TIDBITS
• Hose made pryor to July 1987 will be taken out of service
• Hose that is frozen will be service tested again• Color’d Hoses• All test gauges to have been calibrated in the
last 12 months• MARK COUPLINGS FOR SLIPPAGE
• Check condition of hose test machine.• Make sure caps are on fire hose outlet
connection• Pressure up to 10% higher than service test
needed. 330• Hold pressure for 3 minutes with pump off.• TEST OF MACHINE DONE
Time to test hose
• Apply nozzle to no more than 300 ft of hose.• Charge hose to 45 psi, make sure to discharge
air from line. Check all couplings tighten with spanner.
• Raise pressure no more than 15psi per sec. until desired pressure is reached.
• Allow 1 minute of stabilization per 100ft• Hold service test pressure for 3 minutes
INFO
• If you walk the layout stay 15 ft from the left side of the hose. The left side is defined as the side that is left when facing the free end
• Never stand in front of the free end of the hose , the right, and no less than 15 ft on the left side. Never straddle the hose.
• N• Connect no more than 300 ft hose to valve.• Hose test valve end shall be secured with a
belt tie in or rope hose tool at a point 10 to 15 in from the coupling
• Apply nozzle to no more than 300 ft of hose.• Charge hose to 45 psi, make sure to discharge
air from line. Check all couplings tighten with spanner.
• Raise pressure no more than 15psi per sec. until desired pressure is reached.
• Allow 1 minute of stabilization per 100ft• Hold service test pressure for 3 minutes
OTHER HOSE
• BOOSTER HOSE• 110 percent of maximum working pressure or• normal highest pressure used in the system
• SUCTION HOSE• Attached to suction source• Free end sealed with disk and connected to accurate
vacuum measuring instrument.• A 22 in. mercury vaccum shall be developed.• Hold for 10 mins.