Thermo Second Assesment

download Thermo Second Assesment

of 20

Transcript of Thermo Second Assesment

  • 8/3/2019 Thermo Second Assesment

    1/20

  • 8/3/2019 Thermo Second Assesment

    2/20

  • 8/3/2019 Thermo Second Assesment

    3/20

    Thomas Whittingham 20036515

    INTRODUCTIONto save on the energy required to heat the eco house all most all draughts will be sealed resulting

    in no mass transfer of heat energy throught the hot fluid escaping and cold fluid entering.The

    Building Research Establishment [1] notes that the exfiltration of warm air can account

    for as much as 30% of the heat loss through a buildings envelope.

    As the required air changers required per hour for hermitically sealed house is 0.6 per hour [2] the

    aim of EP consultancy is to design a suitable air replacement system that can extract as mutch

    usefull heat from the warmed slate air , Reducing the enviromental impact of the house. Hope

    fully gainin the aproval of channel fours Kevin mercloud..

    essesially EP will mathmaticaially desighn and anlise sevral different types of heat exchanger

    namely, cross flow, shell and tube and plate type.all spefications will be suitable for the eco

    house. design, sizing and rating analysis shall be conducted through several different methods;

    Log Mean Temperature Difference.

    Epsilon-Number of thermal units.

    Overall Heat Transfer co-efficient.

    Full descriptions of each method shall be given in the body of the report and all geometric

    configurations shall be evaluated and compared from the perspective of price ,effectiveness

    ,practabilty, size, and expected enegy saving.

    heat exchangeres are a device for efectivially tranfering heat between two mediums.the gouvning

    principal that drives this heat transfer is the "Zeroth law" stating that if a fluid or medium is in

    contact with another fluid whoes tempreature is lower than its own, given enough time the two

    fluids will reach thermal equalibrium.the second law of thermodynamics is also of critical

    importance to heat exchangers "energy cannot be created or destroyed only converted from one

    from to another. meaning that the total energy lost from the warm stale air must be gained by the

    cold fresh air. Of course assuming no external heat loss is present and the operation is steady

    state.

  • 8/3/2019 Thermo Second Assesment

    4/20

    Thomas Whittingham 20036515

    Predicted by theory and proven by practise E.P Consultants will supply a correctly specified and

    practically sized heat exchanging air replacement system. Witch shall pay back its initial capital

    out lay in ((((years))

    ANALYSIS OF HEAT EXCHANGER TYPESTo correctly design a heat exchanger to the highest effencie, whitind a size sutable for unobtruise

    operation, Basic fluid stream configurations must be evaluated.

    THE 3 MAIN CLASSIFICATIONS FOR FLUID STREAM CONFIGURATION ARE ;

    Parallel flow

    When the hot fluid and the cold fluid

    stream are flowing in the same

    direction.as both fluids enter the

    exchanger a large temperature

    difference will be present. Along the

    Couse of the exchanger the fluids

    exchange heat, from the hotter to the

    cooler, as the length of the exchanger

    is increased so the fluids approach

    thermal equibrilium.

    as can be seen in FIG[3] the highest

    possible temperatures the cold fluid

    can obtain is the mean of the hot and

  • 8/3/2019 Thermo Second Assesment

    5/20

    Thomas Whittingham 20036515

    cross flow

    The schematic for the house is shown below.

  • 8/3/2019 Thermo Second Assesment

    6/20

    Thomas Whittingham 20036515

    ASSUMPTIONSAssumptions and their respective error are to be quantified later in the report

    As the house is a terrace and no data was available for the heating of the

    two adjoining properties, so the difference in temperature is assumed to be

    zero and so there is no driving force for heat transfer enabling the two

    adjoin wall to be eliminated from the model.

    all walls are assumed to be isothermal flat plates

  • 8/3/2019 Thermo Second Assesment

    7/20

  • 8/3/2019 Thermo Second Assesment

    8/20

    Thomas Whittingham 20036515

    A simplified (user friendly) model is available to the client upon request.

    The following has been included in the model

    conduction

    1. through walls and plaster

    2. through the roof

    3. through the basement

    4. through the front door

    5. through windows

    convection

    1. forced convection (external)

    2. natural convection (internal)

    weather data

    1. 5 minuet data averaged over 2 years. Gaining temperatures and

    wind speeds at applicable times in the day.

    2. extensive use of VBA to extract above values

    interpolation of air properties linked to VBA coding

    iterative calculations to accurately calculate values for h

    CALCULATIONSMost of the formulas used in the report are taken and adapted from "introduction

    to THERMAL and FLUIDS ENGINEERING" {3}

    Giving conductive heat transfer as

  • 8/3/2019 Thermo Second Assesment

    9/20

    Thomas Whittingham 20036515

    Q=k*A*T1-T2L

    {3}

    And conductive heat transfer as

    Q=h*a*(Ts-Tf)

    {3}

    Combing the two expressions for the wall facing SSW gives (noting that the arrears are exactly

    the same for each surface)

    And then for the windows facing SSW

    With the h values being worked out with a series of calculation's

    Analysed first is forced convection (h outer)

    (considering fluid flow over an isothermal flat plate.)

    Firstly calculated is the Reynolds number given by (where x is the length of plate under

    consideration)

    Re=*v*x {3}

    And Pr is given by

    Pr=kcp {3}

    Then imputing the two values gained in to below formula

    Nu=Hlk=0.664Re12*Pr13

    {3}

    Re arranging to give the value for the external h value

  • 8/3/2019 Thermo Second Assesment

    10/20

    Thomas Whittingham 20036515

    Now for the internal value of h (natural conduction )

    First needed is the volume expansivity of air:

    =1k For an ideal gas {3}

    Next the Grashof number:

    Gr=g**Ts-Tf*L32

    {3}

    Multiplication of the Grashof number by the prandalt number gives rise to Rayleigh

    number: and if the geometry of the plate is known a Nusselt number can be

    gained. From:

    Nu=0.1*Ra13

    {3}

    or more aptly

    Nu=0.825+0.387*Ra161+0.429Pr9168272

    As the Ts is not known a guess has to made initially iterations are then carried out

    through the rearrangement of the above formulas. a detailed run through one

    iteration will be included in the appendix.

    All k values were taken from {4}

    For the iteration of h values (internal) the following sequence was followed

    A guess was made for the surface temperature. giving Ts as (Tf -2)

    Allowing a Q value to be calculated. and thus a value for h

    Re arranging the formula to give a nusselt number.

    Nu=hlk

    Taking this back to the Rayleigh number

  • 8/3/2019 Thermo Second Assesment

    11/20

    Thomas Whittingham 20036515

    And then back to the surface temperature (in this case for the roof)

    Re inserting this value of Ts in to the original formula (remembering to enableiterative calculation's)

    Giving accurate h values for all walls and roofs.

    INTERPERELATION of air properties the below table was graphed and interpolated

    for all the relevant air properties.

    C kg/m3 kg/m.s kj/kg.K W/mK Temp(c) Cp K Pr

    -20 1.3958 1.6222000E-05 1005.4 0.022507 0.72467

    -15 1.3687 1.6478000E-05 1005.4 0.022903 0.72337-10 1.3426 1.6731100E-05 1005.5 0.023296 0.72212-5 1.3175 1.6982100E-05 1005.5 0.023686 0.720920 1.2933 1.7231000E-05 1005.6 0.024073 0.719775 1.2699 1.7478100E-05 1005.7 0.024548 0.71866

    10 1.2474 1.7722000E-05 1005.8 0.02484 0.7175915 1.2257 1.7965100E-05 1005.9 0.025219 0.7165720 1.2047 1.8205100E-05 1006.1 0.025596 0.7155925 1.1845 1.8444100E-05 1006.3 0.025969 0.7146530 1.1649 1.8681000E-05 1006.5 0.026341 0.7137535 1.1459 1.8915100E-05 1006.7 0.02671 0.71289

    40 1.1275 1.9148100E-05 1006.9 0.027076 0.7120745 1.1098 1.9379100E-05 1007.2 0.02744 0.71128

    QUANTIFICATION OF ASSUMPTIONS"Radiation heat loss will be near zero"

  • 8/3/2019 Thermo Second Assesment

    12/20

    Thomas Whittingham 20036515

    As shown above the total radiative heat loss for all the windows is a pitifully small value not worth

    addition to the total heat loss.

    Radiation only becomes an apparent heat transfer mechanism at larger temperatures due to theforth power. Exhibiting exponential transformation.

    "all walls are assumed to be isothermal flat plates"

    If actual surface roughness was taken in to account the solution would be far

    beyond the scope of our model and having a small effect on the major causes of

    heat loss.

    "In the double glazing no convection of heat takes place only conduction

    mechanisms are present."

    Again too complex for the model to include. As the air is in an enclosed surface

    heat rising on the inner surface will then fall down the outside surface as it cools

    transferring heat along its journey. a reasonable assumption therefore is

    conduction of air is the only medtoh of transport.

    "The house will be steady state"

    For the purposes of the model, major sources of heat loss have to be identified not

    a complete analogy of the house. So for the purposes of the model constructed atransient model would require more time and experience resulting in a higher

    price for the customer.

  • 8/3/2019 Thermo Second Assesment

    13/20

    Thomas Whittingham 20036515

    RESULTS

    Price including vat = 660.764

    Co2 emission from {6}

    Price for kWh of gas {5}

    Shown below is the heat loss for one day in May at time's 16:00-22:00

  • 8/3/2019 Thermo Second Assesment

    14/20

    Thomas Whittingham 20036515

    SUGGESTED IMPROVEMENTSAs observed from the above table a huge relative heat loss is present in the ground floor windows

    facing NNW.

    Calculations were then carried out by our team inserting a double glazed window in to the

    mathematical model where there once was a single glazed window.

    With the double glazing added:

    Q calculation'sfor windowNNW GFtemp inner 20

    temp outer11.057

    34total area ofwindow 5.68length of glass 0.004length of air 0.08

  • 8/3/2019 Thermo Second Assesment

    15/20

    Thomas Whittingham 20036515

    gapk for glass 0.96

    k for air0.0252

    19

    h inner

    10.210

    97

    h outer25.360

    88

    Q=15.309

    13

    Giving rise to a calculated saving of 43.25 per year

    With the new windows and fitting costing around 700 pay back can be expected within 16 years.

    More expensive and invasive heat retention technology is available on the market. Theseinnovations can save the client much more on their energy bills a discussion of the clients wished

    capital expenditure is advised and a suitable energy saving strategy can be implemented.

    Some examples to consider are:

    Floor insulation,Solid wall insulation,a chimney balloon, planting trees on the front

    and back of the properties to block the flow of wind. Less obvious methods include

    having 2 Mediterranean neighbours.

    CONCLUSION

    The total calculated heat loss for the house under investigation is Kwh/Y

    With a carbon cost of KG/co2

    And a capital cost of 660.7

  • 8/3/2019 Thermo Second Assesment

    16/20

    Thomas Whittingham 20036515

    With the installation of double glazing on the ground floor NNW an expected saving of 43.25/y is

    possible

    Further consultation between client and engineering team will lead to capital identified asavailable for improvements to be properly managed. Resulting in greater carbon and capital

    savings for you the costumer.

    REFERENCES{1}

    T = Tmean - Tamp * e[ -Depth * (/365/)0.5] * COS {2/365 * [tnow - tshift - Depth/2 * (365//)

    0.5]}

  • 8/3/2019 Thermo Second Assesment

    17/20

    Thomas Whittingham 20036515

    From

    Kasuda, T., and Archenbach, P.R. "Earth Temperature amd Thermal Diffusivity at

    Selected Stations in the United States", ASHRAE Transactions, Vol. 71, Part 1,

    1965

    {2}

    http://www.sheffieldweather.co.uk/Weather%20Data.htm

    Taken on 20/10/2011

    {3}

    "introduction to THERMAL and FLUIDS ENGINEERING " by Deborah A. Kaminski. Michael K Jensenpublished by WILEY

    {4}

    http://www.engineeringtoolbox.com/ on the 20/10/2011

    {5}

    http://www.biomassenergycentre.org.uk/portal/page?

    _pageid=75,59188&_dad=por tal

    {6}

    http://www.engineeringtoolbox.com/co2-emission-fuels-d_1085.html

    examples of excell sheet

    http://www.sheffieldweather.co.uk/Weather%20Data.htmhttp://www.engineeringtoolbox.com/http://www.biomassenergycentre.org.uk/portal/page?_pageid=75,59188&_dad=por%20talhttp://www.biomassenergycentre.org.uk/portal/page?_pageid=75,59188&_dad=por%20talhttp://www.engineeringtoolbox.com/co2-emission-fuels-d_1085.htmlhttp://www.engineeringtoolbox.com/http://www.biomassenergycentre.org.uk/portal/page?_pageid=75,59188&_dad=por%20talhttp://www.biomassenergycentre.org.uk/portal/page?_pageid=75,59188&_dad=por%20talhttp://www.engineeringtoolbox.com/co2-emission-fuels-d_1085.htmlhttp://www.sheffieldweather.co.uk/Weather%20Data.htm
  • 8/3/2019 Thermo Second Assesment

    18/20

    Thomas Whittingham 20036515

  • 8/3/2019 Thermo Second Assesment

    19/20

    Thomas Whittingham 20036515

  • 8/3/2019 Thermo Second Assesment

    20/20

    Thomas Whittingham 20036515