TI service item description - nak-mci.ir
Transcript of TI service item description - nak-mci.ir
TI service item description Page 1
TI service item description
TI service item description Page 2
Contents 1. General ............................................................................................................................................. 5
2. TIS0001.01 C antenna line ............................................................................................................... 5
3. TIS0002.01 C TRS line ....................................................................................................................... 6
4. TIS0003.01 CIntg General TRS Node ................................................................................................ 7
5. TIS0004.01 Extra work(Site clean up, site folder etc) ...................................................................... 7
6. TIS0005.01 File based CIntg BS ........................................................................................................ 7
7. TIS0006.01 I 1 5-8 antenna line add ................................................................................................ 8
8. TIS0007.01 I 1 5-8 antenna line basic .............................................................................................. 8
9. TIS0008.01 I 1-2 antenna line add ................................................................................................... 9
10. TIS0009.01 I 1-2 antenna line basic ................................................................................................. 9
11. TIS0010.01 I 7-8 antenna line add ................................................................................................. 10
12. TIS0011.01 I 7-8 antenna line basic ............................................................................................... 10
13. TIS0012.01 I coupler/Di/Triplexer .................................................................................................. 11
14. TIS0013.01 I DDF basic ................................................................................................................... 11
15. TIS0014.01 I dish up to 120 cm ...................................................................................................... 12
16. TIS0015.01 I dish up to 60 cm ........................................................................................................ 12
17. TIS0016.01 I BS plinth .................................................................................................................... 13
18. TIS0017.01 I BS system module ..................................................................................................... 13
19. TIS0018.01 I BS sector modules .................................................................................................... 14
20. TIS0019.01 I floor mount 19-23 cab .............................................................................................. 15
21. TIS0020.01 I floor mount 19-23 open frame ................................................................................. 16
22. TIS0022.01 I outdoor BS cab ......................................................................................................... 16
23. TIS0023.01 I panel antenna up to 2.5m ......................................................................................... 17
24. TIS0024.01 IC cable 75/120 ohm basic .......................................................................................... 17
25. TIS0025.01 IC cable IDU-ODU basic ............................................................................................... 18
26. TIS0026.01 IC FO cable basic.......................................................................................................... 18
27. TIS0027.01 IC LAN cable basic ....................................................................................................... 19
28. TIS0028.01 IC macro outdoor power basic .................................................................................... 19
29. TIS0029.01 IC MW HSB or dual pol kit ........................................................................................... 20
30. TIS0030.01 IC MW ODU ................................................................................................................. 21
31. TIS0031.01 IC ODU and dish up to 120cm ..................................................................................... 22
TI service item description Page 3
32. TIS0032.01 IC ODU and dish up to 60cm ....................................................................................... 22
33. TIS0033.01 IC PCM x-connection 75ohm ....................................................................................... 23
34. TIS0034.01 IC PDF .......................................................................................................................... 24
35. TIS0035.01 IC RG-214 Flexbus or IFL run basic .............................................................................. 24
36. TIS0036.01 IC RG-223 Flexbus run basic ........................................................................................ 25
37. TIS0037.01 IC SDH MW indoor unit ............................................................................................... 25
38. TIS0038.01 IC TRS indoor unit ........................................................................................................ 26
39. TIS0039.01 Implementation supervising BS-CT ............................................................................. 27
40. TIS0040.01 Installation planning BS-CT ......................................................................................... 28
41. TIS0041.01 Rem Flexbus per 10m .................................................................................................. 29
42. TIS0042.01 Rem MW ODU ............................................................................................................. 30
43. TIS0043.01 Rem ODU and dish up to 120cm ................................................................................. 30
44. TIS0044.01 Rem ODU and dish up to 60cm ................................................................................... 31
45. TIS0045.01 Rem TRS indoor unit ................................................................................................... 32
46. TIS0046.01 Site survey BS site ....................................................................................................... 33
47. TIS0047.01 Site survey TRS ............................................................................................................ 33
48. TIS0048.01 Transport DOP/Site to Site 0-3,5t regulr ..................................................................... 34
49. TIS0049.01 Travel ........................................................................................................................... 35
50. TIS0050.01 Travel add (Extra site visit) .......................................................................................... 35
51. TIS0051.01 Travel TRS .................................................................................................................... 36
52. TIS0052.01 I BS RF modules ........................................................................................................... 36
53. TIS0053.01 Rem macro BS or power cabinet................................................................................. 37
54. TIS0054.01 IC Micro BS Power module .......................................................................................... 38
55. TIS0055.01 Rem panel antenna up to 2.5m .................................................................................. 38
56. TIS0056.01 Rem 1-2 antenna line add ........................................................................................... 39
57. TIS0057.01 Rem 7-8 antenna line add ........................................................................................... 39
58. TIS0058.01 Swap documentation .................................................................................................. 40
59. TIS0059.01 Rem micro BS equipment............................................................................................ 40
60. TIS0060.01 Site Audit & Documentation ....................................................................................... 40
61. TIS0063.01 Fusion and OTDR test .................................................................................................. 41
62. TIS0065.01 Repeater Telecom implementation ............................................................................ 41
63. TIS0066.01 High Power Repeater acceptance and documentation .............................................. 41
TI service item description Page 4
64. TIS0066.02 Low Power Repeater acceptance and documentation ............................................... 42
65. TIS0067.01 IBS DAS installation per antenna.................................... Error! Bookmark not defined.
66. TIS0068.01 DAS installation (feeder or fiber) per 10m .................................................................. 42
67. TIS0069.01 Conduit and Duct installation ........................................ Error! Bookmark not defined.
68. TIS0070.01 RRU or RU installation .................................................... Error! Bookmark not defined.
69. TIS0071.01 I BS Remote RF modules ............................................................................................. 42
70. TIS0071.02 I Optical fiber up to 100 m .......................................................................................... 43
71. TIS0072.01 Test Call ....................................................................................................................... 44
72. TIS0071.07 S General Fiber Optic Installation & Commissioning .................................................. 44
73. TIS0064.07 IC General Indoor Antenna System (SISO) .................................................................. 44
74. TIS0064.09 IC General Indoor Antenna System (MIMO) ............................................................... 45
75. TIS0062.05 Subway DAS Installation per antenna (SISO) .............................................................. 46
76. TIS0062.06 Subway DAS Installation per antenna (MIMO) ........................................................... 47
77. TIS0062.03 Tunnel DAS Installation per Antenna (SISO) ............................................................... 47
78. TIS0062.07 Tunnel DAS Installation per antenna (MIMO) ............................................................. 48
79. TIS0055.02 Rem IBS Antenna ......................................................................................................... 49
TI service item description Page 5
General
Includes
These activities are included for every service item: - Unpacking the delivery - Inventory checking of the delivery and discrepancy reporting - Preparation of documentation for the work performed under the specific service item as part of the site folder or link folder - Waste disposal including transportation, recycling of the waste according to our environmental requirements and cleaning of the site in relation to and in the scope of the works performed under the specific Service Item.
Excludes
These activities are excluded from the service item, if not indicated in the includes
section of that specific service item
TIS0001.01 C antenna line
Commissioning of antenna line
Service
Commissioning of the antenna line in its complete length including antenna measurements. Project specific processes and work instructions with limitations and thresholds to be reached are applicable and will be defined accordingly. The interface for the measurements (top of BTS or internal jumpers) will be defined from the project. As standard measurements can be counted tests such as Return Loss, Cable Loss, Antenna Isolation Test and Distance to Fault. The measurement equipment such as Site Master has to be calibrated and must fulfill the specifications given from the project.
Excludes
Installation of antenna. Installation of antenna line Installation of active and passive antenna line components, such as Bias Tee, MHA, diplexer, triplexer, combiner, etc.
Testing of any other equipment than feeder line and antenna.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 C Antenna Line 100% 1 pcs
2 Return Loss Measurement 100% 1 pcs Processes, work instruction and measurement limits according the project are applicable
3 Cable Loss Measurement 100% 1 pcs Processes, work instruction and measurement limits according the project are applicable
TI service item description Page 6
4 Isolation Test Measurement 100% 1 pcs Processes, work instruction and measurement limits according the project are applicable
5 Distance To Fault Measurement 100% 1 pcs Processes, work instruction and measurement limits according the project are applicable
6 Documentation 100% 1 pcs
TIS0002.01 C TRS line
Commissioning of transmission line
Service
Commissioning of a transmission line, which may include the following Installation of test equipment and data cables that are needed to perform the commissioning. Installation of physical loop at the other end of the link. Remote loop activation for the other end of the link. Performance of BER test between two sites (covering one or more TRS links). Performance of T1, E1 or other leased line testing between two sites (covering one or more TRS links). Run test according to test procedure using the provided bit sample. Analysis of test results. Complete any test reports related to the test results (if required).
Material
Excludes
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Supply and 100% 1 pcs
installation of test equipment and data cables
2 Installation of 100% 1 pcs Remote loop activation physical loop
3 Performance of 100% 1 pcs
BER test between two
sites
4 Analysis of test 100% 1 pcs Complete any test reports results related to the test results
TI service item description Page 7
TIS0003.01 CIntg General TRS Node
Commissioning and Integration of General TRS Node Equipment
Service
Fastening of plug-in units in their positions. Commissioning of transmission node equipment in its installed configuration. Integration of the transmission node basic configuration up to the maximum capacity. Creation of the transmission node in Network Management System.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Commissioning of General TRS 100% 1 pcs Commissioning of basic
Node transmission node 2 Integration of General TRS Node 100% 1 pcs Integration of basic
transmission node 3 NE Creation in NMS 100% 1 pcs
TIS0004.01 Extra work (Site cleanup, site folder etc.)
Extra work, Site cleanup, compilation of site folder etc.
Service
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Extra work 100% 1 pcs
2 Site clean up 100% 1 pcs
3 Completion of site folder 100% 1 pcs
TIS0005.01 File based CIntg BS
File based commissioning and integration of base station
Service
Creation of the HW configuration (On-site) Define site ID (On-site) Activate needed line interfaces (On-site) Defining O&M channel in A-bis X-connection table (On-site) Perform test calls (on site) if applicable
Excludes
Manual creation of A-bis X-connections Manual creation of time slot allocation.
TI service item description Page 8
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Set up specified integration 100% 1 pcs According to project
parameters specifications 2 BS Testing 100% 1 pcs According to project
specifications 3 Documentation 100% 1 pcs According to project
specifications 4 Test calls (on site) 0% 1 pcs If applicable
TIS0006.01 I 1 5-8 antenna line add
Installation of maximum extra 10m of 1 5/8" antenna line.
Service
Installation of additional meters of 1 5/8" feeder cable with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials.
Excludes
Installation of additional length of a different RF feeder cable than 1 5/8". Installation of the basic length of the RF feeder including connectors and their waterproofing. Installation of jumper cables. Installation of RF feeder labels. Testing of the complete RF feeder run.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable Installation 100% 10 m Incl fixing
TIS0007.01 I 1 5-8 antenna line basic
Installation of a 1 5/8" antenna line basic length
Service
Dismantling and reassembly of the cable entry or gland. Installation of 1 5/8" feeder cable in the defined length with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials, labels and connectors. Installation of jumper cables with fixing accessories, waterproofing materials and labels,. Termination of the antenna line to the Base Station. Termination of the antenna line to the antenna including waterproofing of the outdoor connector (if antenna exists).
Excludes
Installation of antenna. Installation of active and passive antenna line components, such as Bias Tee, MHA, diplexer, triplexer, combiner, etc. Installation of cable support structures. Installation of additional 1 5/8" feeder cable. Installation of any
TI service item description Page 9
other type of RF feeder cable. Commissioning of antenna line and antenna
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable Installation 100% 40 m Incl. Grounding and waterproof. 2 Jumper Installation 100% 1 lot Incl. Sealing
TIS0008.01 I 1-2 antenna line add
Installation of maximum extra 10m of 1/2" antenna line.
Service
Installation of additional meters of 1/2" feeder cable with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials.
Excludes
Installation of additional length of a different RF feeder cable than 1/2". Installation of the basic length of the RF feeder including connectors and their waterproofing. Installation of jumper cables. Installation of RF feeder labels. Testing of the complete RF feeder run.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable Installation 100% 10 m Incl. fixing
TIS0009.01 I 1-2 antenna line basic
Installation of a 1/2" antenna line basic length
Service
Dismantling and reassembly of the cable entry or gland. Installation of 1/2" feeder cable in the defined length with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials, labels and connectors. Installation of jumper cables with fixing accessories, waterproofing materials and labels. Termination of the antenna line to the Base Station. Termination of the antenna line to the antenna including waterproofing of the outdoor connector (if antenna exists).
Excludes
Installation of antenna. Installation of active and passive antenna line components, such as Bias Tee, MHA, diplexer, triplexer, combiner, etc. Installation of cable support structures. Installation of additional 1/2" feeder cable. Installation of any other type of RF feeder cable. Commissioning of antenna line and antenna
TI service item description Page 10
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable Installation 100% 20 m Incl. Grounding and waterproof. 2 Jumper Installation 0% 1 lot Incl. Sealing
TIS0010.01 I 7-8 antenna line add
Installation of maximum extra 10m of 7/8" antenna line.
Service
Installation of additional meters of 7/8" feeder cable with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials.
Excludes
Installation of additional length of a different RF feeder cable than 7/8". Installation of the basic length of the RF feeder including connectors and their waterproofing. Installation of jumper cables. Installation of RF feeder labels. Testing of the complete RF feeder run.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Feeder Cable Installation 100% 10 m DNxxx Incl fixing
TIS0011.01 I 7-8 antenna line basic
Installation of a 7/8" antenna line basic length
Service
Dismantling and reassembly of the cable entry or gland. Installation of 1 run 7/8" feeder cable in the defined length with fixing accessories (clamps, cable ties), grounding kits and waterproofing materials, labels and connectors. Installation of jumper cables with fixing accessories, waterproofing materials and labels, Termination of the antenna line to the Base Station. Termination of the antenna line to the antenna including waterproofing of the outdoor connector (if antenna exists).
Excludes
Installation of antenna. Installation of active and passive antenna line components, such as Bias Tee, MHA, diplexer, triplexer, combiner, etc.
TI service item description Page 11
Installation of cable support structures. Installation of additional 7/8" feeder cable. Installation of any other type of RF feeder cable. Commissioning of antenna line and antenna
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable Installation 100% 30 m Incl. Grounding and waterproof. 2 Jumper Installation 100% 1 lot Incl. Sealing
TIS0012.01 I coupler/Di/Triplexer
Installation of coupler/Di/Triplexer, on the antenna line (down and top)
Service
Installation of one coupler/Di/Triplexer with additional fixing material including connection to the antenna line (only if RF feeder exists) with installation of waterproofing. Installation of additional jumpers with fixing materials, and labels including installation of waterproofing. Installation of label for the coupler.
Excludes
Commissioning of antenna line and antenna Installation of more than two coupler. Installation of antenna line including other active and passive components.
Special cases and other requirements
If the antenna line is installed in the same time as the coupler, the supply and installation of waterproofing for the RF feeder-coupler connector as well as termination of the RF feeder to the coupler are part of the antenna line installation.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of jumper 100% 2 lot Incl. labeling 2 Installation of Coupler 100% 2 pcs Inc. fixing & labeling
TIS0013.01 I DDF basic
Installation of DDF, basic configuration type
Service
Installation of a DDF system basic configurations including mounting materials. Installation
TI service item description Page 12
of DC power cable with fixing accessories, labels and connectors (cable shoes) in the defined length. Installation of labels for the DDF and DC breakers.
Material
Excludes
Installation of other DDF configurations.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 DDF Installation 100% 1 pcs DNxxx For basic config.
2 DC Power Cable Installation 100% 3 m DNxxx Incl. labeling & testing
TIS0014.01 I dish up to 120 cm
Installation of dish up to 120 cm.
Service
Assembling of microwave dish in all its parts. Installation of microwave dish up to 120 cm in diameter with labels and fixing accessories. Installation of dish side strut (if applicable).
Excludes
Installation of the dish pole and bracket. Installation of feeder line.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 Dish installation 100% 1 pcs DNxxx Incl. fixing accessories and labeling and rough alignment.
TIS0015.01 I dish up to 60 cm
Installation of dish up to 60 cm.
Service
Installation of microwave dish up to 60 cm in diameter with labels and fixing accessories.
Excludes
Installation of the dish pole and bracket.
TI service item description Page 13
Installation of feeder line.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 Dish installation 100% 1 pcs DNxxx Incl. fixing accessories and labeling and rough alignment.
TIS0016.01 I BS plinth
Installation of base station plinth
Service
Installation and fixing of base station plinth on floor, wall or pole/mast. Installation of grounding cable for the base station plinth with fixing accessories (cable ties), labels and connectors (lugs) up to the defined length including testing of the complete cable run.
Excludes
Installation of more than one base station plinth. Installation of 19" rack, indoor or outdoor cabinet. Transportation of the equipment to the site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of BS plinth 100% 1 pcs Incl. fixing or pole mounting 2 Installation of Grounding Cable 100% 3 m Incl. labeling & testing
TIS0017.01 I BS system module
Installation and installation testing of Flexi base station system module
Service
Installation of integrated transmission plug-in unit (base station system module). Installation of base station system module including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of grounding cable between base station system module and base station plinth with fixing accessories (cable ties) including testing of the complete cable run. Installation of DC power cable with fixing accessories (cable ties), labels and connectors (shoes) up to the defined length if applicable including testing of the complete cable runs. Installation of alarm cable with fixing accessories (cable ties), labels and connectors up to the defined length including testing of the complete cable run. Installation of labels for DC breakers, AIB and ADM. Terminating of FlexBus cable, fiber optic or PCM cables to the integrated transmission plug-in unit (only for existing cables). Installation testing of the Base Station system unit and integrated transmission plug-in unit.
Excludes
TI service item description Page 14
Installation of more than one base station system module. Installation and Commissioning of an external DC Power Supply System. Installation of any other integrated transmission plug-in unit not defined in customer contract. Supply, installation and testing of transmission connections and links. Testing of external alarms from AIB or ADB up to alarm generating sensors. Installation and commissioning of transmission indoor unit (other than integrated). Transportation of the equipment to the site.
Special cases and other requirements
Cross-connecting of external alarms in Alarm Distribution Module is not included in this Service item, because it is assumed that the incoming alarms and the alarm cable share the same ADM.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of BS system 100% 1 pcs Incl. fixing, casing, front and
module back covers 2 Installation of Int. TRS PIU 100% 1 pcs Incl label, TRM vable
termination term. 3 Installation of Grounding Cable 100% 2 m Incl. testing 4 Installation of DC Power Cable 100% 10 m Incl. labeling & testing 5 Installation of Ext. Al. Cable 100% 7 m Incl. labeling & testing 6 Installation testing of BS 100% 1 pcs
system module
TIS0018.01 I BS sector modules
Installation of base station sector modules (for not integrated TRX and DDU)
Service
Installation of base station TRX module(s) including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of base station DDU/RTC module including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of grounding cable between base station TRX module(s) and Flexi base station plinth with fixing accessories (cable ties) including testing of the complete cable run if applicable Installation of delivered internal Power cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Connecting of DDU/RTC module power cable to the base station TRX module. Installation of delivered internal databus cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Installation of delivered Wide Band Combiner(s) (WBC), including power cable between the WBC and base station TRX module if applicable Installation of delivered internal RF cables between the base station TRX module and DDU/RTC module or/and Wide Band Combiners. Connecting RF antenna line to the base station DDU/RTC module.
Excludes
TI service item description Page 15
Installation of more than one base station DDU/RTC module. Installation of more than four base station TRX modules. Installation and commissioning of base station antenna line. Commissioning of base station DDU/RTC and TRX modules. Transportation of the equipment to the site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of BTS 100% 1 pcs Incl. fixing, casing, front and
DDU/RTC Module back covers 2 Installation of BTS TRX 50% 4 pcs Incl. fixing, casing, front and
Module back covers 3 Installation of grounding cable 20% 2 m Incl. testing 4 Installation of internal power cable 100% 2 pcs Length is 2m 5 Installation of internal databus cable 100% 2 pcs length is 2m 6 Installation of Wide Band Combiner 50% 6 pcs Incl. Power cable
(WBC)
7 Installation of internal RF cables 50% 22 pcs
8 Connecting of DDU/RTC power 100% 1 pcs
Cable
9 Connecting of RF antenna line 100% 2 pcs
TIS0019.01 I floor mount 19-23 cab
Installation of floor mount 19-23 inch cabinet
Service
Installation of a floor-standing 19 or 23 inch cabinet with floor fixing material and label. Installation of an AC power distribution strip for the 19 or 23 inch cabinet with mounting material. Installation of AC power cable with fixing material and labels up to the defined length. Installation of DC power cable with fixing material, labels and connectors (lugs) up to the defined length. Installation labels for AC power breaker and ground termination point (bus bar port). Installation of the grounding cable up to the defined length including labeling of the ground termination point
Excludes
Installation of DC power distribution frame.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 19-23 inch Cabinet Installation 100% 1 pcs Floor-standing 2 19-23 inch Cabinet AC Strip Install. 100% 1 pcs
3 Grounding Cable Installation 100% 7 m Incl. labeling & testing 4 AC Power Cable Installation 100% 7 m Incl. labeling & testing
TI service item description Page 16
TIS0020.01 I floor mount 19-23 open frame
Installation of floor-standing 19-23 inch open frame
Service
Installation of a floor-standing open 19 or 23 inch frame with floor fixing material and label. Installation of an AC power distribution strip for the 19 or 23 inch frame with mounting material. Installation of AC power cable with fixing material and labels up to the defined length. Installation of DC power cable with fixing material, labels and connectors (lugs) up to the defined length. Installation labels for AC power breaker and ground termination point (bus bar port). Installation of the grounding cable up to the defined length including labeling of the ground termination point.
Material
Excludes
Installation of DC power distribution or frame enclosures.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 19/23inch Frame Installation 100% 1 pcs DNxxx Floor-standing
2 19/23inch Frame AC Strip 100% 1 pcs DNxxx Install.
3 Grounding Cable 100% 7 m DNxxx Incl. labeling & testing Installation
4 AC/DC Power Cable 100% 7 m DNxxx Incl. labeling & testing Installation
TIS0022.01 I outdoor BS cab
Installation of outdoor base station cabinet
Service
Installation and fixing of outdoor base station cabinet Installation of grounding cable for the outdoor base station cabinet with fixing accessories (cable ties), labels and connectors (lugs) up to the defined length including testing of the complete cable run. Optional installation of cabinet Air Filter Optional installation of Smoke detector Optional installation of cabinet Site Support module.
Excludes
Installation of more than one outdoor base station cabinet.
TI service item description Page 17
Installation of 19" rack, indoor cabinet or base station plinth Transportation of the equipment to the site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of outdoor BS 100% 1 pcs Incl. fixing
cabinet
2 Installation of grounding cable 100% 3 m Incl. labeling & testing 3 Installation of Cabinet Air Filter 0% 1 pcs
4 Installation of Smoke detector 0% 1 pcs
5 Installation of Site Support module 0% 1 pcs
TIS0023.01 I panel antenna up to 3.5m
Installation of RF panel antenna higher than 0.5 and up to max. 3.5m
Service
Installation of grounding cable with fixing accessories (cable ties), labels and connectors (lugs) up to the defined length. Installation of labels for the antenna. Installation of panel antenna bigger than 0.5m and up to 2.5m with its own mounting brackets and tilting kits. Termination of the grounding cable to the grounding termination point (port of a grounding bus bar). Termination of the feeder line to the antenna (only if RF feeder exists). Adjustment of the panel antenna azimuth and tilt.
Excludes
Installation of antenna holder pole or mast. Installation of Omni or panel antenna smaller than 0.5m or bigger than 2.5m. Antenna line testing. Installation of antenna holder pole or mast. Installation of jumpers and feeder cables.
Special cases and other requirements
If the antenna line is installed in the same time like the antenna, the installation of waterproofing for the RF feeder antenna connector as well as termination of the RF feeder to the antenna are part of the antenna line installation.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Grounding Cable Installation 100% 7 m Incl. labeling 2 RF Antenna Installation 100% 1 pcs Inc. fixing & labeling 3 Adjustment of RF Antenna 100% 1 pcs Azimuth, tilting
TIS0024.01 IC cable 75/120 ohm basic
TI service item description Page 18
Installation and testing of a 75/120 ohm Cable interconnection cable with a basic length
Service
Installation of 75/120 ohm Cable for any network module up to the specified length including fixing accessories, labels and connectors Terminating of the cable to the equipment and existing DDF/MDF block Installation of a label on the DDF/MDF block Testing of the cable in its complete length
Excludes
Installation of jumpers Installation of DDF/MDF blocks Installation of cable exceeding basic length
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Cable installation 100% 20 m incl. label, termination, test
TIS0025.01 IC cable IDU-ODU basic
Installation and commissioning of IDU-ODU cable in the basic length (1+0)
Service
Installation of 75/125 ohm cable from IDU in rack up to ODU on tower. Dismantling and reassembly of the cable entry. Installation of IDU-ODU cable in the basic length with fixing accessories (clamps, fixing ties) labels, waterproofing material and grounding kits. Termination of IDU-ODU cable (connectors).
Excludes
Installation of ODU. Installation of IDU. Installation of IDU-ODU cable support structure.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 IDU-ODU cable. 100% 10 m DNxxx Incl. fixing accessories, labels,
waterproofing material and grounding kits.
2 Connectors 100% 2 pcs DNxxx
TIS0026.01 IC FO cable basic
Installation and testing/commissioning of specified length of fiber optic cable or patch cord
Service
TI service item description Page 19
Installation of up to specified length of fiber optic cable or patch cord with fixing accessories, labels and connectors (if needed). Installation of protection tube, duct, trunk or conduit for the fiber optic cable. Cleaning of FO connectors and plugging on both ends according installation manual. Testing of the fiber optic cable run in its complete length. Terminating of the fiber optic cable run to the equipment or the ODF.
Excludes
Installation of fiber optic cable and its protection above specified length.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Installation of FO Pigtail Cable 100% 1 pcs DNxxx Incl. fixing and labelling
100% 2 pcs DNxxx Pigtail splicing 2 Installation of FO Cable 100% 20 m DNxxx Incl. Protection, label, term,
test 0% 2 pcs DNxxx Connector mounting
3 Cleaning of FO connector 100% 2 pcs DNxxx Standard cleaning process 0% 2 pcs DNxxx Cleaning process for 10Gbs or higher speed FO with microscope
4 Commissioning of FO Cable 100% 20 m DNxxx Incl. Documentation
TIS0027.01 IC LAN cable basic
Installation and testing/commissioning of basic length of LAN cable
Service
Installation of LAN cable with fixing accessories, labels and connectors. Testing of the LAN cable run in its complete length (if applicable). Terminating of the LAN cable to an existing patch panel at each end.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 LAN Cable Installation 100% 10 m DNxxx Incl label, term, test
TIS0028.01 IC macro outdoor power basic
Installation and commissioning of outdoor macro DC power site support basic
Service
Installation of grounding cable with fixing accessories (cable ties), labels and connectors (lugs) up to the defined length including testing of the complete cable run. Installation of AC power cable with fixing accessories (cable ties), labels and connectors (lugs) up to the defined length including testing of the complete cable run. Installation of alarm cable with fixing accessories (cable ties), labels and connectors up to the defined length including testing of the complete cable run. Installation of Q1 cable with fixing accessories (cable ties), labels and connectors up to the defined length including testing of the complete cable run if applicable. Installation of labels for AC breaker, grounding termination points, AIB, ADM and Q1 termination point.
TI service item description Page 20
Installation of Site Support cabinet fixing materials. Installation of outdoor macro Site Support or extension cabinet and application kits including cabinet fixing. Installation of outdoor macro extension cabinet inter-cabling to the Site Support cabinet. Installation of battery shelves which are part of the delivery to the Site Support cabinet. Installation of delivered controller and rectifier units. Installation of Line Terminal Equipment unit if part of the delivery. Installation of batteries. Installation of delivered internal cabling. Commissioning of the Site Support cabinet units and rectifiers including LTE if part of the delivery.
Excludes
Installation and commissioning of more than one Support Site cabinet. Installation and commissioning of indoor macro or micro Support Site cabinet. Installation of additional battery shelves. Testing of external alarms from AIB or ADB up to alarm generating sensors. Transportation of the equipment to the site.
Special cases and other requirements
This Service item covers installation of one basic cabinet only. Cross-connecting of external alarms in Alarm Distribution Module is not included in this service item, because it is assumed that the incoming alarms and the alarm cable share the same ADM.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of Grounding Cable 100% 10 m Incl. labeling & testing 2 Installation of DC Power Cable 100% 10 m Incl. labeling & testing 3 Installation of Ext. Al. Cable 0% 10 m Incl. labeling & testing 4 Installation of remote access Cable (if 100% 10 m Incl. labeling & testing
applicable) 5 Installation of Cabinet 100% 1 pcs Incl. fixing 6 Installation of Batt. Shelf 100% 2-3 pcs
7 Installation of Battery string 100% 2-3 pcs Incl. Intercon. Cables 8 Installation of PIUs, Rectifiers 100% 8-12 pcs 2 PIUs, 6 rectifiers 11 Commissioning of Site Support 100% 1 pcs Docum., alarm test incl.
TIS0029.01 IC MW HSB or dual pol kit
Installation and Commissioning of microwave Hot Stand-by kit or circulator
Service
Installation of grounding cable up defined length with fixing accessories (cable ties), labels and connectors (cable lugs) including testing of the grounding cable in its complete length. Termination of the grounding cable to the grounding termination point (port on a grounding bus bar). Installation of Hot Stand-by Kit or circulator Installation of an additional outdoor unit (if applicable) and the coupler. Commissioning of the additional outdoor unit.
TI service item description Page 21
Testing of the link with Hot Stand-by Kit or circulator Re-commissioning of the indoor unit.
Excludes
Installation of a second microwave antenna. Installation and alignment of MW antennas.
Special cases and other requirements
This Service Item is normally ordered in pairs unless it is used as part of the replacement of one Hot Stand-by kit.
The supply of labels and grounding cable upto 1m is also included in this Service Item.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Grounding Cable Installation 100% 1 m DNxxx Incl. labeling 2 HSB Kit Installation 100% 1 pcs xxx Incl. labeling 3 Circulator Installation 100% 1 pcs xxx Incl. labeling 4 ODU Installation 0% 1 pcs xxx Incl. labeling 5 ODU Commissioning 0% 1 pcs xxx
6 Link Testing 100% 1 pcs xxx Link testing for HSB or circulator
7 IDU Commissioning 100% 1 pcs xxx
TIS0030.01 IC MW ODU
Installation and commissioning of microvawe outdoor unit
Service
Installation of the microwave outdoor unit including the suspension unit if delivered (only used for PowerHopper) and alignment unit, if applicable (including Rough alignment) Installation of waveguide if applicable. Installation of grounding cable up to defined length with fixing accessories (cable ties), labels and connectors (cable lugs) including testing of the grounding cable in its complete length. Termination of the grounding cable to the grounding termination point (port of a grounding bus bar). Installation of outdoor unit label or sticker for marking of the dish. Termination of a TRS cable to the Outdoor Unit and installation of waterproofing materials for the ODU-TRS cable connector (if TRS cable exists). Commissioning of the outdoor unit (including Fine alignment)
Excludes
Installation of microwave antenna. Installation of the antenna pole and bracket. Installation of FlexBus cable.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Grounding Cable Installation 100% 1 m DNxxx Incl. labeling 2 ODU Installation 100% 1 pcs DNxxx Incl. Rough alignment and
labeling
TI service item description Page 22
3 Suspension Installation 0% 1 pcs only with PowerHopper 4 Waveguide Installation 0% 1 pcs
5 ODU Commissioning 100% 1 pcs DNxxx Incl. Fine alignment
TIS0031.01 IC ODU and dish up to 120cm
Installation and Commissioning of outdoor unit and dish up to 120cm
Service
Installation of outdoor unit including the suspension unit if delivered (only used for PowerHopper) and alignment unit (including the rough alignment). Installation of waveguide if applicable. Installation of microwave antenna support rod with fixing accessories. Installation of microwave antenna up to 120cm in diameter. Installation of grounding cable up to defined length with fixing accessories (cable ties), labels and connectors (cable lugs) including testing of the grounding cable in its complete length. Termination of the grounding cable to the grounding termination point (port of a grounding bus bar). Installation of outdoor unit label or sticker for marking of the dish. Termination of a IDU-ODU cable to the Outdoor Unit. Application of waterproofing materials on the ODU connector. Commissioning of the outdoor unit (including the fine alignment).
Excludes
Installation of the antenna pole and bracket. Installation of IDU-ODU cable. Installation and commissioning of TRS Outdoor Unit and MW antenna other than 120cm in diameter.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Grounding Cable Installation 100% 1 m DNxxx Incl. labeling 2 ODU Installation 100% 1 pcs DNxxx Incl. Rough alignment and
labeling 3 Suspension Installation 0% 1 pcs only with PowerHopper 4 Waveguide Installation 0% 1 pcs
5 Ant. Support Rod Installation 0% 1 pcs DNxxx
6 MW Antenna Installation 100% 1 pcs DNxxx Diam. up to 120cm 7 ODU Commissioning 100% 1 pcs DNxxx Incl. Fine alignment
TIS0032.01 IC ODU and dish up to 60cm
Installation and Commissioning of outdoor unit and dish up to 60cm
Service
Installation of outdoor unit including the suspension unit if delivered (only used for PowerHopper) and alignment unit (including the rough alignment). Installation of microwave antenna up to 60cm in diameter.
TI service item description Page 23
Installation of waveguide if applicable. Installation of grounding cable up to the defined length with fixing accessories (cable ties), labels and connectors (cable lugs) including testing of the grounding cable in its complete length. Termination of the grounding cable to the grounding termination point (port of a grounding bus bar). Installation of outdoor unit label or sticker for marking of the dish. Termination of a FlexBus to the Outdoor Unit and installation of waterproofing materials for the ODU-FlexBus connector (if FlexBus exists). Commissioning of the outdoor unit (including the fine alignment)
Excludes
Installation of the antenna pole and bracket. Installation of FlexBus cable. Installation and commissioning of integrated outdoor unit and antenna (MetroHopper).
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Grounding Cable Installation 100% 1 m DNxxx Incl. labeling 2 ODU Installation 100% 1 pcs DNxxx Incl. Rough alignment and
labeling 3 Suspension Installation 0% 1 pcs only with PowerHopper 4 Waveguide Installation 0% 1 pcs
5 MW Antenna Installation 100% 1 pcs DNxxx Diam. up to 60cm 6 ODU Commissioning 100% 1 pcs DNxxx Incl. Fine alignment
TIS0033.01 IC PCM x-connection 75ohm
Installation and testing/commissioning of 75 ohm PCM cross-connection cable
Service
Installation of 75 ohm PCM cross-connection cable with fixing accessories and labels. Terminating of the PCM cross-connection cable to an existing DDF block at each end. Testing of the PCM cross-connection cable in its complete length including jumpers. Installation of analogue X.25 cross-connection cable with fixing accessories and labels. Terminating of the analogue X.25 cross-connection cable to an existing DDF block at each end. Installation of clock synchronization cross-connection cable with fixing accessories and labels. Terminating of the clock synchronization cross-connection cable to an existing DDF block at each end.
Material
Excludes
Installation of 120 ohm PCM cross-connection cable.
Special cases and other requirements
Bill of Quantities
TI service item description Page 24
Pos Category Occurrence Qnt Unit Remark
1 PCM X-Con. 100% 5 m Incl label, term, test Cable Installation
0% 5 m Incl label, term, test
0% 15 m Incl label, term, test
2 X.25 X-Con. 100% 5 m Incl label, term, test Cable Installation
3 Clock X-Con. 100% 5 m Incl label, term, test Cable Installation
0% 15 m Incl label, term, test
TIS0034.01 IC PDF
Installation and commissioning of power distribution
Service
Installation of DC power cable in the defined length with fixing accessories, labels and connectors (cable shoes). Installation of grounding cable up to the defined length with fixing accessories, labels and connectors (cable lugs). Installation of labels for terminating points of the DC power cable (DC breakers). Installation of label for the Power Distribution Frame or panel. Installation of the Power Distribution Frame in a19-inch cabinet. Installation of a distribution panel on the wall or in a cabinet. Testing/commissioning of the Power Distribution Frame and measurement of voltage on the output breakers
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Installation 100% 1 pcs DNxxx 19-inch PDF incl. labeling &
testing 0% 1 pcs DNxxx Power distribution panel incl. labeling & testing
2 Grounding Cable Installation 100% 3 m DNxxx Incl. labeling & testing 3 DC Power Cable Installation 100% 14 m DNxxx Incl. labeling & testing
TIS0035.01 IC RG-214 Flexbus or IFL run basic
Installation and commissioning of one Flexbus run (i.e. RG214 for FH or LCF38-50 for PH) in the basic length
Service
Installation of Flexbus cable (RG-214 or LCF38-50) with fixing accessories (clamps, cable ties for taping), labels, waterproofing material and kits, grounding kits, and connectors in the defined length. Installation of jumper cables with fixing accessories (cable ties) and labels. Termination of the grounding kits to grounding termination points (ports of grounding bus bars).
TI service item description Page 25
Termination (including waterproofing) of the Flexbus run to the TRS Outdoor Unit and TRS Indoor Unit. Commissioning/testing of the complete Flexbus run.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 FlexBus Installation 100% 10 m DNxxx Inc. label, g.-k., sealing
100% 2 pcs DNxxx Connector fitting 2 Jumper Installation 0% 1 m DNxxx Incl. label & sealing 3 FlexBus Run Testing 100% 1 pcs DNxxx
TIS0036.01 IC RG-223 Flexbus run basic
Installation and commissioning of one RG-223 Flexbus run in the basic length
Service
Installation of RG-223 coaxial cable with fixing accessories (clamps, cable ties for taping), labels, waterproofing material and kits, grounding kits, and connectors in the defined length. Installation of jumper cables with fixing accessories (cable ties) and labels for the RG-223 cable. Termination of the grounding kits to grounding termination points (ports of grounding bus bars). Termination (including waterproofing) of the RG-223 feeder line to the TRS Outdoor Unit and TRS Indoor Unit. Commissioning/testing of the complete RG-223 run.
Excludes
Installation of RG-223 cable above the defined length.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Flexbus Installation 100% 10 m DNxxx Inc. label, g.-k., sealing
100% 2 pcs DNxxx Connector fitting 2 Jumper Installation 0% 0 m DNxxx Incl. label & sealing 3 Flexbus Run Testing 100% 1 pcs DNxxx
TIS0037.01 IC SDH MW indoor unit
Installation and commissioning of a SDH split MW indoor unit
Service
Installation of Indoor Unit into a 19 inch, N3 frame, cabinet.or Outdoor Case. Installation of DC power cable in the defined length with fixing accessories, labels and connectors Installation of management interface cable in the defined length with fixing accessories, labels and connectors.
TI service item description Page 26
Installation of external alarms cable in the defined length with fixing accessories, labels and connectors (if applicable, e.g. for repeater sites). Installation of labels. Termination of IDU-ODU cable to the Indoor Unit . Installation of plug-in units into the Indoor Unit of the basic configuration. Installation of Auxiliary traffic channels in the defined length with fixing accessories, labels and connectors (if applicable, e.g. for repeater sites). Installation of adapting cables in FOC installation. Installation of an optional Line interface plug-in board (155Mb/s). Commissioning of the transmission indoor unit.
Excludes
Installation of 19 inch, N3 frame, cabinet.or Outdoor Case Installation of PCM cables. Installation of optical fiber cables. Installation of the IDU-ODU cable. Installation of PCM add/drop.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 TRS Indoor Unit Installation 100% 1 pcs DNxxx Incl labeling 2 DC Power Cable Installation 100% 3 m DNxxx Incl. labeling & testing
0% 0.5 m DNxxx FOC installation: connection within FOC
3 Grounding Cable Installation 100% 3 m DNxxx Incl labeling & testing 0% 0.5 m DNxxx FOC installation: connection within FOC
4 Mgt Cable Installation 100% 10 m DNxxx Incl labeling & testin 100% 10 m DNxxx Not applicable for installation of Indoor Unit into FOC
5 Auxiliary traffic channels 100% 1 pcs DNxxx Lug crimping/Conn. mounting 6 Ext. Al. Cable Installation 100% 7 m DNxxx Incl labeling & testing
0% 0.5 m DNxxx FOC installation: connection within FOC
7 Auxiliary traffic channels Inst. 100% 6 pcs DNxxx Incl labeling & testing 8 (155 Mb/s) installation 100% 1 pcs xxx Incl labeling & testing 9 Adapting cables installation 0% 1 set DNxxx FOC installation:connection
within outdoor cables 10 TRS Indoor Unit Commiss. 100% 1 pcs DNxxx
11 Line cable 100% 4 pcs DNxxx Incl labeling & testing
TIS0038.01 IC TRS indoor unit
Installation and commissioning of a transmission indoor unit
Service
Installation of fixing materials and accessories for the Indoor Unit. Installation of Indoor Unit into a 19 inch, N3 frame, cabinet or Outdoor Case Installation DC power cable in the defined length with fixing accessories, labels and connectors Installation of management cable in the defined length with fixing accessories, labels and connectors. Installation of external alarms cable in the defined length with fixing accessories, labels and
TI service item description Page 27
connectors (if applicable, e.g. for repeater sites). Installation of labels for DC breakers. Termination of a IDU-ODU cable to the Indoor Unit Installation of plug-in units into the Indoor Unit of the basic configuration. Installation of adapting cables. Installation of Line cable Commissioning of the transmission indoor unit.
Excludes
19 inch, N3 frame, cabinet.or Outdoor Case. Installation of PCM cables. Installation of the IDU-ODU cable. Installation of an integrated Indoor Unit. Installation of additional TRS sub-module. Installation of PCM add/drop.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 TRS Indoor Unit Installation 100% 1 pcs DNxxx Incl labeling 2 DC Power Cable Installation 100% 3 m DNxxx Incl. labeling & testing
0% 0.5 m DNxxx FOC installation: connection within FOC
3 Grounding Cable Installation 100% 3 m DNxxx Incl labeling & testing 0% 0.5 m DNxxx FOC installation: connection within FOC
4 Management Cable Installation 100% 10 m DNxxx Incl labeling & testing 5 Ext. Al. Cable Installation 100% 7 m DNxxx Incl labeling & testing
0% 0.5 m DNxxx FOC installation: connection within FOC
6 Line cable installation 100% 2 pcs DNxxx Incl labeling & testing 7 TRS Indoor Unit Commiss. 100% 1 pcs DNxxx
8 Adapting cables installation 0% 1 set DNxxx FOC installation:connection within outdoor cables
TIS0039.01 Implementation supervising BS-CT
Supervising of network element implementation and commissioning on a Base Station or Cellular Transmission sites
Service
Implementation and commissioning supervising activities for a network element being implemented on a Base Station or Cellular Transmission site, which may include the following Supervising of implementation activities at site in line with local implementation processes (including participation in the Pre Installation Site Meeting (PSIM), coordination of the implementation activities at the site. Verification of delivery-, installation-, commissioning-, integration- and customer signoff phases according to the contract scope. First line technical assistance for field teams and act as main contact with project team for fault resolution. Reporting of site-specific implementation progress to project management and updating of project tools. Controlling, scheduling and progress monitoring of field based implementation
TI service item description Page 28
resources. Compilation of Site or Link Folder from documents created in course of the implementation throughout the implementation process until customer signoff. Ensuring the site quality.
Excludes
Performance of site surveys. Performance of installation planning.
Special cases and other requirements
Reporting of site-specific implementation progress to Nokia Siemens Networks project management and updating of Nokia Siemens Networks’s project tools, including but not limited to E doc and E tracker. All completed work should be updated in the appropriate tools on the day of the activity (or no later than 10.00am the following working day) To include site logs, electronic certificates & test results, completion dates, Site Deficciency Reports(SDR)and data storeage files. The Partner is resp. for the following act • In field 1st line support for the deployed resources, Responsible for "first time right" site visit
success for activities within their region. • Every effort to proactively clear site SDR’s during planned works. As a minimum all partner and
as many Nokia Siemens Networks responsible SDR’s are closed at the commissioning activity. • On milestone completion, a warranty of the site works is complete, all certificates are
received and logged and the whole site is ready for customer acceptance – Process to be defined and agreed.
• First line technical support for field teams
• Spares management / provisioning for teams within their control (excluding actual returns loop spare handling managed nationally by partner organisation)
• Main contact with project team for fault resolution • Exceptions reporting and responsible for "Lessons Learned" meetings
• Ensure teams are working to latest version documentation, procedures and software
releases.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Supervising of BS-CT 100% 1 pcs
Implementation
TIS0040.01 Installation planning BS-CT
Installation planning for base station or transmission sites
TI service item description Page 29
Service
Installation planning activities for base station or transmission sites, which may include the following Preparation of Site Layout drawings and sketches based on existing site documentation and drawings as part of the Site Folder for one network element or a site with all related equipment (DC power supply, 19-inch frames or cabinets, feeder and antenna lines, antennas, peripherals, lamp panels). Listing of Ancillary Materials and determining their quantities (can be part of the Site Folder or Link Folder) for the site or the network element and all related equipment.
Excludes
Performance of site survey for installation planning. Installation planning for additional network elements. Implementation supervisioning.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 BS-CT Inst. Planning 100% 1 pcs DNxxx
TIS0041.01 Rem Flexbus per 10m
Removal of Flexbus cable per 40 meters
Service
Disconnection of the grounding kits from the grounding termination points (ports of bus bars) if applicable. Disconnection and deinstallation of Flexbus Cable (e.g. RG-214/RG-223) including cable fixing, grounding kits and jumper cables (if applicable) on the defined lengthrs. Packaging of the removed grounding kits and clamps. Collecting of the removed items in a designated area at the site.
Material
Excludes
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Removal of cable 100% 10 m Removal and spooling up
TI service item description Page 30
TIS0042.01 Rem MW ODU
Removal of microvawe outdoor unit
Service
De-commissioning of the MW outdoor unit and additional MW outdoor unit as part of the Hot Stand-by Kit (if applicable). Disconnection of the TRS cable from the MW outdoor unit (if TRA cable exists). Disconnection of the grounding cable from the grounding termination point and MW outdoor unit. Removal of the grounding cable including cable fixing up to the defined length. De-installation and packaging of the MW outdoor unit and alignment unit as well as the additional MW outdoor unit as part of the Hot Stand-by Kit (if applicable). Disconnection of coupler, removal and packaging of Hot Stand-By Kit (if applicable). Collecting of the removed items in a designated area at the site.
Material
Excludes
Removal of microwave antenna. Removal of the FlexBus cable.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 ODU Decommissioning 100% 1 pcs
2 Cable Removal 100% 10 m
3 HSB Kit Deinstallation 0% 1 pcs Incl. packaging
4 ODU Deinstallation 100% 1 pcs Incl. packaging
TIS0043.01 Rem ODU and dish up to 120cm
Removal of outdoor unit and MW antenna up to 120cm
Service
De-commissioning of the TRS Outdoor Unit and additional TRS Outdoor Unit as part of the Hot Stand-by Kit (if applicable). Disconnection of theIDU-ODU cable from the TRS Outdoor Unit
TI service item description Page 31
Disconnection of the grounding cable from the grounding termination point and TRS Outdoor Unit. Removal of the grounding cable including cable fixing up to the defined length. De-installation and packaging of the microwave antenna up 120cm in diameter. De-installation and packaging of the TRS Outdoor Unit and alignment unit as well as the additional TRS Outdoor Unit as part of the Hot Stand-by Kit (if applicable). Disconnection of coupler, removal and packaging of Hot Stand-By Kit. De-installation and packaging of the microwave antenna support rod with mounting accessories. Collecting of the removed items in a designated area at the site.
Material
Excludes
Removal of microwave antenna with the diameter other than 120cm. Removal of theIDU-ODU cable.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 ODU 100% 2 pcs
Decommissioning
2 Cable Removal 100% 10 m
3 MW Ant. 100% 1 pcs Up to 120 cm incl. Deinstallation packaging
4 MW Ant. Support 100% 1 pcs Incl. packaging Frame Deinst.
5 HSB Kit 0% 1 pcs Incl. packaging Deinstallation
6 ODU 100% 2 pcs Incl. packaging Deinstallation
TIS0044.01 Rem ODU and dish up to 60cm
Removal of outdoor unit and MW antenna up to 60cm
Service
De-commissioning of the TRS Outdoor Unit and additional TRS Outdoor Unit as part of the Hot Stand-by Kit (if applicable). Disconnection of theIDU-ODU cable from the TRS Outdoor Unit Disconnection of the grounding cable from the grounding termination point and TRS Outdoor Unit. Removal of the grounding cable including cable fixing up to the defined length. De-installation and packaging of the microwave antenna up 60cm in diameter. De-installation and packaging of the TRS Outdoor Unit and alignment unit as well as the additional TRS Outdoor Unit as part of the Hot Stand-by Kit (if applicable). Disconnection of coupler, removal and packaging of Hot
TI service item description Page 32
Stand-By Kit. De-installation and packaging of the microwave antenna support rod with mounting accessories. Collecting of the removed items in a designated area at the site.
Material
Excludes
Removal of microwave antenna with the diameter other than 60cm. Removal of theIDU-ODU cable.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 ODU 100% 2 pcs DNxxx
Decommissioning
2 Cable Removal 100% 10 m DNxxx
3 MW Ant. 100% 1 pcs DNxxx Up to 60 cm incl. packaging Deinstallation
4 MW Ant. Support 100% 1 pcs DNxxx Incl. packaging Frame Deinst.
5 HSB Kit 0% 1 pcs DNxxx Incl. packaging Deinstallation
6 ODU 100% 2 pcs DNxxx Incl. packaging Deinstallation
TIS0045.01 Rem TRS indoor unit
Removal and packing of a transmission indoor unit including 16x2 upgrade panel (if applicable)
Service
Decommissioning and power-down of the TRS Indoor Unit. Disconnection of IDU-ODU cables and incoming and outgoing PCM cables. Disconnection and removal of the DC power cable up to the defined length. Disconnection and removal of the management interface cable up to the defined length. Disconnection and removal of the external alarms cable up to the defined length. Disconnection and removal of FlexBus, PCM and management cables between the TRS Indoor Unit and the Extension Unit (if applicable). Removal of labels from the DC breaker and TRS Indoor Unit. Removal and packaging of the plug-in units from the TRS Indoor Unit and the Extension Unit. Removal and packaging of the Extension Unit (if applicable). Removal and packaging of the TRS Indoor Unit. Collecting of the removed items in a designated area at the site.
Material
TI service item description Page 33
Excludes
Removal of IDU-ODU cable. Removal of TRS Outdoor Unit.
Special cases and other requirements
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
1 Removal of 100% 35 m DNxxx Incl. fixing materials and Cable labels
2 Removal of TRS 100% 1 pcs DNxxx Incl. decomm., labels, Ind. Unit packaging
3 Removal of 0% 1 pcs DNxxx Incl. packaging Extension Unit
TIS0046.01 Site survey BS site
Site survey BS site
Service
Conduct of a site survey on a base station site and preparation of related documents including photographs (if applicable) and the relevant site survey check list.
Excludes
Installation planning. Implementation supervisioning.
Special cases and other requirements
This Service Item may include multiple network elements, which are implemented at the same phase at the same site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Site Survey 100% 1 pcs DNxxx Per survey
TIS0047.01 Site survey TRS
Site survey of a micro wave transmission site (one end)
Service
Conduct of a site survey of a transmission site (one end of the link) and preparation of related documents including photographs (if applicable) and the relevant site survey check list.
Excludes
TI service item description Page 34
Installation planning. Implementation supervisioning. Site survey for the other end of the complete link
Special cases and other requirements
This Service Item may include multiple network elements, which are implemented at the same phase at the same site. In case of a microwave link, this Service Item shall be ordered once for each end of the link.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Site Survey TRS site 100% 1 pcs Site Survey One end of the link
template document
TIS0048.01 Transport DOP/Site to Site 0-3,5t regulr
Transportation of low-volume cargo
Service
Carrying or moving cargo from the storage area, or in case of removal, from a designated area at the site, and loading of the cargo onto the vehicle as described below. Transportation of tools, materials or equipment in a truck/lorry with the payload capacity up to 3.5 tons for an initial distance from the storage area to site. (or return travel of the vehicle). Transportation of the same volume of cargo by train. Travel by ferry for the passangers and the vehicle in both directions if needed. Carrying or moving the cargo from the vehicle into the equipment room, battery room, rooftop or other designated area at the site, or in case of removal, into the storage area. Accommodation of the or passangers and secure parking of the vehicle if overnight stay is needed. Insurance of the persons, vehicle, tools, materials and equipment within the scope of this Service Items.
Excludes
Transportation of cargo in a vehicle with the payload capacity above 3.5 tons. Transportation by helicopter. Hoisting of the cargo by crane. Travel of personnel other than the driver and the aids for cargo loading and unloading.
Special cases and other requirements
This Service Item also covers the cases where one aditional stop is made on the route to and on the route back from the destination for the purpose of loading or unloading additional cargo up to the capacity of the vehicle, which is used especially for microwave links. In case of shipping the cargo by airplane, this Service Item shall be ordered in such a quantity so that the price of the air-ticket and handling or storing of the cargo at the airport is compensated.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark
TI service item description Page 35
1 Transport DOP/Site to Site 0+3,5t 100% 200 km DNxxx 100km in 2 dirs, accom. regulr
TIS0049.01 Travel
Travel of persons to the site up to
Service
Travel of one or multiple persons by car (station wagon, MPV, or off-road SUV) or train within a region/nation in both directions. Transportation of tools, materials or equipment in the same car up to the capacity of the trunk or carrying capacity of the persons and moving of the transported tools, materials or equipment onto and from the site (equipment room, battery room, rooftop, any other part of the site). Travel by ferry for the person(s) and the car in both directions if needed. Travel time cost of the person or persons including accommodation if overnight stay is needed. Insurance of the persons, vehicles, tools, materials and equipment within the scope of this Service Items.
Excludes
Transportation of goods above the capacity of the car or the persons. Travel by helicopter.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Travel 100% 1 National
TIS0050.01 Travel add (Extra site visit)
Travel additional distance or additional site visit.
Service
Travel of one or multiple persons by car (station wagon, MPV, or off-road SUV) or train for an additional distance in both directions. Transportation of tools, materials or equipment in the same car up to the capacity of the trunk or carrying capacity of the persons and moving of the transported tools, materials or equipment onto and from the site (equipment room, battery room, rooftop, any other part of the site). Travel by train for the person(s) and the car in both directions if needed. Travel by ferry for the person(s) and the car in both directions if needed. Travel by helicopter for the person(s) in both directions if needed. Travel by plane for the person(s) in both directions if needed. Travel by any other means for the person(s) in both directions if needed. Travel time cost of the person or persons including accommodation if overnight stay is needed. Insurance of the persons, vehicles, tools, materials and equipment within the scope of this Service Item.
TI service item description Page 36
Material
Excludes
Transportation of goods above the capacity of the car or the persons.
Special cases and other requirements
This Service Item also covers the cases where one additional stop is made on the route to and the route from the destination.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Travel addittional 100% 50 km
TIS0051.01 Travel TRS
Travel transmission
Service
All travel related to carry out the tasks in the sales package by one or more people on a MWR end or similar task, which normally only takes part of a day to implement. Travel by car (station wagon, MPV, or off-road SUV), or train or other means needed for the team to get to the site. Travel by ferry for the person(s) and the car if needed. Travel time cost of the person or persons including accommodation if overnight stay is needed as long as required for completing the agreed tasks in the sales package. Transportation of tools, materials or equipment in the same car up to the capacity of the trunk or carrying capacity of the persons and moving of the transported tools, materials or equipment onto and from the site (equipment room, battery room, rooftop, any other part of the site). Insurance of the persons, vehicles, tools, materials and equipment within the scope of this service item. Including transportation of equipment from WH to Site
Excludes
Travel by helicopter. Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Travel Transmission 100% 1 pcs All travel related to the sales
package
TIS0052.01 I BS RF modules
Installation of RF base station RF modules.
TI service item description Page 37
Service
Installation of base station TRX module(s) including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of base station DDU/RTC module including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of grounding cable between base station TRX module(s) and base station plinth with fixing accessories (cable ties) including testing of the complete cable run if applicable Installation of delivered internal Power cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Connecting of DDU/RTC module power cable to the base station TRX module. Installation of delivered internal data bus cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Installation of delivered Wide Band Combiner(s), including power cable between the WBC and base station TRX module if applicable Installation of delivered internal RF cables between the base station TRX module and DDU/RTC module or/and Wide Band Combiners. Connecting RF antenna line to the base station DDU/RTC module.
Excludes
Installation of more than three base station DDU/RTC module. Installation of more than four base station TRX modules. Installation and commissioning of base station antenna line. Commissioning of base station DDU/RTC and TRX modules. Transportation of the equipment to the site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of BTS 100% 1 pcs Incl. fixing, casing, front and
DDU/RTC Module back covers 2 Installation of Flexi BTS TRX 50% 4 pcs Incl. fixing, casing, front and
Module back covers 3 Installation of grounding cable 20% 2 m Incl. testing 4 Installation of internal power cable 100% 2 pcs Length is 2m 5 Installation of internal databus cable 100% 2 pcs length is 2m 6 Installation of Wide Band Combiner 50% 6 pcs Incl. Power cable
(WBC)
7 Installation of internal RF cables 50% 22 pcs
8 Connecting of DDU/RTC power 100% 1 pcs
Cable
9 Connecting of RF antenna line 100% 2 pcs
TIS0053.01 Rem macro BS or power cabinet
Uninstalling and removing of BS/power cabinet
Service
Uninstalling of BS/power cabinet units and cable in the defined length with removing accessories.
Excludes
TI service item description Page 38
Travel Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Un-installation 100% 1 pcs 19-inch BS/power cabinet.
TIS0054.01 IC Micro BS Power module
Installation and Commissioning testing of Micro base station power module
Service
Installation of power plug-in unit.Installation of base station Power module including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of grounding cable between Micro base station power module and base station plinth with fixing accessories (cable ties) including testing of the complete cable run. Installation of DC power cable with fixing accessories (cable ties), labels and connectors (shoes) up to the defined length if applicable including testing of the complete cable runs. Installation of alarm cable with fixing accessories (cable ties), labels and connectors up to the defined length including testing of the complete cable run. Installation of labels for DC breakers.
Excludes
Installation of more than one Micro base station power module. Installation
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of Flexi BS Power 100% 1 pcs Incl. fixing, casing, front and
Module back covers 2 Installation of Grounding Cable 100% 2 m Incl. testing 3 Installation of DC Power Cable 100% 10 m Incl. labeling & testing 4 Installation of Ext. Al. Cable 100% 7 m Incl. labeling & testing
TIS0055.01 Rem panel antenna up to 2.5m
Dismantle of RF panel antenna higher than 0.5 and up to max. 2.5m
Service
Disconnection of the feeder cable from the antenna Un-Installation of panel antenna bigger than 0.5m and up to 2.5m with its own mounting brackets and tilting kits. Disconnection of the feeder cable from the antenna
Termination of the feeder line to the antenna Removal of the grounding cable including cable fixing up to the defined length. De-installation and packaging of the Antenna. Collecting of the removed items in a designated area at the site.
TI service item description Page 39
Preparing asset sheet of uninstalled equipments.
Excludes
Un-Installation of antenna holder pole or mast. Antenna line testing. Un-Installation of antenna holder pole or mast. Un-Installation of jumpers and feeder cables.
Special cases and other requirements Water proofing of antenna ports are mandatory to avoid damaging antenna.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Grounding Cable un-Installation 100% 7 m Incl. labeling 2 RF Antenna un-Installation 100% 1 pcs Inc. fixing & labeling
TIS0056.01 Rem 1-2 antenna line add
Un-Installation of maximum 10m of 1/2" antenna line.
Service
Un-Installation of 10 meters of 1/2" feeder cable with fixing accessories (clamps, cable ties), grounding kits , jumpers and waterproofing materials.
Excludes
Un Installation of RF antenna
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Feeder Cable un-Installation 100% 10 m Incl fixing and jumpers
TIS0057.01 Rem 7-8 antenna line add
Un-Installation of maximum 10m of 7/8" antenna line.
Service
Un-Installation of 10 meters of 7/8" feeder cable with fixing accessories (clamps, cable ties), grounding kits , jumpers and waterproofing materials.
Excludes
Un Installation of RF antenna
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
TI service item description Page 40
1 Feeder Cable un-Installation 100% 10 M Incl fixing and jumpers
TIS0058.01 Swap documentation
Swap detail design and document.
Service Preparing before and after swap detail design, asset sheet.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Site plan 100% 1 pcs
2 Asset sheet 100% 1 pcs
3 Completion of site folder 100% 1 pcs
TIS0059.01 Rem micro BS equipment
Uninstalling and removing of BS/power module of micro site
Service
Uninstalling of plinth x 3 Uninstalling of system module including bracket and casing (if applicable) x1 Uninstalling of RF module including brackets and casing (if applicable) x 2 Uninstalling related cable and accessories of micro equipment.
Excludes Travel
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Un-installation 100% 1 pcs Micro equipment.
TIS0060.01 Site Audit & Documentation
Sit audit and reporting
Service
Site visit Completing Report (Pre-defined Excel form) Preparing Detail design
TI service item description Page 41
This service is to provide requested data which is defined by customer for existing node in network. \
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Site audit and compete Report preparation 100% 1 pcs
TIS0063.01 Fusion and OTDR test
Service of fusion and OTDR test
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 fusion and OTDR test 100% 1 pcs
TIS0065.01 Repeater Telecom implementation Service of installation commissioning and integration of Repeater site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1
Equipment installation commissioning and integration for a repeater site 100% 1 pcs
TIS0066.01 High Power Repeater acceptance and documentation Service of acceptance test and documentation to deliver repeater site to customer
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Acceptance visit test and documentation and site delivery 100% 1 pcs
TI service item description Page 42
to customer.
TIS0066.02 Low Power Repeater acceptance and documentation Service of acceptance test and documentation to deliver repeater site to customer
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1
Acceptance visit test and documentation and site delivery to customer. 100% 1 pcs
TIS0068.01 DAS installation (feeder or fiber) per 10m
Service of installation of DAS system feeder or fiber including fixing cable
Provisioning and installation of required feeder or fiber protections such as every types of conduit, PVC pipe, duct or trunk. Installation of connectors and sealing connections if necessary. Provisioning and installation of standard labels for all DAS components. Provisioning and installation of all needed connectors Provisioning and installation of all necessary fixing accessories.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 DAS Installation Feeder or Fiber 100% 10 M
TIS0071.01 I BS Remote RF modules
Installation of Remote RF modules
Service
Installation of base station TRX module(s) including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of base station DDU/RTC module including casing, fixing of earthquake protection screws, front and back covers if applicable. Installation of grounding cable between base station TRX module(s) and base station plinth with fixing accessories (cable ties) including testing of the complete cable run if applicable
TI service item description Page 43
Installation of delivered internal Power cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Connecting of DDU/RTC module power cable to the base station TRX module. Installation of delivered internal data bus cabling between base station TRX module(s) and system module, including fixing accessories (cable ties). Installation of delivered Wide Band Combiner(s), including power cable between the WBC and base station TRX module if applicable Installation of delivered internal RF cables between the base station TRX module and DDU/RTC module or/and Wide Band Combiners. Connecting RF antenna line to the base station DDU/RTC module. Instillation of fiber and power cable between remote RF module and system module with fixing material
Excludes
Installation of more than 1 base station DDU/RTC module. Installation of more than four base station TRX modules. Installation and commissioning of base station antenna line. Commissioning of base station DDU/RTC and TRX modules. Transportation of the equipment to the site.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 Installation of BTS 100% 1 pcs Incl. fixing, casing, front and
DDU/RTC Module back covers 2 Installation of Remote radio unit 100% 1 pcs Incl. fixing, casing, front and
back covers 3 Installation of grounding cable 20% 2 m Incl. testing 4 Installation of power cable 100% 40 m Up to 40m
5 Installation of internal databus cable/fiber 100% 40 m Up to 40 m
6 Installation of Wide Band Combiner 50% 1 pcs Incl. Power cable (WBC)
7 Installation of internal RF cables 50% 3 pcs
8 Connecting of DDU/RTC power 100% 1 pcs
Cable
9 Connecting of RF antenna line 100% 2 pcs
TIS0071.02 I Optical fiber up to 100 m Installation and testing/commissioning of specified length of fiber optic cable or patch cord
Service
Installation of up to specified length of fiber optic cable or patch cord with fixing accessories, labels and connectors (if needed). Installation of protection tube, duct, trunk or conduit for the fiber optic cable. Cleaning of FO connectors and plugging on both ends according installation manual. Testing of the fiber optic cable run in its complete length. Terminating of the fiber optic cable run to the equipment or the ODF.
Excludes
Installation of fiber optic cable and its protection above specified length.
TI service item description Page 44
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Installation of FO Pigtail Cable 100% 1 pcs DNxxx Incl. fixing and labelling
100% 2 pcs DNxxx Pigtail splicing 2 Installation of FO Cable 100% 100 m DNxxx Incl. Protection, label, term,
test 0% 2 pcs DNxxx Connector mounting
3 Cleaning of FO connector 100% 2 pcs DNxxx Standard cleaning process 0% 2 pcs DNxxx Cleaning process for 10Gbs or higher speed FO with microscope
4 Commissioning of FO Cable 100% 100 m DNxxx Incl. Documentation
TIS0072.01 Test Call Making test call for each antenna after site on air
TIS0071.07 S General Fiber Optic Installation & Commissioning Installation and testing/commissioning of optical fiber up to 48 core per line meter in a route.
Service
Installation of up to specified length of fiber optic cable with fixing accessories, labels and connectors (if needed). Installation of protection tube or conduit for the fiber optic cable. Installation of fusion box/cassette (if needed) Cleaning of FO connectors and plugging on both ends according installation manual testing of the fiber optic cable run in its complete length. Terminating of the fiber optic cable run to the equipment or the ODF.
Bill of Quantities
Pos Category Occurrence Qnt Unit Component Remark 1 Installation of FO Pigtail Cable 100% 1 pcs DNxxx Incl. fixing and labelling
100% 2 pcs DNxxx Pigtail splicing 2 Installation of FO Cable 100% 20 m DNxxx Incl. Protection, label, term,
test 0% 2 pcs DNxxx Connector mounting
3 Cleaning of FO connector 100% 2 pcs DNxxx Standard cleaning process 0% 2 pcs DNxxx Cleaning process for 10Gbs or higher speed FO with microscope
4 Commissioning of FO Cable 100% 20 m DNxxx Incl. Documentation 5 Installation of Fusion box/Cassette 100% 1 pcs DNxxx
TIS0064.07 IC General Indoor Antenna System (SISO) Installation and commissioning of one indoor GSM antenna.
Service
TI service item description Page 45
Service of installation of one indoor antenna to prepare indoor coverage in a residential building, hospital, shopping center, official places, governmental, industrial, commercial building, hotel, airport … including provisioning and installation of mounting kit. Installation of 40m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Provisioning and installation of standard labels for all DAS components.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 40 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 40 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 2 pcs
5 Mounting installation 100% 1 pcs
6 Jumper installation 100% 2 pcs
7 Connector installation 100% 4 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0064.09 IC General Indoor Antenna System (MIMO) Installation and commissioning of one indoor GSM antenna.
Service
Service of installation of one indoor antenna to prepare indoor coverage in a residential building, hospital, shopping center, official places, governmental, industrial, commercial building, hotel, airport … including provisioning and installation of mounting kit. Installation of 80m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Installation of connectors and sealing connections if necessary. Provisioning and installation of standard labels for all DAS components.
Exclude
TI service item description Page 46
Provisioning and installation of cable tray
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 80 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 80 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 4 pcs
5 Mounting installation 100% 1 pcs
6 Jumper installation 100% 4 pcs
7 Connector installation 100% 8 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0062.05 Subway DAS Installation per antenna (SISO) Installation and commissioning of one indoor GSM antenna.
Service
Service of installation of one indoor antenna to prepare indoor coverage in a subway station including provisioning and installation of mounting kit. Installation of 40m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Provisioning and installation of standard labels for all DAS components.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 40 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 40 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 2 pcs
5 Mounting installation 100% 1 pcs
TI service item description Page 47
6 Jumper installation 100% 2 pcs
7 Connector installation 100% 4 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0062.06 Subway DAS Installation per antenna (MIMO) Installation and commissioning of one indoor GSM antenna.
Service
Service of installation of one indoor antenna to prepare indoor coverage in a subway station including provisioning and installation of mounting kit. Installation of 80m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Installation of connectors and sealing connections if necessary. Provisioning and installation of standard labels for all DAS components.
Exclude
Provisioning and installation of cable tray
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 80 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 80 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 4 pcs
5 Mounting installation 100% 1 pcs
6 Jumper installation 100% 4 pcs
7 Connector installation 100% 8 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0062.03 Tunnel DAS Installation per Antenna (SISO) Installation and commissioning of one indoor GSM antenna.
TI service item description Page 48
Service
Service of installation of one indoor antenna to prepare indoor coverage in a tunnel (subway, rural or urban) including provisioning and installation of mounting kit. Installation of 100m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Provisioning and installation of standard labels for all DAS components.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 100 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 100 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 2 pcs
5 Mounting installation 100% 1 pcs
6 Jumper installation 100% 2 pcs
7 Connector installation 100% 4 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0062.07 Tunnel DAS Installation per antenna (MIMO) Installation and commissioning of one indoor GSM antenna.
Service
Service of installation of one indoor antenna to prepare indoor coverage in a tunnel (subway, rural or urban) including provisioning and installation of mounting kit. Installation of 200m feeder cable per antenna including provisioning of all necessary fixing accessories. Provisioning and installation of required feeder protections such as every types of conduit, PVC pipe, duct or trunk. Installation of all passive DAS components such as jumper, combiner, splitter, tapper, and coupler including provisioning of all necessary fixing accessories and mounting kits. Installation of connectors and sealing connections if necessary. Provisioning and installation of standard labels for all DAS components.
Exclude
Provisioning and installation of cable tray
TI service item description Page 49
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark
1 Feeder installation 100% 200 m
40m feeder per antenna should be measured totally for all installed antennas in one site.
2 Antenna Installation 100% 1 pcs Including mounting material
3 Conduit & Duct installation 100% 200 m Including material
4 Combiner/Coupler/Splitter/Tapper 100% 4 pcs
5 Mounting installation 100% 1 pcs
6 Jumper installation 100% 4 pcs
7 Connector installation 100% 8 pcs including sealing if needed
8 Site Survey 100% 0.1 pcs
TIS0055.02 Rem IBS Antenna
Removal and packing of an indoor GSM antenna Service
Disconnection of the feeder cable from the antenna Un-Installation of antenna with its own mounting kits Disconnection of the feeder cable from the antenna Termination of the feeder line to the antenna Un-installation and packaging of the Antenna Collecting of the removed items in a designated area at the site. Preparing asset sheet of uninstalled equipment Un-Installation of jumpers and feeder cables
Special cases and other requirements Water proofing of antenna ports are mandatory to avoid damaging antenna.
Bill of Quantities
Pos Category Occurrence Qnt Unit Remark 1 RF Antenna un-Installation 100% 1 pcs Inc. packing & labeling