DGA Analysis
• It look as if that when the transformer reaches
above 55° C the oil starts to produces ethane
• There is usually higher than expected
Hydrogen
• The water content will be higher than
expected. Water can have up to 200 ppm to
400ppm and still be consider normal
(saturates around 1000 ppm)
DGA continued
• DP number can not be counted on as with
mineral oil the equation is for mineral oil this
has been field verified with forensic
teardowns
• Oxidization stability
DGA Example New Transformer designed
for Natural Ester
240 MVA top rated
GAS Date Date Date Date
09/08/2011 05/19/2011 03/02/2011 12/15/2010
Temp C 56 29 52 3
Hydrogen 51 44 55 <5
Methane <1 2 <1 <1
Ethane 144 124 138 <1
Ethylene <1 <1 1 <1
Acetylene <1 <1 <1 <1
Carbon
Monoxide
64 75 39 25
Carbon Dioxide 613 405 243 42
Oxygen 2192 3458 3425 3318
Nitrogen 97781 88923 86167 21971
Water 19 37 11 62
Retro filled unit
GAS Date Date Date Date
07/21/201 05/20/2010 06/23/2009 11/09/2007
Temp C 33 24 53 32
Hydrogen 5 5 <5 <5
Methane 5 6 2 6
Ethane 400 374 430 270
Ethylene 33 17 19 10
Acetylene <1 <1 <1 <1
Carbon
Monoxide
68 34 46 32
Carbon Dioxide 2171 1911 2220 1212
Oxygen 3671 5865 12794 4388
Nitrogen 78147 77776 121018 7361078
Water 78 66 151 49
Retro filled unit earlier
GAS Date Date- NEF Date - mineral Date - mineral
11/06/2002 11/04/2001 03/27/2001 06/04/199
Temp C 8 32 4 30
Hydrogen <5 <5 5 <5
Methane 3 2 5 11
Ethane 3 12 6 11
Ethylene 2 4 5 15
Acetylene <1 <1 <1 <1
Carbon
Monoxide
<25 61 <25 <25
Carbon Dioxide 1081 792 1076 6637
Oxygen 2044 7267 2192 1383
Nitrogen 88116 82970 99169 82129
Water 33 35 16 12
Testing
• Power factor: expect higher than expected results 2 to 3 times higher than mineral oil results after the natural ester has thermo cycled into the insulation can take up to a year
• Power factor testing in cold will give you false results due the fact that water freezes. Winding resistance to ground is much lower than expected in retro-filled units, and it will take some time for it to show up in new units (M ohms to K ohms)
• SFRA results are similar to mineral oil results but do not compare a retro filled unit to the old mineral oil
Power Factor Results 2006 before
Retro-fill with NEF
Equiv 10kV % Pwr Factor
# Insul. KV mA Watts Meas PF Corr PF
1 CH + CHL 10.01 36.658 1.945
2 CH 10.007 14.461 0.547 0.38 0.37
3 CHL (UST) 10.005 23.184 1.377 0.59 0.58
4 CHL 23.197 1.398 0.6 0.59
5 CL + CHL 2.501 49.449 3.028
6 CL 2.5 26.259 1.655 0.63 0.62
7 CHL (UST) 2.5 23.188 1.377 0.59 0.58
8 CHL 23.19 1.373 0.59 0.58
PF Results after Retro-fill 2010, after
NEF™ has thermo-cycled
Equiv 10kV % Pwr Factor
# Insul. KV mA Watts Meas PF Corr PF
1 CH + CHL 10.11 37.494 3.813 1.02 1
2 CH 10.1 14.58 1.14 0.78 0.76
3 CHL (UST) 10.006 22.902 2.662 1.16 1.14
4 CHL 22.914 2.673 1.17 1.15
5 CL + CHL 2.5 49.023 6.083 1.24 1.22
6 CL 2.501 26.117 3.511 1.34 1.31
7 CHL (UST) 2.5 22.904 2.58 1.13 1.11
8 CHL 22.906 2.573 1.12 1.1
Power Factor Results 2001 before
Retro-fill with NEF
Equiv 10kV % Pwr Factor
# Insul. KV mA Watts Meas PF Corr PF
1 CH + CHL 10.0 64.43 2.026
2 CH 10.0 13.29 0.684 0.49 0.49
3 CHL (UST) 10.0 51.11 1.394 0.27 0.27
4 CHL 51.14 1.378 0.27 0.27
5 CL + CHL 2.0 14.59 0.506
6 CL 2.0 14.23 0.505 0.35 0.35
7 CHL (UST) 2.0 0.358 0.005 0.14 0.14
8 CHL 0.36 0.001 0.03 0.03
PF Results after Retro-fill 2007, after
NEF™ has thermo-cycled
Equiv 10kV % Pwr Factor
# Insul. KV mA Watts Meas PF Corr PF
1 CH + CHL 10.004 79.834 3.567
2 CH 10.002 15.479 0.906 0.59 0.57
3 CHL (UST) 10.002 64.344 2.654 0.41 0.39
4 CHL 64.355 2.661 0.41 0.41
5 CL + CHL 2.0 13.218 1.385 0.96
6 CL 2.0 12.743 1.384 1.09 1.08
7 CHL (UST) 2.0 0.477 0.012 0.25 0.24
8 CHL 0.475 0.001 0.02 0.02
Fire Point/Operational Differences
• Flash point greater than 300 ° C
• Need to be aware of other requirements
pertaining to quantity of oil for fire protection
NFPA still requires fire protection after 10,000
gallons
• The retro-filled transformer will run hotter
versus a newly designed transformer for NEF
unit about 10 ° to 15 ° C
Storage and Handling
• Try to minimize mixing mineral oil with NEF
• Retro-filled benefits disappeared at a 7% mixture with mineral oil - fire point
• Keep it in a sealed air tight container and if it is in a white tote don’t leave it the sun, it will start to oxide
• The EPA has not recognized the differences between mineral oil and NEF for containment or spills