8/3/2019 Timers 7PU60
1/2
I
The Siemens 7PU60 20 Timersprovide adjustable star timei.e.[(2-20/6-60 sec)/(20-200 sec)]and fixed Star to Delta transfertime (i.e. 50 ms)
Technical Data
Rated insulationVoltage : 500V AC
Setting time ranges
Type Setting time range7PU60-20-3N.. 2-20/6-60 secs.
(can be selectedwith selectorswitches)
7PU60 20-4N.. 20-200 secs(Selector Switch isnot functional)
Operating temperature:-25C to + 55C
Rated operatingCurrent : Ie AC 15 at 220V=3A
at 440V=1AIe DC 13 at 220V=0.1A
Operating Voltage range :
Not Applicable for 7PU6020 3NW20.8 to 1.1 x Us(Us = Rated Voltage)
Setting accuracy: 25% in sectorscale
Recovery time: 150 msRepeat accuracy: 0.5%
Selection
Timers type 7PU60 203N..areprovided with 2 time setting
ranges. Selection of range is donewith Selector Switch, Provided onthe front plate of timer. Timer type7PU60 204N.. has one settingrange (Selector switch is notfunctional)
AC Voltage Voltage Code110V J2
220/240V N2380/440V T2220/400V W2
Installation
Snapped on standard DIN
mounting rail (35 mm) to EN50022
orFixed by two M 3.5 screws on aplain surface. Plain washers and
Electronic Star Delta TimerType: 7PU60 20
Operating Instructions
spring washers must be used.
For mounting dimension refer fig-1
Can be mounted in any position.
Allowable conductor
Cross Section.
Solid 2 x 2.5 mm2
Stranded with end sleeves:
2 x 1.5 mm2
Terminal screws: M3.5
Tightining Torgue: 80 to 120 NCm
Terminal diagram:
See front plate of the timer
Functional diagram:
Ref. Fig: 2
1) Apply rated voltage to terminalsA1/A2
2) Y contact (17/18) closes
instantanously and remainsclosed for set time ty which is
adjustable between 2-20/6-60/20-200 sec.
3) D contact (27/28) closes afterset time (ty) + dead time (td)(i.e. Star to Delta transfertime + 50 ms)
Fig. - 1
15
23.5
2112
DIN Rail mounting feature
88
95
M3.5 Fixing screws (2X)
Fig. - 2
-
8/3/2019 Timers 7PU60
2/2
Connection Diagram:
Control Circuit Wiring DiagramRefer Fig 3
1/N/PE ~ 50Hz Supply
S0 = Push Button OFF (1NC)
S1 = Push Button ON (1NO)
K1 = Line Contactor with 2NO
Auxiliary Contacts.
K2 = Star Contactor with 1NO + 1NCAuxiliary Contacts.
K3 = Delta Contactor with 1 NCAuxiliary Contacts.
K4 = Star Delta Timer with 1NOinstantaneous and 1NO delayed
Auxiliary Contacts.F1 = Overload Relay.
F0 = Backup Fuse.
Main Circuit Wiring DiagramRefer Fig 4
3 ~ 50Hz V
K1 = Line Contactor
K2 = Star Contactor
K3 = Delta Contactor
F1 = Overload Relay
F0 = Backup Fuse
Siemens Ltd.SGR-01-111-006This replaces SGR-01-111-005
Product development is a continuous process. Consequently
the data indicated in this leaflet is subject to change withoutprior notice. For latest issue contact our sales offices.
Instruction No. 4I00880115786 203