Tibbie Base Paper 2

download Tibbie Base Paper 2

of 13

Transcript of Tibbie Base Paper 2

  • 8/8/2019 Tibbie Base Paper 2

    1/13

    IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005 425

    On the Practical Design of a Sliding ModeVoltage Controlled Buck Converter

    Siew-Chong Tan , Student Member, IEEE, Y. M. Lai , Member, IEEE, Martin K. H. Cheung, andChi K. Tse, Senior Member, IEEE

    AbstractThis paper presents a simple and systematic approachto the design of a practical sliding mode voltage controller for buckconverters operating in continuous conduction mode. Various as-pects of the design, including the associated practical problems andthe proposed solutions, are detailed. A simple and easy-to-followdesign procedure is also described. Experimental results are pre-sented to illustrate the design procedure.

    Index TermsBuck converter, continuous conduction mode,hysteresis band, sliding mode control, variable structure system.

    I. INTRODUCTION

    SLIDING mode (SM) controllers were introduced initially

    for variable structure systems (VSS) [1][4]. Characterized

    by switching, dc/dc converters are inherently variable structured

    [5]. Therefore, it is appropriate to apply SM controllers to dc/dc

    converters. This is especially true for buck converters operating

    in the continuous conduction mode (CCM), which have measur-

    able continuous controllable states (output voltage and its time

    derivative) [5], [6].

    Although well known for their stability and robustness toward

    parameter, line, and load variations (ability to handle large tran-

    sients), SM controllers are seldom used in power converters.

    This is mainly due to the lack of understanding in its design

    principle by power supply engineers [7], as well as the lack of a

    systematic procedure in existing literature, which can be used to

    develop such controllers. This can be attributed to the fact that

    much of the work on the subject has been reported from the con-

    trols viewpoint, rather than the circuits viewpoint. Hence, the

    focus had been on the theoretical aspects of the control, while

    the practical aspects of the implementation are still rarely dis-

    cussed [5][13].

    Consequently, many design issues pertaining to the im-

    plementation of SM controlled converters have not been

    sufficiently covered. One such issue is on the design and

    constriction of the converters switching frequency. Althoughdifferent methods (hysteresis; constant sampling frequency;

    constant on-time; constant switching frequency; and limited

    maximum switching frequency) were proposed to limit the

    switching frequency [14], they fall short of a set of systematic

    design methods and implementation criteria.

    Manuscript received August 22, 2003; revised July 30, 2004. This work wassupportedby a Grant provided by The Hong Kong Polytechnic University underProject G-T379. Recommended by Associate Editor P. Mattavelli.

    The authors are with the Department of Electronic and Information Engi-neering, Hong Kong Polytechnic University, Hong Kong (e-mail: [email protected]).

    Digital Object Identifier 10.1109/TPEL.2004.842977

    Concurrently, there was also an alternative approach of

    limiting the switching frequency, which is through the incor-

    poration of a constant ramp function into the controller to

    determine the switching of the converter [7], [15]. The main

    advantage of this approach is that the switching frequency

    is constant under all operating conditions, and it is easily

    controllable through varying the ramp signal. Basically, there

    are two methods of implementing this constant frequency

    operation. The first method is to encode the ramp signal into

    the discontinuous SM switching function of the controller [15].The advantage of this method is that it is straightforward and

    simple to implement. However, this comes at an expense of

    additional hardware circuitries, as well as deteriorated transient

    response in the systems performance caused by the superpo-

    sition of the ramp function upon the SM switching function.

    The second method is to compare the continuous input signal

    (commonly termed as ) generated from the SM equations

    derived from the equivalent control method, with the ramp

    waveform to create the switching operation [7]. Conceptually,

    this is analogous to the way in which fixed switching frequency

    is obtained in classical PWM control schemes whereby the

    control signal is compared to the ramp waveform [16]. The

    advantage of this method over the previous method is thatthere is no need for additional hardware circuitries since the

    switching function is replaced by the PWM modulator and that

    transient response is not deteriorated. However, the drawback

    of this method is that the implementation of the equivalent

    control law to obtain requires computations that are too

    complicated to be implemented with analog controllers [8]. On

    the other hand, even though possible, the implementation of

    digital controllers on power converters is costly and unpopular.

    Considering that these methods were introduced with the pri-

    mary objective of suppressing high switching frequency [14],

    their disadvantages probably outweigh their advantages since

    this may easily be performed by controlling the hysteresis bandof the SM switching function.

    Hence, one objective of this paper is to introduce a mathemat-

    ical model for the hysteresis band method that was originally

    proposed in [14], so that engineers may conveniently adopt it

    for the implementation of the SM controller. Nevertheless, this

    paper is still principally focused on introducing a simple ap-

    proach that is easily applicable in the development of a sliding

    mode voltage controlled (SMVC) buck converter, to bridge the

    gap between the control principle and circuit implementation.

    To present a complete exposition, mathematical derivations and

    theoretical analyzes which extend from the work of [5] are firstly

    performed. Moreover, the approach is presented in a manner

    0885-8993/$20.00 2005 IEEE

  • 8/8/2019 Tibbie Base Paper 2

    2/13

    426 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    Fig. 1. Basic structure of an SMVC buck converter.

    involving only a standard SMVC buck converter model and

    some simple guided steps and design equations. This allows de-

    signer to skip through laborious preliminary derivations when

    performing the controllers design.

    Section II details the theoretical derivation of an ideal SMVC

    buck converter, the description of the problems associated withpractical implementation, and the proposed solutions to these

    problems. Section III presents a standard converter model with

    a simple design procedure. In Section IV, the experimental re-

    sults under various operating conditions are given. These exper-

    iments were conducted on a converter that was designed using

    the proposed procedure. Finally, Section V gives the conclusion

    to the paper.

    II. THEORETICAL DERIVATION

    This section covers the theoretical aspects of the SMVC con-

    verter. Complete mathematical derivations of both the ideal andpractical converter designs are presented.

    A. Mathematical Model of Buck Converter

    To illustrate the underlying principle, the state space descrip-

    tion of the buck converter under SM voltage control, where the

    control parameters are the output voltage error and the voltage

    error dynamics (in phase canonical form) [8], is first discussed.

    Fig. 1 shows the schematic diagram of an SMVC buck con-

    verter. Here, the voltage error and the voltage error dynamics

    (or the rate of change of voltage error) under CCM, can be

    expressed as

    (1)

    where , , are the capacitance, inductance, and load

    resistance, respectively, , , and are the reference,

    input, and sensed output voltage, respectively, 1 or 0 is the

    switching state of power switch . Then, by differentiating

    (1) with respect to time, the state space model can be obtained

    as

    (2)

    The graphical representation of individual substructures of

    the system with 1 and 0, for different starting

    conditions, are shown in Fig. 2. It can be seen that when ,

    the phase trajectory for any arbitrary starting position on the

    phase plane will converge to the equilibrium point (

    , 0) after some finite time period. Similarly, when

    , all the trajectories converge to equilibrium point ( ,0). These characteristics will be exploited for the design of

    the SM voltage controller.

    B. Design of an Ideal SM Voltage Controller

    In SM control, the controller employs a switching function

    to decide its input states to the system [1]. For SM voltage con-

    troller, the switching state can be determined from the control

    parameters and using the switching function

    (3)

    where is the control parameter (termed as sliding coefficient)

    to be designed; ; and . By enforcing

    , a sliding line with gradient can be obtained. The pur-

    pose of this sliding line is to serve as a boundary to split the

    phase plane into two regions. Each of this region is specified

    with a switching state to direct the phase trajectory toward the

    sliding line. It is only when the phase trajectory reaches and

    tracks the sliding line toward the origin that the system is con-

    sidered to be stable, i.e., 0 and 0.

    The specification of the switching state for each sector in the

    case of a second order system like the buck converter can be

    graphically performed by observing the behavior of the trajecto-

    riesin Fig. 3, which is a combination of the two plots in Fig. 2. It

    can be observed that if the phase trajectory is at any arbitrary po-sition above the sliding line ( 0), e.g., point , must

    be employed so that the trajectory is directed toward the sliding

    line. Conversely, when the phase trajectory is at any position

    below sliding line, e.g., point , 0 must be employed for

    the trajectory to be directed toward the sliding line. This forms

    the basis for the control law

    when

    when(4)

    Although abiding the hitting condition [5], which states that

    the system trajectory must eventually reach the sliding line, the

    control law in (4) only provides the general requirement thatthe trajectories will be driven toward the sliding line. However,

    there is no assurance that the trajectorycan be maintained on this

    line. To ensure that the trajectory is maintained on the sliding

    line, the existence condition, which is derived from Lyapunovs

    second method [17] to determine asymptotic stability, must be

    obeyed [1], [6]

    (5)

    Thus, by substituting the time derivative of (3), the condition

    for SM control to exist is

    forfor

    (6)

  • 8/8/2019 Tibbie Base Paper 2

    3/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 427

    (a) (b)

    Fig. 2. Phase trajectories of the substructure corresponding to (a) u = 1 and (b) u = 0 for different starting ( x ; x ) positions.

    Fig. 3. Phase trajectories of the substructure corresponding to both u = 1 and

    u =

    0 for different( x ; x )

    starting positions.

    where is an arbitrarily small positive quantity. Substituting (2)

    and (4) into (6), the inequalities become

    (7)

    where

    (8)

    The above conditions are depicted in Fig. 4 for the two respec-

    tive situations: (a) and (b) . In both fig-

    ures,Region1 represents 0 andRegion2 represents 0.

    SMwillonlyoccur onthe portion ofthesliding line, , that

    covers both Regions 1 and 2. In this case, this portion is within

    and , where is the intersection of 0 and 0; and

    is the intersection of 0 and 0.Since the phase trajec-

    tory will slide to the origin only when it touches 0 within, it will overshoot the sliding line if the trajectory landed

    Fig. 4. Regions of existence of SM in phase plane: (a) > 1 = R C

    and(b)

  • 8/8/2019 Tibbie Base Paper 2

    4/13

    428 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    respectively, a phase trajectory that moves away from the phase

    plane origin and an that does not tend to zero.

    C. Design of a Practical SM Voltage Controller

    In this section, a practical SM voltage controller is consid-

    ered. The sliding line defined in the previous section is rede-

    fined to accommodate for hardware limitations. Additionally,a hysteresis band is introduced to the sliding line as a form of

    frequency control to suppress high frequency switching. The re-

    lationship of hysteresis band versus switching frequency of the

    SMVC buck converter is derived.

    1) Redefinition of Sliding Line: As previously mentioned,

    SM controller requires the continuous assessment of the param-

    eters and for its control. By substituting (1) and (9) into

    (3), we have

    (12)

    where and . From the equation,the terms ( ) and are the feedback state variables

    from the converter that should be amplified by gain coefficients

    and respectively, before a summation is performed. This,

    from a practical perspective, does generate a problem. Noting

    that capacitance in power converters is usually in the micro-

    farad ( ) range, its inverse term will be significantly higher

    than and . Hence, the overall gain coefficients and

    will become too high for practical implementation. If forcibly

    implemented, the feedback signals may be driven into satura-

    tion, thereby causing (12) to provide unreliable information for

    the control.

    In view of that, it is simpler to reconfigure the switching func-

    tion to the following description:

    (13)

    where ; and . From (1) and

    (9), we get

    (14)

    Thus, the practical implementation of becomes independent

    of , thereby reducing the amplification of the feedback signals.

    With this sliding line, the conditions for SM control to exist are

    (15)

    where

    (16)

    An interesting point here is that although there is modification tothe equations, the maximum existence region will still occur

    Fig. 5. Phase trajectory for (a) ideal SM operation and (b) actual SM operationwith chattering.

    at . In addition, the response time is still maintained

    at .

    2) Introduction of Hysteresis Band: Ideally, a converter will

    switch at infinite frequency with its phase trajectory moving on

    the sliding line when it enters SM operation [see Fig. 5(a)].

    However, in the presence of switching imperfections, such as

    switching time constant and time delay, this is not possible. The

    discontinuity in the feedback control will produce a particular

    dynamic behavior in the vicinity of the surface trajectory known

    as chattering [see Fig. 5(b)] [1][4].

    If the chattering is left uncontrolled, the converter system

    will become self-oscillating at a very high switching frequency

    corresponding to the chattering dynamics. This is undesirable

    as high switching frequency will result in excessive switching

    losses, inductor and transformer core losses, and EMI noise is-

    sues [18]. Hence, most PWM power supplies are designed to op-

    erate with switching frequencies between 40 kHz and 200 kHz

    [18]. Furthermore, since chattering is introduced by the imper-

    fection of controller ICs, gate driver, and power switches, it is

    difficult to predict the exact switching frequency. Hence, the de-

    sign of the converter and the selection of the components will

    be difficult.To solve these problems, the control law in (4) is rede fined as

    when

    when(17)

    where is an arbitrarily small value. The reason for introducing

    a hysteresis band with the boundary conditions and

    is to provide a form of control to the switching frequency of

    the converter. This is a method commonly employed to alleviate

    the chattering effect of SM control [17]. With this modification,

    the operation is altered such that if the parameters of the statevariables are such that , switch of buck converter

    will turn on. Conversely, it will turn off when . In the

    region , remains in its previous state. Thus, by

    introducing a region where no switching occurs,

    the maximum switching frequency of the SM controller can be

    controlled. This alleviates the effect of chattering. Additionally,

    it is now possible to control the frequency of the operation by

    varying the magnitude of .

    3) Calculation of Switching Frequency: To control the

    switching frequency of the converter, the relationship between

    the hysteresis band, , and switching frequency, , must be

    known.

    Fig. 6 shows the magnified view of the phase trajectory whenit is operating in SM. and are the vectors of state variable

  • 8/8/2019 Tibbie Base Paper 2

    5/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 429

    Fig. 6. Magnified view of the phase trajectory in SM operation.

    velocity for and , respectively. It was previously

    derived in [2] that

    (18)

    where is the time taken for vector to move from position

    to ; and is the time taken for vector to move from

    position to . By substituting in (18)

    (19)

    where

    for

    for

    we have

    (20)

    Further substitution of (15) into (20) results in

    (21)

    Therefore, the time period for one cycle in which the phase tra-

    jectory moves from position to is equivalent to (22) shown

    at the bottom of the page. Since the cycle is repeated (cyclic)

    throughout the SM steady-state operation, the frequency of the

    converter when it is operating in SM can be expressed as (23)

    shown at the bottom of the page. Using , the above

    equation becomes

    (24)

    Considering that and are nonconstant parameters con-

    sisting of respectively dc signals of and and time varying

    perturbations of and , we can resolve (24) into

    (25)

    using small-signal approximation where

    (26)

    (27)

    with representing the steady-state (nominal cyclic) switching

    frequency and representing the ac varying (perturbed) fre-

    quency of the converter. This indicates that if there are

    significantly small variations in the input and output voltages,

    i.e., and , the converter will be operating

    at a steady-state switching frequency of with very little ac

    frequency perturbation, i.e., . Since only the nom-

    inal steady-state operating conditions are considered in the

    controllers design, only (26) is required when it comes to the

    design of the steady-state switching frequency of the converter.

    III. STANDARD DESIGN PROCEDURE

    A standard SMVC buck converter module is proposed in this

    section, along with a step by step design procedure for practical

    implementation. A design example is provided for illustration.

    A. Standard SMVC Converter Model

    Fig. 7 shows the proposed SMVC buck converter. The SM

    controller comprises basically a differential amplifier circuit

    V; a voltage follower circuit ; a difference amplifier circuit

    ; and a noninverting Schmitt Trigger circuit . Similar to

    (22)

    (23)

  • 8/8/2019 Tibbie Base Paper 2

    6/13

    430 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    Fig. 7. Standard SMVC buck converter.

    TABLE ISPECIFICATIONS OF BUCK CONVERTER

    conventional schemes, the feedback sensing network for is

    provided by the voltage divider circuit, and . Addition-

    ally, a low resistance current transformer is placed in series

    with the filter capacitor to obtain the capacitor current, .

    B. Design Steps

    The design of the buck converter is well covered in the lit-

    erature [18][20]. Our discussion here starts with the assump-

    tion that the converters parameters are known and are given in

    Table I.

    These parameters are calculated on the basis that the con-

    verter is to be operated in CCM for 13 V to 30 V and

    0.5 A to 4 A. The maximum peak to peak ripple voltageis 50 mV.

    1) Step 1: The current sensing gain, , is set at a value such

    that the measured capacitor current, is equal to the ac-

    tual capacitor current, .

    2) Step 2: Setting reference voltage 3.3 V, is cal-

    culated using the expression

    (28)

    Also, and are related by

    (29)

    Fig. 8. Calculated

    values for inductances of 50 H

    , 100 H

    , 110.23 H

    (actual inductance), and 150 H

    at switching frequencies of up to 300 kHz.

    Choosing as 870 , we get .

    3) Step 3: From (14), the gain required for the amplification

    of the signal ( ) is . Hence, V and V are

    related by

    V V (30)

    Choosing V , we get V . Additionally,

    the resistors, , for the difference amplifier circuit: , are

    chosen as 10 k .

    4) Step 4: The parameter of the hysteresis band, , can be

    obtained from the re-arranged form of (26), i.e.,

    (31)

    where , , and are the nominal parameters of the con-

    verter. A plot giving the calculated values for different induc-

    tances and switching frequencies is shown in Fig. 8.

    The actual inductance, , used in the design is 110.23 .

    It should be noted that for CCM. Thus, substituting

    into (31), is calculated as 0.136.1

    5) Step 5: The setting of for the hysteresis band can be per-

    formed by adjusting the ratio of and of , using anequation derived from the mathematical description of a nonin-

    verting Schmitt Trigger (38), i.e.,

    (32)

    where and are respectively the positive and nega-

    tive voltage supplies to Schmitt Trigger . Choosing as

    110 , resistor is set as 12 .

    1The presence of hysteresis band in switching function introduces an errorin the output voltage. It is important to limit the hysteresis band

    to a smallvalue to minimize this error. On the other hand, if

    is too small, it may be very

    sensitive to change of

    (i.e., highd f = d

    ). A good value is to set

    in the range0 : 1 0 : 2 . Otherwise, a different inductance may be used to keep withinthe range.

  • 8/8/2019 Tibbie Base Paper 2

    7/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 431

    Fig. 9. Full schematic diagram of the SMVC buck converter prototype.

    Fig. 10. Calculated, simulated, and experimentally measured averageswitching frequencies f at nominal operating condition V = 2 4 V and

    R = 6

    for different hysteresis band

    settings.

    IV. EXPERIMENTAL RESULTS

    This section evaluates the performance of the SMVC buck

    converter that is designed using the procedure described inSection III. The full schematic diagram of the experimental

    prototype is shown in Fig. 9.

    A. Verification of Design Equation

    Fig. 10 shows the graphs of the converters average switching

    frequency for different values at nominal operating condi-

    tion V and , that are obtained from calcu-

    lation, simulation, and experiment. Specifically, the calculation

    is performed using the proposed design (26) and the simulation

    is carried out in Matlab/Simulink using the circuit expression

    of the proposed controller. Basically, the simulation and experi-

    mental data are in good agreement with the calculated data. Thesmall discrepancy between the experimental data and both the

    calculated and simulated data is mainly due to component tol-

    erances and finite time delay of practical circuitries. In practical

    development, fine tuning of is still required to achieve the de-

    sired .

    Fig. 11 shows the graphs of the measured average switching

    frequency and average output voltage against for load

    resistances 3, 6, and 12 . From the figure, is notablyhigher with lower , and is lower with lower . Addi-

    tionally, a major point to highlight is that at low , i.e., high

    switching frequency, the voltage regulation is tighter and more

    accurate. In our design, by setting 0.1 0.2 in the design,

    we limit the voltage accuracy within 0.12 V (i.e., of

    ) error.

    B. Steady-State Performance

    Our experiment hereafter uses a controller that is fine-tuned

    to a switching frequency of 200 kHz by replacing with a

    16 k resistor, thereby setting 0.1.

    Fig. 12 shows an example of the output voltage ripple, in-

    ductor current, and switching state waveforms of the SMVC

    buck converter at steady-state operation. Performing to design

    expectation, the converter operates at an average switching fre-

    quency of 199 kHz, with smallfrequency fluctuations, and

    the output voltage ripple (without considering the ringing

    oscillation) is around 10 mV (i.e., of ), under the

    nominal operating condition 24 V and .

    C. Load Variation

    Fig. 13 gives the experimentally measured and for load

    resistance . It can be concluded that voltage

    regulation of the converter is robust to load variation, with only

    a 0.37 V deviation (i.e., 3.1% of ) in for

    the entire load range, i.e., load regulation averages

    at 0.04 V . Additionally, the experimental readings also indi-

    cate that there is a change of switching frequency when the load

    vary. From the figure, the variation of switching frequency with

    respect to load resistance averages at .

    Theoretically, the nonlinear expression of can be ob-

    tained by differentiating (23) with respect to , i.e.,

    (33)

    D. Line Variation

    The experimentally measured and for input voltage

    range V 30 V are plotted in Fig. 14. It can be

    observed that both and increase with increasing .

    Specifically, output voltage deviation is 0.14 V (i.e., 1.2% of

    ) for the entire input range, i.e., line regulation

    averages at 8.235 mV/V. The variation of switching

    frequency with respect to input voltage averages

    at 10.176 kHz/V. Theoretically, the nonlinear expression of

    can be obtained by differentiating (24) with respect to

    , i.e.,

    (34)

  • 8/8/2019 Tibbie Base Paper 2

    8/13

    432 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    Fig. 11. (a) Experimentally measured average switching frequencyf

    and (b) average output voltageV

    atV = 2 4

    V andR =

    3, 6, and 12

    for different

    hysteresis band settings.

    Fig. 12. Waveforms ofV

    ,i

    , andu

    at steady-state operation under nominal

    operating conditions V = 24 V and R = 6 .

    Fig. 15 shows the output voltage ripple waveform of the con-

    verter operating at nominal load when is sinusoidally varied

    from 17.5 V to 29.0 V at a frequency of 100 Hz. This was per-formed to test the robustness of the converter to a slowly varying

    input voltage. It is found that the maximum peak to peak output

    voltage is around 235 mV, i.e., the input voltage ripple rejection

    is 33.8 dB at 100 Hz. The converter has displayed adequate

    control performance against audio susceptibility.

    E. Variation

    The dynamic behavior of the converter corresponding to dif-

    ferent sliding coefficients is also investigated. Fig. 16(a)(f)

    show the output waveforms of the operation with load resis-

    tance that alternates between and

    for the controller with sliding coefficients: (a) ,(b) , (c) , (d) , (e)

    Fig. 13. Experimentally measured values of average switching frequency fand average output voltage V for different load resistance R .

    , and (f) , respectively. The re-

    sults are summarized in Table II.

    Noticeably, as increases, the dynamic response of the con-

    verter improves with shorter settling time and lower overshoots.This is in good agreement with our theory that dynamic response

    improves with increasing . However, when is too high, the

    converter is unstable [see Fig. 16(f)]. This is due to the distor-

    tion of the control signal caused by the saturation of amplified

    feedback signal [refer to the discussion related to (12)].

    Fig. 17(a)(f) show the output waveforms of the startup oper-

    ation for the controller with the same set of sliding coefficients.

    The purpose is to examine the oscillatory behavior of the re-

    sponse due to , which exercises direct influence on the exis-

    tence region in the control. Consistent with theory, the degree

    of oscillation increases with the increasing . Since the magni-

    tude of the oscillations will be high for heavy loads, the effect

    of oscillation due to should be taken into consideration whendesigning high power converters.

  • 8/8/2019 Tibbie Base Paper 2

    9/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 433

    Fig. 14. Experimentally measured values of average switching frequency fand average output voltage V for different input voltage V .

    Fig. 15. Waveforms of V and V under the operating condition whereby V issinusoidally varied from 17.5 V to 29 V at a frequency of 100 Hz, and R =6 .

    F. ESR Variation

    The converter is also subjected to an ESR variation test.

    The idea is to investigate the effect of the output capacitors

    ESR on the switching behavior of the converter. Fig. 18(a)(c)

    illustrates the experimental waveforms of the converter withthe same output capacitance, for different ESR values (25 ,

    125 , and 225 ), operating under nominal load condi-

    tions 24 V and . As expected, output voltage

    ripples are higher with larger values of ESR. However, the

    variation of ESR does not influence the behavior of capacitor

    current. In all cases, the peak-to-peak capacitor current remains

    at 0.36 A, while the average switching frequency is at around

    200 kHz. Hence, it is evident that output capacitors ESR has

    little influence on the switching frequency.

    V. FURTHER DISCUSSION

    This section discusses the merits and drawbacks of the pro-posed standard SMVC converter as compared to conventional

    current mode and voltage mode converters. Suggestions to alle-

    viate the various drawbacks are also provided.

    A. Advantages

    The main advantage of the SMVC converter is the simplicity

    in the controllers design and implementation. Unlike conven-

    tional current mode and voltage mode controllers which requirespecial techniques (e.g., pole placement method) to estimate

    their controllers gain parameters, the SM voltage controllers

    parameters can be precisely calculated from simple mathemat-

    ical equations.

    Furthermore, since the SMVC controller is designed from the

    large-signal converter model, it is stable and robust to large pa-

    rameter, line, and load variations. This is also a major advantage

    over conventional current mode and voltage mode controllers

    which often fail to perform satisfactorily under parameter or

    large load variations because they are designed from the lin-

    earized small-signal converter models [21].

    B. Disadvantages

    One major disadvantage of the proposed SMVC converter is

    that it has a nonzero steady-state voltage error. This is due to

    the adoption of the phase canonical form in the design, which

    makes the controller a proportional-derivative (PD) type of feed-

    back controller [21], and the presence of hysteresis band in the

    switching function, which being nonzero in its average value

    also introduces an error in the output voltage [5].

    Another disadvantage of the proposed converter is that its

    steady-state switching frequency is affected by the line and load

    variations (refer to Figs. 13 and 14). For line variation, this

    can be understood from (26) where with preset design param-

    eters , , and , a deviation in the input supply, , will re-

    sult in a change in the steady-state dc switching frequency, .

    Specifically, increases as increases. For load variation,

    the change in switching frequency is caused by two compo-

    nents. First, it is due to the imperfect feedback loop that causes

    a small steady-state error in the output voltage which in turn

    causes small deviation of the switching frequency from its nom-

    inal value [see (26)]. Second, it is due to the mismatch be-

    tween the nominal load and operating the load. This can be un-

    derstood from (23) where with preset control parameter

    for a certain nominal load , a change inoperating load from its nominal value will lead to a fre-

    quency not given by (24).

    C. Possible Solutions

    The steady-state voltage error can easily be eliminated by

    converting the controller into a PID-type through the introduc-

    tion of an integrator to process the voltage error signal [5], [15].

    Such controllers are well-known and will not be discussed in

    this paper.

    One possible method of maintaining the switching frequency

    against line variation is by introducing an adaptive feed-for-

    ward hysteresis band control that varies the hysteresis bandwith the change of . Practically, this can easily be performed

  • 8/8/2019 Tibbie Base Paper 2

    10/13

    434 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    Fig. 16. Experimental waveforms of output voltage ripple V and inductor current i under step load change that alternates between R = 1 2 and R = 3 for controller with sliding coefficients (a) = 0 : 5 = R C , (b) = 1 = R C , (c) = 2 = R C , (d) = 1 0 = R C , (e) = 1 0 0 = R C , and (f) = 5 0 0 = R C .

    by imposing a variable power supply, and , which

    changes with variation, to power the Schmitt Trigger circuit

    [see (40)].

    An adaptive feedback controller that varies the parameter,

    , with the change of load , can be incorporated to main-

    tain the switching frequency of the converter against load vari-

    ation. The idea is to adaptively maintain the operating status

    at for all load conditions. Such system has been

    proposed in [22] to improve systems performances. Here, itis suggested as a means to also maintain the validity of (24) so

    that becomes independent of . Hence, the effect of fre-

    quency variation caused by the mismatch between the nominal

    and the operating load is eliminated. Additionally, with better

    regulated steady-state output voltage with the adaptive feed-

    back control scheme [22], the issue of switching frequency

    deviation due to the variation of the output voltage is also

    alleviated.

    Details of the design and derivation of such adaptive feed-

    forward and feedback control schemes will be addressed in thesubsequent paper.

  • 8/8/2019 Tibbie Base Paper 2

    11/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 435

    TABLE IIDYNAMIC BEHAVIOR OF THE EXPERIMENTAL SMVC CONVERTER FOR DIFFERENT SETTINGS UNDER STEP LOAD CHANGE

    Fig. 17. Experimental waveforms of output voltage V and inductor current i under nominal operating conditions V = 2 4 V and R = 3 for controller withsliding coefficient (a) = 0 : 5 = R C , (b) = 1 = R C , (c) = 2 = R C , (d) = 1 0 = R C , (e) = 1 0 0 = R C , and (f) = 5 0 0 = R C during startup.

    Fig. 18. Experimental waveforms of output voltage rippleV

    , capacitor currenti

    , and the generated gate pulseu

    for SMVC converter with 100 F filter

    capacitor of (a) E S R = 2 5 m ; (b) E S R = 1 2 5 m ; and (c) E S R = 2 2 5 m , at constant load resistance R = 6 .

    VI. CONCLUSION

    A detailed analysis of the design principle of a SMVC buck

    converter is presented. The discussion takes into consideration

    the practical aspects of the converter. The sliding line for an ideal

    controller is redefined to meet practical limitations. A hysteresisband is introduced to the sliding line to the solve the problem

    of chattering. The relationship between the hysteresis band and

    the switching frequency is derived. To facilitate implementation,

    a standard SM converter module is introduced. Design guide-

    lines are provided in a simple step by step manner. The exper-

    imental results are presented to verify the converter design andprocedure.

  • 8/8/2019 Tibbie Base Paper 2

    12/13

    436 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 20, NO. 2, MARCH 2005

    APPENDIX I

    DERIVATION OF SMALL-SIGNAL MODEL OF SWITCHING

    FREQUENCY RELATIONSHIP WITH HYSTERESIS BAND

    The variables , , and from (24) are first separated into

    their steady-state and small-signal terms

    (35)

    Substituting (35) into (24), we have

    (36)

    Since the output voltage ripple is very small, i.e., is verysmall, the cross term of can be neglected. Hence (36)

    becomes

    (37)

    From (37), the steady-state equation and the small-signal equa-

    tion can be obtained as given in (26) and (27).

    APPENDIX II

    DERIVATION OF VARIABLE POWER SUPPLY DESCRIPTION

    FOR SCHMITT TRIGGER IN FEEDFORWARDHYSTERESIS BAND CONTROL

    The description of a noninverting Schmitt Trigger is ex-

    pressed as

    (38)

    Substituting this into (31), we have

    (39)

    Considering that both and must be balanced when

    powering the Schmitt Trigger, the power supply description

    should be

    (40)

    REFERENCES

    [1] V. Utkin, J. Guldner, and J. X. Shi, Sliding Mode Control in Electro-

    mechanical Systems. London, U.K.: Taylor and Francis, 1999.[2] V. Utkin, Sliding Modes in Control Optimization. Berlin, Germany:Springer-Verlag, 1992.

    [3] C. Edwards and S. K. Spurgeron, Sliding Mode Control: Theory andApplications. London, U.K.: Taylor and Francis, 1998.

    [4] W. Perruquetti and J. P. Barbot, Sliding Mode Control in Engi-neering. New York: Marcel Dekker, 2002.

    [5] G. Spiazzi and P. Mattavelli, Sliding-mode control of switched-modepower supplies, in The Power Electronics Handbook. Boca Raton,FL: CRC Press LLC, 2002, ch. 8.

    [6] R. Venkataramanan,A. Sabanoivc, andS. Cuk, Sliding mode controlof

    dc-to-dc converters, in Proc. IEEE Conf.IndustrialElectronics, ControlInstrumentations (IECON), 1985, pp. 251258.[7] V. M. Nguyen and C. Q.Lee, Indirect implementations of sliding-mode

    control law in buck-type converters, in Proc. IEEE AppliedPower Elec-tronics Conf. Expo (APEC), vol. 1, Mar. 1996, pp. 111115.

    [8] , Tracking control of buck converter using sliding-mode withadaptive hysteresis, in Proc. IEEE Power Electronics Specialists Conf.(PESC), vol. 2, Jun. 1995, pp. 10861093.

    [9] S. K. Mazumder, A. H. Nayfeh, and A. Borojevic, Robust control ofparallel dc-dc buck converters by combining integral-variable-structureand multiple-sliding-surfacecontrol schemes,IEEE Trans. Power Elec-tron., vol. 17, no. 3, pp. 428 437, May 2002.

    [10] J. Mahdavi, A. Emadi, and H. A. Toliyat, Application of state spaceaveraging method to sliding mode control of pwm dc/dc converters, inProc. IEEE Conf. Industry Applications Society (IAS), vol. 2, Oct 1997,pp. 820827.

    [11] L. Martinez-Salamero, J. Calvente, R. Giral, A. Poveda, and E. Fossas,

    Analysis of a bidirectional coupled-inductor Cuk converter operating insliding mode, IEEE Trans. Circuits Syst. I, vol. 45, no. 4, pp. 355363,Apr. 1998.

    [12] H. Sira-Ramirez, Sliding motionsin bilinear switched networks,IEEETrans. Circuits Syst., vol. 34, no. 8, pp. 919933, Aug. 1987.

    [13] H. Sira-Ramirez andM. Rios-Bolivar, Slidingmode control of dc-to-dcpower converters via extended linearization, IEEE Trans. Circuits Syst.

    I, vol. 41, no. 10, pp. 652 661, Oct 1994.[14] B. J. Cardoso, A. F. Moreira, B. R. Menezes, and P. C. Cortizo, Anal-

    ysis of switching frequency reduction methods applied to sliding modecontrolled dc-dc converters, in Proc. IEEE Applied Power ElectronicsConf. Expo (APEC), Feb. 1992, pp. 403410.

    [15] P. Mattavelli, L. Rossetto, G. Spiazzi, and P. Tenti, General-purposesliding-mode controller for dc/dc converter applications, in Proc. IEEEPower Electronics Specialists Conf. (PESC), Jun. 1993, pp. 609615.

    [16] D. M. Mitchell,DC-DCSwitchingRegulatorAnalysis. New York:Mc-Graw-Hill, 1998.

    [17] J. J. E. Slotine and W. Li, Sliding control, in Applied Nonlinear Con-trol. Englewood Cliffs, NJ: Prentice -Hall, 1991, ch. 7.

    [18] H. W. Whittington, B. W. Flynn, and D. E. Macpherson, Switched Mode

    Power Supplies : Design and Construction, 2nd ed. New York: Wiley,1997.

    [19] E. Rogers, Understanding buck power stages in switch mode powersupplies, in Mixed Signal Products: Texas Instruments, 1999.

    [20] K. H. Billings, Switchmode Power Supply Handbook, 2nd ed. New

    York: McGraw-Hill, 1999.[21] V. S. C. Raviraj and P. C. Sen, Comparative study of proportional-in-

    tegral, sliding mode, and fuzzy logic controllers for power converters,IEEE Trans. Ind. Applicat., vol. 33, no. 2, pp. 518524, Mar./Apr. 1997.

    [22] S. C. Tan, Y. M. Lai, M. K. H. Cheung, and C. K. Tse, An adaptivesliding mode controller for buck converter in continuous conductionmode, in Proc. IEEE Applied Power Electronics Conf. Expo (APEC),Feb. 2004, pp. 13951400.

    Siew-Chong Tan (S00) received the B.Eng. (withhonors) and M.Eng. degrees in electrical and com-puter engineering from the National University ofSingapore, Singapore, in 2000 and 2002, respec-tively, and is currently pursuing the Ph.D. degree atHong Kong Polytechnic University, Hong Kong.

    His research interests include motor drives andpower electronics.

  • 8/8/2019 Tibbie Base Paper 2

    13/13

    TAN et al.: SLIDING MODE VOLTAGE CONTROLLED BUCK CONVERTER 437

    Y. M. Lai (M92) received the B.Eng. degree inelectrical engineering from the University of WesternAustralia, Perth, Australia, in 1983, the M.Eng.Sc.degree in electrical engineering from University ofSydney, Sydney, Australia, in 1986, and the Ph.D.degree from Brunel University, London, U.K., in1997.

    He is an AssistantProfessorwith Hong Kong Poly-

    technic University, Hong Kong, and his research in-terests include computer-aided design of power elec-tronics and nonlinear dynamics.

    Martin K. H. Cheung received the B.Eng. (withhonors) degree and the M.Phil. degree in electronicengineering from the Hong Kong Polytechnic Uni-versity, Hong Kong, in 2000 and 2003, respectively.

    He is currently a Project Assistant in the Depart-ment of Electronic and Information Engineering,

    Hong Kong Polytechnic University. His mainresearch interests include RF circuit design and

    switch-mode power supplies design.

    Chi K.Tse (M90SM97)receivedthe B.Eng. (withfirstclasshonors) degreein electrical engineering andthe Ph.D. degree from the University of Melbourne,Australia, in 1987 and 1991, respectively.

    He is presently a Professor with Hong KongPolytechnic University, Hong Kong, and his researchinterests include nonlinear systems and power elec-tronics. He is the author of Linear Circuit Analysis

    (London, U.K.: Addison-Wesley 1998) and Complex Behavior of Switching Power Converters (BocaRaton: CRC Press 2003), coauthor of Chaos-Based

    Digital Communication Systems (Heidelberg, Germany: Springer-Verlag,2003), and co-holder of a U.S. patent. He is an Associate Editor for the

    International Journal of Systems Science. Since 2002, he has been appointed asGuest Professor by the Southwest China Normal University, Chongqing, China.

    Dr. Tse received the L.R. East Prize from the Institution of Engineers, Aus-tralia, in 1987, the IEEE TRANSACTIONS ON POWER ELECTRONICS Prize PaperAward in 2001, the Presidents Award for Achievement in Research (twice), andthe Facultys Best Researcher Award. He was an Associate Editor for the IEEETRANSACTIONS ON CIRCUITS AND SYSTEMS PART IFUNDAMENTAL THEORYAND APPLICATIONS, from 1999 to 2001, and since 1999, he has been an Asso-ciate Editor for the IEEE TRANSACTIONS ON POWER ELECTRONICS.