COMBINED CYCLE JOURNAL, Third Quarter 2008 105 SPECIAL ISSUE: OUTAGE HANDBOOK POWER AUGMENTATION V irtually everyone directly involved in the design, opera- tion, and maintenance of gas- turbine-based powerplants is well aware of the adverse effects high ambient temperatures and dirty rotating blades and stationary vanes have on compressor performance and power production capability. Cooling inlet air. The most efficient way to maximize output and rev- enue during the warm months, when power prices typically are highest, is by cooling ambient air before it enters the compressor. Recall that gas-turbine (GT) output is directly proportional to the air mass flow rate. But, since the volumetric flow rate is relatively fixed, the mass flow of the turbine decreases as ambient temperature increases—warmer air being less dense. Evaporative coolers, historically the most popular of the technol- ogy alternatives for GT inlet cooling, reduce temperature by evaporation of water that cascades over a wet- ted honeycomb media as air passes through the media. Wetted media can cool the inlet air to within a few degrees of the ambient wet-bulb tem- perature. Fogging has become a popular evaporative tech- nology over the last decade and now there are well over 1000 systems installed on GTs worldwide. They satu- rate GT inlet air by spraying very fine droplets of water into the air stream. Fogging systems are capable of cool- ing the inlet air to the wet- bulb temperature, so they’re more effective than wetted media. Chillers can cool the inlet air to temperatures much lower than those possible with evaporative systems. Mechanical (electric) and absorption (steam) chill- ers can maintain any desired inlet air temperature down to about 42F, independent of ambient wet-bulb temperature. But they have signifi- cantly higher capital and operating costs than evaporative technologies. Negative impacts of compressor fouling include reduced compressor air flow, pressure ratio, and efficien- cy, which cause a “rematching” of the turbine and compressor and a drop in power output and thermal efficiency. At least one expert estimates that fouling is responsible for 70% to 85% of the total performance loss experi- enced by GTs during operation. Out- put losses of between 2% (favorable conditions) and 15% to 20% (adverse conditions) have been attributed to fouling. To learn more, access www. combinedcyclejournal.com/archives. html, click Fall 2004, click “Gain a competitive edge with a better under- standing of GT compressor fouling, washing” on the cover. The two primary methods for maintaining GT compressors at high efficiency are offline and online wash- ing. Goals of the former are to clean a dirty compressor and restore power and efficiency to virtually “new and clean” values. Objectives of online washing are to keep the compressor clean, thereby extending the period between shutdowns required for offline cleaning and retaining desired power output and efficiency. Important to glean from the forego- ing is that injection of water into the inlet air stream and/or directly into the compressor are industry best practices critical to achieving plant pro forma performance and power- production goals. While all OEMs are concerned with what goes into their GTs, compressors for the 7F series of engines manufactured by GE Ener- gy, Atlanta, may be more sensitive than at least some others to impinge- ment by water droplets associated with evaporative cooling and online washing. This conclusion by the editors is drawn from user comments regard- ing operating restrictions imposed on customers by several of the OEM’s technical information let- ters (TILs), most recently TIL 1603. Users have told the editors that this let- ter, released in mid 2008, strongly suggests that cus- tomers comply with its oper- ating guidelines to mitigate erosion of blades in the first stage of the compressor— so-called R-zero (R0). Owners with OEM service agreements presumably would jeopardize their con- tracts if they didn’t imple- ment the 1603 directives. Those not bound by GE agreements might decide to do otherwise, but could run afoul of insurance carriers that believe OEM guide- lines should be followed. Several owner/operators told the editors that the OEM’s TIL recommends To fog or not to fog: What is the answer? Learned at Next meeting: Apr 19-23, 2009 Birmingham (Ala) Sheraton Details at www.ctotf.org

Transcript of To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of...

Page 1: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

COMBINED CYCLE JOURNAL, Third Quarter 2008 105

SPECIAL ISSUE: OUTAGE HANDBOOK POWER AUGMENTATION

Virtually everyone directly involved in the design, opera-tion, and maintenance of gas-turbine-based powerplants

is well aware of the adverse effects high ambient temperatures and dirty rotating blades and stationary vanes have on compressor performance and power production capability.

Cooling inlet air. The most efficient way to maximize output and rev-enue during the warm months, when power prices typically are highest, is by cooling ambient air before it enters the compressor. Recall that gas-turbine (GT) output is directly proportional to the air mass flow rate. But, since the volumetric flow rate is relatively fixed, the mass flow of the turbine decreases as ambient temperature increases—warmer air being less dense.

Evaporative coolers, historically the most popular of the technol-ogy alternatives for GT inlet cooling, reduce temperature by evaporation of water that cascades over a wet-ted honeycomb media as air passes through the media. Wetted media can cool the inlet air to within a few degrees of the ambient wet-bulb tem-perature.

Fogging has become a popular evaporative tech-nology over the last decade and now there are well over 1000 systems installed on GTs worldwide. They satu-rate GT inlet air by spraying very fine droplets of water into the air stream. Fogging systems are capable of cool-ing the inlet air to the wet-bulb temperature, so they’re more effective than wetted media.

Chillers can cool the inlet air to temperatures much lower than those possible with evaporative systems. Mechanical (electric) and absorption (steam) chill-

ers can maintain any desired inlet air temperature down to about 42F, independent of ambient wet-bulb temperature. But they have signifi-cantly higher capital and operating costs than evaporative technologies.

Negative impacts of compressor fouling include reduced compressor air flow, pressure ratio, and efficien-cy, which cause a “rematching” of the turbine and compressor and a drop in power output and thermal efficiency.

At least one expert estimates that fouling is responsible for 70% to 85% of the total performance loss experi-enced by GTs during operation. Out-put losses of between 2% (favorable conditions) and 15% to 20% (adverse conditions) have been attributed to fouling. To learn more, access www.combinedcyclejournal.com/archives.html, click Fall 2004, click “Gain a competitive edge with a better under-standing of GT compressor fouling, washing” on the cover.

The two primary methods for maintaining GT compressors at high efficiency are offline and online wash-

ing. Goals of the former are to clean a dirty compressor and restore power and efficiency to virtually “new and clean” values. Objectives of online washing are to keep the compressor clean, thereby extending the period between shutdowns required for offline cleaning and retaining desired power output and efficiency.

Important to glean from the forego-ing is that injection of water into the inlet air stream and/or directly into the compressor are industry best practices critical to achieving plant pro forma performance and power-production goals. While all OEMs are concerned with what goes into their GTs, compressors for the 7F series of engines manufactured by GE Ener-gy, Atlanta, may be more sensitive than at least some others to impinge-ment by water droplets associated with evaporative cooling and online washing.

This conclusion by the editors is drawn from user comments regard-ing operating restrictions imposed on customers by several of the OEM’s

technical information let-ters (TILs), most recently TIL 1603. Users have told the editors that this let-ter, released in mid 2008, strongly suggests that cus-tomers comply with its oper-ating guidelines to mitigate erosion of blades in the first stage of the compressor—so-called R-zero (R0).

Owners with OEM service agreements presumably would jeopardize their con-tracts if they didn’t imple-ment the 1603 directives. Those not bound by GE agreements might decide to do otherwise, but could run afoul of insurance carriers that believe OEM guide-lines should be followed.

Several owner/operators told the editors that the OEM’s TIL recommends

To fog or not to fog: What is the answer?

Learned at

Next meeting: Apr 19-23, 2009Birmingham (Ala) Sheraton

Details at www.ctotf.org

Page 2: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

106 COMBINED CYCLE JOURNAL, Third Quarter 2008

SPECIAL ISSUE: OUTAGE HANDBOOKPOWER AUGMENTATION

Users, consultants share fogging views, experiences

After listening to Thomas Mee at the CTOTF’s Fall Turbine Forum in Tucson, the editors contacted

several users and consultants regard-ing their views and experiences with fogging—most specifically, its impact on compressor-blade erosion. The effort to provide more balanced cover-age of the on-going industry debate did not achieve the level of success envisioned. Calls were initiated during the busy outage season and, under-standably, many were not returned. Below are “sound bites” from con-versations with the editors and e-mail replies to specific questions.

Economic justification for fogging. A cross section of the industry offered the following:n Expect fogging to increase power

output by 7% to 8% given 20 deg F of cooling. One user’s calcula-tions was based on ambient condi-tions of 95F dry bulb, 75F wet bulb.

n Heat rate may improve by as much as a few percent; exact number depends on cycle arrangement and site conditions. The heat-rate improvement on a combined-cycle plant is negligible.

n Double-digit NOx emissions reductions are possible on some engines under certain conditions.

n Lower capital cost than other tra-ditional inlet-air cooling options. One user put the total installed cost per “fogging kilowatt” at about $70 for 7EAs and $80 for earlier GTs—certainly inexpensive peak power. All systems were ret-rofitted.

n Another user’s calculations showed the annual owning/oper-ating cost of a fogging system for a 7FA was $200,000 per annum less than that for a media-type evap cooler. Reasons include efficiency and output losses associated with the pressure drop across the wetted media. This is true even when one considers the higher cost of the demineralized water required for fogging. Comments specific to the 7FA fog-

ging debate:n We fog several 7FAs. Knowing

there are serious consequences to wet R0s, we are cautious and dili-gent about monitoring. We expect some erosion and consequently follow the guidelines of TIL 1603 very closely. We also fog 7EAs but don’t have the same level of con-cern regarding erosion damage to them that we have for the 7FAs.

n The OEM should develop more

specific and quantitative blade-deterioration criteria than the 8-mil erosion limit that it has specified. Once the 8-mil limit is reached, you have to operate dry. Our expe-rience indicates you will erode 8 mils quickly when conducting reg-ular online water washes. I believe washing has a far greater impact on erosion than fogging.

n Anything that damages the leading edge of a compressor blade reduc-es its fatigue resistance and that blade will crack sooner than one not so damaged. But the root cause of R0 cracking is blade harmonics—period. My experience indicates the OEM’s fogging system is a mainte-nance nightmare and it is linked to leading-edge erosion.

n We do offline water washes only, no online washing (multiple responses).

n Plant’s 7241 7FA with a flared compressor and enhanced P-cut blades operates in base-load com-bined-cycle service. It is fogged about 1500 hr/yr. The enhanced P-cuts, which replaced original non-P-cut blades, have a service history spanning more than 16,000 hours and have been inspected six times. Blades have noticeable ero-sion but the OEM does not require dental molds on airfoils of this design.

The original fogging system was installed downstream of the inlet bleed-heat header and just upstream of the trash screen and inlet duct elbow, above the compressor inlet. It was replaced nearly four years ago with a more robust system having nearly twice the number of spray nozzles and relocated to just behind the inlet filters. The new array’s 0.006-in. orifice nozzles replaced 0.008-in. nozzles.

Online washing is done every other day when temperature is above 50F; offline washing is a semi-annual event. Goal when the fog system is in service: 90% relative humidity as determined by Vaisala Inc instrumentation at the compressor inlet. Fogging is initiated automatically when ambi-ent temperature reaches 62F. A nozzle monitoring system warns when low pressure or high flow is indicated. Plant periodically experiences filter plugging and the affected filters are replaced when this occurs.

n Cracked R0 blades have been

found on a significant percentage of units inspected in the last nine months of 2008. Industry scuttle-butt is that the OEM will be issu-ing (no date known) a technical information letter recommending initial-inspection and reinspec-tion guidelines as well as a rec-ommended inspection interval.

n Online wash five minutes daily. No other information provided.

n Dovetail cracks found on R0 blades of one GT in a 2 × 1 con-figuration after only 1600 hours of operation and 132 starts. No water ever was used in the machine at this plant, which is located well inland (no “ring of fire” effects).

n Cracking found on R0 blades of 7FAs located more than 25 miles from the coast. These units sit across the fence from another OEM’s GTs which are problem-free.

n Plant was commissioned with standard R0 blades. They were replaced a year later with P-cuts to mitigate the risk of blade liberation resulting from leading-edge ero-sion and/or FOD. In less than three years, the P-cuts were refitted with standard blades to mitigate risk from P-cut cracking. Plant then stopped fogging to prevent the possibility of blade erosion; units never had been washed online. Despite the precautions, a crack was found in one of the pristine blades two years later.

n We have done only one offline wash on this unit, never an online wash. No other information pro-vided.

n Our 7FA Model 7221 (unflared compressor) in base-load com-bined-cycle service was fogged approximately 1500 hr/yr for about nine years. Fogging stopped when P-cut blades were removed and replaced with non-P-cut airfoils. The original R0 blades had more than 12 mils of erosion after about six years of fogging service when replaced with P-cuts. Approximate-ly three years later the P-cuts were removed. The OEM UT-inspected the blades and errantly condemned them for cracking that could not be confirmed off the engine.

Online washing is done every other day when temperature is above 50F; offline washing is a semi-annual event. Fogging array with nearly 900 nozzles is located just behind the inlet filters; silencer,

Page 3: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

COMBINED CYCLE JOURNAL, Third Quarter 2008 107

time limits for online washing that depend on the design of R0 blades installed. Recall that the OEM has changed the design of its blades sev-eral times since the first F-class unit went into operation.

TIL 1603 also is said to present intervals for so-called “dental-mold” impressions of the leading edges of R0 blades to determine if erosion is within what the OEM considers safe limits. If it is not, repairs may be required to mitigate cracking risk.

A concern of several users who spoke with the editors was that the recommended intervals between inspections for erosion were of rela-

tively short duration (in some cases, 100 hours of “wet” operation or less). Wet operating hours are defined as hours of operation with fogging, water wash, or with an evapora-tive cooler that has water droplets stripped off because of improper design/operation. As for the expenses associated with inspection (staff and outage time, lab costs, etc), who pays? A rhetorical question: the owner, of course. Is the expense bud-geted? Doubtful.

A few plant personnel a lso expressed concerns about a level playing field. They said the inspec-tion interval associated with a non-

Need More Power?

Fog inlet cool ing – starting from only $25/kW

Changing the way the world boosts power

MeeFog increases output by as much as 20%.

Over 700 gas turbine installations worldwide.

Reduces CO2 and NOx emissions.

Easy retrofit, only 1-3 day outage.

Improves heat rate.

1-626-359-4550 www.meefog.com/gtpower

Inlet fogging boosts gas turbine power.

On over40 GE 7FA

units

Users, consultants share fogging views, experiences inlet bleed-heat header, and trash screen are downstream of the nozzle array.Years of fogging experience on

several dozen 7EAs and earlier engines allowed a major user to offer others in the industry the following observations:n Fogging is an inexpensive but very

effective way of boosting power output in warm weather.

n O&M effort generally is low-level and low-cost.

n Zinc deposits on inlet guide vanes (IGVs) and other compressor parts were caused by high-purity fog water washing off the galvanizing from inlet silencers.

n Accelerated corrosion of non-stain-less inlet ductwork and plenums was experienced, driving replace-ment with stainless steel parts.

n More rapid corrosion of IGVs caused binding and pivot-shaft breakage on old units.

n Sufficient inlet-duct and plenum drainage is very important.

n Proper winterization is necessary to avoid freeze damage to spray nozzles and headers.

n Seal debris from high-pressure fogging pumps can plug nozzles.

n Biological fouling of nozzles will occur if fogging systems remain unused and full of water for several weeks.

n Dental molds taken at the request of the OEM revealed negligible erosion after years of summertime fogging use during peak periods. Total fogging hours numbered less than 1000 on any machine.Final notes:

n Positive results with both fog-ging and wet compression have been profiled at meetings of the Western Turbine Users, which focus on GE aeros. In fact, at the 2007 meeting one user presenter suggested upgrading to a fog-ging system if you have difficulty maintaining evap-cooler efficiency (access www.combinedcyclejour-nal.com/archives.html, click 2Q/2007, click “Western Turbine Users” on the cover and scroll to subhead “Keep compressor inlet cool, clean to ensure top perfor-mance” on p 28.

n Noteworthy, perhaps, is that while one OEM is striving to keep water out of its compressors, another is responding to customer interest by promoting wet compression in its large frames. For details, access www.combinedcyclejournal.com/archives.html, click 2Q/2008, click “D5-D5A Users” on issue cover.

Page 4: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

108 COMBINED CYCLE JOURNAL, Third Quarter 2008

SPECIAL ISSUE: OUTAGE HANDBOOKPOWER AUGMENTATION

OEM evaporative cooling system was five times that of the interval suggested for the OEM’s offering. At least one user considered that unfair; he believes his third-party vendor’s evaporative system is superior to the OEM’s. While a statistically valid and objective survey on the subject is virtually impossible to conduct, it is possible to visually quantify the amount of water in droplet form being ingested by the compressor during fogging operation.

Someone else said that the inspec-tion intervals for the online washing system provided with his 7FA were less than 50 hours and the washing duration was limited to only a few minutes daily. However, if he could get the owner to buy the OEM’s latest washing system, the inspection inter-val would go up about 20-fold and the daily wash cycle could return to what this user considered “normal.”

That’s probably not going to hap-pen. With the current state of the economy, it’s not unusual to hear that capital budgets have been frozen and also that maintenance intervals are being extended. Short-staffed and under-funded, some plant man-agers say they no longer afford to do online water washes, just offline washes a couple of times annually.

There are obvious fuel and capac-ity penalties associated with that operating philosophy in most areas of the country. But perhaps those costs are charged to “a different budget.” For example, if the plant is “regu-lated,” the fuel-cost increase attrib-uted to a dirty compressor might be a “pass-through” to the customer.

There’s a strong connection between compressor fouling and the effective-ness of inlet-air filtration. In some locations, it may make sense to con-sider the installation of HEPA filters ahead of the compressor if elimina-tion of online washing is a goal. Expe-rience at several plants with Mit-subishi F- and G-class engines has been positive. The editors have not been able to identify anyone with GE machines doing this yet. If you are, please write [email protected].

Owner/operators also should not overlook the potential value of coat-ings on compressor blades. Titanium nitride and other formulations show promise in protecting against solid-particle impact damage as well as liq-uid-droplet erosion (access www.com-binedcyclejournal.com/archives.html, click 2Q/2008, click WTUI on issue cover and scroll to “Advancements in compressor coatings” on p 52). Keep in mind that an OEM service agreement may preclude the use of coatings—at least those not offered by GE.

Erosion concerns in GE F frames may just disappear with the planned introduction of the OEM’s new com-pressor rotor in spring 2009. Howev-er, cost undoubtedly will be an issue.

A third-party alternative, also expected in the spring, is said to offer redesigned airfoils to accommodate as much online washing and inlet-air evaporative cooling as users might want to use. This would be a far-less-costly alternative, but it undoubtedly would violate the terms of the OEM’s service agreements. Plus, this solu-tion would require your insurer’s approval.

CTOTF looks for answersThe roiling controversy over whether evaporative inlet cooling systems and/or online washing systems can be held accountable for R0 blade erosion—and if one or both can, to what degree—was the motivation for inviting Thomas Mee III, chairman and CEO, Mee Industries Inc, Monrovia, Calif, to address delegates to the CTOTF 2008 Fall Turbine Forum on fog-ging technology.

Mee participated in the group’s GE Roundtable in mid September, focusing on optimizing fog evaporation and min-imizing compressor water ingress. Dominion Energy’s Larry Rose, vice chairman of the roundtable, moderated the session. Previously, members of the Combustion Turbine Operations Task Force had heard from a representative of Gas Tur-bine Efficiency, Orlando, Fla, on the technology of online washing (access www.combinedcyclejournal.com/archives.html, click 2Q/2006, click “CTOTF” on issue cover and scroll to p 56).

By way of background, Mee Indus-tries has supplied nearly 750 fogging systems for GTs worldwide (81 for GE F frames) and it claims global market leadership in this sector. Many Mee systems have more than 10 years of experience; also, a sig-nificant percentage were designed for wet compression—so-called high fogging (access www.combinedcy-clejournal.com/archives.html, click spring 2004, click “Recent experience indicates wet compression meets expectations when done correctly” on issue cover).

The challenge for any moderator of an electric-power industry meeting is to keep supplier presenters focused on the technology and to resist the temptation to discuss features and

benefits. Judging from a few user comments, Mee met expectations. He can talk endlessly, or so it seems, about the physics of water droplet behavior in GT systems. One reason is the company’s history of research on the subject. A “summary” of this work is presented in three compre-hensive papers published as part of the “Proceedings of ASME Turbo Expo 2002.”

Mee’s message was that fog drop-lets don’t directly cause erosion. While compressor suctioning of unat-omized, flowing, and pooling water is potentially conducive to problematic wear and tear of R0 blades, proper design of fog and drain systems can prevent damage from these sources.

He began with a brief discussion of factors critical to the design of an effective fogging system. Drop-let size is of primary importance because small droplets evaporate

quickly. Those too large to evaporate in less than two seconds—the approximate time it takes air passing through the inlet filters to reach the compressor—will either fall out on the duct floor or enter the compres-sor.

The majority of existing fogging systems use either impaction-pin (Fig 1) or

swirl-jet nozzles. “Both nozzles create an expanding conical spray plume,” Mee told the group, “which gets pro-gressively thinner as it moves away from the orifice.” Eventually, turbu-lence created by the interaction of the high-velocity water jet with the surrounding air causes the plume to break apart. Surface tension causes

Mee

1. Most fogging systems use either the impaction-pin (shown) or swirl-jet nozzle. Both create an expanding conical spray plume, but the former is said to produce droplets of smaller size

Impaction pin Orifice diameter, 150 microns

O-ring seal

Type-316 stainless steel

Stainless steel water distribution tube

Replaceable internal filter captures particles down to 40 microns

Page 5: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

COMBINED CYCLE JOURNAL, Third Quarter 2008 109

SPECIAL ISSUE: OUTAGE HANDBOOK POWER AUGMENTATION

the water particles to adopt a spheri-cal shape.

Impaction-pin nozzles form a

conical plume by impacting the high-velocity water jet from an open orifice against the small pin shown in the illustration. Research by Mee Industries indicated that impaction-pin nozzles produce smaller droplets than swirl-jet nozzles when com-pared on a level playing field—that is, the same flow rate, pressure, etc.

Specifically, Mee Industries’ impaction-pin nozzles are designed to produce a fog in which 90% of the droplets are 20 microns or smaller. To put this in perspective, consider that the average human hair is 100 microns in diameter (Fig 2).

Size really does matter. Mee took a

few minutes to discuss the physical nature of water droplets. “Droplets are spheres,” he said, “and thinking of them only in terms of diameter can be very misleading.” When someone speaks of a 30-micron droplet that seems very small, he continued, but it has nearly three-and-a-half times the mass of a 20-micron droplet and falls out of the air stream twice as fast (Fig 3).

Laboratory tests conducted by Mee Industries determined that 20-mi-cron droplets were “table stakes” in the design of a fog system for the sen-sitive 7F frame (Figs 4 and 5). Mee said this was confirmed in the field.

2. Impaction-pin nozzles produce a fog with 90% of the droplets 20 microns or smaller, Thomas Mee told CTOTF attendees in explaining the capabilities of his company’s product

20-micron droplet

Strand of hair, 100 microns

3. Droplets are spheres and thinking of them only in terms of diameter can be very misleading

20-microndroplet

■ 3.4 times more mass and force of impact than a 20-micron droplet

■ 33% less surface area per unit volume

■ Rate of fall is twice as fast■ Twice the potential for

fallout from centrifuging

30-micron droplet

60-micron droplet■ 27 times more mass and force

of impact than a 20-micron droplet

■ 66% less surface area per unit volume

■ Rate of fall is nine times faster■ Nine times the potential for

fallout from centrifuging

4. Smaller droplets produced by impaction-pin nozzles create a smoke-like white plume

Page 6: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

110 COMBINED CYCLE JOURNAL, Third Quarter 2008

SPECIAL ISSUE: OUTAGE HANDBOOKPOWER AUGMENTATION

In Fig 4, note that the small droplets produced by impaction-pin nozzles create a smoke-like white plume that spreads to a diameter of about 12 inches only about a foot from the spray nozzle.

A comparison photo shown to attendees revealed that the larger droplets from swirl-jet nozzles pro-duced a plume with a defined edge and a spray that is less opaque.

Another important fact: Measure-ments taken during the lab tests show that droplets cease to coalesce inside the spray plume less than a foot from the nozzle—in fully humidi-fied air. This means that it’s impor-tant to measure droplet size far enough from the nozzle orifice to get the true size of droplets produced by that nozzle.

Location, location, location. Fun-damentals reviewed, Mee explained why he believes the 7F series of machines is seeing more water at the compressor inlet than necessary. Fig 6 shows that the OEM’s recom-mended location for fog nozzles in its F frames generally does not allow sufficient time for droplet evapora-tion and can lead to flowing water at the compressor inlet.

Referring back to Fig 5, note that droplet diameter after one second of evaporation time is about five times

larger than after two seconds. It fol-lows, Mee continued, the more time you allow for evaporation the less likely it is for an R0 blade to experi-ence erosion on the leading edge.

He suggested locating the nozzle array immediately downstream of the

air filters (Fig 7). This would allow about two seconds for evaporation—twice the time available than when following the OEM’s guidelines for fog-nozzle location. Mee mentioned that his company’s first fog system for an F-series machine was designed

0

20

40

60

80

100

0 0.5 1 1.5 2Time, sec

0

6

12

18

24

30

5. Chaker diagram illustrates how quickly 20-micron droplets evaporate on a dry summer day

Rel

ativ

e hu

mid

ity, % Relative humidity

Air temperature

Droplet diameter

Dia

met

er, m

icro

ns/A

ir te

mpe

ratu

re, C

6. OEM’s recommended location for fog nozzles in its F frames generally does not allow sufficient time for droplet evaporation and can lead to flowing water at the compressor inlet

Recommended nozzle location allows droplet residence time of more than two seconds

OEM’s nozzle location allows droplet residence time of less than one second

7. Fog-nozzle manifold immediately downstream of the air inlet filters allows about two seconds for droplet evaporation in a typical 7FA

8. The large variation in air velocity across the inlet duct must be considered when design-ing a fogging system. More nozzles are needed in areas of high velocity, fewer where the velocity is relatively low (above)

Install more fog nozzles in this high-velocity area of the inlet duct

13 ft/sec

11 ft/sec

6 ft/sec

3 ft/

sec

9. Improper design of the fogging system results in flowing water at the compressor inlet and a greater likelihood of erosion damage to first-stage blades (left)

Flowing water on the duct wall is sucked over the inlet scroll

Water flowing down the rear wall accumulates on the inlet cone and can be sucked into the compressor

Air flow prevents pooled water from draining away

11. Small gutter installed around the compressor inlet prevents suctioning of water over the bellmouth. Details provided here are patent-protected

FRONT VIEW

Compressor inlet

Duct wall Expansion joint

Stainless steel gutter

TOP VIEW

10. A proper system for removing flowing water minimizes the probability of erosion damage

Floor gutters and drains

Wall gutters and drains (details in Fig 12)

Gutter around inlet (details in Fig 11)

Perforated plate and drain

Consider relocating trash screen

False floor allows water to drain away

Page 7: To fog or not to fog: What is the answer? - ccj- · PDF file... and maintenance of gas-turbine-based powerplants ... efficiency are offline and online wash- ... n We do offline water

COMBINED CYCLE JOURNAL, Third Quarter 2008 111

this way. After fogging well over 1000 hours annually for nearly 10 years, the operator reported relatively little blade erosion attributable to fogging.

Mee paused to discuss the impor-tance of proper nozzle manifold design in preventing water accumulation at the compressor inlet. He showed a CFD (computational fluid dynam-ics) plot at the filter wall of a typical 7FA to illustrate the large variation in velocity across the ductwork (Fig 8). The message: Air velocity must be considered by designers in the place-ment of nozzles to avoid localized over-saturation. Translation: More nozzles are required in high velocity areas than in low-velocity regions of the ductwork.

However, no matter how tight the design, the inlet-air system is dynamic and sensitive to changes in air temperature, humid-ity, wind direction and velocity, GT load, etc. This makes it impossible to “tune” the system to main-tain the ideal 100% satura-tion condition at the com-pressor inlet throughout a given production run.

Windows at the bellmouth for visual inspection of pooling or running water are a good idea. Flowing

water at the inlet can be avoided by setting the fog system control param-eter so the system always slightly “under-fogs.” This can dramatically reduce the amount of water at the compressor inlet.

Mee then showed attendees where to look for flowing water during oper-ation (Fig 9):n On ductwork walls; be sure it is

not being sucked over the inlet scroll.

n On the rear wall; be sure it is not accumulating on the inlet cone and being sucked into the com-pressor.

n On the floor; be sure pooled water is not being sucked into the com-pressor.

Locating spray nozzles as close to the air filters as practical and designing the nozzle array to accom-modate the velocity profile across the ductwork are critical to success, for sure. But proper design and arrange-ment of gutters and drains also are necessary to provide the contingency to accommodate varying operating conditions.

Fig 10 shows where Mee recom-mended gutters and drains to mini-mize the probability of free water gaining access to the compressor. Also note the recommendation for moving the trash screen further upstream than the OEM’s traditional placement—this to prevent conden-sation of fog and the formation of

large droplets close to the compressor inlet.

Fig 11 shows details of the small gutter Mee Indus-tries installs around the compressor inlet to prevent suctioning of water over the bellmouth; Fig 12 the details of wall gutters and drains. Mee mentioned the company has a patent that covers methods for remov-ing flowing and pooling water from the inlet ducts so it cannot be suctioned into the compressor as un-atomized water. ccj

12. Wall gutters and drains are important for preventing water ingestion into the compressor

Compressor inlet

Cover prevents high-velocity air from scooping water out of stainless steel gutter

Wall gutter is locatedabove expansion joint to prevent water from becoming airborne as it flows over expansion joint