The new Generation Wood Gasification Boilers

6
The New Generation Ventum Series leaps forward in gasification technology making them the fastest selling boilers in their class across Europe. It is designed for efficiency, economy and protection of the environment. With 92% efficiency, emissions (250 mg/m3 CO) below European and German regulations, adaptable to wood fuel moistures up to 33%, superior health and safety features and easy to use electronic controls, this gasification boiler is a testament of quality and perfection. Ventum Series The new Generation Wood Gasification Boilers Europe’s Fastest Selling Wood Gasification Boiler.

Transcript of The new Generation Wood Gasification Boilers

Page 1: The new Generation Wood Gasification Boilers

The New Generation Ventum Series leaps forward in gasification technology making them the fastest selling boilers in their class across Europe. It is designed for efficiency, economy and protection of the environment. With 92% efficiency, emissions (250 mg/m3 CO) below European and German regulations, adaptable to wood fuel moistures up to 33%, superior health and safety features and easy to use electronic controls, this gasification boiler is a testament of quality and perfection.

Ventum Series The new Generation Wood Gasification Boilers

Büyükelçi Sokak No:9 Kavaklıdere - Ankara / Türkiye T: +90 312 468 09 11 F: +90 312 468 45 96 www.arikazan.com

Tech

nica

l Spe

cific

atio

nsO

PERA

TIN

G C

ON

DIT

ION

S

97

85-55

55

3

4.5

230 Vac, 50 Hz

Ø80 x500mm Ø80 x 700mm

10

89 113 137 200

70504030

<60dB

1000 1500

5

2000 3000

125

11,0 3,2 5,5 23,0

110 140 230

Hard Wood, 15% < Humidity < 30%*

°C

-

°C

°C

-

-

Pa

Pa

mbar

lt

dB

lt

h

kg

bar

bar

Safety Limit Temperature

Boiler Class

Setting Range of Operating Temperature

Min. Water Return Temperature

Operating Pressure

Boiler Test Pressure

Electrical Connection

Recommended Fuel Types

Minimum Required Stack Draught

Boiler Gas Side Resistance

Boiler Water Side Pressure Drop ΔT = 10 °C

Fuel Filling Volume

Noise Level

Required Accumulation Tank Volume

Apx. Combustion Endurance

W1 - Width

W2 - Total width with cover plates

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

in stand-by

in full load, 100%

mm

W

W

lt

kg

600

650

1060

1060 13101210 1360

1165

715 865 955 1005

1437

890

90 104 104 168

385

740x1100x1355 740x1100x1495 740x1100x1595 740x1410x1650

425 450 600

146514151315

1360

125 - 130 146 -150

1 1⁄2”

1 1⁄2”

3⁄4”

1⁄2”

1137 1287 1387

590

380

975

57

1,8

1125

64

2,3

1225

70

2,9

1275

79

4,6

inch

inch

inch

L1 - Length

H1 - Height

H2 - Total Height

H6 - Height of Stack Connection

Stack Diameter ØD1 (inner-outer)

Water Content

Approx. Empty Weight

Tranport Dimensions

Hot Water OutletConnection

Water InletConnection

Safety Cooling Heat Exchanger15 °C, 2 bar cold water

Filling & Drain Connection

Flue Gas Temperature

Average Mass Flow Rate of Solid Pollutants (dust)

Average Electricity Consumption

CO

Diameter, ØD2

Diameter, ØD3

Diameter, ØD4

Diameter, ØD2

Position, H3

Position, H4

Position, H5

Position, L2

MA

IN D

IMEN

SIO

NS

EMIS

SIO

NRA

TES

POW

ERCO

NSU

MP-

TIO

NS

TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS

CAPA

CITY Nominal Heat Output

kW

kcal/h 17.200

20

90,1

30

90,4

CLASS 5 acc. To EN 303-5

40

91,2

60

91,7

25.800 34.400 51.600

%Direct E�ciency

BOILER TYPE

VG20 VG30 VG40 VG60UNIT

°C

g/h

mg/m3

145-165

<700

3

Europe’s Fastest Selling Wood Gasification Boiler.

Page 2: The new Generation Wood Gasification Boilers

Ventum Series Wood Gasification Boilers FEATURES

As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable and connectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is further increased as well as decreasing refuelling intervals.

• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement, • Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeableemergencyheatdischargesystem”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.

Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler

Special air ducts inside the doors allowspre-heating combustion air via natural air flow

Cleaning made easier by a simple swing of anexternal lever

Electronic Management with Smart Control panel is able to checkflue gas temperature and regulate the fan for optimal

heat production output.

*Large loading door at waist level

Interchangable Overheat Discharge Assembly

Observation Glass to Monitor Gasification Process

Bypass system automatically engages and prevents smokebursts when the door is open meeting highest Health and Safety

Standards in force.

Independently adjustable Primary and seconday air inlets

Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuumeliminating the possibility of a smoke leakage

to the ambient

Faster and longer gasification

• High > 92 % net.• Low emissions < 250 mg/m3 CO

• Only 15 mg/m3 dust.

Page 3: The new Generation Wood Gasification Boilers

Ventum SeriesWood Gasification Boilers FEATURES

As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable andconnectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is furtherincreased as well as decreasing refuelling intervals.

• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement,• Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeable emergency heat discharge system”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.

Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler

Special air ducts inside the doors allows pre-heating combustion air via natural air flow

Cleaning made easier by a simple swing of an external lever

Electronic Management with Smart Control panel is able to check flue gas temperature and regulate the fan for optimal

heat production output.

*Large loading door at waist level

Interchangable Overheat Discharge Assembly

Observation Glass to Monitor Gasification Process

Bypass system automatically engages and prevents smokebursts when the door is open meeting highest Health and Safety

Standards in force.

Independently adjustable Primary and seconday air inlets

Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuumeliminating the possibility of a smoke leakage

to the ambient

Faster and longer gasification

High > 92 % ne o e i ion < 250 mg/m3 CO

nly 15 mg/m3 d

Page 4: The new Generation Wood Gasification Boilers

Ventum SeriesWood Gasification Boilers FEATURES

As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable andconnectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is furtherincreased as well as decreasing refuelling intervals.

• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement,• Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeable emergency heat discharge system”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.

Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler

Special air ducts inside the doors allowspre-heating combustion air via natural air flow

Cleaning made easier by a simple swing of anexternal lever

Electronic Management with Smart Control panel is able to checkflue gas temperature and regulate the fan for optimal

heat production output.

*Large loading door at waist level

Interchangable Overheat Discharge Assembly

Observation Glass to Monitor Gasification Process

Bypass system automatically engages and prevents smoke bursts when the door is open meeting highest Health and Safety

Standards in force.

Independently adjustable Primary and seconday air inlets

Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuum eliminating the possibility of a smoke leakage

to the ambient

Faster and longer gasification

High > 92 % neo e i ion < 250 mg/m3 CO

nly 15 mg/m3 d

Page 5: The new Generation Wood Gasification Boilers

The New Generation Ventum Series leaps forward in gasification technology making them the fastestselling boilers in their class across Europe. It is designed for efficiency, economy and protectionof the environment. With 92% efficiency, emissions (250 mg/m3 CO) below European and Germanregulations, adaptable to wood fuel moistures up to 33%, superior health and safety featuresand easy to use electronic controls, this gasification boiler is a testament of qualityand perfection.

Ventum Series The new Generation Wood Gasification Boilers

Büyükelçi Sokak No:9 Kavaklıdere - Ankara / Türkiye T: +90 312 468 09 11 F: +90 312 468 45 96 www.arikazan.com

Tech

nica

l Spe

cific

atio

nsO

PERA

TIN

G C

ON

DIT

ION

S

97

85-55

55

3

4.5

230 Vac, 50 Hz

Ø80 x500mm Ø80 x 700mm

10

89 113 137 200

70504030

<60dB

1000 1500

5

2000 3000

125

11,0 3,2 5,5 23,0

110 140 230

Hard Wood, 15% < Humidity < 30%*

°C

-

°C

°C

-

-

Pa

Pa

mbar

lt

dB

lt

h

kg

bar

bar

Safety Limit Temperature

Boiler Class

Setting Range of Operating Temperature

Min. Water Return Temperature

Operating Pressure

Boiler Test Pressure

Electrical Connection

Recommended Fuel Types

Minimum Required Stack Draught

Boiler Gas Side Resistance

Boiler Water Side Pressure Drop ΔT = 10 °C

Fuel Filling Volume

Noise Level

Required Accumulation Tank Volume

Apx. Combustion Endurance

W1 - Width

W2 - Total width with cover plates

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

mm

in stand-by

in full load, 100%

mm

W

W

lt

kg

600

650

1060

1060 13101210 1360

1165

715 865 955 1005

1437

890

90 104 104 168

385

740x1100x1355 740x1100x1495 740x1100x1595 740x1410x1650

425 450 600

146514151315

1360

125 - 130 146 -150

1 1⁄2”

1 1⁄2”

3⁄4”

1⁄2”

1137 1287 1387

590

380

975

57

1,8

1125

64

2,3

1225

70

2,9

1275

79

4,6

inch

inch

inch

L1 - Length

H1 - Height

H2 - Total Height

H6 - Height of Stack Connection

Stack Diameter ØD1 (inner-outer)

Water Content

Approx. Empty Weight

Tranport Dimensions

Hot Water OutletConnection

Water InletConnection

Safety Cooling Heat Exchanger15 °C, 2 bar cold water

Filling & Drain Connection

Flue Gas Temperature

Average Mass Flow Rate of Solid Pollutants (dust)

Average Electricity Consumption

CO

Diameter, ØD2

Diameter, ØD3

Diameter, ØD4

Diameter, ØD2

Position, H3

Position, H4

Position, H5

Position, L2

MA

IN D

IMEN

SIO

NS

EMIS

SIO

NRA

TES

POW

ERCO

NSU

MP-

TIO

NS

TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS

CAPA

CITY Nominal Heat Output

kW

kcal/h 17.200

20

90,1

30

90,4

CLASS 5 acc. To EN 303-5

40

91,2

60

91,7

25.800 34.400 51.600

%Direct E�ciency

BOILER TYPE

VG20 VG30 VG40 VG60UNIT

°C

g/h

mg/m3

145-165

<700

3

Europe’s Fastest Selling Wood Gasification Boiler.

Page 6: The new Generation Wood Gasification Boilers

TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS Unit

BOILER TYPE

VG20 VG30 VG40 VG60 VG80 VG100

CAPACITY Nominal Heat Output kW 20 30 40 60 80 100

kcal/h 17.200 25.800 34.400 51.600 68.800 86.000

Direct Efficiency % 90,1 90,4 91,2 91,7 91,5 91,3

OPERATING CONDITIONS

Boiler Class - CLASS 5 acc. To EN 303-5

Safety Limit Temperature °C 97

Setting Range of Operating Temperature °C 85 - 55

Min. Water Return Temperature °C 55

Operating Pressure bar 3

Boiler Test Pressure bar 4,5

Electrical Connection - 230 Vac , 50 Hz

Recommended Fuel Types - Ø80x500 mm Ø80x700 mm Ø80x1000 mm 2xØ80x500mm

Hard Wood, 15% < Humidity < 30% *

Minimum Required Stack Draught Pa 10

Boiler Gas Side Resistance Pa 125 110 140 230 240 250

Boiler Water Side Pressure Drop

DT = 20 °C mbar 11,0 3,2 5,5 23,0 25,0 28,0

Fuel Filling Volume lt 89 113 137 200 385

kg 30 40 50 70 135

Approximatelly Combustion Period h 5

Required Accumulation Tank Volume lt 1000 1500 2000 3000 4500 5500

Airborne Noise Level dB < 60 dB

MAIN DIMENSIONS

Boiler Width, W1 mm 600 650

Total Width with Cover Plates, W2 mm 650 700

Boiler Lenght, L1 mm 1060 1360 1635 1805

Boiler Height, H1 mm 1060 1210 1310 1360 1610

Total Height, H2 mm 1165 1315 1415 1465 1715

Stack Diameter, ØD1 (inner-outer) mm 125-130 146-150 176-180

Height of Stack Connection, H6 mm 715 865 955 1005 1225

Water Content lt 90 104 114 168 285 345

Approx. Empty Weight kg 385 425 450 600 860 960

Hot Water Outlet Connection

Diameter, ØD2 inch 1 1/2” 2’’

Position, H3 mm 1137 1287 1387 1437 1766

Position, L2 mm 590 890 1147 1317

Water Inlet Connection

Diameter, ØD2 inch 1 1/2” 2’’

Position, H4 mm 380 435

Safety Cooling Heat Exchanger 15 °C, 2 bar cold water

Diameter, ØD3 inch 3/4”

Position, H5 mm 975 1125 1225 1275 1525

Filling & Drain Connection

Diameter, ØD4 mm 1/2”

EMISSION RATES Flue Gas Temperature °C 145-165

Average Mass Flow Rate of Solid Pollutants (dust)

g/h 1,8 2,3 2,9 4,6 9 10

CO mg/m³ < 700

POWER CONSUMPTIONS

Average Electricity Consumption

in stand-by W 3

in full load, 100% 57 64 70 79 85 90

Technical Specifications