6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

Transcript of Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use...

Page 1: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

1

Top secretSecret

Internal use onlyPublic

VRV to AHU connectionApplication guide

Page 2: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

2

Title - Internal use only3

BasicsIn this chapter we will learn about:• How VRV can be useful for AHU air treatment

• What are the benefits of this application

• What possibilities do you have

01.

Title - Internal use only4

THE BASICS

Supply AirInlet Air

Adjustment damper

Filter section

Treatment section

Fan section

View: SECTION

Post-heating section

Humidification section

Drop separator

Here we can apply VRV for cooling or heating the supplied

air in DX coils.

Where to use VRV?

Page 3: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

3

Title - Internal use only5

THE BASICS

What do you need to use VRV for cooling and heating the air in the AHU?

R410A gas

R410A liquid

communication Thermistors

EXV control

1. Outdoor unit(s)

(work as CCU)

3. Expansion valve set

(refrigerant flow and pressure control in DX coil)

2. Air Handling Unit with properly

designed DX coils (Daikin or 3rd Party)

4. Control box (controls the expansion

valve set and outdoor unit(s) capacity

2a (optional). Air Handling Unit

control box (Daikin or 3rd Party)

5. Local or central remote controllers (in some cases)

Title - Internal use only6

THE BASICS

What are the benefits?

1) Immediate Cooling and Heating under any ambient or room conditions → less heat transfer losses, fast and accurate response to load changes → better comfort and less energy consumption compared to water cooling/heating coils coupled with chillers.

2) Better management of load for medium size spaces due to VRV technologies. • Total solution: AHU can work together with other VRV indoor units in same system • Extended operating range • Accurate temperature control due to inverter capacity management• Quick switchover between cooling & heating.→ better comfort and wider possibilities compared to water systems and ON/OFF CCUs.

3) Top Energy Efficiency and reliability• Energy saving due to inverter technology• No inrush current• Less start/stop cycles, longer compressors lifetime• VRV IV: VRT control is furthermore increasing seasonal efficiency• VRV IV: numerous settings targeting either higher efficiency or quick response.→ lower running costs

4) Continuous Heating with VRV IV dedicated heat pump range:• Avoid Cold drafts during defrost cycle• Fresh air can be continuously supplied at comfortable temperatures→ better comfort

Page 4: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

4

Title - Internal use only7

THE BASICS

What are the configuration possibilities?

DX coil + ERQ outdoor unit

ERQ (up to 25 kW)

•Pair combination (1 outdoor+ 1 DX kit)

•Heat pump

VRV IV Heat pump (up to 150 kW on Multi combination)

•Pair combination(1 outdoor + 1 DX kit)

•Multi combination: (1 outdoor+ several DX kits):

- AHU+AHU

- AHU+VRV IU (only return air control is available in this case)

Supply air temperature controlor

Return air temperature control

VRV IV Heat recovery (up to 150 kW on Multi combination)

•Multi combination:

- AHU+VRV IU

DX coils + VRV IV outdoor unit

Supply air temperature controlor

Return air temperature controlReturn air temperature control

Title - Internal use only8

THE BASICS

What are the temperature control possibilities?

Td (discharge air temperature

sensor)

Tr (room air temperature sensor)

Return Air Supply Air

Ts (supply air temperature

sensor)

Te (evaporator temperature

sensor)

DDC controller(AHU’s own

controller, collecting data from sensors

and forming capacity demand signal)

X: Control of supply or return air temperature ( uses Td, Ts or Tr- all field supplied sensors) with external controller (DDC) using an un-proportional 0~10 V algorithm for capacity control

Y: Control of evaporating/condensing temperature, indirect room temperature control (uses Te- Daikin supplied) with 3rd party thermostat and Daikin controller BRC1D52 or BRC1E52A/B used for field settings and error indication

Z: Control of supply or return air temperature (uses Ts or Tr- Daikin or field supplied sensors) with Daikin controller BRC1D52 or BRC1E52A/B used for control, field settings and error indication

W: Control of supply or return air temperature (uses Td, Ts or Tr- all field supplied sensors) with external controller (DDC) using a proportional 0~10 V algorithm for capacity control

Page 5: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

5

Title - Internal use only9

Selection and build-upIn this chapter we will learn about:• How the selection process goes

• What components do you need in each case

• What are the restrictions and limitations

02.

Title - Internal use only10

LINE-UP (WHAT DO YOU HAVE TO SELECT FROM)

1. Outdoor unitsThe following ranges are suitable:• ERQ (11-28 kW);• VRV IV HP RXYQ-T/RYYQ/T/RYMQ-T(22-150 kW)• VRV IV HR REYQ-T (22-150 kW)• Water Cooled VRV RWEYQ-T (22-84 kW)

2. Control boxes:• EKEQFCBA (for all types of VRV and ERQ)• EKEQDCBA (for ERQ only)• EKEQMCBA (for VRV only)

Model EKEXV50 EKEXV63 EKEXV80 EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250 EKEXV400 EKEXV500

Allowedcoil

capacity, kW

(cooling)

5,0-6,2 6,3-7,8 7,9-9,9 10,0-12,3 12,4-15,4 15,5-17,6 17,7-24,6 24,7-30,8 35,4-49,5 49,6-61,6

Allowed coil

capacity,kW

(heating)

5,6-7,0 7,1-8,8 8,9-11,1 11,2-13,8 13,9-17,3 17,4-19,8 19,9-27,7 27,8-34,7 39,8-55,0 55,1-69,3

4. Expansion valves sets:

3. Air handling units:

AHU

Daikin 3rd Party

Easy (500-33000 m3/h)

Professional (750-144000 m3/h)

Energy (750-100000 m3/h)

Modular (500-25000 m3/h)

Integrated Daikin DDC controllers

possible

Page 6: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

6

Title - Internal use only11

SELECTION PROCESS

Step 1. Calculate the required coil capacity, determine coil parameters and select expansion valves

Air flow

On coil air temperature and humidity (summer/wi

nter)

Off coil air temperature (summer/wi

nter)

Coil capacity (cooling/heating)

Coil parameters

Volume

# of circuits

# and type of expansion valve sets

AHU selection software

VRV selection software

At this stage consider limitations (refer to EXV data books):• Allowed MIN and MAX cooling capacity for EXV sets• Allowed MIN and MAX heating capacity for EXV sets

AHU software suggests 65 kW single circuit coil. Is it OK?

No, max. capacity for single circuit is 61,6 kW. You need to split your coil.

AHU software suggests 6 kW double circuit coil (3+3 kW). Is it OK?

No, min. capacity for single circuit is 5 kW. You need to go to 1 circuit coil.

Title - Internal use only12

SELECTION PROCESS

Step 2. Determine your system configuration and select control box(es) and outdoor units

System configuration

Pair

VRV

ERQ

EKEQDCB(A)

EKEQFCB(A)

Multi

Single AHU with multi-circuit coil

Several AHUs

AHUs and VRV indoor

units

EKEQFCB(A)

EKEQMCB

Based on selected EXV capacity (@

step 1), if ≤28 kW

Based on selected EXV capacity (@

step 1), if > 28 kWSelect the

outdoor unit based on total connected EXV

capacity

Select the outdoor unit

based on total connected EXV

capacity

X/Y Control

X/Y/W Control

X/Y/W Control

Z Control

VRV selection software

EKEQFCB(A)X/Y/W Control

Z Control

It is important to understand how temperature control modes work to select the most appropriate for your

project!

Page 7: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

7

Title - Internal use only13

TEMPERATURE CONTROL MODES

X-Control – how it works?

Measurements of:• Tr or• Ts or• Td

0-10 V signal

Capacity step signal to the outdoor unit:• Level 1• Level 2• Level 3• Level 4• Level 5

ΔT=0 +ΔTmax-ΔTmax

V - voltage input to the control box

ΔT0V

5V

10V

ΔT – is the difference between the set point and the

temperature measured by the sensor;

ΔTmax – maximum allowed difference between the

set point and the temperature measured by the sensor, 2-50C – is programmed during commissioning.

DDC controller EKEQF control box

Voltage from the DDC controller is linear function of ΔT:

V =5

∆Tmax× ∆T + 5

Depending on the input voltage, EKEQ control box will send to the outdoor unit the capacity step signal:

EXV is controlled to provide certain Te (evaporation

temperature)

Capacity level Cooling Heating

Level 1 Capacity ↓↓ Capacity ↑↑

Level 2 Capacity ↓ Capacity ↑

Level 3 Keep current capacity

Level 4 Capacity ↑ Capacity ↓

Level 5 Capacity ↑↑ Capacity ↓↓

Title - Internal use only14

TEMPERATURE CONTROL MODES

X-Control – how it works (continued)?

Measurements of:• Tr or• Ts or• Td

0-10 V signal

Capacity step signal to the outdoor unit:• Level 1• Level 2• Level 3• Level 4• Level 5

DDC controller EKEQF control box

EXV is controlled to provide certain Te (evaporation

temperature)

Level 10V

1,8V

3,8V

6,8V

8,8V

Level 2

Level 3

Level 4

Level 5

If the voltage from DDC is increasing:

Level 10V

1,2V

3,2V

6,2V

8,2V

Level 2

Level 3

Level 4

Level 5

If the voltage from DDC is decreasing:

The EKEQ controller switches between capacity levels like this:

10V 10V

What are the benefits? When to use this type of control? It is expensive to buy and setup…

The benefits are:• Fast response to load variation

(capacity is immediately changed as a function of measured temperature)

• Precise temperature controlYou may use this type of control in comfort sensitive applications. This is also used by default in Daikin AHU controls.

Page 8: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

8

Title - Internal use only15

TEMPERATURE CONTROL MODES

Y-Control – how it works?

3rd Party Thermostat EKEQF control box

Outdoor unit

EKEXV EV box

Measures room temperature, sends ON/OFF signal to control box when set point is reached

ON/OFF signal

Settings, incl. Te/Tc

BRC1(D,E)

Used to make the necessary settings

Te/Tc control

Te/Tc control

• Evaporation and condensing temperatures (for cooling and heating modes respectively) are fixed, by field settings on remote controller:• Te = 5…120C (default 80C)• Tc = 43…490C (default 460C)

• The system will only deviate from set Te/Tc in case of safe modes activation

How does the system work?

What are the benefits? When to use this type of control? Looks very easy and cheap, what are the drawbacks?

• Cheap and simple solution (no additional DDC controller required)

• No direct temperature control. Room temperature may fluctuate significantly

You may use this type of control in comfort insensitive applications with constant cooling/heating load (technical rooms).

Title - Internal use only16

TEMPERATURE CONTROL MODES

Measurements of:• Tr or• Ts or• Td

0-10 V signal

Capacity step signal to the outdoor unit:• Level 1 = 0% capacity• Level 2 = 40% capacity• Level 3 = 60% capacity• Level 4 = 80% capacity• Level 5 = 100% capacity

DDC controller EKEQF control box

EXV is controlled to provide certain Te (evaporation

temperature)W-Control – how it works?

DDC outputs the voltage signal proportional to ΔT

(same as X-control)

𝑉 =∆𝑇

∆𝑇𝑚𝑎𝑥× 10

EKEQ box selects the capacity step and sets it by fixing the

Te/Tc at certain level (not direct % of capacity!)

The system tries to adjust the compressor speed to reach ΔT=0 with this Te/Tc

ΔT measurement

Capacity level

Voltage from DDC controller

Te setting (cooling)

Tc setting (heating)

Approx. % of capacity

Level 1 0,8 - - 0 (OFF)

Level 2 2,5 13,50C 310C 40

Level 3 5 110C 360C 60

Level 4 7,5 8,50C 410C 80

Level 5 9,2 60C 460C 100

We can (though indirectly) set the % of system capacity by means of 0-10 V signal.Most of the AHU controllers available in the market are suitable for this without any additional programming.

Page 9: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

9

Title - Internal use only17

TEMPERATURE CONTROL MODES

W-Control – how it works (continued)?

Measurements of:• Tr or• Ts or• Td

0-10 V signal

Capacity step signal to the outdoor unit:• Level 1 = 0% capacity• Level 2 = 40% capacity• Level 3 = 60% capacity• Level 4 = 80% capacity• Level 5 = 100% capacity

DDC controller EKEQF control box

EXV is controlled to provide certain Te (evaporation

temperature)

What are the benefits? When to use this type of control? Looks very similar

to X-control…

The benefits are:• Direct temperature control (capacity is changed as a function of measured temperature)• Most standard AHU controllers are suitable without additional programming• Due to variable refrigerant temperature no cold/hot draftsBut:• Slower response to load variation -> room temperature fluctuation, less accurate temperature control

(compared to X-Control), because of longer control sequence:

Measure Adjust capacity Measure Set target T Reach target TAdjust capacity

(fine tune)

X-Control W-Control

You can use this type of control to combine VRV/ERQ with 3rd

party AHUs, if you need supply temperature control

Title - Internal use only18

TEMPERATURE CONTROL MODES

Z-control – how it works?

This is the only possible mode in multi-AHU or VRV indoors + AHU configurations.

Daikin or 3rd Party Thermistor

Outdoor unit

EKEXV EV box

Measures room temperature, sends ON/OFF signal to control box when set point is reached

Room or supply air temperature

information Settings, incl. Tset (set point temperature)

BRC1(D,E)

Used to control the system and make the necessary settings

EXV control (depending on Tset-Tr(or Ts)

Capacity command

Superheat/subcool information

EKEQM

Works the same as ‘normal’ VRV indoor unit (cooling and heating):• Tr(Ts)-Tset ↑ -> EXV opening ↑,

outdoor unit capacity ↑(superheat/subcool decrease) -> more refrigerant flow, more capacity.

• Tr(Ts)-Tset ↓ -> EXV opening ↓, outdoor unit capacity ↓(superheat/subcool increase) -> less refrigerant flow, less capacity.

What are the benefits? When to use this type of control?

• Cheap and simple solution, no need to use the additional controllers, etc.

• You can combine VRV units and AHUs in one system, or connect several AHUs to 1 outdoor unit.

• No supply temperature control, comfort conditions can be affected by hot/cold drafts

You can use this mode if there is no particular supply temperature required or you want to combine VRV indoors and AHUs in one system.

Page 10: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

10

Title - Internal use only19

NECESSARY COMPONENTS AND LIMITATIONS

ERQ/VRV IV Heat Pump 8 and 10 HP

EKEQ*Control Box

EKEXVExpansion Valve

R410A gas

R410A liquid

communication

Thermistors

EXV control Air Handling Unit (AHU)

EKEXV class

63

80

100

125

140

200

250

• To control the temperature of the air leaving or returning to the AHU, by means of an external DDC device (X and W control)

• To control indirectly the room air temperatureby fixing Te or Tc (Y control)

• To control the temperature of the returning air to AHU by means of a Daikin controller (Z control)

EKEQFCBA EKEQD

What do I need for pair application (coil capacity ≤ 25 kW)?

Min 5 m, max. 50 mM

ax +

/-3

0 m

Max. 5 m

Max

+/-

5 m

0-10 V

DDC Controller

Title - Internal use only20

NECESSARY COMPONENTS AND LIMITATIONS

What do I need for pair application (coil capacity > 25 kW)?

VRV IV Heat Pump CH/Non-CHWater cooled VRV

EKEQ*Control Box

EKEXVExpansion Valve

R410A gas

R410A liquid

communication

Thermistors

EXV control Air Handling Unit (AHU)

• To control the temperature of the air leaving or returning to the AHU, by means of an external DDC device (X and W control)

• To control indirectly the room air temperatureby fixing Te or Tc (Y control)

EKEQFCBA

Min 5 m, max. 50 m

Max

+/-

30 m

Max. 5 m

Max

+/-

5 m

0-10 V

DDC Controller

EKEXVclass

200

250

400

500

Page 11: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

11

Title - Internal use only21

NECESSARY COMPONENTS AND LIMITATIONS

What do I need for pair application (coil capacity more than 50 kW, multi-circuit)?

Supply air (or return air) temperature control (X, Y, W)

F1F2 F1F2F1F2

• Max 3 DX kits/AHU• Connection ratio between 90~110%• Temperature control by DDC (0-10 V signal)

EKEQFCBA EKEQFCBA EKEQFCBA

Thermistors

EXV control

0-10 V

EKEXV class

63

80

100

125

140

200

250

400

500

Interlaced coil (max. 3 circuits). Max. capacity =

50 kW x 3 = 150 kW

DDC Controller

EXV control EXV control

Piping length limitations are the same as for single circuit coils:• OU → (each) EXV kit = 5..50 m• EXV kit → AHU = 5 m max.• Level difference between OU and AHU = 30 m max.

VRV IV Heat Pump CH/Non-CHWater cooled VRV

22

NECESSARY COMPONENTS AND LIMITATIONS

Only return air temperature control (Z) is possible. Like VRV indoor units.

F1F2

F1F2

• Connection ratio is limited between90~110%

• Unlimited number of DX kits/AHUs within connection ratio

• Control by iTM II and/or local Daikin controllers (MANDATORY) EKEQMCBA

EKEQMCBA

What do I need for multi application (several AHUs in one circuit)?BRC1(D,E)

BRC1(D,E)

EKEXV

EKEXV

EKEXV class

63

80

100

125

140

200

250

400

500

AHU DX coils. Number of circuits is theoretically

unlimited.

Piping length limitations:• EXV kit → AHU = 5 m max.• The rest are the same as for “normal” VRV

application (check VRV data book/installation manual)

VRV IV Heat Pump

CH/Non-CHWater

cooled VRV

P1P2

P1P2

Page 12: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

12

Title - Internal use only23

NECESSARY COMPONENTS AND LIMITATIONS

Only return air temperature control

(Z) is possible.

F1F2F1F2

F1F2F1F2

Conditions:• Unlimited DX kits/AHUs (within connection

ratio)• Connection ratio between 50~110%• VRV indoors should be min 50% ratio• Control by iTM II and/or individual wired

remote controllers (MANDATORY)

EKEQMCBA

EKEXV

VRV IU VRV IU VRV IU

P1P2 P1P2 P1P2

P1P2EXV control

BRC1(D,E) BRC1(D,E) BRC1(D,E)

AHU DX coil (theoretically unlimited number of circuits)

BRC1(D,E)

VRV IV Heat Pump CH/Non-CHWater cooled VRVVRV IV Heat Recovery

• VRV Indoors are mandatory in this case!

• Hydrobox connection is not possible!

Piping length limitations:• EXV kit → AHU = 5 m max.• The rest are the same as for “normal” VRV application (check VRV data book/installation manual)

What do I need for multi application (AHUs and VRV indoors in one circuit)?

24

NECESSARY COMPONENTS AND LIMITATIONS

What other possibilities do I have?

EKEXVEKEQMCBA

EKEXVEKEQMCBA

EKEXVEKEQMCBA

DX Kit 1

DX Kit 2

DX Kit N

DX

Outdoor Only Z-Control

If for some reason you need to work with more than 3-circuit coil with one outdoor unit, it is possible, but only in Z control mode.

EKEXVEKEQMCBA

EKEXVEKEQMCBA

EKEXVEKEQMCBA

DX Kit 1

DX Kit 2

DX Kit N

DX

Outdoor 1

Outdoor N

Only Z-Control

You can also connect several outdoor units to 1 multi-circuit coil, but only in Z control mode. Thus you can obtain theoretically unlimited capacity.

Coil (multi-circuit)

Coil (multi-circuit)

Page 13: Top secret Internal use only - Recair Oy · PDF file6/8/2016 1 Top secret Secret Internal use only Public VRV to AHU connection Application guide

6/8/2016

13

Title - Internal use only25

COIL REQUIREMENTS

How to select DX coil properly? Is the coil selected by AHU selection software suitable for VRV application?

AHU DX coils Single circuitNo special requirements

Multi-circuit

With face control With row control Interlaced

Circuit 1

Circuit 2

Circuit 1

Circuit 2

Circuit 1

Circuit 2

Problems:• Temperature stratification at partial

load -> comfort issues

Benefits:• Simple construction, cheap

Problems:• Not possible to reach coil capacity

balance -> reliability issues

Benefits:• Simple construction, cheap, compact

Problems:• Complex construction

Benefits:• Even leaving air temperature• Coil capacity balanced

Only this solution is allowed for multi-circuit coils application!

Capacity ≤ 50 kWYES

NO

All these coil types you may get from AHU selection software