The Use of Gaseous Insulation in High Voltage Circuit-breakers

35
The Use of Gaseous Insulation in High Voltage Circuit-breaker Chapter 13

description

Chapter 13. The Use of Gaseous Insulation in High Voltage Circuit-breakers. 13.1 Introduction. Concept of circuit breaker. - PowerPoint PPT Presentation

Transcript of The Use of Gaseous Insulation in High Voltage Circuit-breakers

Page 1: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

The Use of Gaseous Insulation in High Voltage Circuit-breakers

Chapter 13

Page 2: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.1 Introduction

The basic construction of circuit breaker entails the separation of contacts in an

insulating fluid. The circuit breakers are constructed using either a metal closure with

two terminal bushings or an enclosure of insulating material with metal end caps.

Metal

Insulation

Insulating fluid Insulating fluid

Concept of circuit breaker

Function of insulating fluid

- Extinguishment of the arc drawn between the contacts when the circuit breaker opens

- Provision of adequate electrical insulation between the contacts and from each contact

to earth

1/34

Page 3: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Insulating fluid for circuit-breaker

- Many insulating fluids are suitable for arc-extinction and the fluid chosen varies

with the rating and type of circuit-breaker

- The insulating fluid commonly used for circuit-breakers :

Air at atmospheric pressure, Compressed air, oil (which produces hydrogen for arc

extinction), ultra-high vacuum, Sulphur hexafluoride (SF6)

Insulating fluid for ancillary equipment of circuit-breaker

- Because arc interruption is not involved, the fluid can be chosen simply on its insulating

merits.

- Current transformers, Voltage transformers, Busbars

- Arcton-12 (difluorodichloromethane) :

Formation of carbon and chlorine during arcing

13.1 Introduction

2/34

Page 4: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.2 Modern switchgear practice

Classification of circuit breakers

- According to the insulating medium used for arc-extinction

~ 11kV : air-break type (using air at atmospheric pressure) or oil-break type

11kV ~ 66kV : mainly oil-breakers are in use

132kV ~ 275kV : oil-break type (small-oil or bulk-oil) and gas-blast type

400kV ~ 750kV : almost exclusively of the gas-blast type

Extra high voltage gas-blast circuit breakers

- Compressed air : up to 1000 lb/in2

- Operating pressure of SF6 : 200 lb/in2

- In any design, the gaseous insulation works in conjunction with solid insulation,

and circuit breaker equipments differ basically in the form of the insulation from

earth

3/34

Page 5: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.2 Modern switchgear practice

Two principal arrangements used for extra high voltage breakers

- Metal tank insulated from ground

- Compressed gas is used

- Tank is supported by a porcelain insulator

- Several units can be used in series for the

highest voltages

Live-tank type Dead-tank type

- Tank being at ground potential

- Contacts are insulated from the tank by

compressed gas in parallel with solid

insulation immersed in the gas

4/34

Page 6: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.2 Modern switchgear practice

Basic types in the extra high voltage gas blast breakers

- Live or dead tank construction combined with either air or SF6 as extinguishing media

- An evaluation of the respective merits of each type is complex because a large number

of parameters must be taken into account (cost, size, maintenance, noise, extensibility,

testing, insulation reliability etc.)

5/34

Page 7: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.1. Live-tank circuit breakers

Construction

- A number of similar circuit breaking units are used in series per phase

- Up to 12 breaks per phase are used for the highest breaking capacities at 400kV

- Up to 24 breaks per phase are used for 750kV

- The number of breaks is dictated by the limitation of testing station capacity rather than

interrupting capacity possible per break

- The tank is permanently charged with compressed gas and encloses two breaks

connected in series, the tank being tied electrically to the mid-point potential between

breaks

- For 400kV, if twelve breaks are required, then

two live tanks can be supported by a single

porcelain insulator, making three support

insulators in all phase

6/34

Page 8: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

- An insulating operating-rod and the ‘topping-up’ gas feed pipe are located inside

the support porcelain

- The insulating operating-rod and the ‘topping-up’ gas feed pipe are usually made in

epoxy resin bonded glass fibre material

- During a breaking operation, the blast valve is opened so that gas exhausts from the

tank to atmosphere

- The action of the high velocity gas flow through the nozzles brings rapid de-ionization

of the arc column and extinction at a current zero

13.3 Gas-filled equipment

13.3.1. Live-tank circuit breakers

7/34

Page 9: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Pollution

13.3 Gas-filled equipment

13.3.1. Live-tank circuit breakers

- A major problem is the reduction in the flashover voltage external to the breaker due to

the atmospheric pollution (industrial or coastal)

- Non-graded insulation, is more vulnerable than graded insulation

- When non-graded support insulators are used, sufficient creepage distance must be

provided over the insulator to ground (2.5 ~ 3.5 cm/kVrms of line voltage)

Voltage distribution

- For a multi-break circuit breaker, the natural distribution of voltage between the breaks

depends on the relative values of the capacitance between contacts and the capacitance

to earth

- For good grading the capacitance between contacts should be high and the capacitance

to earth low

- To obtain a more uniform voltage distribution, additional capacitance (or resistance) is

usually added across each break 8/34

Page 10: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.1. Live-tank circuit breakers

9/34

Page 11: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Current transformers

- Associated with circuit breakers are current transformers which transform the current in

the high voltage line into a proportionate current, usually a lower one, at earth potential

- The output from the transformer is used for metering and as a signal to open the circuit

breaker if system conditions become abnormal

- Current transformers associated with live tank breakers

are of the separately mounted post type,

unless the circuit breakers are accommodated

inside a building in which case ring type

current transformers can be mounted on

the wall bushings feeding the building

13.3 Gas-filled equipment

13.3.1. Live-tank circuit breakers

10/34

Page 12: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.2. Dead-tank circuit breakers

Construction

- ‘Dead tank’ breakers employ a single metal tank at earth potential

- Bulk oil switchgear → gas blast market

- When the breaker is tripped, the blast valve opens for several half-cycles and high-

pressure gas flows down the blast pipes through interrupting nozzles into the main tank

- Pressure in the main tank rises slightly and original conditions are restored by pumping

gas from the main tank back into the high-pressure reservoir

- Typical operating pressure : SF6, high pressure reservoir (200lb/in2)

main tank (30lb/in2)

11/34

Page 13: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.2. Dead-tank circuit breakers

- Blast noise is considerably reduced because there is no exhaust to atmosphere

- Exhaust gases ejected from gas blast circuit breakers may not be completely de-ionized

and in any case can be at a high temperature, thereby reducing the flashover voltage

between the circuit breaker and adjacent structures. Since there is no exhaust from

breakers and to adjacent structures can be a minimum. This is particularly useful for

indoor switching stations

- Closed-circuit gas systems avoid ejecting large quantities of gas to atmosphere and the

only gas fed to the circuit breaker is that needed to replace leaks. As all gas supplied to

a circuit breaker must be dry, this reduction in consumption permits the use of more

simple gas drying plant

Advantage of a closed circuit gas system

12/34

Page 14: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

- A major advantage of the dead tank construction is free from the hazard of atmospheric

pollution

- During the interruption, the gas exhausting into the main tank can carry particles

formed by erosion of the contacts, nozzles and decomposition of the gas

- This dust can be filtered and lied along insulating surfaces

- Dust consists of metallic oxides or metallic fluoride which have good electric strength

when dry

Pollution

13.3 Gas-filled equipment

13.3.2. Dead-tank circuit breakers

- External to the breaker, there are two leakage path

to earth at the bushings but as these are graded,

the hazard are reduced

13/34

Page 15: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

- With a multi break circuit breaker operating under conditions of severe pollution,

a flashover to earth on the breaker itself would be much more serious if it occurred

at the middle of the breaker, than at one of the terminals because only a fraction of the

circuit breaker breaks is available to interrupt the fault of current.

- Dead tank multi break circuit breakers have better insulation security between the

terminals than do live tank breakers where the mid breaks bay be supported by exposed

ungraded insulation

- A dead tank breaker is more affected by loss

of gas pressure but the risk of such a loss

is negligible

Pollution

13.3 Gas-filled equipment

13.3.2. Dead-tank circuit breakers

14/34

Page 16: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

- The breaks are physically close together, hence the capacitance across of breaks can be

made relatively high

- The capacitance to earth is determined by the diameter of the tank, which from this

aspect alone should be as great as possible

- For breakers using an expensive gas such as SF6, the tank diameter must be small and

dimensions are dictated by the clearance required to earth in a gas of high electric

strength

- For such breakers, the capacitance to earth is high and additional capacitors are

provided across each break to improve the voltage distribution

Voltage distribution

13.3 Gas-filled equipment

13.3.2. Dead-tank circuit breakers

- Ring type current transformers are fitted over the bushings on both sides of the breaker

- This arrangement provides a saving in cost compared to post type transformers and

eliminates the corresponding exposed insulation

Current transformer

15/34

Page 17: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.3. Gas-filled current transformers

- At 132, 275 and 400kV, the conventional primary insulation for current transformers is

oil-impregnated paper

- The manufacturing problems associated with this insulation are formidable,

particularly at voltages of 400kV and above

- Large quantities of paper tape are applied to the primary conductor and lengthy

processing under carefully controlled conditions is necessary to ensure dryness and full

impregnation

Limitation of conventional insulation

Most recent design

- Focused on the use of electro-negative gases

16/34

Page 18: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.3. Gas-filled current transformers

Illustration of current transformer

oil impregnate paper insulation type gaseous insulation type

17/34

Page 19: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.3 Gas-filled equipment

13.3.3. Gas-filled current transformers

Advantages of gas filled current transformer

- Manufacturing process are more simple and shorter

- No voids and less dielectric loss

- Fire risk elimination

- Weight saving

- easier carriage of short circuit current than a hair pin shape conductor

Disadvantages of gas filled current transformer

- Sealing problems are more difficult

- Stronger porcelain insulator is need to withstand the internal gas pressure

- Voltage grading along the porcelain is more difficult

18/34

Page 20: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

- Simple gases : air, oxygen, hydrogen, nitrogen, carbon dioxide

- Electronegative gases : SF6, Arctons, nitriles

Gases for circuit breaker or for their ancillary equipment

Important preferred properties of gas

- High electric strength

- Thermal and chemical stability

- Low liquefaction temperature

- Non-inflammability

- High thermal conductivity

- Physiological inertness

- Commercial availability at moderate cost

- Arc-extinguishing ability

19/34

Page 21: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

- Air is the cheapest and most widely used for circuit breaking

- Hydrogen has a better arc-extinguishing ability and its thermal conductivity is seven

times that of air, but its electric strength in fairly uniform fields is about half that of air

Because of the risk of explosion, hydrogen-SF6 mixtures have been suggested

- Nitrogen has a similar electric strength to air and offers no advantage in circuit

breaking

- The electric strength of carbon dioxide is similar to air and its arc-extinguishing

properties are better than air at least at moderate current

- Oxygen is a good extinguishing medium but is too active chemically, so it has been

used in water circuit breakers where it is produced along with hydrogen during

decomposition of the water by arc

Simple gases

20/34

Page 22: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

- SF6 has outstanding arc-quenching properties and good electric strength

- The fluorocarbon gases are unsuitable by virtue of their decomposition products and

high dissociation temperatures

- The nitriles have not been tested for use in circuit breakers

Electronegative gases

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

→ OF ALL THESE GASES, ONLY TWO, AIR AND SF6, ARE USED IN

COMMERCIAL GAS BLAST CIRCUIT BREAKERS

21/34

Page 23: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

Air

- The greater proportion of gas blast circuit breakers use compressed air for circuit

interruption

- The compressed air supply system is a vital part of an air blast circuit breaker and upon

which the switchgear relies for mechanical operation, interrupting ability and internal

insulation

- The ensure adequate dryness of the air, moisture is removed by refrigeration, by drying

agent, or by storing at several times the working pressure and then expanding to the

working pressure for use in circuit breaker

22/34

Page 24: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Sulphur hexafluoride (SF6)

- Circuit breakers are assed by their ability to withstand the transient voltage that appears

across the contacts immediately after current interruption (re-striking voltage)

- SF6 is capable of interrupting a rate of rise of re-striking voltage of about four times that

of air at the same pressure (200lb/in2) and the same current

- If rate of mass through the interrupting nozzle is used as a common criterion, then SF6

has about twice the performance of air

- SF6 has an electrical strength of about two or three times that of air at the same pressure,

and at 2 atm its strength is comparable with that of transformer oil

- Although SF6 is normally a vapour, it can be liquefied at moderate pressures and stored

in steel cylinders in much the same manner as carbon dioxide

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

23/34

Page 25: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Sulphur hexafluoride (SF6)

- Metal fluorides which may be formed during the interruption of short circuit currents are

removed from the circuit breaker tank by filtering the gas through activated alumina

- During operation of the circuit breaker, the gaseous decomposition products which can

be toxic in the presence of moisture, are removed using the activated alumina as an

absorber

- SF6 cannot be used much above 200lb/in2 unless the gas is heated to avoid liquefaction

(Circuit breakers using SF6 at 200lb/in2 have heaters installed in the high pressure

reservoir)

- The breaking capacity of a circuit breaker is approximately proportional to the gas

pressure; therefore it is possible for a compressed-air ‘break’ to have a higher

interrupting capacity than an SF6 break at the expense of increased gas pressure

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

24/34

Page 26: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

13.4.1. Gases for circuit breakers

Gas pressure – flashover voltage characteristics of insulation gases

25/34

Page 27: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

13.4.2. Gases for current transformers and busbars

- Arc-extinguishing properties can be forgotten, the problems become more simple

Gases filling current transformers and busbars

26/34

Page 28: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.4 Practical gases for switchgear

13.4.2. Gases for current transformers and busbars

Dilution of SF6 with other gases

- Undiluted sulphur hexafluoride has been used at 30 ~ 40lb/in2 for gas insulated current

transformer designed recently

- Small additions of SF6 to nitrogen can produce electric strengths much greater than that

of pure nitrogen

- The breakdown value of 20% SF6, 80% N2 by pressure is approximately 80%

breakdown value of pure SF6

- Work has been done on the dilution of SF6 both with nitrogen and with Arcton-12 (CF2Cl

2) in order to save cost

- The cost of pure SF6 is relatively small compared to that of the porcelain contains it

- If suitable gas can be found having an electric strength twice that of SF6, then the

diameter of the porcelain could be approximately halved

- This could bring overall savings in cost 27/34

Page 29: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

28/34

13.5 Design data

Knowledge requirement to design the structural insulation

- The voltages during service and during proving test

- The voltage gradient at conductor surfaces and along solid insulating surfaces

- Basic data on the electric strength of the gases and materials employed in the equipment

Insulation levels for 400kV circuit breakers

- Highest system voltage : 420kV - Impulse withstand to earth (1/50) : 1425kVp - Impulse withstand between phases and terminals of one phase (1/50) : 1640kVp - Power frequency (dry) 1min withstand : 680kV - Power frequency (dry) momentary withstand : 800kV - Power frequency (wet) 30s withstand : 630kV - Minimum visible corona voltage : 340kV - Minimum internal discharge voltage : 280kV - Minimum external axial creepage distance over porcelain insulators Outdoor circuit breaker to earth : 460in Indoor circuit breaker to earth : 400in Between terminals of one phase : 500in

Page 30: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

29/34

13.5 Design data

13.5.1. Gas filled bushing

Design parameters which require evaluation

- The gas to be used and the operating pressure

- The dimensions x, y, z, etc.

- The effect of electrode materials, short circuit

currents, moisture, dust, temperature, leaks,

conditioning, and pollution

Gases

- Relatively low pressure : SF6 (45lb/in2), High pressure : Air

- SF6 is used : porcelain weather-shield is sufficient to contain the gas

- Air is used : necessary to provide a linear of epoxy-glass-fibre tube

Page 31: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.5 Design data

13.5.1. Gas filled bushing

Dimensions

- Gap x :

• determined from calculations of stress at the inner electrode and from data on the

strength of gas

• designed to withstand voltages greater than the external flashover voltage of the bushing30/34

Page 32: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Dimensions

- The length of the weather shield p :

• determined by the 50 cycle and switching surge performance of porcelain and polluted

conditions (Typically 132kV porcelain of length p is about 65in)

- The total creepage distance z :

• between 1.0 ~ 1.15in/kV of system line voltage for operation (ex. 132 ~ 152 in for a

132kV system)

- The length and position of the earthed cylindrical screens (h1, h2)

• determined by experiment : h1 and the external diameter of the bushing are sufficient to

reduce the stress in the air ate the surface of the porcelain to less than 15kVp/cm

h2 is chosen to give favorable stressing along the length y of lower insulating tube which

is in compressed gas

13.5 Design data

13.5.1. Gas filled bushing

31/34

Page 33: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

Design data for insulated members in compressed gases

- Right cylindrical insulating members in uniform field gap

- The spacer efficiencies (ratio of flashover voltage to gas breakdown strength) up to 90%

can be achieved at the lower pressures(10 ~ 30lb/in2)

- In general, it is found for spacers immersed in SF6 and N2 at pressures up to 45lb/in2 in

uniform field that,

• cylindrical spacers have a higher flashover voltage than corrugated spacers

• The surface finish of the spacer material should be as smooth as possible and the spacer

electrode contact as intimate as possible for the highest spacer efficiencies

A spacer material of low permittivity may also be an advantage

• Spacer efficiency often decrease with increase in gas pressure and this effect is more

marked with SF6 than with N2

13.5 Design data

13.5.1. Gas filled bushing

32/34

Page 34: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.5 Design data

13.5.1. Gas filled bushing

33/34

Page 35: The  Use of Gaseous Insulation  in High Voltage Circuit-breakers

13.5 Design data

13.5.2. Future requirement

34/34

- Equipment such as circuit breakers and current transformers is designed to be free from

internal discharge at 15% above the normal phase to neutral system voltage

- The design of equipment for 400 and 750kV requires data on the breakdown of gaps

and gas/solid interfaces of a metre in length at gas pressures up to 100 atm

- Data of this kind require the use of very high test voltages and the construction of large tes

t

rings

- Both these requirements are costly and work of this type is usually only fostered in

industrial laboratories

- A reliable technique for translating breakdown data from small models to full sized

equipment would be of obvious value