TIA-607-B - Network Bonding and Grounding Presentation

35
8/16/2012 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 1

Transcript of TIA-607-B - Network Bonding and Grounding Presentation

Page 1: TIA-607-B - Network Bonding and Grounding Presentation

8/16/2012

This presentation to be used in

conjunction with:

• Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11

• Samples in DC-GROUND-KIT

1

Page 2: TIA-607-B - Network Bonding and Grounding Presentation

8/16/2012

Network Bonding and Grounding: TIA-607-B – Generic Telecommunications Bonding and

Grounding (Earthing) for Customer Premises

2

Tom Turner

Product Manager, Power & Grounding

[email protected]

800-777-3300 x88290

Page 3: TIA-607-B - Network Bonding and Grounding Presentation

Presentation objectives

Topics

• Scope of TIA-607-B, Generic Telecommunications Bonding and Grounding

(Earthing) for Customer Premises

• Grounding and bonding system implementation according to TIA-607-B,

including:

– Data centers

– Telecommunications closets

Throughout the presentation

• Requirements from TIA-607-B and products that solve issues identified in the

standard

• Common problems and how to avoid those issues

Order of presentation: start at equipment and work out to earth

3

Page 4: TIA-607-B - Network Bonding and Grounding Presentation

BICSI credits available for this presentation

Qualifies for one credit:

• RCDD CEC

• Installer

• Technician

• Certified Trainer

Please make sure we have your:

• Name, as you want it to appear on your certificate of course completion

• Name of the company you work for

• Your E-mail address (so we can send you the certificate)

4

Page 5: TIA-607-B - Network Bonding and Grounding Presentation

Purpose and scope of TIA-607-B

TIA-607-B grounding is normative

and applies to entire building, not

just data center

TIA-607-B, ―Generic

Telecommunications

Bonding and

Grounding (Earthing)

for Customer

Premises‖, is now

approved!

Scope now

includes

grounding of

ITE

Page 6: TIA-607-B - Network Bonding and Grounding Presentation

What is TIA-607-B?

Scope: Specifies requirements for a generic telecommunications bonding and grounding infrastructure, and its interconnection to other systems, for locations where telecommunications equipment will be or are installed

Major revision of J-STD-607-A:

• Includes G&B of telecommunications spaces (distributors and computer rooms)

• Continued harmonization efforts (as practicable) on terminology and practices with international standards

Scope of TIA-607-B

TBB

Distributors

Computer

Rooms

TGB

TMGB

Page 7: TIA-607-B - Network Bonding and Grounding Presentation

Implementation of a telecommunications grounding and

bonding system per TIA-607-B

• Bond the equipment to the racks/cabinets

• Ensure that the racks/cabinets have electrical

continuity

• Bond the racks/cabinets back to the electrical

panel

• Bond nearby conductive items such as pathways

and building steel to the telecommunications

grounding and bonding system

Page 8: TIA-607-B - Network Bonding and Grounding Presentation

Equipment in cabinets and racks

“Rather than relying

on the ac power cord

ground wire, it is

desirable that

equipment be

grounded in a

verifiable manner as

described in this

Standard.”

Figure 7—Example of three methods to bond equipment and racks to ground

TIA-607-B:

Page 9: TIA-607-B - Network Bonding and Grounding Presentation

Implementing the equipment

grounding requirement

Bond equipment

with a jumper

when possible

Bonding screws have thread-

forming threads and

serrations under the head

that remove the paint off

mounting flanges and patch

panels (RGTBSG-C)

Bonding cage nuts have

teeth that cut paint when

installed (CBN4K)

9

Page 10: TIA-607-B - Network Bonding and Grounding Presentation

Some equipment isn’t designed for a supplemental

bonding system

• Can’t add a jumper

• Can’t add a bonding screw or a bonding cage nut

That’s OK. So long as the AC power system and the telecom bonding

system are bonded together, no safety issues result

Most servers cannot be

grounded directly to the

telecommunications

grounding system

Page 11: TIA-607-B - Network Bonding and Grounding Presentation

Ground strip kits

• Ground strips have same x-

sectional area as #6 AWG wire

• Strips also future-proof against a

future installer bonding to the rack

without thread-forming screws

RGS Family

Install the

strip on the

vertical rail

and bond all

other

jumpers to it

Page 12: TIA-607-B - Network Bonding and Grounding Presentation

TIA-607-B requires racks and cabinets to

be electrically continuous

• Electrical continuity must be

confirmed through the use of

bonding jumpers, bonding

hardware, or the removal of paint

• Bonding jumpers must be a

minimum of #12 AWG

Bare metal bonding tabs that automatically create electrical

continuity when cabinet is assembled

All Panduit racks and

cabinets are electrically

continuous, eliminating the

need for jumpers

Page 13: TIA-607-B - Network Bonding and Grounding Presentation

If the rack/cabinet is not electrically continuous, use a

busbar

• Bond busbar to rack/cabinets

with thread-forming screws to

create electrical continuity

between the equipment

mounting rails

• Bond to busbar with 2-hole lug

tongues for long-term

connection reliability

Thread-

forming

screws

2-hole lug

mounting

Page 14: TIA-607-B - Network Bonding and Grounding Presentation

New terminology introduced by TIA-607-B:

Telecommunications Equipment Bonding

Conductor (TEBC)

• “The TEBC

connects the

TMGB/TGB to

equipment

racks/cabinets”

• Minimum

separation from

power and

telecom cables is

50 mm (2 in)

Example TEBCs routed along auxiliary cable brackets (which help to maintain 50 mm separation)

TEBCs

TEBCs are bonded to the TGB

Page 15: TIA-607-B - Network Bonding and Grounding Presentation

Acceptable telecommunications equipment bonding

conductor topologies for the telco closet, per TIA-607-B

Rack

bonding

conductor

(RBC)

Telecommunications

equipment bonding

conductor (TEBC)

Page 16: TIA-607-B - Network Bonding and Grounding Presentation

Use two-hole lugs to bond to busbars and racks &

cabinets. Compression is required on busbars

One hole mechanical lug

Two hole compression lug

Page 17: TIA-607-B - Network Bonding and Grounding Presentation

Connector considerations – TIA-607-B

Mechanical connectors are

allowed for bonding the

TEBC/RGB to racks, but

Panduit recommends

compression to prevent

loosening

Page 18: TIA-607-B - Network Bonding and Grounding Presentation

Mesh-BN: a collection of components (As per CENELEC documents, includes

TIA-942’s Data Center Grounding Infrastructure as the “Supplemental

Bonding Network” and IEEE Std 1100 calls the MCBN), per TIA-607-B

Information technology

equipment (ITE)

Racks and cabinets

Cabling pathways

(not shown)

Building steel

Supplemental bonding grid

(SBG)

Conduits

Rack bonding conductor

(RBC)

Page 19: TIA-607-B - Network Bonding and Grounding Presentation

Watch for this common problem

Common Bonding Network Jumper Kit (RGCBNJ660P22)

When you see a supplemental bonding grid (SBG) with nothing attached to it, the customer intended to have grounding but got nothing!!! Making this

bond was in no one’s scope of work...

(20% of the data centers have this problem)

Specify who

bonds the racks

to the SBG!

Page 20: TIA-607-B - Network Bonding and Grounding Presentation

HTAP Crimping

• HTCT HTAPs require 12

tons of compression

• CT-2930/L is

recommended

• Can use other

manufacturers’ tools

and retain UL

Listing/CSA Certification

• Must use Panduit

locator dies

Patented

locating rib

guarantees full-

width crimp 1st

time, every

time!

HTCT HTAP

CD-930H-250 Locator Die

CT-2930/L

Page 21: TIA-607-B - Network Bonding and Grounding Presentation

Conductor sizing isn’t only about electrical issues…

Size matters!

Standards call for a minimum #6

AWG for mechanical strength

Source: Picture from Internet

Page 22: TIA-607-B - Network Bonding and Grounding Presentation

Supplemental bonding grid construction per TIA-607-B

• #6 AWG round wire or

2‖ wide copper strips

bonded at intersections

• Minimum grid density is

3 m (10 ft) centers

• Minimum 1/0 bond to

TGB/TMGB

Example supplemental bonding grid

Page 23: TIA-607-B - Network Bonding and Grounding Presentation

Example SBG construction

Make aisle grounds

convenient to racks

and cabinets

Cross aisle grounds

every 10 feet

•Use #6 AWG wire

•Use pedestal

grounding clamps at

conductor

intersections

• Bond to AC power

ground through a

local TGB

Page 24: TIA-607-B - Network Bonding and Grounding Presentation

GPQC family of access floor grounding (Mesh-BN)

products

• Up to two each of #6 AWG-2/0

conductors

• Rated for fault current (not all

commonly installed access floor

connectors are)

• Models for access floor

pedestals from ¾‖ to 2‖

diameters

Hinged U-bolt design allows

for ―no look‖ installation—

saving 67% of installation

time

Page 25: TIA-607-B - Network Bonding and Grounding Presentation

Preventing loose busbar connections 25

Two-hole

compression

lugs required

on TGB &

TMGB

(Type LCC-W)

Telecommunications

Grounding Busbar

(TGB), BICSI/TIA-607

hole pattern

(Type GB2B, or Part GB2B0306TPI-1)

BICSI-607 stainless

steel TGB hardware

stack-up

(Parts HDW1/4-KT, HDW3/8-KT)

Page 26: TIA-607-B - Network Bonding and Grounding Presentation

Operability testing of power

connectors

UL 486A, CSA 22.2 4 samples must pass all tests

• Wire secureness test

• Static heating test

• Wire pull-out test

NEBS Level 3 Must be UL Listed

9 samples must pass all tests

• Vibration test

• Wire pull-out

• Temp & humidity cycle

• Hydrogen sulfide corrosion

• 30 day salt fog corrosion

• Wire pull-out

• AC fault current

• Lightning test

• Wire pull-out test

• Stress corrosion cracking

Page 27: TIA-607-B - Network Bonding and Grounding Presentation

Do you already own the tools?

Panduit lugs can be crimped with select competitors’ tools and

dies and still retain UL/CSA approvals and NEBS Level 3

performance

Page 28: TIA-607-B - Network Bonding and Grounding Presentation

ASTM 545-97: Electroplated Coatings of Tin

Panduit doesn’t rest—while others are

cheapening their lugs to compete

with foreign competition, Panduit is

improving quality by moving to Class

C plating as a standard offering*

28

* Running change, in process

Others

Panduit

Page 29: TIA-607-B - Network Bonding and Grounding Presentation

What else needs to be bonded?

• IEEE studies have indicated that the point of diminishing

financial returns with respect to lightning strikes is 2 meters

(6 feet)

• Bond anything that could become charged that a person

could bump while working on a rack/cabinet for safety

• Therefore, bond any conductive path within six feet of your

racks/cabinets

Page 30: TIA-607-B - Network Bonding and Grounding Presentation

Bond cable tray and ladder rack sections

Split bolts – use tin plated if

outdoors (Panduit SBC &

SBCT, respectively)

#6 AWG conductor,

green w/yellow jacket

– OR –

PANDUIT® Wyr-Grid™ and

GRIDRUNNER™ hardware

automatically bonds sections,

eliminating the need for jumper

wires

Specify systems that

automatically bond to

reduce chances of error

Page 31: TIA-607-B - Network Bonding and Grounding Presentation

Armored fiber cables per TIA-607-B

Page 32: TIA-607-B - Network Bonding and Grounding Presentation

Armored fiber optic

cable To grounding

system

Armored fiber grounding cable clamp

• Mechanical clamp design is

entirely external to armor—no

risk of damage to fibers

• Clamp assembly has more

current-carrying capability

than the armor it attaches to

Mechanical

clamp

assembly

Cover protects

clamp and

provides neat

appearance

Page 33: TIA-607-B - Network Bonding and Grounding Presentation

Telecommunications Bonding Backbone (TBB)

• Purpose of TBB is to reduce

potential differences between

interconnected

telecommunications systems

on different floors

• Originates at TMGB and

extends throughout building

using telecom pathways

• Connects TGBs that exist in

each distributor

TBB and its bonds, adapted from Figure 32, TIA-607-B

Page 34: TIA-607-B - Network Bonding and Grounding Presentation

34 TIA-607-B TBB sizing

Page 35: TIA-607-B - Network Bonding and Grounding Presentation

• Specify current-rated connectors

(access floor)

• Specify compression connectors

rather than mechanical

connectors (connections to

racks)

• Panduit builds features into its

products that facilitate grounding

• Panduit has a broad line of

power and grounding

connectors that are tested to the

most rigorous reliability

assurance standards. Specifying

these standards minimizes your

risk

35 Summary

Thank you! Questions?