PSTs have their
minimum impedance at zero phase shift which increase
with the phase angle. PSTs can be considered as voltage
sources with internal impedances that vary with phase angle
shift.
As can be seen in the vector diagram, under load condition,
the phase angle shift is affected by the PST's internal
impedance. The internal phase shift b of the PST can be
calculated as [2]
(3)
Where cos(f) is the load power factor.
The effective phase shift under load is given by
These relations not only have impact on the transformer
design but also on the selection of load tap changer. The
PSTs rated phase-shift is generally defined at no-load but
as can be seen from the equations, it is not possible to
achieve this phase angle under load in advance position.
Also if the no-load angle is exceeded in retard position,
over excitation will occur in parts of PST.
TYPES OF PSTs
The different types of PSTs can be better understood if
certain terminologies are defined.
Symmetrical PST: Under no-load the magnitude of the
PST's source and load voltages are equal, independently
of the phase angle between them.
Quadrature: It refers to the boost voltage introduced by
the PST being perpendicular to the line voltage at one
terminal.
The basic types of PSTs can be Symmetrical or non-
symmetrical, they can be single core or dual core and they
can be single tank or dual tank.
There are also many other types or design possibilities
which makes the subject of PST development very
challenging.
Types of Phase shifting transformers
Non-symmetrical quadrature type
iLRPST+jXPST
VS VL VLeff
VS
iLXPST
iL
VL iLRPST
VLeff
Load
No Load
Fig. 4 PST equivalent circuit and phasor diagram
( ) ( )
( ) ( )
cos sinarctan
sin cos
L PST PST
L L PST PST
I X R
V I X R
= +
ADVANCE
LOAD NO LOAD =
RETARDLOAD NO LOAD = +
Phase shifting
transformer
Quadrature
symmetricalQuadrature
non symmetrical
Single core Two core
Single Tank Dual tank
Fig. 5 Types of PSTs
Fig. 6 Asymmetrical PST
I-29
Session I Paper 6
-
8/2/2019 Topic I - Paper - 6
3/7
I-30
Session I Design For Reliability
In this type of PST the quadrature voltage is achieved by
connecting the regulating winding of phase B to the Delta
connection point of phase A and B and so on. The
advantage of this type is that it has no exciting transformer.
The major disadvantage of this type is the tap changer and
regulating winding being directly exposed to system
disturbances. Special measures are required to ensure their
impulse withstand capability.
Symmetrical quadrature type single-core
This is an extension of the non-symmetrical type whichcan be achieved with an additional tap changer.
Two-core symmetrical quadrature PST
This is the standard and classical solution with series and
exciting transformers each built on its own core but with
windings electrically interconnected.
Single tank/Dual tank
These are possible design options for 2 core designs.
Depending on size, voltage class, etc., the Series and
Exciting transformers could be housed in the same tank or
in separate tanks. Obviously housing in separate tanks has
the disadvantages of being more expensive and that the
inter-connection between the units needs to be redone at
site.
PSTs FOR SCOTTISH AND SOUTHERN ENERGY
plc
Application
In the Scottish power system, two double-circuit 275kV
parallel lines run north to south via the east coast to
transport Hydroelectric and Wind energy. One double-circuit 132kV line runs north to south via the west coast
and a single 132 kV line runs north to south via the east
coast for the same purpose. When there is a fault on one of
the 275kV lines the power tries to flow through the 132kV
system since its impedance is smaller under that condition.
This leads to over loading of the 132kV lines.
In this case three PSTs were needed to control the active
(real) power flows in the non faulty lines so that each of
these lines could be used to its rated capacity without over
loading the 132kV lines.
The PSTs will be bypassed using bypass switch undernormal condition. Thus there is possible impulse condition
with both Source and Load terminals connected together.
Ratings and special requirements
Basic ratings
Site1 (Fiddes substation)
1 x 150 MVA, 132 kV class, 50 Hz, 550 kV BIL with
phase angle shift under load of +/-15, using load tap
changer with +/-8 steps
Site2 (Errochty substation)2 x 240MVA, 132 kV class, 50 Hz, 550 kV BIL with phase
angle shift under load of +10/-20, using load tap changer
with +/-8 steps
Special requirements
l Transformers to comply with IEC 76 standards.
Requirements specific to PSTs to be as per IEEE
C57.135 [2], which are the only available standards
for this kind of applications.
Fig. 7 Symmetrical PST
Fig. 8 Quadrature-booster PST
-
8/2/2019 Topic I - Paper - 6
4/7
I-31
Session I Paper 6
l Dual core with separate series and exciting
transformer, Quadrature booster designs preferred.
l Dual tank design anticipated due to transportation
limitations. A maximum height of 4.87 m and weight
of 220 T is allowed on the roads approaching the
final site in UK. Single tank designs meeting these
transportation limits are acceptable.l Use of non-linear voltage limiting devices to control
internal voltages to be avoided.
l 115% chop wave test required
l Special impulse test required with both Source and
Load terminals connected together to simulate the
PST bypass condition.
l The ratio of zero sequence to positive sequence
impedance to be smaller than 9 (Z0/ZP< 9)
l 110% over voltage and frequency variation of 47.5
to 52 Hz
Design approach
l A classical design concept of a two-core symmetrical
Quadrature booster was applied
l An extremely compact design concept was applied
in order to house both, series and exciting units in a
single tank while meeting size and weight
transportation requirements. Such compactness was
achieved by using tall and slim design concept with
low impedance. Special care was taken to assure
withstand capability against short circuits.
l Series transformer and exciting transformer are built
on separate 3 leg cores with electrical interconnection
between them
l A tertiary delta winding was introduced in the
exciting transformer in order to meet the zero
sequence impedance requirement
l Use of a special dual multi-layer design on the series
transformer delta winding to achieve controlled
dielectric stresses during lightning impulse condition.
l Center-fed exciting winding so that the high voltageconnection with the series winding is made at the
center, away from core ground potential. The two
transformer heights and dimensions were closely
matched to facilitate the interconnection inside the
tank
l Fully interleaved exciting winding
l Special 2 layer tap winding with leads connected to
high speed resistance type tap changer.
Design details
Basic design
The winding disposition on the two cores is indicated
below.
Impedance calculation and loss control
FEM based leakage flux analyses were used to determine
size and position of tank shunts and clamp shunts.
Impedance calculations were performed with the help of
field calculation tool based on Bessel functions.
a) Series transformer b) Exciting transformer
Dielectric design
Impulse calculations using LC network based software
were performed for each of the following conditions: a)
Impulse on S (or L) terminal with the other terminal
grounded b) Impulse on S & L terminals connected
(bypassed PST). For condition b) the center connection
point voltage was estimated to rise to 1034kV during the
550 kV full wave impulse test.
Electrostatic stress analyses were performed for all critical
locations and special contouring and insulation components
were used wherever necessary.
DELTA
SERIES
LTC2
LTC1
TERTIARY
EXCITER
Series unit Exciting unit
Fig. 9 PST windings layout
Fig. 10 Electromagnetic FEM simulations.
a) b)
-
8/2/2019 Topic I - Paper - 6
5/7
I-32
Session I Design For Reliability
Design reviews were conducted at every stage of the
development process.
Manufacturing
l All windings and core were built to close dimensional
tolerance
l Pre-fit of the units inside tank was necessary to make
measurements for final interconnection at center.
l After final housing of the units, special contoured
high voltage inter connection was done by skilled
person inside the tank. Connections inspected and
approved by Quality Assurance and Engineering by
physical inspection inside tank.
l Special manufacturing process evolved by buildinga prototype for the dual multi-layer type delta
winding.
Photograph below shows the two units assembled and
housed inside the common tank.
Testing
Special features of some of the factory tests are highlighted
here
Phase angle measurement
Phase angles were measured according to proposed method
in IEEE C57.135 [2]. The phase shift was also recorded inoscilogram, see figure below.
Dielectric tests
Lightning impulse
Low voltage recurrent surge impulse tests were done with
both series and excitation units electrically connected to
verify impulse voltage calculations. Some of these
measurements were done with both assemblies outside the
tank and inside the tank. The measured values were close
to calculated values.
Fig. 11 Typical stress plot: Series transformer main gap
at highest stress region
Fig. 12 Series and exciting transformers assembled
inside tank
Fig. 13 S and L wave shapes when S leads L
S
N
L
S
N
L
Fig. 14 Lightning impulse test on S (or L) terminal and
on S+L terminals (bypassed PST)
Fig. 15 Low voltage recurrent surge impulse-test.
Impulse response at the exciter T connection point
-
8/2/2019 Topic I - Paper - 6
6/7
I-33
Session I Paper 6
Besides impulse test on S and L terminal, special lightning
impulse test including 115% chop wave condition were
applied to (S+L) connected together. The calculated and
RSG test results at the T point for 1.2/50s full wave
impulse applied to (S+L) is shown in Fig. 15. The
maximum values by test are lower than calculated values.
The difference is attributed to a) Measurement for this case
was done in air outside tank and b) Our calculations do
not consider damping.
Induced voltage test
For this test the unit was energized through a set of
temporary test bushings brought out of the tap windings.
Both 1-phase and 3-phase induced tests were conducted
as per IEC standard [3].
Loss measurement
In PST the loss distribution in series and exciting units
vary with the phase angle. Typical loss distribution of the
measured values for 240MVA unit is shown in table.
Temperature rise test
With single tank design, temperature rise test for obtaining
oil rise values do not pose any difficulties. But measurement
of gradients of each of the windings needs special methods.
Gradient of each winding including the LTC winding was
measured either by direct or indirect measurements.
1. Resistance of Series winding of ST can be measured
directly between S & L ( R+R= 2R in the diagram
below)
2. For the Exciting winding it will be an indirect
measurement as follows
S & L terminals to be connected & resistance to neutral
was measured. This will give (R/2 + Re) ohms. Since R is
known, Re can be calculated.
3. Resistance of Delta winding & LTC winding are
measured using temporary test bushings connected
to LTC.
Test frequency
The phase shifters were designed for frequency of 50Hz
to suit the Scottish system. However the test frequency at
the Pauwels Canadian plant was 60Hz and hence
conversion factors were applied to the tests results in orderto get guaranteed design parameters at 50Hz. Useful
guidance was taken from IEEE Tutorial for the conversion
factors [3].
Test summary
All the tests on both the ratings were very successful. All
three units passed all tests first time right.
l The measured phase angles were within 1% of the
guaranteed values.
l The maximum P.D level was 103 pC.
l The maximum hot spot temperature was 68.50C.l The special zero sequence impedance ratio
requirement of Zo-open /Z positive was fully met.
(Photo of unit under test)
CONCLUSIONS
As can be seen the design and development of Phase
shifting transformers are unique. It was a challenge to meet
Table 1 Summary of tested losses on 240 MVA PST
Series Exciting Total
unit unit
No load loss kW
Zero phase shift 0 26.8 26.8
Maximum phase shift 21.2 26.8 48
Load loss kW
Zero phase shif 224.3 0 224.3
Maximum phase shift 224.3 268.7 493
Total loss kW
Zero phase shif 224.3 26.8 251.1
Maximum phase shift 245.5 295.5 541
Series winding on ST
Excitingwinding Re []
R []R []
S L
N
Fig. 16 T network used to calculate the exciting winding
resistance
Fig. 17 240 MVA phase shifter on site.
Courtesy of Scottish and Southern Energy plc
-
8/2/2019 Topic I - Paper - 6
7/7
I-34
Session I Design For Reliability
the transport limits with the single-tank design. Considering
various advantages it was worth the efforts since this
approach gives the best satisfaction to the ultimate
customer. All the three units have reached site and they
are presently undergoing field trials.
REFERENCES
1. W. Seitlinger, "Phase Shifting Transformers,
Discussion of Specific Characteristics", CIGRE
Session 1998
2. IEEE Std C57.135-2001 "IEEE Guide for the
Application, Specification, and Testing of Phase-
Shifting Transformers", IEEE Power Engineering
Society, 2002
3. E.G. teNyenhuis, R.S. Girgis, "50Hz to 60Hz
conversion factors for transformer performance
parameters". IEEE/PES Transformer Committee
Tutorial session April 16,2002
4. IEC standard 60076 IEC: 2000 "Power transformers".
5. Axel Kramer "On-Load Tap-changers for Power
transformers by (MR publication)"
6. Scottish Hydro-Electric Transmission Ltd"Specification for Quadrature booster transformers".
Enquiry No:C33995/01
ACKNOWLEDGEMENTS
The authors express their sincere thanks to Scottish and
Southern Energy plc., for providing the system details and
site photographs.
The authors also acknowledge the support provided by the
management and colleagues at Pauwels Canada Inc.,