THE FUTURE OF INTEGRATED POWER AND PROCESS · PDF file · 2017-01-10PROTECTIVE...
Transcript of THE FUTURE OF INTEGRATED POWER AND PROCESS · PDF file · 2017-01-10PROTECTIVE...
ISSN 2167-3594 NETISSN 2167-3594 NETA WORLD JOURNAL PRINTA WORLD JOURNAL PRINTISSN 2167-3586 NETISSN 2167-3586 NETA WORLD JOURNAL ONLINEA WORLD JOURNAL ONLINE
WIN
TER
2016
PAGE 68
RREEGGISTISTEER TR TOODDAY
INSIDE!INSIDE!INSIDE!INSIDE!INSIDE!INSIDE!INSIDE!PPRREEVVIEIEWW G GUUIDIDEE
CELEBRATE NETA’S 45TH ANNIVERSARY
THE FUTURE OF
AND PROCESS AUTOMATIONINTEGRATED POWER
PROTECTIVE RELAY MISOPERATIONS AND ANALYSISPROTECTIVE RELAY MISOPERATIONS AND ANALYSIS
RELAY COLUMNRELAY COLUMN
Original Protection SettingsFigure 3 shows the original relay settings
for this breaker failure scheme.
Fault Current SignalsFigure 4 shows the oscillography captured by
the relay at the time of the trip.
Figure 5 shows the current phasors measured
by the protective relay when the breaker failure
occurred.
Figure 4:Figure 4: Fault Event OscillographyFault Event Oscillography
Figure 3: Breaker Failure Settings
44 • WINTER 2016
Figure 5:Figure 5: Fault Current PhasorsFault Current Phasors
PROTECTIVE RELAY MISOPERATIONS AND ANALYSISPROTECTIVE RELAY MISOPERATIONS AND ANALYSIS
RELAY COLUMNRELAY COLUMN
Case 1 ConclusionCase 1 ConclusionThe breaker failure trip occurred because I
C was
above the current detector pickup setting and
input 4 (BFI) was asserted.
The breaker failure function may be used for a
unit breaker rather than a generator breaker. It is
limited in that no fault detector is associated with
the unit breaker. Output contact operation would
occur if any of the initiate contacts close, and the
52b contact indicated a closed breaker after the
set time delay. The corresponding logic is shown
in Figure 6.
CASE 2: TRANSFORMERDIFFERENTIAL TRIP DUE TO SYMPATHETIC INRUSHThe transformer differential relay protecting
the step-up transformer at a processing plant
tripped when a nearby large GSU at a power
plant was energized from the high side. The trip
was due to sympathetic inrush current flowing
through the step-up transformer (Figure 7).
Original Protection SettingsOriginal Protection SettingsFigure 8 shows the original settings for the
transformer differential protection.
Fault Current SignalsFigure 9 shows the oscillography captured by the
relay at the time of the trip. Note that current
input IAW1 is almost completely offset, and there
is some distortion in other current inputs as well.
Figure 6: Fault Current Phasors
Figure 7: System Operating Conditions (Arrows Indicate Direction of Inrush Current)
Figure 8: 87T Settings
Figure 9:Figure 9: Fault Event Oscillography (Raw Waveforms)Fault Event Oscillography (Raw Waveforms)
NETAWORLD • 45
PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS4646 • WINTER 2016WINTER 2016
RELAY COLUMNRELAY COLUMN
Harmonic Restraint CalculationsFigure 10 shows the second harmonic content
of the current inputs at the time of the trip. The
second harmonic differential current present
when the trip occurred was as follows:
A-Phase = 17 percent
B-Phase = 13 percent
C-Phase = 13 percent
The ratio of harmonic to fundamental differential
current used to restrain the transformer differential
protection is calculated as follows (Figure 11):
If the ratio is greater than the restraint setting,
then the transformer differential protection is
blocked (Figure 12).
The original second harmonic restraint setting was
20 percent for the electro-mechanical transformer
differential relay. The customer used the same
setting for the multi-function numerical relay that
replaced the original electro-mechanical relay.
Figure 10 showed that a setting of 20 percent was
not sensitive enough to detect the sympathetic
inrush current flowing through the step-up
transformer.
Case 2 ConclusionFor several decades, electro-mechanical relays
had a fixed harmonic inhibit level of 20 percent.
This worked well for a period of time until
transformer manufacturers began making better
transformers that used less material and were
designed with smaller tolerances. Therefore,
modern laminated-steel-core transformers will
not reliably produce 20 percent second harmonic
current during inrush.
Based upon this particular event, an 11 percent
setting for the second harmonic restraint would
be the most reliable. Note that the multi-function
numerical relay in this application actually uses
the root mean square (RMS) of the second and
fourth harmonic differential current, but that
still was not enough to restrain the protection.
Figure 10:Figure 10: Fault Event Oscillography (Second Harmonic Content)Fault Event Oscillography (Second Harmonic Content)
Figure 11: Even Harmonic Restraint Equation
Figure 12: Even Harmonic Restraint Logic
RELAY COLUMN
FINAL CONCLUSIONThe technical analysis of these two relay
misoperations, along with examples of how to use
the data recorded by a relay during these types of
conditions, should help you understand why each
misoperation occurred and how to implement
best practices for each particular application.
Knowing that the first misoperation was due to
an incorrect relay setting, while the second was
due to an incorrect application, should clarify the
need for careful attention during the design andneed for careful attention during the design and
initial work stages.initial work stages.
Steve Turner, an IEEE Senior Member, is
a Senior Applications Engineer at Beckwith
Electric Company. His previous experience
includes work as an application engineer with
GEC Alstom and as an application engineer
in the international market for SEL, focusing
on transmission line protection applications.
Steve worked for Duke Energy (formerly Progress Energy), where
he developed a patent for double-ended fault location on overhead
transmission lines. He has a BSEE and MSEE from Virginia Tech.
Steve has presented at numerous conferences, including Georgia Tech
Protective Relay Conference, Western Protective Relay Conference,Protective Relay Conference, Western Protective Relay Conference,
Energy Council of the Northeast, and Doble User Groups, as well asEnergy Council of the Northeast, and Doble User Groups, as well as
various international conferences.various international conferences.