The pieces for offshore DC grids are almost in place. There are no technical barriers. Erik Koldby,...
-
Upload
dylan-derick-stewart -
Category
Documents
-
view
214 -
download
0
Transcript of The pieces for offshore DC grids are almost in place. There are no technical barriers. Erik Koldby,...
The pieces for offshore DC grids are almost in place. There are no technical barriers.
Erik Koldby, ABB A/S, Bo Westman and Mats Hyttinen, ABB AB, EWEA 2012-04-17
The DC breaker is often seen as a barrier to DC gridsBut DC switches have been in service since the 1970’s!
A typical mechanical DC circuit breaker (MRTB) 4000 A, 125 kV Breaking time 40 ms
Transfer breakers developed for bipolar LCC
Today the solution is standard SF6 AC circuit breakers with a passive or an aktive parallel LC resonanse circuit
Principle for an active resonance mechanical HVDC circuit breaker
But the breaking time make these solutions insufficient for DC grids
UDC
Cigré 13-06 1976
© ABB Group Slide 3PowDoc id
Fast: Breaking times of less than 2ms
Powerful Current breaking capability of 16kA
Efficient Transfer losses are less than 0.01%
Modular Easily adapted to actual voltage & current ratings
Reliable Protective current limitation, functional check while in service
Proven Power electronic design similar to converter technology
DC breakers are no longer a showstopper for large HVDC grids
Hybrid DC breaker is well suited for HVDC grids
© ABB Group Slide 311MR0339
© ABB Group Slide 4PowDoc id
Hybrid DC BreakerFast breaking within time delay of selective protection
Normal operation: Current flows in low-loss bypass
Proactive control: Load commutation switch transfer current into Main Breaker switch, the Ultra Fast Disconnector opens with very low voltage stress
Current limitation: Main Breaker switch commutates fault current into parts of the sectionalized arrester bank
Fault clearance: Main Breaker switch commutates fault current into arrester bank
© ABB Group Slide 411MR0339
© ABB Group Slide 5PowDoc id
A possible development: First Regional HVDC gridsCan be built today with proven technology
A typical regional DC grid is defined as a system that constitutes of one protection zone for DC earth faults.
To temporarily and rarely lose the whole HVDC system has a limited impact on the overall power system.
Fast restart of the faultless part of the system
HVDC breakers are not needed Normally radial or star network
configurations Limited power ratingRegional DC grid with
optimized voltage level.
© ABB Group Slide 511MR0339
© ABB Group Slide 6PowDoc id
Line fault handling in regional DC grid DC earth faults vs other faults
DC earth faults All AC breakers (X) open
DC switches (-) open and isolate the faulty part
Start-up of none-faulty part
Faults in controls, auxiliaries etc cause a trip of the converter:
The rest of the system continues without interruption
In point-to-point transmission, regional HVDC grids and interregional HVDC grids
One protection zone for DC earth faults
=~
=~
=~
P1
P2 x
x
x
=~
=~
=~
P1
P2 x
x
x
Several protection zones for faults in
controls, auxiliaries
© ABB Group Slide 611MR0339
© ABB Group Slide 7PowDoc id
Later step: An interregional DC grid
An interregional HVDC grid is defined as a system that needs several protection zones for DC earth faults.
Developments focus: HVDC breakers and fast protections Grid Power flow control/Primary
control: automatic control Master control: start/stop, re-
dispatching On-going Cigré WG B4.52 ”HVDC Grid
Feasibility study”
© ABB Group Slide 711MR0339
Example: 420 kV circuit breakers
1960s: Air blast 1970s and 1980s: Minimum oil 1980s and 1990s: SF6
You know there will be development – you just do not know how and when – but behave like they did in the 50’es: Act on what is available. Europe needs the new grids! The lack of a DC Circuit breaker is no longer a valid excuse
What will the future bring?Inspiration: Look back on AC circuit breakers