Nofirno Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD Sealing Systems are the UK market leaders in the supply of cable and pipe sealing systems for the marine and offshore industries, having extensive experience and knowledge of supplying offshore engineers with specialist sealing solutions for over 20 years. The systems enhance the integrity of fire, gas and watertight boundaries when penetrating with pipes or cables and are proven in the North Sea on major upgrade projects for Statoil, Norsk Hydro, Shell, BP, Talisman and ConocoPhillips. The RISE NOFIRNO Multi cable transit and RISE NOFIRNO pipe penetration systems have been tested in accordance with the IMO 2010 FTP Code to prove integrity in “A-0” and “H-0” without any insulation applied. The new IMO International Code for Application of Fire Test Procedures, 201 0 (201 0 FTP Code), took effect from 1 July 2012 and addresses the importance of separate fire tests for pipe penetrations and cable transits through “A-0” divisions and “A-60” divisions; Many sub divisions within a modern ship and offshore platforms are classified under IMO SOLAS 74 and IMO MODU (2009) as “A-0” and “H-0” where there is a risk of hydrocarbon fire. It is vitally important that pipe penetrations and cable transits are installed as tested in “A-0” and “H-0” divisions and any insulation (if required and applied in the fire test) is also then applied in practice. An “A-0” test is more difficult for a pipe penetration and cable transit to pass, since there is normally no fire insulation fitted on an “A-0” division. The penetration and cable transit is subjected to a far greater heat load because of the tremendous amount of radiated heat in addition to the normal conducted heat as shown in the image above. This increased heat load could then result in integrity failure with fire breaking through a pipe penetration or cable transit within the 60 minutes. All “A” class fire tests are for a duration of 60 minutes, “A-60” divisions are required to maintain the insulation & integrity for 60 minutes and “A-0” divisions must still contain a fire (integrity) for 60 minutes but because we are not concerned about temperature rise (insulation) there is normally no insulation applied. The only way many “A-60” approved systems can pass the “A-0” fire test is if they are locally insulated to protect them; this is not always then applied in the field. The previous FTP code only made reference to “A” class divisions, any testing on “A-60” divisions was assumed to satisfy the criteria for all “A” class divisions including: “A-0”; certificates were issued for “A-0 - A-60” on the basis of “A-60” testing (but drawings showed insulation applied), there were no separate tests required for “A-0” divisions. This distinction is now much clearer. Extracts from The new IMO International Code for Application of Fire Test Procedures, 2010 (201 0 FTP Code); Cable Solutions Worldwide Ltd Craigearn Business Park Morrison Way, Kintore Aberdeenshire, AB51 0TH e [email protected] 44 1467 633790 (tel) 44 1467 631284 (fax) 1st4cables.com

Transcript of The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest...

Page 1: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Nofirno Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations

CSD Sealing Systems are the UK market leaders in the supply of cable and pipe sealing systems for the marine and offshore industries, having extensive experience and knowledge of supplying offshore engineers with specialist sealing solutions for over 20 years. The systems enhance the integrity of fire, gas and watertight boundaries when penetrating with pipes or cables and are proven in the North Sea on major upgrade projects for Statoil, Norsk Hydro, Shell, BP, Talisman and ConocoPhillips.

The RISE NOFIRNO Multi cable transit and RISE NOFIRNO pipe penetration systems have been tested in accordance with the IMO 2010 FTP Code to prove integrity in “A-0” and “H-0” without any insulation applied.

The new IMO International Code for Application of Fire Test Procedures, 201 0 (201 0 FTP Code), took effect from 1 July 2012 and addresses the importance of separate fire tests for pipe penetrations and cable transits through “A-0” divisions and “A-60” divisions;

Many sub divisions within a modern ship and offshore platforms are classified under IMO SOLAS 74 and IMO MODU (2009) as “A-0” and “H-0” where there is a risk of hydrocarbon fire. It is vitally important that pipe penetrations and cable transits are installed as tested in “A-0” and “H-0” divisions and any insulation (if required and applied in the fire test) is also then applied in practice.

An “A-0” test is more difficult for a pipe penetration and cable transit to pass, since there is normally no fire insulation fitted on an “A-0” division. The penetration and cable transit is subjected to a far greater heat load because of the tremendous amount of radiated heat in addition to the normal conducted heat as shown in the image above. This increased heat load could then result in integrity failure with fire breaking through a pipe penetration or cable transit within the 60 minutes.

All “A” class fire tests are for a duration of 60 minutes, “A-60” divisions are required to maintain the insulation & integrity for 60 minutes and “A-0” divisions must still contain a fire (integrity) for 60 minutes but because we are not concerned about temperature rise (insulation) there is normally no insulation applied. The only way many “A-60” approved systems can pass the “A-0” fire test is if they are locally insulated to protect them; this is not always then applied in the field.

The previous FTP code only made reference to “A” class divisions, any testing on “A-60” divisions was assumed to satisfy the criteria for all “A” class divisions including: “A-0”; certificates were issued for “A-0 - A-60” on the basis of “A-60” testing (but drawings showed insulation applied), there were no separate tests required for “A-0” divisions.

This distinction is now much clearer. Extracts from The new IMO International Code for Application of Fire Test Procedures, 2010 (201 0 FTP Code);

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Page 2: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Pipe and duct penetrations

“A-0” class pipe penetrations are recommended to be performed in an uninsulated (“A-0”) bulkhead/deck. If the pipe penetrations are tested as an “A-60” class penetration, any insulation fitted (on the penetration itself and 200 mm around) will be required to be fitted also for class “A-60”. “A-0” penetrations shall not be approved without an “A-0” test although tested and approved as “A-60”.

Cable Transits

“A-0” class cable transits are recommended to beperformed in an uninsulated (“A-0”) bulkhead/deck. If the cable transits are tested as “A-60” penetration, any insulation fitted on an exposed side (on the cable transits itself and 200 mm around) will be required to be fitted also for “A-0”. “A-0” cable transits shall not be approved without an “A-0” test although tested and approved as “A-60”.

Golden Eagle Development Offshore Oil Platforms

UK North Sea CB&I/Nexen -supply RISE NOFIRNO system, sealing 970 pipe penetrations across both platforms to protect against hydrocarbon jet fires J30/ H60 and blast overpressures of 1 bar.

Shell Upgrade Program

RISE NOFIRNO system used to replace original pipe penetration seals over 13 platforms, (average of approximately 250 pipe penetrations per platform) to prevent corrosion; AO - A60 & HO- H120 rated.

Projects Benefits

RISE NOFIRNO flexible pipe penetration system is one of the most adaptive systems for sealing straight and angled pipe penetrations and can even accommodate multiple pipe runs, significantly saving in space. The system remains elastic and can therefore accommodate significant pipe movement in all directions.

SLIPSIL Plug pipe penetration combines simple installation with high performance sealing.

Certified for use in all A) - A60 & H0 - H120 bulkheads and decks

Certified for use in all A0 - A60 & H0 - H120 bulkheads and decks, with no insulation required on fire hazard side

Certified for use in A-0 and H-0 areas without any additional insulation required

2 hour Jet Fire rated without any additional insulation & gas and watertight after an A60 fire test

Easy addition & removal of cables & up to 50% space saving over modular block style Multi Cable Transits

A-0 and H-0 areas without any additional insultation required

2 hour Jet Fire rated without any additional insulation & gas and watertight after an A-60 fire test

Prevents corrosion inside the penetration by preventing moisture build up inside the penetration seal

Remains elastic to accommodate movement between pipe systems and the structure, ensuring integrity is maintained throughout the life of the structure

RISE NOFIRNO Multi Cable Transit is one of the most flexible & safest systems for sealing cable transits.

ConocoPhillips Jasmine Platform (New Build)

Supplied RISE NOFIRNO system to seal 316 pipepenetrations with service pipes ranging from 26.7mm to 508mm, A60 & J30 rated.

BP

Andrew Redevelopment, Azeri & Magnus

Other Projects

Nexen

Buzzard

Talisman

Fulmar A, Montrose Alpha, Clyde, Claymore & Tartan

Apache

Forties Alpha, Forties Echo & Beryl Alpha

Page 3: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Amercable Gexol

Gexol® Insulated Oil & Gas Cables are the industry’s standard for premium power, control and instrumentation performance. Gexol cables prove their value daily in the punishing operating environments of offshore drilling and petroleum facilities around the world.

Offshore applications challenge cable construction with relentless heat, vibration, salt corrosion, drilling mud and mechanical stress. And reliability is a huge issue – because it’s a long, long way to the nearest cable warehouse. You can depend on Gexol Insulated Oil & Gas cables for safe, reliable performance in the harshest operating conditions.

Nexans AmerCable’s Gexol® (pronounced Jex-all) Oil & Gas cables are the industry standard for high quality Type P power, control, instrumentation and VFD cables.

Gexol cables are designed for mission-critical applications where reliable performance in extremely hazardous operating conditions is essential for worker safety and profitable production. Gexol cables prove their value daily in the punishing operating environments of offshore drilling and petroleum facilities around the world.

Value Benefits

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Power, control, instrumentation and VFD constructions

Highest ampacity ratings

Superior dielectric properties

Exceeds CSA cold bent/cold impact (-40°C/-35°C)

Drilling mud resistant

Oil resistant

Extremely flexible for easy installation and longerservice life

Shortest lead times and best on-time delivery

Severe Cold Durability

Exceeds CSA Cold Bend / Cold Impact (-40°C/-35°C)

Flame Retardant

Certified to IEC 92-3 (332-3A) and IEEE 1580

Drilling Mud Resistant Oil Resistant

Page 4: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

CE-TEK Enclosures

CE-TEK’s products are made from a wide range of materials including: stainless steel, ABS, polycarbonate, GRP, die-cast aluminium and many more.

Certification is available to the latest ATEX/IEC Ex standards of EN 60079 and by constant development we are now able to manufacture enclosures to withstand fire conditions (950° C for 3 hours) and also for permanent submersion (IP68) to water depths of up to 3000 metres. CE-TEK have also successfully developed and manufactured a variety of bespoke enclosures to meet exacting customer and environmental requirements.

New developments include fully waterproof housings for plasma, LED and LCD screen televisions for outdoor use.

They are vandal proof and include a range of climatic solutions for variable weather conditions and can be made to size to suit any type of flat screen display.

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Page 5: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

NEK606 BFOU RFOU

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Voltage Rating 3.6/6kV, 6/10kV, 8.7/15kV85

IEC 60092-354

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction DetailsConductor Screen - Semi-conducting compound

Insulation - HF-EPR as per IEC 60092-351Fire proof layer - Mica tape

Insulation Screen - Semi-conducting compoundMetallic Screen - Tinned copper wire braid or Tinned Copper tapeInner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606

IEC 60332-3 Cat. AFIEC 60754-1 & 2IEC 61034-2

BFOU BFCU NEK606 Type Cable

Voltage Rating 3.6/6KV, 6/10KV, 8.7/15KV85

IEC 60092-354

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction DetailsConductor Screen - Semi-conducting compoundInsulation - HF-EPR as per IEC 60092-351Insulation Screen - Semi-conducting compoundMetallic Screen - Tinned copper wire braid or Tinned Copper tapeInner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606IEC 60332-3 Cat. AFIEC 60754-1 & 2IEC 61034-2

RFOU RFCU NEK606 Type Cable

Voltage Rating 0.6/1kV85

IEC 60092-353

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction DetailsInsulation - HF-EPR as per IEC 60092-351Inner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606IEC 60332-3 Cat. AFIEC 60754-1 & 2IEC 61034-2

Voltage Rating 250V85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction DetailsInsulation - HF-EPR as per IEC 60092-351Collective Screen - Copper or aluminium backed polyester tape with tinned copper drain wireInner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606IEC 60332-3 Cat. AFIEC 60754-1 & 2IEC 61034-2

RFOU(c) RFCU(c) NEK606 Type CableVoltage Rating 250V

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Fire Proof Layer - Mica tape

Construction Details

Insulation - HF-EPR as per IEC 60092-351Collective Screen - Copper or aluminium backed polyester tape with tinned copper drain wireInner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606IEC 60331IEC 60332-3 Cat. AFIEC 60754-1 & 2IEC 61034-2

BFOU(c) BFCU(c) NEK606 Type Cable

RFOU RFCU NEK606 Type Cable

Voltage Rating 0.6/1kV85

IEC 60092-353

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction Details

Insulation - HF-EPR as per IEC 60092-351Fire Proof Layer - Mica tape

Inner Covering - Halogen-free compoundArmour - Tinned copper wire braidSheath - IEC 60092-359, SHF2

Applied StandardsNEK 606

IEC 60332-3 Cat. AFIEC 60331

IEC 60331

IEC 60754-1 & 2IEC 61034-2

BFOU BFCU NEK606 Type Cable

Page 6: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Voltage Rating 250V

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction Details

Insulation - HF-EPR as per IEC 60092-351

Individual Screen - Copper or aluminium backed polyester tape with tinned copper drain wire

Inner Covering - Halogen-free compound

Armour - Tinned copper wire braid

Sheath - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60754-1 & 2

IEC 61034-2

RFOU(i) RFCU(i) NEK606 Type Cable

Voltage Rating 250V

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction Details

Insulation - HF-EPR as per IEC 60092-351

Individual & Collective Screen - Copper or aluminium backed polyester tape with tinned copper drain wire

Inner Covering - Halogen-free compound

Armour - Tinned copper wire braid

Sheath - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60754-1 & 2

IEC 61034-2

RFOU(i/c) RFCU(i/c) NEK606 Type Cable

Voltage Rating 250V

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2

Fire Proof Layer - Mica tape

Construction Details

Insulation - HF-EPR as per IEC 60092-351

Individual & Collective Screen - Copper or aluminium backed polyester tape with tinned copper drain wire

Inner Covering - Halogen-free compound

Armour - Tinned copper wire braid

Sheath - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60331

IEC 60754-1 & 2

IEC 61034-2

BFOU(i/c) BFCU(i/c) NEK606 Type CableVoltage Rating 250V

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2

Fire Proof Layer - Mica tape

Construction Details

Insulation - HF-EPR as per IEC 60092-351

Individual Screen - Copper or aluminium backed polyester tape with tinned copper drain wire

Inner Covering - Halogen-free compound

Armour - Tinned copper wire braid

Sheath - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60331

IEC 60754-1 & 2

IEC 61034-2

BFOU(i) BFCU(i) NEK606 Type Cable

Voltage Rating 0.6/1kV

85

IEC 60092-3

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction Details

Insulation - HF-EPR as per IEC 60092-351

Sheath - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60754-1 & 2

IEC 61034-2

RU NEK606 Type Cable

Voltage Rating 0.6/1kV

85

IEC 60092-353

Maximum Conductor Temperature

Conductor - IEC 60228 Class 2Construction Details

Insulation - IEC 60092-359, SHF2

Applied Standards

NEK 606

IEC 60332-3 Cat. AF

IEC 60754-1 & 2

IEC 61034-2

UX NEK606 Type Cable

Page 7: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Top Drive Service Loops

Nexans AmerCable manufactures OEM-quality serviceloops and supplies them to you without OEM hassles.All land and offshore drilling top drive service loopsare engineered and produced at our state-of-the-artcable and service loop production facilities.

Value Benefits

Standard loop packages for NOV (VARCO), Tescoand Can Rig

Custom Loop Designs

Nexans AmerCable offers custom engineered service loop solutions that deliver higher levels of safety and productivity.

NOV, VARCO, TDX, TDS, and IDS are trademarks owned by National Oilwell Varco, LP or its related entities. Nexans AmerCable is not affiliated with National Oilwell Varco or its related entities.

TESCO and its associated trademarks are trademarks owned by Tesco Corporation or its related entities. Nexans AmerCable is not affiliated with Tesco Corporation or its related entities.

CANRIG and its associated trademarks are trademarks owned by Canrig Drilling Technology Inc. or its related entities. Nexans AmerCable is not affiliated with Canrig Drilling Technology Inc. or its related entities.

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Potted or non-potted

300V – 15kV AC

DC Power

Instrumentation

Composite Power & Control

Thermocouple

Fiber Optic

Electro-Optic

Available with or without quick disconnects

Page 8: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Core bundles, which are specifically designed for service loops, are expertly produced at our 500,000 sq. ft. El Dorado, Arkansas cable manufacturing facility.

Nexans AmerCable has been producing top drive service loops since 1993. Our professionally engineered service loops are built to withstand the hazardous operating conditions and dynamic stress of land drilling operations.

Service loops are completed at our 80,000 sq. ft.manufacturing facility in Houston, Texas. Bundles areinserted in hoses and fully potted (non-potted also available). Our highly experienced technicians add couplers/connectors as specified, then each loop is computer tested and packaged in weatherproof containers.

With Nexans AmerCable you can expect:Nexans AmerCable offers a standard line of top driveservice loop packages, including:

Short lead times

Standard Gexol® cables

Low smoke halogen-free

CIR® – Crush & Impact Resistant (without external armoring)

CIR® Arctic Grade – for extreme cold operating conditions

VFD cables - five constructions

GexSIS-125 switchboard wire

DLO

Reliable on-time delivery

Outstanding engineering and technical support

Great customer service

Cables are available in a variety of constructions, including:

NOV (VARCO)

TDS – 11

TDS – 9

TDS – 10

TDS – 3

TDS – 8

IDS

PS2

(Conversion Kit from loose cables to hanging loop)

TESCO

All Makes & Models

CANRIG

All Makes & Models

Page 9: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

QFCI MUD Resistant Fibre Optic Cable - Fire Resistant / MUD Resistant / Flame Retardant / Halogen Free / DNV approved

QFCI MUD ResistantFibre Optic Cable - Fire Resistant / Flame Retardant / Halogen Free / NEK 606 code F1

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

Central Strength Member Steel strength member or glass fibre reinforced plastic (FRP)

Thermoplastic material (PBT), jelly filled

Fire resistant mica/glass tapes

EIA/TIA 598

1 - Red / 2 - Green - others White

Thermoplastic rods

Loose tubes (and fillers) are stranded around a steel strength member

Black LSZH compound

Galvanised Steel Wire Braid (GSWB)

Black LSZH compound

Loose Tube

Fire Barrier

Fibre Colour Code

Tubes Colour Code

Filler Elements

Cable Core

Inner Jacket

Metallic Armour

Outer Jacket 1

SHF2 compound (mud, oil, hydrocarbon resistant and UV stabilized)

Outer Jacket 2

Product Specifications - Physical Characteristics

Central Strength Member Steel strength member or glass fibre reinforced plastic (FRP)

Thermoplastic material (PBT), jelly filled

Fire resistant mica/glass tapes

EIA/TIA 598

1 - Red / 2 - Green - others White

Thermoplastic rods

Loose tubes (and fillers) are stranded around a steel strength member

Black LSZH compound

Galvanised Steel Wire Braid (GSWB)

Black LSZH compound

Loose Tube

Fire Barrier

Fibre Colour Code

Tubes Colour Code

Filler Elements

Cable Core

Inner Jacket

Metallic Armour

Outer Jacket 1

Product Specifications - Physical Characteristics

Page 10: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Cable Solutions Worldwide, stock and distribute Cat 5e Data cables designed for Marine and Offshore applications. All cables are offered with a Galvanised Steel Wire Braid and a choice of either a standard LSOH jacket or a mud resistant LSOH Polyurethane Jacket. The PU jacket offers enhanced chemical and mud resistance.

Cat 5e Offshore Grade

Data Cables

Cable Solutions Worldwide, stock and distribute Profibus DP and Profibus PA cable designed for Marine and Offshore applications. All cables are offered with a Galvanised Steel Wire Braid and a choice of either a standard LSOH jacket or a mud resistant LSOH Polyurethane Jacket.

Profibus Marine Grade

Cable Solution’s knowledge and experience of their customers requirements combined with the technical expertise “in-house”, has meant that these specialised products are the fastest growing part of Cable Solutions’ product portfolio.

We are specialising in pre-terminated fibre assemblies to operate reliably in the most harsh of environments both on and offshore. Pre-terminated versions with any combination of cores or armouring arrangements are available on any part of the globe within days. These can be made to any length with full protection to ensure the job gets done.

Cable Solutions Worldwide, stock and distribute Fibre Optic cables designed for Marine and Offshore applications. All cables are offered with a Galvanised Steel Wire Braid and a choice of either a standard LSOH jacket or a mud resistant LSOH PolyurethaneJacket. Please download an example of the datasheet for a 12 core fibre. These are stocked in either 4, 8, 12, 24 or 48 fibre configerations. the diameter of the cable remains the same whichever one you choose. The PU jacket offers enhanced chemical and mud resistance.

We also supply all of the patch panels to suit, loaded or blank and a full range of SC and ST type connectors and the test equipment to suit.

Fibre Optic Products & Assemblies

Cable Solutions, stock and distribute Cat 6 Data cable designed for offshore applications. FTP (Screened) & UTP (unscreened) versions are available and all cables are offered with a Galvanised Steel Wire Braid or tinned Copper Wire Braid and a choice of either a standard LSOH jacket or a mud resistant LSOH Polyurethane Jacket. The PU jacket offers enhanced chemical and mud resistance.

Cat 6 Offshore Grade

Cable Solutions Worldwide, stock and distribute Cat 7 Datacable designed for Marine and Offshore applications. All cables are offered with a Galvanised Steel Wire Braid and a choice of either a standard LSOH jacket or a mud resistant LSOH Polyurethane Jacket. The PU jacket offers enhanced chemical and mud resistance.

Cat 7 Offshore Grade

Page 11: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

Subsea Bespoke Cable Manufacture

Our composite cables are designed using high spec stranded wire for the best flexibility in dynamic applications. Whether its for Instrumentation, Fibre optic, Power or control, Cable Solutions can provide an in-house designed cable specification to suit your exact requirements with MOQ’s as low as 100mtrs.

Cable Solutions specialise in the custom design and manufacture of customer specified harsh environment, underwater and composite cables.

With years of experience supplying cable into the subsea and marine sectors, Cable Solutions has gained unrivalled experience and a unique portfolio of bespoke cable designs through its in house design department. All cables are designed using flexible specification wire and materials making Cable Solutions subsea cable perfect for harsh environment dynamic applications.

Cable Solutions Worldwide LtdCraigearn Business ParkMorrison Way, KintoreAberdeenshire, AB51 0TH

e [email protected] 1467 633790 (tel)44 1467 631284 (fax)1st4cables.com

ROV & tether cables

Armoured & strain bearing cable

Subsea umbilicals

Towed array

Diver comms cable

Fibre optic

Oceanographic / harsh environment / underwater

Subsea lighting & camera cable

Offshore to shore power and data

Low MOQ’s

Page 12: The latest fire test procedures for AO & HO multi cable ... Multi Cable and Pipe Transits The latest fire test procedures for AO & HO multi cable transits and pipe penetrations CSD

HS-SK 915 HS-SK 725

HS-SK 814

HS-SK 013.A HS-SK 880

HS-SK 807