Form No. S3447-516Supersedes S3447-715Page 1 of 16
Copper Tube / Aluminum Fin Coils: Grooved copper tubing and enhanced aluminum fins provide maximum heat transfer and high energy efficiency. Evaporator coil constructed with hydrophilic fin stock that seals fin surface against aluminum oxide formation, is resistant to mold and mildew growth (tested to ASTM D3273, no growth) and reduces beading of condensate on the fin surface. Optional phenolic-coated coils are also available.
Twin Blowers: Move air quietly. All models feature variable speed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.
ECM Indoor Blower Motor: Features a variable speed motor providing super-high efficiency, low sound levels and soft-start capabilities. The motor is self-adjusting to provide the proper airflow rate for the staged capacity, and for higher static pressure in ducted installations without user adjustment or wiring changes.
Heat Pump Compressor: Scroll 2-Stage Compressors are standard on all 2½ to 5 ton models. Eliminates need for crankcase heater.Double isolated floating compressor mounting system, compressor sound blanket, and discharge muffler for reduced outdoor sound level.
Phase Rotation Monitor: Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
R-410A Refrigerant: Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
Liquid Line Filter Drier: Standard on all units. Protects system against moisture.
Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on, beige textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.Stainless Steel cabinets available.
Foil Faced Insulation: Standard on all units.
Electrical Components: Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or rotary disconnect switch.
Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages are factory or field installed for all 2 through 5 ton models. Features easy slide-in field assembly with various BTUH outputs.
Condenser Fan and Motor Shroud Assembly: Slide out for easy access.
Filter Service Door: Separate service door provides easy access for filter change.
One Inch, Disposable Air Filters: Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.
Solid State Electronic Heat Pump Control: Provides efficient 30, 60 or 90 minute defrost cycle. A thermistor sensor, speed up terminal for service and 10 minute defrost override are standard on the electronic heat pump control.
High & Low Pressure Switches are Auto-Reset: Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
Five Minute Compressor Time Delay: Short cycle protection is standard. Built into the heat pump control.
Emergency Heat Circuit: Permits continuous operation of the system.
Barometric Fresh Air Damper: Standard on all units. Allows up to 25% outside fresh air. Not installed if other optional vent packages selected.
The Bard Wall-Mount Heat Pump is a self-contained energy efficient heating and cooling system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.
Six ventilation options are available.See Page 3 for details on these options.
Built-in Circuit Breakers: Standard on all electric heat versions of single and three phase (230/208 volt) equipment. Rotary disconnects are standard on all electric heat versions of three phase (460 volt) equipment.
Slope Top: Standard feature for water run-off.
Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Top Rain Flashing: Standard feature on all models.
Ventilation System Packages
THE WALL-MOUNT™ STEP CAPACITY “QUIET CLIMATE” HEAT PUMPSIntegrated Part Load Value (IPLV) Efficiency Up To 15.0 BTU/WATT
• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2013.• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.• Commercial Product - Not intended for Residential application.
Engineered Features
Models: T30S to T60S Up to 11.0 EERHeating Capacities: 19,000 to 52,000 BTUH Cooling Capacities: 22,400 to 56,000 BTUH
Green refriGerant
r-410a
Form No. S3447-516Supersedes S3447-715Page 2 of 16
MODELS T30S1-A T30S1-B T30S1-C T36S1-A T36S1-B T36S1-CElectrical Rating – 60 Hz 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3
Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506Compressor--Circuit A
Voltage 230/208 230/208 460 230/208 230/208 460Rated Load Amps 9.6 / 10.8 7.1 / 8.0 4.0 11.5 / 12.9 8.8 / 9.8 4.9Branch Circuit Selection Current 13.1 8.7 4.3 15.3 11.7 5.8Lock Rotor Amps 73 / 73 58 / 58 28 83 / 83 73 / 73 38Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & CondenserFan Motor--HP--RPM--SPD 1/5 - 1050 - 1 1/5 - 1050 - 1 1/5 - 1050 - 1 1/3 - 825 - 2 1/3 - 825 - 2 1/3 - 825 - 2Fan Motor--Amps 1.5 1.5 .8 2.5 2.5 1.1Fan--DIA/CFM 20"-1900 20"-1900 20"-1900 24"-2900 24"-2900 24"-2900
Blower Motor & Evap.Blower Motor--HP-RPM-SPD 1/3 Var. 1/3 Var. 1/3 Var. 1/2 Var. 1/2 Var. 1/2 Var.Blower Motor--Amps 2.8 2.8 2.8 3.2 3.2 3.2CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)
900 - .10 900 - .10 900 - .10 1100 - .15 1100 - .15 1100 - .15
Filter Sizes (inches) STD. 16 x 30 x 1 16 x 30 x 1 16 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1Basic Unit Weight --LBS. 400 400 400 490 490 530 Barometric Fresh Air Damper 4 4 4 4.5 4.5 4.5 Blank-Off Plate 1 1 1 1 1 1 Motorized Fresh Air Damper 11 11 11 11.5 11.5 11.5 Commercial Room Ventilator 35 35 35 42 42 42 Economizer 64 64 64 50 50 50 Energy Recovery Ventilator 52 52 52 81 81 81
MODELS T30S1 T36S1 T42S1 T48S1 T60S1Cooling BTUH, Stage 1 (Partial Capacity) 80/67-80EER @ Part Load (80/67-80) Stage 1 CoolingOperating CFM
22,40014.0650
27,00015.0800
31,00014.9900
37,00015.61000
45,00015.21300
High Temp. Heating 47°BTUH, Stage 1 (Partial Capacity)Operating CFM
19,000650
22,600800
26,000900
30,8001000
38,0001300
MODELS T42S1-A T42S1-B T42S1-C T48S1-A T48S1-B T48S1-C T60S1-A T60S1-B T60S1-CElectrical Rating – 60 Hz 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3
Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506Compressor--Circuit A
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460Rated Load Amps 14.1 / 16 11.2 / 12.7 5.6 16.8 / 19.2 11.1 / 12.7 5.8 21.4 / 23.3 13.1 / 14.2 6.2Branch Circuit Selection
Current18.0 14.2 6.3 21.2 14.1 6.5 27.2 16.6 7.3
Lock Rotor Amps 96 / 96 88 / 88 44 104 83 / 83 41 153 / 153 110 / 110 52Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & CondenserFan Motor--HP--RPM--SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/2-1025-1 1/2-1025-1 1/2-1025-1Fan Motor--Amps 2.5 2.5 1.2 2.5 2.5 1.2 3.8 3.8 3.8Fan--DIA/CFM 24"-2900 24"-2900 24"-2900 24"-2900 24"-2900 24"-2900 24"-3700 24"-3700 24"-3700
Blower Motor & Evap.Blower Motor--HP-RPM-SPD 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var. 3/4 Var.Blower Motor--Amps 4.0 4.0 4.0 4.9 4.9 4.9 4.9 4.9 4.9CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)
1250 - .15 1250 - .15 1250 - .15 1550 - .2 1550 - .2 1550 - .2 1650 - .2 1650 - .2 1650 - .2
Filter Sizes (inches) STD. 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1 20 x 30 x 1Shipping Weight --LBS. 500 500 540 560 560 605 565 565 610 Barometric Fresh Air Damper 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Blank-Off Plate 1 1 1 1 1 1 1 1 1 Motorized Fresh Air Damper 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 11.5 Commercial Room Ventilator 42 42 42 42 42 42 42 42 42 Economizer 50 50 50 50 50 50 50 50 50 Energy Recovery Ventilator 81 81 81 81 81 81 81 81 81
MODELS T30S1 T36S1 T42S1 T48S1 T60S1Cooling BTUH, Stage 2 (Full Capacity) j 80/67-95EER jRated CFM
28,00010.8900
33,80011.01100
39,50011.01250
46,50011.01550
56,00010.71650
IPLV (Integrated Stage 1 and Stage 2) jl 80/67-80 13.7 14.7 14.6 15.0 14.9High Temp Heating (47F) BTUH, Stage 2 (Full Capacity)COP jmRated CFM
27,8003.30900
33,0003.401100
39,0003.301250
43,0003.501550
52,0003.301650
Low Temp Heating (17F) BTUH, Stage 2 (Full Capacity)COP mRated CFM
16,6002.20900
20,0002.401100
23,0002.201250
27,0002.301550
34,6002.401650
j Certified in accordance with ARI Standard 390-2003 for single package vertical units EER = Energy Efficiency Ratio - BTU/WATT efficiencyl Integrated Part Load Value - BTU/WATT efficiency (combines Stage 1 & 2 performance)m COP = Coefficient of Performance - BTU/WATT efficiency
Capacity and Efficiency Ratings at Partial Capacity
Specifications 2-1/2 through 3-Ton
Specifications 3-1/2 through 5 Ton
Certified Capacity and Efficiency Ratings at Full Capacity
Form No. S3447-516Supersedes S3447-715Page 3 of 16
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory, or field-installed at a later date.
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL A blank off plate is installed on the inside of the service door. It covers the air inlet openings which restricts any outside air from entering into the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONALThe built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper. The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. The CRV is power open - spring return on power loss. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”
Four Models Available: CRVS - spring return on power loss or deactivation CRVP - power return (will not close on power loss) CHCRV - modulating actuator with spring return on power loss or deactivation CRVMWH - modulating spring return on power loss or deactivation
ECONOMIZER - ECONWM-Series OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
• ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.• ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:• Fully modulating• Honeywell Direct Drive Hi-Torque Actuator• No linkage required• Simple single blade design• Positive shut-off with non-stick gaskets• Electronic DB and/or Enthalpy sensors depending upon version• Honeywell JADE™ electronic economizer module with precision settings and diagnostics• DB or Enthalpy economizer versions available WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERV OPTIONAL The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM (depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs. Heat transfer efficiency is up to 67% during summer and 75% during winter conditions. The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only. The ERV is designed to be internally mounted behind the service door in the WA, WH or WL model wall-mount units. It can be built-in at the factory or field installed as an option. ERV-*3 and ERV-*5 can be independently adjusted for intake and exhaust rates. 3" air intake hood is standard.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space. Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
Ventilation System Packages
Barometric Fresh Air Damper
Motorized Fresh Air Damper
Commercial Room Ventilator
Economizer
Energy Recovery Ventilator
Form No. S3447-516Supersedes S3447-715Page 4 of 16
Commercial Room Ventilator Performance Data : CRVS-3, CRVP-3 & CRVMWH
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
A B C D E F
Airf
low
(cfm
)
Vent Position
T30*1 High Speed Total and Ventilation Airflow
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
0
100
200
300
400
500
600
700
800
900
0 A B C D E F
Airf
low
(cfm
)
Vent Position
T24H High Speed Total and Ventilation AirflowT30* Low Speed Total And Ventilation Airflow
Total Air 0 ESP
Total Air .2 ESP
Total Air .4 ESP
Vent Air 0 ESP
Vent Air .2 ESP
Vent Air .4 ESP
Airfl
ow (c
fm)
T30*1 High Speed Total and Ventilation Airflow
T24* High Speed Total and Ventilation AirflowT30* Low Speed Total And Ventilation Airflow
Airfl
ow (c
fm)
Form No. S3447-516Supersedes S3447-715Page 5 of 16
Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5
0200400600800
10001200
A B C D E F
Airf
low
(CFM
)
Blade Position
T36S1 with CRVS-5,CRVP-5 & CHCRV-5
Vent Air, Cooling/Heating Mode Total Air, Cooling/Heating Mode
0
200
400
600
800
1000
1200
1400
A B C D E F
Airf
low
(CFM
)
Blade Position
T42S1 with CRVS-5,CRVP-5 & CHCRV-5
Vent Air, Cooling/Heating Mode Total Air, Cooling/Heating Mode
Form No. S3447-516Supersedes S3447-715Page 6 of 16
Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5
Commercial Room Ventilator Performance Data : CRVS-5, CRVP-5 & CHCRV-5
0
100
200
300
400
500
600
0 2 4 6 8 10 12 14 16 18
Air f
low
(CFM
)
Vent Position
T48S1 Vent Airflow
Blower Only Vent Airflow 0.2 ESP
High Speed Comp Vent Airflow 0.2 ESP
A B C D E F
0
100
200
300
400
500
600
700
0 2 4 6 8 10 12 14 16 18
Air f
low
(CFM
Vent Position
T60S1 Vent Airflow
High Speed Comp Vent Airflow 0.2 ESP
Blower Only Vent Airflow 0.2 ESP
A B C D E F
Form No. S3447-516Supersedes S3447-715Page 7 of 16
This Page Intentionally Left Blank
Form No. S3447-516Supersedes S3447-715Page 8 of 16
Performance and Application Data - ERVF-*3 (T30S1)
LEGEND:
VLT = Ventilation Load - TotalVLS = Ventilation Load - SensibleVLL = Ventilation Load - LatentHRT = Heat Recovery - TotalHRS = Heat Recovery - SensibleHRL = Heat Recovery - LatentWVL = Ventilation Load - LatentWHR = Heat Recovery - Total
ERVF-*3 WINTER HEATING PERFORMANCE(INDOOR DESIGN CONDITIONS 70°F DB)
AmbientO.D.
VENTILATION RATE
400 CFM75% EFF.
325 CFM76% EFF.
250 CFM77% EFF.
DB/°F WVL WHR WVL WHR WVL WHR
65 2160 1620 1755 1333 1350 1039
60 4320 3240 3510 2667 2700 2079
55 6480 4860 5265 4001 4050 3118
50 8640 6480 7020 5335 5400 4158
45 10800 8100 8775 6669 6750 5197
40 12960 9720 10530 8002 8100 6237
35 15120 11340 12285 9336 9450 7276
30 17280 12960 14040 10670 10800 8316
25 19440 14580 15795 12004 12150 9355
20 21600 16200 17550 13338 13500 10395
15 23760 17820 19305 14671 14850 11434
SUMMER COOLING PERFORMANCE(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
AmbientO.D.
VENTILATION RATE -- 400 CFM63% EFFICIENCY
VENTILATION RATE -- 325 CFM64% EFFICIENCY
VENTILATION RATE -- 250 CFM65% EFFICIENCY
DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL
105757065
190801296012960
129601296012960
612000
1202081648164
816481648164
385500
155021053010530
105301053010530
497200
992167396739
673967396739
318200
1192581008100
810081008100
382500
775152655265
526552655265
248600
100
8075706560
2808019080109801080010800
1080010800108001080010800
172808280180
00
1769012020671768046804
68046804680468046804
108865216113
00
2281515502892187758775
87758775877587758775
140406727146
00
146019921570956165616
56165616561656165616
89854305
9300
1755011925686267506750
67506750675067506750
108005175112
00
114077751446043874387
43874387438743874387
70193363
7300
95
8075706560
28080190801098086408640
86408640864086408640
19440104402340
00
1769012020691754435443
54435443544354435443
1224765771474
00
2281515502892170207020
70207020702070207020
1579584821901
00
146019921570944924492
44924492449244924492
1010854281216
00
1755011925686254005400
54005400540054005400
1215065251462
00
114077751446035103510
35103510351035103510
78974241950
00
90
8075706560
28080190801098064806480
64806480648064806480
21600126004500
00
1769012020691740824082
40824082408240824082
1360879382835
00
2281515502892152655265
52655265526552655265
17550102373656
00
146019921570933693369
33693369336933693369
1123265522340
00
1755011925686240504050
40504050405040504050
1350078752812
00
114077751446026322632
26322632263226322632
877451181828
00
85
8075706560
28080190801098043204320
43204320432043204320
23760147606660
00
1769012020691727212721
27212721272127212721
1496892984195
00
2281515502892135103510
35103510351035103510
19305119925411
00
146019921570922462246
22462246224622462246
1235576753463
00
1755011925686227002700
27002700270027002700
1485092254162
00
114077751446017551755
17551755175517551755
965259962705
00
80
75706560
190801098037802160
2160216021602160
1692088201620
0
12020691723811360
1360136013601360
1065955561020
0
15502892130711755
1755175517551755
1374771661316
0
9921570919651123
1123112311231123
87984586842
0
11925686223621350
1350135013501350
1057555121012
0
775144601535877
877877877877
68733583658
0
75706560
109803780
0
000
109803780
0
69172381
0
000
69172380
0
89213071
0
000
89213071
0
57091965
0
000
57091965
0
68622362
0
000
68622362
0
44601535
0
000
44601535
0
NOTE: Sensible performance only is shown for winter application.
Form No. S3447-516Supersedes S3447-715Page 9 of 16
Performance and Application Data - ERVF-*5 (T36S1, T42S1, T48S1 & T60S1)
ERVF-*5 WINTER HEATING PERFORMANCE(INDOOR DESIGN CONDITIONS 70°F DB)
AmbientO.D.
VENTILATION RATE
450 CFM 375 CFM 300 CFM
DB/°F WVL WHR WVL WHR WVL WHR
65 2430 1944 2025 1640 1620 1328
60 4860 3888 4050 3280 3240 2656
55 7290 5832 6075 4920 4860 3985
50 9720 7776 8100 6561 6480 5313
45 12150 9720 10125 8201 8100 6642
40 14580 11664 12150 9841 9720 7970
35 17010 13608 14175 11481 11340 9298
30 19440 15552 16200 13122 12960 10627
25 21870 17496 18225 14762 14580 11955
20 24300 19440 20250 16402 16200 13284
15 26730 21384 22275 18042 17820 14612
SUMMER COOLING PERFORMANCE(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
AmbientO.D. VENTILATION RATE -- 450 CFM VENTILATION RATE -- 375 CFM VENTILATION RATE -- 300 CFM
DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL
105757065
214651458014580
145801458014580
688400
1395294779477
947794779477
447500
178871215012150
121501215012150
573700
1180580188018
801880188018
378600
1431097209720
972097209720
459000
958765126512
651265126512
307500
100
8075706560
3159021465123521215012150
1215012150121501215012150
194409314202
00
2053313952802978977897
78977897789778977897
126356054131
00
2632517887102931012510125
1012510125101251012510125
162007762168
00
1737411805679366826682
66826682668266826682
106925123111
00
2106014310823581008100
81008100810081008100
129606210135
00
141109587551754275427
54275427542754275427
86834160
9000
95
8075706560
31590214651235297209720
97209720972097209720
21870117442632
00
2053313952802963186318
63186318631863186318
1421576341711
00
26325178871029381008100
81008100810081008100
1822597872193
00
1737411805679353455345
53455345534553455345
1202864591447
00
2106014310823564806480
64806480648064806480
1458078301755
00
141109587551743414341
43414341434143414341
976852461175
00
90
8075706560
31590214651235272907290
72907290729072907290
24300141755062
00
2053313952802947384738
47384738473847384738
1579492133290
00
26325178871029360756075
60756075607560756075
20250118124218
00
1737411805679340094009
40094009400940094009
1336577962784
00
2106014310823548604860
48604860486048604860
1620094503375
00
141109587551732563256
32563256325632563256
1085463312261
00
85
8075706560
31590214651235248604860
48604860486048604860
26730166057492
00
2053313952802931593159
31593159315931593159
17374107934870
00
26325178871029340504050
40504050405040504050
22275138376243
00
1737411805679326722672
26722672267226722672
1470191324120
00
2106014310823532403240
32403240324032403240
17820110704995
00
141109587551721702170
21702170217021702170
1193974163346
00
80
75706560
214651235242522430
2430243024302430
1903599221822
0
13952802927641579
13952802927641579
1237264491184
0
178871029335432025
2025202520252025
1586282681518
0
11805679323381336
1336133613361336
1046954571002
0
14310823528351620
1620162016201620
1269066151215
0
9587551718991085
1085108510851085
85024432814
0
75706560
123524252
0
000
123524252
0
80292764
0
000
80292764
0
102933543
0
000
102933543
0
67932338
0
000
67932338
0
82352835
0
000
82352835
0
55171899
0
000
55171899
0
LEGEND:
VLT = Ventilation Load - TotalVLS = Ventilation Load - SensibleVLL = Ventilation Load - LatentHRT = Heat Recovery - TotalHRS = Heat Recovery - SensibleHRL = Heat Recovery - LatentWVL = Ventilation Load - LatentWHR = Heat Recovery - Total
NOTE: Sensible performance only is shown for winter application.
Form No. S3447-516Supersedes S3447-715Page 10 of 16
MODELRated Volts & Phase
No. Field Power
Circuits
Single Circuit Multiple Circuit
jMinimum
Circuit Ampacity
Maximum External Fuse or
Ckt. Brkr.
lField Power Wire Size
lGround
Wire
j Minimum Circuit
Ampacity
MaximumExternal Fuse or Ckt.
Breaker
lField Power Wire
Size
lGround
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
T30S1-A00, A0Z-A04
m -AS8p -AF8
230/208-1
111
1 or 2
23444665
35505070
8886
1010108 24 42 35 45 8 8 10 10
T30S1-B00, B0Z-B06-B09
230/208-3111
183645
254045
1088
101010
T30S1-C0Z-C06-C09
460-3111
101924
152025
141210
141210
T36S1-A00, A0Z-A05-A08-A10
n -A15
230/208-1
11
1 or 21 or 21 or 2
2753697985
4060708090
86444
1010888
272733
425252
404040
456060
888
866
101010
101010
T36S1-B00, B0Z-B06-B09
o -B15
230/208-3
1111
23415052
30455060
10866
10101010
T36S1-C0Z -C06-C09
o -C15
460-3
1111
12212627
15253030
14101010
14101010
T42S1-A00, A0Z-A05-A08-A10
n -A15
230/208-1
11
1 or 21 or 21 or 2
3157738386
4060809090
86443
1010888
313134
425252
404040
456060
888
866
101010
101010
T42S1-B00, B0Z-B06-B09
o -B15
230/208-3
1111
26445353
35506060
8866
10101010
T42S1-C0Z-C06-C09
o -C15
460-3
1111
13222727
15253030
14101010
14101010
T48S1-A00, A0Z-A04-A05-A08-A10
n -A15
230/208-1
11
1 or 21 or 21 or 21 or 2
375763788989
50607090
100100
866433
10108888
37373737
26425252
50505050
30506060
8888
10866
10101010
10101010
T48S1-B00, B0Z-B06-B09
o -B15
230/208-3
1111
28465555
40506060
8866
10101010
T48S1-C0Z-C06-C09
o -C15
460-3
1111
14232829
20253030
12101010
12101010
T60S1-A00, A0Z-A05-A10
n -A15n -A20
230/208-1
11 or 21 or 21 or 21 or 3
45719797
113
6080
100100125
84332
108886
45454545
26525252 26
50505050
30606060 30
8888
10666 10
10101010
10101010 10
T60S1-B00, B0Z-B09
o -B15o -B18
230/208-3
1112
325959N/A
456060N/A
866
N/A
101010N/A 59 28 60 30 6 10 10 10
T60S1-C0Z-C09
o -C15o -C18
460-3
1111
15293034
20303035
1210108
12101010
j These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.l Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.m Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.n Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.o Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.p Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Electrical Specifications — Standard Heat Pumps
Form No. S3447-516Supersedes S3447-715Page 11 of 16
MODELRated Volts & Phase
No. Field Power
Circuits
Single Circuit Multiple Circuit
jMinimum
Circuit Ampacity
Maximum External Fuse or
Ckt. Brkr.
lField Power Wire Size
lGround
Wire
j Minimum Circuit
Ampacity
MaximumExternal Fuse or Ckt.
Breaker
lField Power Wire
Size
lGround
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
T30S1DA00, A0ZDA04
m DAS8p DAF8
230/208-1
111
1 or 2
23444665
35505070
8886
1010108 24 42 35 45 8 8 10 10
T30S1DB00, B0ZDB06DB09
230/208-3111
183645
254045
1088
101010
T30S1DC0ZDC06DC09
460-3111
101924
152025
141210
141210
T36S1DA00, A0ZDA05DA08DA10
n DA15
230/208-1
11
1 or 21 or 21 or 2
2955708085
4060708090
86444
1010888
272733
425252
404040
456060
888
866
101010
101010
T36S1DB00, B0ZDB06DB09
o DB15
230/208-3
1111
24425052
30455060
10866
10101010
T36S1DC0Z DC06DC09
o DC15
460-3
1111
14232829
15253030
14101010
14101010
T42S1DA00, A0ZDA05DA08DA10
n DA15
230/208-1
11
1 or 21 or 21 or 2
3157738386
4060809090
86443
1010888
313134
425252
404040
456060
888
866
101010
101010
T42S1DB00, B0ZDB06DB09
o DB15
230/208-3
1111
26445353
35506060
8866
10101010
T42S1DC0ZDC06DC09
o DC15
460-3
1111
13222727
15253030
14101010
14101010
T48S1DA00, A0ZDA04DA05DA08DA10
n DA15
230/208-1
11
1 or 21 or 21 or 21 or 2
375763788989
50607090
100100
866433
10108888
37373737
26425252
50505050
30506060
8888
10866
10101010
10101010
T48S1DB00, B0ZDB06DB09
o DB15
230/208-3
1111
28465555
40506060
8866
10101010
T48S1DC0ZDC06DC09
o DC15
460-3
1111
14232829
20253030
12101010
12101010
T60S1DA00, A0ZDA05DA10
n DA15n DA20
230/208-1
11 or 21 or 21 or 21 or 3
45719797
113
6080
100100125
84332
108886
45454545
26525252 26
50505050
30606060 30
8888
10666 10
10101010
10101010 10
T60S1DB00, B0ZDB09
o DB15o DB18
230/208-3
1112
325959N/A
456060N/A
866
N/A
101010N/A 59 28 60 30 6 10 10 10
T60S1DC0ZDC09
o DC15o DC18
460-3
1111
15293034
20303035
1210108
12101010
Electrical Specifications — Dehumidification Models
j These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical Code (latest version), Article 310 for power conductor sizing.Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) conductors are in a raceway. Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.l Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.m Maximum KW that can operate with the heat pump on is 4KW. Full heat available during Emergency Heat Mode.n Maximum KW that can operate with the heat pump on is 10KW. Full heat available during Emergency Heat Mode.o Maximum KW that can operate with the heat pump on is 9KW. Full heat available during Emergency Heat Mode.p Maximum KW that can operate with the heat pump on is 8KW. Full heat available during Emergency Heat Mode.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses & conductor wires in accordance with the National Electrical Code & all local codes.
Form No. S3447-516Supersedes S3447-715Page 12 of 16
ModelReturn Air(DB/WB)
Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F
T30S1
75/62Total Cooling
Sensible Cooling31,70024,600
29,40023,500
27,40022,500
25,80021,700
24,40021,000
23,40020,500
22,70020,100
22,20019,900
22,00019,700
22,00019,800
80/67Total Cooling
Sensible Cooling33,80023,800
32,00023,000
30,40022,300
29,10021,700
28,00021,200
27,20020,800
26,70020,600
26,40020,500
26,40020,500
26,60020,700
85/72Total Cooling
Sensible Cooling40,30024,400
37,40023,400
34,90022,400
32,90021,600
31,10020,800
29,80020,200
28,80019,700
28,10019,200
27,80018,900
27,70018,700
T36S1
75/62Total Cooling
Sensible Cooling36,70028,700
34,60028,100
32,70027,400
30,90026,600
29,30026,000
27,80025,300
26,60024,500
25,30023,700
24,20023,000
23,30022,200
80/67Total Cooling
Sensible Cooling39,20027,800
37,70027,500
36,30027,100
34,90026,600
33,80026,200
32,40025,700
31,30025,100
30,20024,500
29,10023,900
28,20023,200
85/72Total Cooling
Sensible Cooling46,70028,500
44,10027,900
41,70027,300
39,40026,400
37,30025,700
35,50024,900
33,80023,900
32,20023,000
30,60022,000
29,30021,000
T42S1
75/62Total Cooling
Sensible Cooling42,10033,400
40,10032,400
38,30031,300
36,50030,400
34,70029,500
33,00028,600
31,30027,800
29,70027,100
28,10026,400
26,50025,700
80/67Total Cooling
Sensible Cooling44,90032,400
43,70031,700
42,50031,000
41,20030,400
39,50029,700
38,40029,100
36,90028,500
35,40028,000
33,80027,400
32,10026,900
85/72Total Cooling
Sensible Cooling53,50033,200
51,10032,200
48,80031,200
46,50030,200
44,20029,200
42,00028,200
39,80027,200
37,70026,300
35,50025,300
33,40024,300
T48S1
75/62Total Cooling
Sensible Cooling48,80039,400
46,60038,500
44,60037,600
42,50036,700
40,50035,700
38,60034,800
36,80033,800
35,00032,800
33,20031,800
31,40030,800
80/67Total Cooling
Sensible Cooling52,10038,200
50,80037,700
49,50037,200
48,00036,700
46,50036,000
45,00035,400
43,40034,700
41,70033,900
39,90033,100
38,00032,200
85/72Total Cooling
Sensible Cooling62,10039,100
59,40038,300
56,90037,400
54,20036,500
51,70035,300
49,20034,300
46,80033,100
44,40031,800
41,90030,500
39,50029,100
T60S1
75/62Total Cooling
Sensible Cooling58,10045,200
55,60043,700
53,20042,400
51,00041,100
48,80039,900
46,70038,800
44,70037,800
42,70036,900
40,80036,000
38,90035,200
80/67Total Cooling
Sensible Cooling62,00043,800
60,60042,800
59,10042,000
57,60041,100
56,00040,300
54,40039,500
52,70038,800
50,90038,100
49,10037,400
47,20036,800
85/72Total Cooling
Sensible Cooling73,90044,900
70,90043,400
67,90042,200
65,00040,800
62,20039,500
59,50038,200
56,80037,000
54,20035,700
51,60034,500
49,10033,300
Capacity Multiplier Factors% of Rated Airflow -10 Rated +10
Total BTUHSensible BTUH
0.9750.950
1.01.0
1.021.05
MODEL 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
T30S1BTUH
WATTSCOP
10,30020901.45
12,20021201.69
14,00021601.90
15,90022002.12
17,30022102.30
18,30022202.42
19,40022202.57
20,50022302.70
23,50023102.99
26,60024003.25
29,00024603.46
30,80024903.63
32,70025303.79
T36S1BTUH
WATTSCOP
14,20023001.81
16,20023402.03
18,20023902.24
20,20024302.44
21,60024602.58
22,40024802.65
23,20025002.72
24,10025202.81
27,80026003.14
31,60026703.47
34,20027303.68
36,20027803.82
38,20028203.97
T42S1BTUH
WATTSCOP
14,00027501.50
16,60028101.74
19,30028701.98
22,00029302.20
23,90029602.37
25,40029702.51
26,90029802.65
28,40029902.79
32,80031303.08
37,30032703.35
40,60033703.53
43,30034303.70
46,00034903.87
T48S1BTUH
WATTSCOP
18,00030101.76
20,60030701.97
23,30031302.19
26,00031902.39
28,00032402.54
29,50032802.64
31,10033202.75
32,70033602.86
37,00034503.15
41,30035403.42
44,60036103.62
47,30036703.78
50,00037303.93
T60S1BTUH
WATTSCOP
24,80037701.93
27,70038502.11
30,60039302.29
33,50040102.45
35,80040802.58
37,60041402.67
39,40042002.75
41,30042602.85
45,80043703.08
50,30044703.30
53,80045603.46
56,70046403.59
59,60047203.70
* 70°F DB indoor return air at rated CFM includes defrost operation below 45°.
j Below 65°F, unit requires a factory or field installed low ambient control. Return air temperature °F.
Full Load Cooling Application Data - Outdoor Temperature °F j
Full Load Heating Application Rating & Outdoor Temperature °F*
Form No. S3447-516Supersedes S3447-715Page 13 of 16
ModelReturn Air(DB/WB)
Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F
T30S1
75/62Total Cooling
Sensible Cooling23,80018,700
22,40017,700
20,70016,800
19,50016,100
18,30015,600
17,40015,200
16,60014,900
15,90014,600
15,40014,600
15,00014,700
80/67Total Cooling
Sensible Cooling25,40018,100
24,10017,300
23,00016,600
22,00016,100
21,00015,700
20,20015,400
19,50015,200
18,90015,100
18,50015,200
18,10015,400
85/72Total Cooling
Sensible Cooling30,30018,600
28,20017,600
26,40016,700
24,90016,000
23,40015,400
22,10014,900
21,10014,500
20,10014,200
19,50014,000
18,80013,900
T36S1
75/62Total Cooling
Sensible Cooling26,40021,300
24,80020,800
23,40020,300
22,10019,800
20,80019,400
19,60018,700
18,30018,200
17,20017,400
16,20016,800
15,00016,100
80/67Total Cooling
Sensible Cooling28,10020,600
27,00020,400
26,00020,100
24,90019,800
23,80019,500
22,80019,000
21,60018,600
20,50018,000
19,40017,400
18,20016,800
85/72Total Cooling
Sensible Cooling33,50021,100
31,60020,700
29,90020,200
28,10019,700
26,50019,200
25,00018,400
23,30017,800
21,80016,900
20,40016,100
18,90015,200
T42S1
75/62Total Cooling
Sensible Cooling30,70023,200
28,50023,000
26,60022,600
24,90022,100
23,40021,500
22,10020,900
21,00020,100
20,20019,200
19,40018,100
18,80017,000
80/67Total Cooling
Sensible Cooling32,70022,500
31,00022,500
29,50022,400
28,10022,100
26,80021,700
25,70021,200
24,80020,600
24,00019,800
23,30018,800
22,80017,800
85/72Total Cooling
Sensible Cooling39,00023,100
36,30022,900
33,90022,500
31,80022,000
29,80021,300
28,10020,500
26,80019,700
25,60018,600
24,50017,300
23,70016,100
T48S1
75/62Total Cooling
Sensible Cooling35,30027,500
34,00027,200
32,60026,800
31,20026,300
29,60025,700
28,10025,100
26,50024,300
24,80023,300
23,00022,400
21,20021,300
80/67Total Cooling
Sensible Cooling37,70026,600
37,00026,600
36,20026,500
35,20026,300
34,00025,900
32,70025,500
31,20024,900
29,50024,100
27,70023,300
25,70022,300
85/72Total Cooling
Sensible Cooling43,30033,900
41,30033,100
39,50032,300
37,50031,400
35,50030,500
33,70029,600
31,80028,700
30,00027,700
28,10026,700
26,30025,700
T60S1
75/62Total Cooling
Sensible Cooling43,30033,900
41,30033,100
39,50032,300
37,50031,400
35,50030,500
33,70029,600
31,80028,700
30,00027,700
28,10026,700
26,30025,700
80/67Total Cooling
Sensible Cooling46,20032,900
45,00032,400
43,80032,000
42,40031,400
40,80030,800
39,20030,100
37,50029,400
35,70028,600
33,80027,800
31,80026,900
85/72Total Cooling
Sensible Cooling55,10033,700
52,60032,900
50,30032,200
47,90031,200
45,30030,200
42,90029,100
40,50028,000
38,00026,800
35,50025,600
33,10024,300
Capacity Multiplier Factors% of Rated Airflow -10 Rated +10
Total BTUHSensible BTUH
0.9750.950
1.01.0
1.021.05
MODEL 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
T30S1BTUH
WATTSCOP
6,50017501.09
7,80017701.30
9,20017901.51
10,50018001.71
11,70018101.90
12,80018102.08
13,90018102.26
15,10018102.45
16,70018502.65
18,40018902.86
19,80019203.03
21,20019403.21
22,50019503.39
T36S1BTUH
WATTSCOP
6,70019601.01
8,40019701.25
10,10019801.50
11,80019901.74
13,40020101.96
14,90020402.15
16,50020602.35
18,00020902.53
20,00020802.82
21,90020803.09
23,70020803.34
25,40021003.55
27,10021103.77
T42S1BTUH
WATTSCOP
8,80023401.11
10,60023601.32
12,50023901.54
14,30024101.74
16,20024101.97
18,10024002.21
20,00023802.47
21,90023702.71
23,60024502.83
25,40025402.93
27,10025903.07
29,00026103.26
30,80026403.42
T48S1BTUH
WATTSCOP
10,80024901.28
12,90025201.50
15,10025501.74
17,20025801.96
18,90025902.14
20,30026002.29
21,60026002.44
23,00026002.60
26,30026702.89
29,50027403.16
32,10027903.38
34,30028203.57
36,40028503.75
T60S1BTUH
WATTSCOP
11,40028601.17
14,20029001.44
17,10029501.70
19,90029901.96
22,70030402.19
25,50031102.41
28,30031702.62
31,00032302.82
33,90032503.06
36,90032603.32
39,70032903.54
42,60033403.74
45,40033803.94
* 70°F DB indoor return air at rated CFM includes defrost operation below 45°.
j Below 65°F, unit requires a factory or field installed low ambient control. Return air temperature °F.
Part Load Cooling Application Data - Outdoor Temperature °F j
Part Load Heating Application Rating & Outdoor Temperature °F*
Form No. S3447-516Supersedes S3447-715Page 14 of 16
Model Rated ESP jMax ESP
Blower Only
lCooling
& Heat PumpStage 1
mCooling
& Heat PumpStage 2
mElectric Heat
T30S .10 .50 650 650 900 900
T36S .15 .50 800 800 1100 1100
T42S .15 .50 800 900 1250 1250
T48S .20 .50 825 1000 1550 1550
T60S .20 .50 850 1300 1650 1650
NominalKW
At 240V j At 208V j At 480V At 460V
KW1-Ph Amps
3-Ph Amps
Btuh KW1-Ph Amps
3-Ph Amps
Btuh KW3-Ph Amps
Btuh KW3-Ph Amps
Btuh
4.0 4.0 16.7 13,652 3.00 14.4 10,239
5.0 5.0 20.8 17,065 3.75 18.0 12,799
6.0 6.0 14.4 20,478 4.50 12.5 15,359 6.0 7.2 20,478 5.52 6.9 18,840
8.0 8.0 33.3 27,304 6.00 28.8 20,478
9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260
10.0 10.0 41.7 34,130 7.50 36.1 25,598
15.0 15.0 62.5 36.1 51,195 11.25 54.1 31.2 38,396 15.0 18.0 51,195 13.80 17.3 47,099
20.0 20.0 83.3 68,260 15.00 72.1 51,195
j These electric heaters are available in 230/208V units only. These electric heaters are available in 480V units only.
• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models
Heat Pump Models
-A00 Models230/208-1
-B00 Models230/208-3
-C00 Models460-3
Heater Model # KW Heater Model # KW Heater Model # KW
T30S1EHT03H-A04BEHT03H-AF8BEHT03H-AS8B
4F8S8
EHT03H-B06BEHT03H-B09B
69
EHT03H-C06EHT03H-C09
69
T36S1
EHS03H-A05BEHT05H-A08BEHT05H-A10BEHT05H-A15B
58
1015
EHT05H-B06BEHT05H-B09BEHS05H-B15B
69
15
EHS05H-C06EHS03H-C09EHS03H-C15
69
15
T42S1
EHS03H-A05BEHT05H-A08BEHT05H-A10BEHT05H-A15B
58
1015
EHS05H-B06BEHS05H-B09BEHS05H-B15B
69
15
EHS05H-C06EHS05H-C09EHS05H-C15
69
15
T48S1
EHT06H-A05BEHT06H-A08BEHT06H-A10BEHT06H-A15B
58
1015
EHT06H-B06BEHT06H-B09BEHT06H-B15B
69
15
EHT06H-C06EHT06H-C09EHT06H-C15
69
15
T60S1
EHT06H-A05BEHT06H-A10BEHT06H-A15BEHT06H-A20B
5101520
EHT06H-B09BEHT06H-B15BEHT06H-B18B
91518
EHT06H-C09EHT06H-C15EHT06H-C18
91518
Heater Packages - Field Installed for Standard & Dehumidification Models
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating & cooling, dry & wet coil conditions and at both 230/208 or 460 volts.j Maximum ESP (inches WC) shown is with 2" thick disposable filter. Blower only CFM is the total air being circulated during continuous fan mode. Airflow remains constant.l Blower only CFM reduces during continuous fan mode. Requires wiring modification; consult Installation Instructions and Wiring Diagram.m CFM output on Cooling or Electric Heat.
Indoor Blower Performance - CFM (0.00" — 0.50" H20) j
Form No. S3447-516Supersedes S3447-715Page 15 of 16
Dimensions of Basic Unit for Architectural & Installation Requirements (Nominal)
MODEL WIDTH(W)
DEPTH(D)
HEIGHT(H)
SUPPLY RETURN
A B C B E F G I J K L M N O P Q R S T
T30S1 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 5.00 12.00 5.00
T36S1T42S1
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
T48S1T60S1
42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
Clearances Required for Service Accessand Adequate Condenser AirflowMODELS LEFT SIDE RIGHT SIDE
All Models 20" 20"
Minimum Clearances Required to Combustible Materials
MODELS j SUPPLY AIR DUCT FIRST THREE FEET CABINET
All Models 1/4" 0"
j Refer to the Installation Manual for more detailed information.
All dimensions are in inches. Dimensional drawings are not to scale.
3"
7.881.00
11"
31.88
Filter Access Panel
Air Outlet
Front View
Condenser
Standardflush ventdoor fornon-ERV/Econ.models
Ventilation Air
W
5.88
F
G
1
1
Heat
models.
1
Electric
Hood forECONWMT
MIS-2487 H
(Lockable)
Built InRain Hood
4° Pitch
Entrance
High VoltageEntrance
Access Panel
Low Voltage
Disconnect
Heater
PanelAccess
AirInlet
Drain
Cond.
Electrical
Side View
Electrical
C. Breaker/
Hood for ERV andECONWMS modelsonly
1.250
H
A
I
D
J
2.13
C
K
Electrical
Side Wall
Entrances
Mounting
Optional
Supply Air Opening
(Built In)
ShippingLocation
Brackets
Return Air Opening
Top RainFlashing
Bottom InstallationBracketBack View
T
B
M
OE
R
S
S
S
S
S P
.44
NQ
L
Unit Charge Rates
UNIT Std. Unit - Lbs.
Dehum. Units - Lbs.
T30S1 - High Efficiency Step Capacity Quiet Climate HP
7.0625 6.625
T36S1 - High Efficiency Step Capacity Quiet Climate HP
10.75 11.5625
T42S1 - High Efficiency Step Capacity Quiet Climate HP
11.625 12.125
T48S1 - High Efficiency Step Capacity Quiet Climate HP
12.00 12.00
T60S1 - High Efficiency Step Capacity Quiet Climate HP
12.4375 12.4375
Form No. S3447-516Supersedes S3447-715Page 16 of 16
Heat Pump Wall-Mount Model Nomenclature
REVISION
j For 0 KW and circuit breakers (230/208 volt) or toggle disconnect (460V) applications, insert 0Z in the KW field of the model number. See Pages 10 & 11. Insert “D” for dehumidification with hot gas reheat. Reference Form 7960-640 for complete details.
T 36 S 1 A 05 X X X X X XMODELNUMBER |
SUPPLY AIROUTLETX - Front (Standard)
COIL OPTIONSX - Standard Hydrophilic Fin Indoor Coil & Uncoated Aluminum Outdoor Coil1 - Phenolic Coated Indoor Coil2 - Phenolic Coated Outdoor Coil3 - Phenolic Coated ID & OD Coil
COLOR OPTIONSX - Beige1 - White4 - Buckeye Gray5 - Desert Brown8 - Dark BronzeS - Stainless Steel
FILTER OPTIONS X - 1-Inch Fiberglass (MERV 2)M - 2-Inch Pleated (MERV 11) P - 2-Inch Pleated (MERV 8)
CAPACITY | 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton60 - 5 Ton
CONTROL MODULES (See Control Module Options)
VOLTS & PHASE | A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW j 0Z - 0KW04 - 4KW05 - 5KW 06 - 6KWF8 - 8KWS8 - 8KW 09 - 9KW 10 -10KW15 -15KW18 -18KW20 -20KW
VENTILATION OPTIONS(See Vent Options Table Below)
STEP CAPACITY HEAT PUMP
SPECIALTY PRODUCTS (Non-Standard)
Form No. S3447
May, 2016
Supersedes: S3447-715
Ventilation OptionsModels T30S1 T36S1, T42S1, T48S1, T60S1
Description Factory InstalledCode No.
Field InstalledPart No.
Factory InstalledCode No.
Field InstalledPart No.
Barometric Fresh Air Damper - Standard X BFAD-3 X BFAD-5
Blank-Off Plate B BOP-3 B BOP-5
Motorized Fresh Air Damper - No Exhaust j M MFAD-3 M MFAD-5
Commercial Ventilator - Modulating Spring Return w/Exhaust C CRVMWH-3 C CHCRV-5
Commercial Ventilator - Spring Return w/Exhaust V CRVS-3 V CRVS-5
Commercial Ventilator - Power Return w/Exhaust P CRVP-3 P CRVP-5
Economizer - Standard - Enthalpy m S ECONWMS-E3B S ECONWMS-E5B
Economizer - Equipment Bldg., Enthalpy n W ECONWMT-E3B W ECONWMT-E5B
Economizer - Equipment Bldg., DB Temp n T ECONWMT-T3B T ECONWMT-T5B
Energy Recovery Ventilator - 230 Volt l R ERVF-A3 j R ERVF-A5 j
Energy Recovery Ventilator - 460 Volt l R ERVF-C3 j R ERVF-C5 j Door Kit for ERVF (Required) N/A WMDK3- l N/A WMDK5- l
Heat Pump Control ModulesLow Pressure
Control j High Pressure
Control jLow Ambient Control
and Relay Start Kit
lStart Kit
mOutdoor
ThermostatFactory Installed Code Field Installed Part
STD STD X X
STD STD T30-48 l 230V n E CMH-20
STD STD T30-48 l 460V n E CMH-21
STD STD T60 l All n E CMH-19
STD STD l Field Installed Only CMC-15 l
STD STD l Field Installed Only SK111 m
STD STD l Field Installed Only CMC-29
STD = Standard Equipmentj The high & low pressure controls are auto reset. Operating circuit includes a lockout feature and is resettable from the wall thermostat. All low pressure controls use a timed bypass circuit to prevent nuisance tripping during low temperature start-up. The low ambient control includes an 8201-008 (fan relay) and permits cooling operation down to 0°F.l PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 is used.m Start capacitor and potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.n ODT. Outdoor thermostat. Field-installed only. Bard Part #8403-061. Comes with weatherproof enclosure. Works in conjunction with multi-stage thermostats offered by Bard and can be configured for any or all of compressor cut-off in heat pump mode, minimum cooling mode and maximum electric heat operation based on outdoor temperature.o Freezestat is standard on dehumidification models. Field installed option for standard units. NOTE: Standard heat pump control board has a 5-minute compressor anti-short cycle timer.
j Intake and exhaust can be independently adjusted. Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)l WMDK Door Kit must be ordered in addition to ERVF Assembly and color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)m Units controlled by thermostats other than Bard 8403-060 or Bard CompleteStat™ may require Bard “8620-220 2-Stage Heat Pump with Economizer” Relay Kit for proper operation.n Partial Full Flow (75% of Rated Cooling Airflow). All ECONWMS versions have 3" deep air intake hood.
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com