The Emergi-Fire Sensa control panel operating with Apollo Alarmsense devices is an advanced and cost-effective 2-wire fire system for small to medium-sized buildings. System flexibility enables use in applications such as ‘dwellings and in houses of multiple occupation’ (HMO) and distributed buildings using a proven and extensive networking capability. In summary this is a flexible, reliable and cost effective fire detection system that is easy to install and extend. Eurofire Sensa panels Eurofire Sensa panels are designed to comply with the European Standard EN54 Parts 2 and 4 and are suitable for BS 5839-1:2002 and BS 5839-6:2004 installations. Panels are available in 4, 8, 12 or 16 zones of fire detection cover, with powerful and flexible setup, control and display capabilities. AlarmSense devices AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) are designed to operate normally on the same pair of zone wires from the panel. A key feature is that alarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices. The principle of priority and non-priority response In a Sensa system, the nominal operating voltage is 12 volts, which enables AlarmSense detectors and manual call points (MCPs) to operate. Sounders and beacons operate at 24 volts, so remain dormant at this stage. When a detector or MCP is activated, the panel will register a change and will take the zone voltage up to 24 volts, which will switch the sounders on. A ‘priority’ set device reacts as a normal sounder in standard use and sounds a full alarm. A ‘non-priority’ set device will give an initial local alert prior to going into full alarm. AlarmSense sounder and sounder beacon bases are changeable between ‘priority’ and ‘non-priority’ modes. ‘Non-priority’ devices are intended for use in HMO type applications where there are a number of individual dwellings. The operating method is intended to help reduce the instances of unwanted alarms and give a local warning before the full alarm/evacuation. A sounder-beacon base (with a detector on the base seat) when set to ‘non-priority’, will sound a local alert for 2 minutes at that locality. People in the vicinity or occupants in the dwelling will be the first warned of a possible fire situation or false alarm. They will have 2 minutes to investigate and rectify a false alarm, (i.e. heat or fumes from cooking). After 2 minutes, if the detector is still activated, the Eurofire panel will go into a full fire situation. At any time during the alert period, if another device is activated, the system goes into a full fire situation. Eurofire can be programmed to react to ‘non-priority’ signals in one of two ways: The panel sends out a ‘non-priority’ pattern to the zone, which causes only the sounder on the activated detector to sound, or The panel sends out a ‘non-priority’ pattern to all zones, which have been set to include ‘non- priority’ devices. This will cause any local response (LR) devices set as ‘non-priority’ to also sound – no other ‘non-priority’ devices will sound. If another device of any type or a ‘priority/non- priority’ is activated during the alert period, the system goes into a full fire alarm condition. A ‘non-priority’ alert cannot be generated if the system is already in a fire alarm condition. When a heat detector is attached on a sounder or sounder beacon base, we recommend that the sounder be set as a ‘priority’ device. www.emergi-lite.co.uk Emergi-Fire Sensa with Alarmsense Conventional | Emergi-Fire Sensa with Alarmsense 36

Transcript of The Emergi-Fire Sensa control panel operating - … Emergi-Fire Sensa control panel operating ......

The Emergi-Fire Sensa control panel operatingwith Apollo Alarmsense devices is an advancedand cost-effective 2-wire fire system for small tomedium-sized buildings. System flexibilityenables use in applications such as ‘dwellingsand in houses of multiple occupation’ (HMO)and distributed buildings using a proven andextensive networking capability.

In summary this is a flexible, reliable and costeffective fire detection system that is easy to installand extend.

Eurofire Sensa panelsEurofire Sensa panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are available in 4, 8, 12 or 16 zones of firedetection cover, with powerful and flexible setup,control and display capabilities.

AlarmSense devicesAlarmSense devices (detectors, manual call points,sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair ofzone wires from the panel. A key feature is that alarmsounders can be programmed to operate as so-called‘priority’ or ‘non-priority’ devices.

The principle of priority andnon-priority responseIn a Sensa system, the nominal operating voltage is12 volts, which enables AlarmSense detectors andmanual call points (MCPs) to operate. Sounders andbeacons operate at 24 volts, so remain dormant at thisstage. When a detector or MCP is activated, the panelwill register a change and will take the zone voltageup to 24 volts, which will switch the sounders on.

A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.

AlarmSense sounder and sounder beacon bases arechangeable between ‘priority’ and ‘non-priority’ modes.

‘Non-priority’ devices are intended for use in HMOtype applications where there are a number ofindividual dwellings. The operating method isintended to help reduce the instances of unwantedalarms and give a local warning before the fullalarm/evacuation.

A sounder-beacon base (with a detector on the baseseat) when set to ‘non-priority’, will sound a local alertfor 2 minutes at that locality. People in the vicinity oroccupants in the dwelling will be the first warned of apossible fire situation or false alarm. They will have2 minutes to investigate and rectify a false alarm,

(i.e. heat or fumes from cooking). After 2 minutes, ifthe detector is still activated, the Eurofire panel willgo into a full fire situation. At any time during thealert period, if another device is activated, the systemgoes into a full fire situation.

Eurofire can be programmed to react to ‘non-priority’signals in one of two ways:

The panel sends out a ‘non-priority’ pattern to thezone, which causes only the sounder on theactivated detector to sound, or

The panel sends out a ‘non-priority’ pattern to allzones, which have been set to include ‘non-priority’ devices. This will cause any local response(LR) devices set as ‘non-priority’ to also sound –no other ‘non-priority’ devices will sound.

If another device of any type or a ‘priority/non-priority’ is activated during the alert period, thesystem goes into a full fire alarm condition.

A ‘non-priority’ alert cannot be generated if thesystem is already in a fire alarm condition.

When a heat detector is attached on a sounder orsounder beacon base, we recommend that thesounder be set as a ‘priority’ device.

www.emergi-lite.co.uk

Emergi-Fire Sensa with Alarmsense

Conventional | Emergi-Fire Sensa with Alarmsense

36

BaxteCE
Rectangle

Programming non-priority detectorsfor local alarm operationThe diagram below illustrates a 2-storey block containing3 flats and an entrance lobby. A Eurofire panel controlsthe fire alarm system for all 3 flats. Manual call points aresituated in the lobby and along the corridors. Sounderdetector bases are situated throughout with a separatesounder adjacent to the fire panel.

Scenario 1 – ‘Non-priority’ detector in Flat 1activates owing to fumes from cooking

The base sounder above the detector will sound for 2minutes (alerting the occupants in flat 1).

The sounder beacon (Zone 8) next to the panelactivates, if it is programmed for local response (LR).The occupant has time to expel the smoke from thedetector vicinity.

During this period, the panel indicates ‘Zone 1 LocalAlert’, and sounds the buzzer in the control panel. Theresponsible person has time to investigate the alertand act accordingly. If any detector or MCP activatesduring the alert, the system goes into a full firesituation and sounds the alarm.

After the alert period, with fumes dispersed, the panelwill return to the quiescent state. If the detectorremains activated after the alert period, the panel willgo into a full fire alarm condition.

Scenario 2 – Non-priority detector in Flat 1 isactivated as a real fire condition

The sequence is the same as in the first scenario, untilthe 2-minute alert period is over. After the alertperiod, with a real fire, the detector remains activatedand the panel will go into a full fire alarm condition.

Scenario 3 – Detector or MCP is activated as a fire

The panel goes into a full fire situation. If a ‘non-priority’ detector is activated afterwards – the paneltreats this as a normal detector being activated in afire situation.

www.emergi-lite.co.uk

37

Emergi-Fire Sensa with Alarmsense | Conventional

CIE

Up

Up

Zn3Zn2

Zn1Zn8

Zn4

Zn5

Zn6Zn7

Zone 7

Zone 5

Zone 3Zone 2

Zone 1

# = Set as non-priority detector

#

##

Flat 2

Flat 1

Flat 3

Apartment building with a floor plan of 2 floors: Illustration ofdetector programming for local alarm operation

Floor 1

Floor 2

Zone 6

Zone 4

Key:

Manual call point

Combined sounder-detectorbase (priority set)

Combined sounder-detectorbase (non-priority set)

Sounder-beacon base

Standalone smoke alarm

BaxteCE
Rectangle

Conventional | Eurofire Sensa 2-wire panels

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

38

Eurofire Sensa 2-wire fire panels Benefits and featuresComprehensive zone coverage:Available in 4, 8, 12 or 16 zonemodels.

Zone capacity:Nominally 30 devices per zone.

Soft select:Non-latching or latching zones:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This preventslockout and allows panels to bereset more readily (the panelbeing connected to must have aspare zone and auxiliary contactswith a volt-free pair). Short circuitfire or fault for older systems.

Output wiring:2-wire configuration to the zones,giving reduced wiring cost.

Outputs:4 alarm outputs and auxiliary volt-free contacts, which areprogrammable for continuous,pulsing or delayed operation.Fault volt-free relay contacts.

Sounder delay activation:Eurofire includes a sounder ‘delay-on’ facility. This allows the user toprogramme chosen sounders orbeacons to activate at a latermoment. This is suited toapplications where it is beneficialnot to have undue panic, such asin bars or Soft Play centres.

2-wire and 4-wire systemintegration:The Eurofire system has the abilityto recognise and operate a 4-wirezone, which can potentially save onwiring when a refurbishment isundertaken. For example in a smallhotel or guesthouse where nosounders or sounder-beacons arefitted in bedrooms, a bedroom zonecan be the 2-wire format, withdetectors and alarms wired on thesame pair. Other existing 4-wirezones in the building can remain ifdesired (it will be necessary to checkfor sounder tone compatibility).

Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits, or save on fieldwiring.

Eurofire Sensa is a range of conventional (non-addressable) firedetection panels with extensive safety, technical and practicalfeatures for the installer and user. Eurofire Sensa panels aredesigned to comply with the European Standard EN54 Parts 2 and 4and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are available in 4, 8, 12 or 16 zones of fire detection cover, withpowerful and flexible setup, control and display capabilities and areconfigured to operate with Apollo AlarmSense devices.

The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

BaxteCE
Rectangle

Eurofire Sensa 2-wire panels | Conventional

Panel DisplayThe Eurofire Sensa panel includes an easy to reference display with LCD screen allowing for up to four lines of text,with text programmable for each zone. 6 buttons are included on the front of the panel which can be used to accessthe following functions:

Lamp test, silence alarms, silence buzzer

User zone, sounder and 2-wire sounder isolation

Walk and alarm test facility with mute option

99-event history log that stores any events withtime and date stamp, for the user to scroll

Configurable system message for the user withnormal time and date displayed

The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.

Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

39

Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:

Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).

CAN network

IsolatedCAN

network

CA

NN

ETC

AR

D

CAN network

IsolatedCAN

network

CA

NN

ETC

AR

D

To nextpanel

Illustration: Network of Eurofire panels, in star format[wired to the CAN network facility]

Eurofire c-net

Eurofire c-net Eurofire c-net

BaxteCE
Rectangle

Eurofire Sensa 2-wire panels

Conventional | Eurofire Sensa 2-wire panels www.emergi-lite.co.uk

40

Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points, with settings forboth ‘priority’ and non-priority’.

Eurofire 2-wirezonal layoutThe illustration belowshows a potential schemelayout for a Eurofire panel,over 5 active zones, with1 additional alarm circuit.

Additonal alarmcircuits

Auxiliary relaycontacts

NC C NO +AL2-+AL1-

Aux 1 Aux 2

+Z1- +Z2-

Cla

ssch

ang

e

TTL

fau

lt

GN

D

- 24v +

+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO

Co

mm

on

fau

lt

Pro

gi/p

Bo

mb

aler

t+AL3- +AL4-

Isolated CAN network

HI LO SCR HI LO SCRHI LO SCR HI LO SCR

CAN network

- 24v +- 12v +

Auxoutputs

Auxi/p

- +AC AC

Batt

+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-

Eurofire Sensa 2 wire: Illustration of zonal wiring

Fault 1 Fault 2

2- wire zones; 2 & 4 to 8,wired as priority or non-

priority EOL diode to unused zones [cathode to zone,+ve end]

EOLresistor inunused

alarm ccts

No spurs

EOL diode on last detector[cathode to zone +ve end]

No spurs

o

o

o o

o

Call point -2wKey:

Optical 2wdetector

Priority 2wsounder

2w Sounder, setas non-priority

Standardsounder

o

o

Z1: Priority zone

Z3: Non-priority zone

Key:

o

EOL

Call point

Optical smoke detector

Heat detector

Beamdetector set

End of line device-detector circuit

Sounder (priority)

Sounder-beacon (priority)

Zone: detection circuitwiring

Alarm circuit wiring

SEOLEnd of line device -alarm circuit

RA1

Programmablesounder circuitsfrom the panel

Zone circuits toEurofire 2wSensa panel

Kitchen

Fire exit

Fire exit

Fire exit

Apex roof

o

A1R

o o

oo

o

o

o

o

o

A1R

o

o

o

ROOFWINDOWCONTROL

o

Auxiliarycircuits

Motorisedwindowvents

EOL

EOL

EOL

EO

L

EO

L

SEOL

A1R

BaxteCE
Rectangle

Detectors per zone 30 per zone, maximum

Sounders per zone [1] 30 per zone, maximum

Sounder-Beacons per zone [2] 15 per zone, maximum

Zone Sounder Current (panel total) 1.25A max (see notes 1 & 2)

Sounder current 5mA at either low (70dBA) or high (87dBA) output

Sounders per panel 250

Sounder-Beacon Current 9mA at either low (70dBA) or high (87dBA) output

Sounder-Beacons per panel 135

Inputs Class change, Bomb Alert, Programmable

Display 4 x 20 character LCD + zone fire & fault LEDs and system LEDs

Mains input voltage 230Vac +10% –6% 50Hz

Output auxiliary voltage, DC 24Vdc @ 250mA 12Vdc @ 250mA

Battery size 12V 7AH x 2 (connected in series)

Battery standby Minimum 24 hours (please contact technical sales for further information.)

Construction: Metal back box with moulded polycarbonate front panel in cool grey

Panel dimensions hwd (mm) 469 x 373 x 103

Detector & call point compatibility Sensa – Alarmsense detectors, call points and alarm devices.

Programmable features Extensive via buttons and LCD display

CAN Network Panel and repeater combinations via CAN 2.0b link

Outputs:

Alarm Lines 4

Alarm current total 1.25A- zone sounder current, see note 3

Auxiliary outputs 2 sets of volt free contacts, rated @ 2A 30Vdc

Fault outputs 2 sets of volt free contacts, rated @ 2A 30Vdc

Notes:[1] – Version 2 sounders only[2] – Using version 2 sounder-beacons only[3] – Total Panel Alarm Current is 1.25A. The total zone sounder current must be taken into account when deciding how much load is available for alarm lines

AL1 – 4For example: a maximum of 250 sounders (5mA each) or 135 sounder beacons (9mA each) can be loaded onto the system.

Warning: do not use FAP6 detectors on Alarmsense systems. Although they would appear to work initially, using them could cause severe system malfunction in the longer term. Also beaware that if used with the Sounder/Sounder Beacon Bases the non-priority function will not operate correctly.

Eurofire Repeater panel

PRODUCT ORDER CODE FEUN-RP

Connections 2-core for data from the main panel and 2-core for 24 Vdc power

Display 4 x 20 character LCD with Zone, Fire and Fault LEDs

Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)

Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)

Construction Metal back box with moulded polycarbonate front panel in cool grey

Dimensions hwd (mm) 469 x 373 x 103

Eurofire Sensa 2-wire panels | Conventional

Eurofire Sensa 2-wire panels

www.emergi-lite.co.uk

41

STANDARD ORDER CODE DESCRIPTION

FEWN-4 Eurofire 4 Zone Panel

FEWN-8 Eurofire 8 Zone Panel

FEWN-12 Eurofire 12 Zone Panel

FEWN-16 Eurofire 16 Zone Panel

OPTIONS

Suffix LD Lockable door option for Eurofire Panel

FEUN-RP Eurofire Repeater Panel

ACCESSORIES

F4ALMB 4 way Alarm Extender

F4COB Relay Unit, 4 pole

FEUN-EOL-KIT End of Line Component Kit

FEUN-NETCAN CAN Isolator Assembly

FEUR-BG Semi-recessing bezel grey

FEUN-SPARES Eurofire Spares Pack

To Order

PRODUCT ORDER CODE FEWN-4 FEWN-8 FEWN-12 FEWN-16

No. of zones 4 Zone 8 Zone 12 Zone 16 Zone

Eurofire Sensa, 2-wire panel technical specification

BaxteCE
Rectangle

Conventional | Firetec Sensa 2-wire panels

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

42

Firetec Sensa 2-wire fire panels Benefits and featuresThe panel is easy to install andcomes with a wide range offeatures for the user andmaintenance engineer.

The panel enclosure is shapedwith gentle curves and clean linesto fit in with surrounding décor.

Comprehensive zone coverage:Available in 2, 4 or 8 zone models.

Zone capacity:Nominally 25 devices per zone.

Output wiring:2-wire, giving reduced wiring cost.

Standby duration:48 hours

Walk test:1 man operation

Security coded push button entry:Status can be checked via level 1.Subsequent levels are passwordprotected for the authorised userand engineer respectively

Programmability:Several features such as ‘priority –non priority setting’, ‘delays toalarms’, ‘day mode’ are availableto tailor the function of the panelto local requirements.

Details are listed in thespecification table.

Outputs:Output facilities for Alarm,Volt-free alarm and TTL Fault.

Note: Firetec Sensa 2-wire panelavailable soon. Please contactEmergi-Lite Sales Team for furtherdetails.

STANDARD DESCRIPTIONORDER CODE

FTEW2 Firetec 2 Zone Panel

FTEW4 Firetec 4 Zone Panel

FTEW8 Firetec 8 Zone Panel

Firetec Sensa is a range of conventional (non-addressable) firedetection panels offering a practical, cost effective fire safetysolution for smaller to medium sized premises. Firetec Sensa panelsare designed to comply with the European Standard EN54 Parts 2and 4 and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Firetec Sensa is now more versatile than ever with the ability of handlingdetection and alarm in up to 8 separate zones. Panels are available in2, 4 and 8 zones of fire cover, with flexible setup, control and displaycapabilities, and are configured to operate with ‘2-wire’ Sensa: Alarmsensedetection and alarm devices.

The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.

OPTION

Suffix KS Optional security keyswitch for Firetec panels

BaxteCE
Rectangle

Firetec Sensa 2-wire panels | Conventional

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

43

Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

Display & user interfaceThe Firetec Sensa panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:

Silence alarms or enable/disable zones

Silence buzzer

User zone and 2-wire sounder isolation

Lamp test

Walk and alarm test facility

Reset function

Alarm circuits

NC C NO

Auxiliary relaycontacts

NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-

Ena

ble

dela

y

Cla

ssch

ange

Mon

inpu

t

TT

Lfa

ult

GN

D

C - Classchange switch

End of line resistor10K, on last

sounder

Enable alarmdelay switch

+Aux-24v

Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-

Zones 2,4,5 wired butnot shown

EOL diode to unusedzones [cathode to

zone, +ve end]EOL

resistor inunused

alarm cct

No spurs

Call point

Detector Standard alarm device

C

EOL diode on lastdetector [cathodeto zone +ve end]

No spurs

o

o

o

o

Z1: Priority zoneo

o

Z3: Non-priority zone

o

Priority alarm device

Non-prioity alarm device

Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.

BaxteCE
Rectangle

Conventional | Firetec Sensa 2-wire panels

Firetec Sensa 2-wire panels

www.emergi-lite.co.uk

44

Notes:

1 Total panel alarm current, is total zone alarm current + total sounder current on AL1 & AL2. Total should not exceed 1A.

2 Ensure that maximum number of sounders/sounder-beacon devices does not exceed total current allowed for zones.30 sounders on a zone = 5mA * 30 = 0.15A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on zone.16 sounder-beacons on a zone = 9mA * 16 = 0.144A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on the zone.Sounders and sounder-beacon devices can be used together on a zone but should not exceed the maximum alarm current per zone.

3 Current available for alarm lines AL1 & AL2 = 1A - Total zone alarm current being used.

Detection Circuits Compatible with Emergi-Lite Sensa sounders, manual call points, smoke and heat detectors, Emergi-Lite Sensa zonesounders & zone sounder-beacon bases, Emergi-Lite Sensa priority/non priority devices

Detectors per Zone 25 Detectors per zone

Total Alarm Current (panel total) 1A, see note 1

Maximum Alarm Current Per Zone 0.15A

Sounders Per Zone(Low70dB(A) 5mAHigh87dB(A) 5mA)

25

Sounder-Beacons Per Zone(Low70dB(A) 9mAHigh87dB(A) 9mA)

16

Alarm Lines [AL1 & AL2] 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max, panel total is 1A. Each sounder circuit protected by a resettablefuse - resets when fault is removed. Expandable to 8 circuits in groups of 4 with 4 way alarm extender board

Auxiliary Relay Contacts 2 Sets of volt-free contacts rated 30Vdc @2A - activated during a fire condition when the alarm circuits are activated

Auxiliary Output 24Vdc rated 250mA protected by resettable fuse - resets when fault is removed.

Class Change Connect CC to Gnd terminal to activate sounders.

Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line device

Alarm: Short circuit & open circuit using end of line resistor

Mains Input Voltage 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)

Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery. Temperature compensated charger. Deep discharge protected withcut off at approx. 10.5V. Protected by a resettable fuse - resets when fault is removed.

Battery Standby 48 hours. For more details refer to technical sales for standby calculations.

Supply Fault Monitoring Mains missing - battery missing - battery charger fault

Controls 5 push buttons with coded entry access

Construction Moulded polycarbonate plastic fascia and back box in cool grey

Dimensions hwd (mm) 263 x 337 x 90

Fault Output TTL fault output: Active (5Vdc) when no faults are present - fail safe to off

Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as Priority or Non Priority

Class change can be programmed to illuminate 'general fire' led when activated.Delay of 1-10 mins to alarms activating in a fire condition - this works in conjunction with

Enable delay' input. 'Enable delay' can also be used as a 'day switch/input.'

PRODUCT ORDER CODE FTEW2 FTEW4 FTEW8

No. of Zones 2 Zone 4 Zone 8 Zone

Firetec Sensa, 2-wire panel technical specification

BaxteCE
Rectangle

AlarmSense devices | Conventional

AlarmSense devices

AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair of zone wires from the panel. A key feature is thatalarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices.

A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.

‘Non-priority’ devices are intended for use in HMO typeapplications where there are a number of individualdwellings. The operating method is intended to helpreduce the instances of unwanted alarms and give alocal warning before the full alarm/evacuation.

When a heat detector is attached on a sounder orsounder beacon base, we recommend that the sounderbe set as a ‘priority’ device.

For more information about priority/non-prioritydevices, please refer to pages 36 – 37.

Detector base FAPW2-ASB

The Sensa detector base is specific for the Sensa detector range. Electroniccircuitry is included, which monitors the presence of the detector and willsignal a fault if a device is removed.

SPECIFICATION

Quiescent current at 15V <30µA

Load shown to the zone withhead removed

47Ω for 10ms every 4 seconds

Wiring & polarity 2 wire supply, polarity insensitive

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100

Weight g 55

www.emergi-lite.co.uk

45

FAPW2-ASB

Device benefits and featuresThe table below highlights the key features of the sounder bases and sounder-beacon bases available as part of ourconventional 2-wire range.

PRODUCT CODE DESCRIPTION

FAPW2-BS24W Sounder base W

FAPW2-BSB24W Sounder base beacon C W

FAPW2-CBSW Sounder base cap W

FAPW2-CBSR Sounder base cap R

Feat

ure

s:

Beac

on

Soun

der

Am

ber,

Cle

aror

Red

lens

Red

orW

hite

body

Apo

lloA

lert

/Ev

acto

ne

Inte

grat

edba

se

Con

vent

iona

l

Acc

esso

ries

BaxteCE
Rectangle

www.emergi-lite.co.uk

46

Sounder base unit FAPW2-BS24W

A compact low profile device fitted with a base seat for fitting compatiblesmoke or heat detectors. For standalone use, optional caps in red or whiteare available. The sounder has a volume control (DIL switch selection forhigh or low output) and can operate within the ‘priority/non-priority’signalling regime.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 12V <20µA

Sounder active current @ 24V 5mA

Sound output dBA, high volume 87

Low volume dBA 70 nominal

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Construction Polycarbonate/ABS

Dimensions ø d (mm) 115 x 40

Weight g 150

Standards EN54-3

OPTIONS

FAPW2-CBSW White cap

FAPW2-CBSR Red cap

Conventional | AlarmSense devices

AlarmSense devices

Sounder beacon base FAPW2-BSB24W

A compact low profile device with visual and sound warning indication.The unit is fitted with an integral base seat for fitting compatible smoke orheat detectors. For standalone use, optional caps in red or white areavailable. The sounder has a volume control (DIL switch selection for highor low output) and can operate within the ‘priority/non-priority’ signallingregime.

Suited to premises where visual warning indication is needed for the hardof hearing.

Enables the user to comply with the Disability Discrimination Act (DDA).

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 12V <20µA

Sounder active current @ 24V 9mA

Sound output dBA, high volume 87

Low volume dBA 70 nominal

Operating temperature –20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Construction Polycarbonate

Dimensions ø d (mm) 115 x 40

Weight g 150

Standards EN54-3

OPTIONS

FAPW2-CBSW White cap

FAPW2-CBSR Red cap

FAPW2-BS24W

FAPW2-BSB24W

Application

Owing the level of sound these devices can produce; they are effective forlocal use. For example, in situations where there is a corridor with anumber of adjoining rooms, closed doors can reduce the sound levelsomewhat. Consequently, it is recommended that this type of soundershould be placed in both the room and the corridor.

BaxteCE
Rectangle

www.emergi-lite.co.uk

47

AlarmSense devices | Conventional

AlarmSense devices

Optical smoke detector FAPW2-OP

The optical detector measures the level of smoke particles using lightscatter, then going to alarm at a pre-set threshold.

Integrating optical smoke detector FAPW2-OP-INT

This detector is available for spaces in buildings where smoke particles(cigarette smoke for example) might be present normally, to help avoidfalse alarms.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 2 – 8.5V10.5 – 15V

<1.5mA25 +/- 2mA

Wiring & polarity 2 wire supply, polarity insensitive

Construction Polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-7: 2000

Rate of rise device, grade A1R FAPW2-R6

The detector monitors the rate of temperature rise in the vicinity and willalso trigger when a fixed upper threshold of 50°C is reached.

Fixed temperature detector, grade CS FAPW2-F84

The static heat detector will signify fire, when a preset temperature isreached. The CS device will trigger at 80°C.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 12V24V

<1.5mA25 +/- 2mA

Grades A1R & CS

Wiring & polarity 2 wire supply, polarity insensitive

Construction Polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-5: 2000

FAPW2-OP

FAPW2-R6

FAPW2-F84

BaxteCE
Rectangle

Surface mount unit FMFW2-800

The Sensa call point is fitted with frangible element. A key test facility issituated underside, which is fully reset when the key is removed. The deviceis detected as an operated call point by the Sensa system.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 15V <50µA

Alarm current at 2 – 8.5V10.5 – 15V

<1.5mA25 +/- 2mA

Wiring & polarity 2 wire supply, polarity insensitive

Reset time 1 second

LED indicator Red

Construction Polycarbonate/ABS

Dimensions ø d (mm) 87 x 87 x 52

Weight g 170

Standards EN54-11: 2000

ACCESSORY

RSL800 Fire call point notice sticker

Conventional | AlarmSense devices

AlarmSense devices

www.emergi-lite.co.uk

48

FMFW2-800

Protective covers for manual call pointsA tough protective cover is available to help prevent accidental operationof call points, or prevent unauthorised use by those with malicious intent.The cover is suitable for use in educational buildings, hospitals, nursinghomes or places where the threat of false alarm is prevalent.

STANDARD ORDER CODE DESCRIPTION

FMC-ST30 Surface mount protective cover, with 30mm spacer

FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer

For further options, please contact technical sales.

FMC-ST30

FMC-ST50WP

RSL800

BaxteCE
Rectangle

AlarmSense devices | Conventional

AlarmSense devices

Standard remote indicator unit FAP6-P10

(standard base)A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space.

Remote indicator unit FMFW2-PBD20

(sounder base or sounder beacon base)The PBD version is designed to show indication from a detector fitted to asounder base or sounder beacon base in premises such as an HMO.

SPECIFICATION

LED indicator Red

Construction Polycarbonate/ABS

Termination Terminal block

Dimensions ø d (mm) 85 x 85 x 5

Weight g 38.2

Alarm relay FAPW2-ALR

This ancillary unit allows external items, including paging devices andmagnetic door closers to be connected to the 2-wire fire detection system.The relay can be configured to provide two sets of volt-free contacts foruse by external devices.

Selectable DIL switch features:

A relay-reset delay of 2 seconds is selectable by DIL switch.

Non-priority signals from the fire panel can be recognised at the relayaccording to a DIL switch setting, which could enable the relay to beused as a stand-alone alarm indicator or activate an external functionlike a staff alarm.

SPECIFICATION

Voltage range 9 – 33Vdc

Relay operating voltage >18V

Quiescent current at 12V <20µA

Surge current at relay set voltage 15mA for 20ms

Relay contact ratings 1A at 30Vdc

Wiring & polarity 2 wire supply, polarity sensitive

Termination Connectors accept up to 2.5mm2 cables

Dimensions ø d (mm) 65 x 45 x 25

Weight g 35

Standards EN54

Commissioning note: At commissioning the relay should be reset prior touse. During operation the relay will reset if there is a power loss on the firealarm circuit.

www.emergi-lite.co.uk

49

FAP6-P10

FAPW2-ALR

o o

Remote indicator

Closed roomspace

Normaldetection:

Indicator visible

Corridor

Vision panel in doorSolid door

-ve+

ve-R

Zone

Zone

Zone inZone out

L1 zone +ve

L2 zone -ve

Rem

oteLE

Dboard

R5

Connection of remote LED unit to Sensasounder or sounder-beacon bases

BaxteCE
Rectangle

Eurofire 4-wire panels

Conventional | Eurofire 4-wire panels www.emergi-lite.co.uk

50

Eurofire 4-wire fire panels

Traditionally, conventional fire systems have been wired as ‘4-wire’installations, where the detection and alarm devices are wiredseparately from the panel. This does give some integral protectionwhere the alarm circuit would not be affected by a fault on thedetection side.

Eurofire EN54 is a conventional (non-addressable) fire detection systemwith enhanced safety, technical and practical features for the installer anduser. Eurofire EN54 panels are designed to comply with the EuropeanStandard EN54 Parts 2 and 4 and are suitable for BS 5839-1:2002 andBS 5839-6:2004 installations.

Panels are configured to operate with ‘4-wire’ detection and alarm devicesand are available as a standalone panel for 4, 8, 12 or 16 zones of firecover, ideal for medium sized premises. Alternatively, for larger installationsEurofire can be networked with sister Eurofire panels and repeaters forcomplete cover over the site.

Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.

Benefits and featuresThe panel has an extensive arrayof useful tools and featuresdesigned to help both the installerto set up the system easily and theuser to manage the systemeffectively.

Standby duration:48 hours

Zone capacity:Up to 30 devices per zone.

Soft select:Non-latching or latching on fire:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This methodwill monitor the interconnectionbetween panels and allow panelsto be reset more readily (thepanel being connected to, musthave a spare zone and alarm lineor auxiliary contacts with avolt-free pair). Short circuit fire orfault for older systems.

Security control:Coded push button entry:The status viewer has quick entry atlevel 1. Levels 2 and 3 are passwordprotected for the authorised userand Engineer respectively.

Outputs:4 Programmable Alarm outputs.Fire auxiliary volt-free relaycontacts, which are programmablefor continuous, pulsing anddelayed operation. Fault volt-freerelay contacts.

Output wiring:Conventional 4-wire to the zones.

2-wire zone selection:In instances, where it is desired torun a zone of 2-wire devices, thepanel can be programmed toachieve this by a trainedcommissioning engineer.

Sounder delay activation:A sounder ‘delay-on’ facilityallows the user to programmechosen sounders or beacons toactivate at a later moment. Idealwhere it is beneficial not to haveundue panic, such as in bars orSoft Play centres.

Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits or save on fieldwiring.

BaxteCE
Rectangle

Eurofire 4-wire panels

Eurofire 4-wire panels | Conventionalwww.emergi-lite.co.uk

51

Panel DisplayThe Eurofire panel includes an easy to reference display with LCD screen allowing for up to four lines of text, withtext programmable for each zone. 6 buttons are included on the front of the panel which can be used to access thefollowing functions:

Lamp test, silence alarms, silence buzzer

User zone and sounder isolation

Walk and alarm test facility with mute option

99-event history log that stores any events withtime and date stamp, for the user to scroll

Configurable system message for the user withnormal time and date displayed

The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.

Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.

Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:

Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).

A1 R

c s

o

o

oo

o EO

L

o

EO

L

o

o

EOL

SEOL

SEOL

Network

Zone 8

Eurofire c-net

Zone 1

Zone 7

Zone 2

Illustration: 8 zone Eurofirewith network panel connected

4 sounder circuits, 2shown connected

EO

L

BaxteCE
Rectangle

www.emergi-lite.co.uk

52

Eurofire 4-wire panels

Conventional | Eurofire 4-wire panels

Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points.

Eurofire 4-wire zonal layoutThe illustration below shows a potential scheme layout for a Eurofire panel, over 5 active zones, with 4 alarm circuits.

Alarm circuits

Auxiliary relaycontacts

NC C NO +AL2-+AL1-

Aux 1 Aux 2

+Z1- +Z2-

Cla

ssch

ang

e

TTL

fau

lt

GN

D

- 24v +

+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO

Co

mm

on

fau

lt

Pro

gi/p

Bo

mb

aler

t+AL3- +AL4-

Isolated CAN network

HI LO SCR HI LO SCRHI LO SCR HI LO SCR

CAN network

- 24v +- 12v +

Auxoutputs

Auxi/p

- +AC AC

Batt

+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-

o

o

o

Fault 1 Fault 2

Zones 2-8 wired as Z1

EOL diode to unusedzones [cathode to

zone, +ve end]

EOLresistor in

unusedalarm ccts

No spurs

EOL diode on lastdetector [cathodeto zone +ve end]

o

No spurs

o

c s

o

o

o

o o

oo

o

o

o

o

o

o

o

o

EO

L

EOL

EOL

Programmablesounder circuits from

the panel

Zone circuits toEurofire 4wpanel

Illustration:Scheme layout using aEurofire panel [5 zones active,with four alarm circuits]

EOL

Kitchen

Fire exit

Fire exit

Fireexit

Apex roof

SEOL

SEO

L

SEOL

SEOL

EOL

Key:

o

c s

EOL

Call point

Opticalsmokedetector

Heat detector

Beam detector set

End of line device -detector circuit

Sounder

Sounder-beacon

Zone: detection circuitwiring

Alarm circuit wiring

SEOL End of line device -alarm circuit

BaxteCE
Rectangle

53

www.emergi-lite.co.uk

PRODUCT ORDER CODE FEUN-4 FEUN-8 FEUN-12 FEUN-16

No. of zones 4 Zone 8 Zone 12 Zone 16 Zone

Detectors per zone 30 per zone maximum

No. of alarm lines 4 (expandable to 16 programmed in groups of 4, with card extenders)

Maximum alarm load Total = 1.25A. Maximum per line or circuit = 1A

Inputs Class change. Bomb Alert and Programmable input

Display 4 x 20 character LCD, plus zone fire and fault LEDs

Mains input voltage 230Vac +10%, –6% 50Hz

Output auxiliary voltage, DC 24Vdc & 12Vdc @ 250mA

Battery size 12V 7AH x 2 (connected in series)

Battery standby 24 hours minimum (please contact technical sales for further information.)

Construction: Metal back box with moulded polycarbonate front panel in cool grey

Dimensions hwd (mm) 469 x 373 x 103

Detector & call point compatibility ‘Emergi-Lite Orbis’ and FAP6 smoke and heat with diode base. Manual call points with 220-680 ohm resistor

Outputs:

Auxiliary outputs Two sets of volt-free aux. programmable contacts (rated 2A @ 30Vdc)

Fault outputs Two sets of volt-free fault contacts (rated 2A @ 30Vdc)

Additional options:

FEUN-BG Semi-recessing trim bezel finished in grey

Networking Panels networked using ‘CAN’ Network terminals. An ‘isolated CAN network driver’ is available for isolated networks.Please contact technical sales for particular need

Zone upgrade Where a user expects to expand coverage in the future a special upgradeable version can be supplied.Please specify the requirement when requesting a quotation

Eurofire Repeater panel

PRODUCT ORDER CODE FEUN-RP

Connections 2-core for data from the main panel and 2-core for 24Vdc power

Display 4 x 20 character LCD with Zone, Fire and Fault LEDs

Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)

Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)

Battery size 12V 7AH x 2 (connected in series)

Construction Metal back box with moulded polycarbonate front panel in cool qrey

Dimensions hwd (mm) 469 x 373 x 103

Eurofire 4-wire panels

Eurofire 4-wire panels | Conventional

STANDARD ORDER CODE DESCRIPTION

FEUN-4 Eurofire 4 Zone Panel

FEUN-8 Eurofire 8 Zone Panel

FEUN-12 Eurofire 12 Zone Panel

FEUN-16 Eurofire 16 Zone Panel

OPTIONS

Suffix LD Lockable door option for Eurofire Panels

FEUN-RP Eurofire Repeater Panel

ACCESSORIES

F4ALMB 4 way Alarm Extender

F4COB Relay Unit, 4 pole

FEUN-EOL-KIT End of Line Component Kit

FEUN-NETCAN CAN Isolator Assembly

FEUR-BG Semi-recessing bezel grey

FEUN-SPARES Eurofire Spares Pack

To Order

Eurofire conventional, 4-wire panel technical specification

BaxteCE
Rectangle

Firetec 4-wire panels

Conventional | Firetec 4-wire panels

STANDARD ORDER CODE DESCRIPTION

FTEP1 Firetec 1 Zone Panel

FTEP2 Firetec 2 Zone Panel

FTEP4 Firetec 4 Zone Panel

FTEP8 Firetec 8 Zone Panel

ACCESSORIES

FTE-EOL-KIT End of Line Component Kit

FTE-BG Semi-recessing bezel grey

FTE-SPARES Firetec Spares Pack

www.emergi-lite.co.uk

54

Firetec 4-wire fire panels Benefits and featuresThe panel is easy to install and comes with a widerange of features for the user and maintenanceengineer.

The panel enclosure is shaped with gentle curves andclean lines to fit in with surrounding décor.

Comprehensive zone coverage:Available in 1, 2, 4 or 8 zone models.

Zone capacity:Nominally 25 devices per zone.

Standby duration:48 hours

Walk test:1 man operation

Display and user interface:Indicators for information, fire, fault and ‘fire & fault’

Security coded push button entry:Status can be checked via level 1. Subsequent levelsare password protected for the authorised user andengineer respectively

Programmability:A number of features are available including‘latching/unlatching zones’, ‘delays to alarmactivation’, ‘monitored input’ (which can be on or off).Programmability is detailed in the specification table.

Outputs:A set of output facilities for Alarm, Volt-free alarmand TTL fault

Traditionally, conventional fire systems havebeen wired as ‘4-wire’ installations, where thedetection and alarm devices are wiredseparately from the panel. This does give someintegral protection where the alarm circuitwould not be affected by a fault on thedetection side.

Firetec is a conventional (non-addressable) firedetection panel that is suited for fire detectioncoverage in smaller premises, such as offices andshops. The panel is configured to operate with ‘4-wire’detection and alarm devices and is available as astandalone panel for 1, 2, 4 or 8 zones of fire cover.

Firetec panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.

Panels are supplied as a complete package, with allend of line devices, batteries and a logbook included.

Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.

OPTION

Suffix KS Optional security keyswitch for Firetec panels

BaxteCE
Rectangle

Firetec 4-wire panels

Firetec 4-wire panels | Conventionalwww.emergi-lite.co.uk

55

Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.

Display & user interfaceThe Firetec 4-wire panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:

Silence alarms or enable/disable zones

Silence buzzer

User zone and sounder isolation

Lamp test

Walk and alarm test facility

Reset function

Alarm circuits

NC C NO

Auxiliary relaycontacts

NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-

o

o

o

Enab

led

elay

Cla

ssch

ang

e

Mo

nin

pu

t

TTL

fau

lt

GN

D

C - Classchange switch

End of line resistor10K, on last

sounder

Enable alarmdelay switch

+Aux-24v

Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-

Zones 2-5 wired as Z1 EOL diode to unusedzones [cathode to

zone, +ve end]

Firetec 8 zone: wiring illustration -zones & alarms

EOL diode on lastdetector [cathodeto zone +ve end]

EOLresistor –unused

alarm cct

No spurs

o

No spurs

o

Call point

Detector

Alarm device

C

Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.

The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.

BaxteCE
Rectangle

www.emergi-lite.co.uk

56

Auxiliary output 24Vdc rated 250mA protected by resettable fuse – resets when fault is removed

Auxiliary relay 2 Sets of volt-free contacts rated 30Vdc @2A – activated during a fire condition when the alarm circuits are activated

Panel controls & indicators:

Controls 5 push buttons (with coded entry access)

Indicators 27 LED indicators for fire, fault or fire and fault

Construction: Moulded polycarbonate plastic fascia and back box in cool grey

Dimensions hwd (mm) 263 x 337 x 90

Weight (Kg), without battery 2.55

Cable requirements To comply with the recommendations of BS 5839-1:2002, section 26 for cables, wiring and other interconnections

Detector & call point compatibility * Compatible with Emergi-Lite Orbis smoke and heat detectors with diode base.* Compatible with FAP6 smoke and heat detectors with diode base.

* Compatible with 220 – 680 Ohm Manual Call Points (MCP).

Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as 470 Ohm or short circuit fire detection

Class change can be programmed to illuminate ‘general fire’ led when activated.Delay of 1-10 mins to alarms activating in a fire condition – this works in congunction with

Enable delay’ input. ‘Enable delay’ can also be used as a ‘day switch/input.’

Class Change Connect CC to Gnd terminal to activate sounders

Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line deviceAlarm: Short circuit & open circuit using end of line resistor

Fault Output TTL fault output: Active (5Vdc) when no faults are present – fail safe to off

Additional options:

FTEP-BG Recessing bezel kit

Alarm Lines 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max. 2 Alarm circuits per panel each rated @ 24Vdc 1A max.

Panel total is 0.5A Panel total is 1A

Each sounder circuit protected by a resettable fuse – resets when fault is removed

Expandable to 8 circuits in groups of 4 with 4 way alarm extender board

Power supply:

Supply Fault Monitoring 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)

Supply Fault Monitoring Mains missing – battery missing – battery charger fault

Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery

Battery charger Battery charger is temperature compensated

Battery deep discharge protection Battery is deep discharge protected (cut off at approx. 10.5V)

Battery fuse protection Battery protected by resettable fuse – resets when fault is removed

Battery Standby [up to 4z, then 8z] 72 hours with 20 detectors per zone and 30 mins of0.75A alarm load

48 hours with 20 detectorsper zone and 30 mins of

1A alarm

For more details refer to technical sales for standby calculations

Firetec 4-wire panels

Conventional | Firetec 4-wire panels

PRODUCT ORDER CODE FTEP1 FTEP2 FTEP4 FTEP8

Zones of Fire Protection 1 2 4 8

Detectors per zone 25

Firetec conventional, 4-wire panel technical specification

BaxteCE
Rectangle

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

Emergi-Lite Orbis detectors

Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofiresystems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within agiven zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.

Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,complemented by operational and maintenance enhancements.

Features:

StartUp: Correct installation – a flashing red LED

Continuity link: Zone wiring can be voltagetested before commissioning

Wide-angle optics: Responsive to fires with blackor white smoke

Drift Compensation: Calibrated sensitivity levelsare maintained despite contamination

DustDefy: Dust ingress prevented while airflow isunimpeded

Transient Rejection: Abnormal readings arefiltered out to reduce false alarms

DirtAlert: A flashing yellow LED will indicatewhen the drift compensation limit has beenreached

SensAlert: A flashing yellow LED indicatesincorrect sensor operation

Fast Test: A 4 second test confirms correct detector operation

E-Z Fit slots: Remove and refit the base without dismounting the fixing screws

Detector base with diode FAPO-TDB

The standard detector base has a diode fitted beneath the connectors. Alink feature enables voltage testing of zone wiring before commissioning.

The base is a five terminal unit – positive IN, positive OUT, Negative IN &OUT, remote LED negative and functional earth (screen) wire. Two fixingcentre positions are provided at 51 and 60mm.

SPECIFICATION

Construction White moulded polycarbonate

Termination Connectors accept up to 2.5mm2 cables

Dimensions ø d (mm) 100 x 15

Weight g 60

Detector relay base FAPO-TRB

The relay base has a single pole voltage free changeover contact for use toswitch ancillary equipment. When the detector goes to alarm the relay isenergised and changes state.

Contacts rated at 30Vdc, 1A.

SPECIFICATION

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 15

Weight g 60

FAPO-TDB

FAPO-TRB

57

BaxteCE
Rectangle

www.emergi-lite.co.ukConventional | Emergi-Lite Orbis detectors

58

Optical smoke detector FAPO-OPT

The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.

Recommended for general purpose use to give early warning of fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)

Weight g 75, 135 with base

Standards EN54-7: 2000

Optical smoke and thermally FAPO-MUS

enhanced detectorThe detector uses optical and heat sensing technology in deciding when totrigger an alarm condition. The unit is designed as a smoke detector andcannot be switched from smoke to heat detection.

This detector is more sensitive to fast burning, flaming fires than theoptical model. Ideal for where heat is prevalent at an early stage inthe fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)

Weight g 80, 140 with base

Standards EN54-7: 2000

Emergi-Lite Orbis detectors

FAPO-OPT

FAPO-MUS

BaxteCE
Rectangle

59

www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

Emergi-Lite Orbis detectors

Heat detectors – FAPO-HR1, FAPO-HR2, FAPO-HR3

Fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.

Classification – maximum application temperature: HR1 = 50ºC, HR2 = 65ºC,HR3 = 80ºC

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42

Weight g 100

Standards EN54-5: 2000

STANDARD ORDER CODE DESCRIPTION

FAPO-HR1 Heat detector – Fixed upper threshold 50ºC, A2S

FAPO-HR2 Heat detector – Fixed upper threshold 65ºC, BS

FAPO-HR3 Heat detector – Fixed upper threshold 80ºC, CS

Heat detectors – FAPO-RR1, FAPO-RR2 , FAPO-RR3

Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

Readings are taken every 2 seconds, the stored values are compared againsta preset value to decide if an alarm level has been reached.

Classification – maximum application temperature: RR1= 50ºC, RR2 = 65ºC,RR3 = 80ºC

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 97 x 36 (100 x 51 inc base)

Weight g 70, 130 with base

Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION

FAPO-RR1 Heat detector -Rate of rise with fixed upper threshold 50ºC, A1R

FAPO-RR2 Heat detector -Rate of rise with fixed upper threshold 65ºC, BR

FAPO-RR3 Heat detector -Rate of rise with fixed upper threshold 80ºC, CR

FAPO-HR1

FAPO-RR1

BaxteCE
Rectangle

Conventional 4-wire detectors

www.emergi-lite.co.ukConventional | Conventional 4-wire detectors

60

Detector base with diode FAP6-STB

The standard detector base has a diode fitted beneath the connectors.

SPECIFICATION

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 15

Weight g 60

Relay base FAP6-RLB

The relay base incorporates a set of volt-free changeover contacts, whichwill latch when the detector registers an alarm.

FAP6-STB

FAP6-RLB

Conventional 4-wire detection: The FAP6 rangeIntroducing the FAP6 range of detectors, for use with the Firetec and Eurofire 4-wire panels. FAP6provides proven technology in a slim package, the concise range comprises optical and heat detectors(fixed and rate of rise temperature). In conjunction with Firetec the range is suited to small to mediumsized buildings.

FAP6 is based on series 65technology from Apollo FireDetectors Ltd

SPECIFICATION

Voltage range 9 – 33Vdc

Relay base alarm current at 24V 17mA

Modes Latching

Operating temperature -20 to +70ºC

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100, 25

Weight g 100

BaxteCE
Rectangle

61

www.emergi-lite.co.uk Conventional 4-wire detectors | Conventional

Conventional 4-wire detectors

Relay base, 12 volt FAP6-RLB12

The low voltage relay base incorporates a set of volt-free changeovercontacts that can be used for either latching or non-latching (securitysystem) purposes. To enable control of an automatic door closer,for example.

SPECIFICATION

Voltage range 9 – 15Vdc

Average quiescent current at 12V <10µA

Relay base alarm current, at 12V 20mA

Modes Latching or non-latching

Operating temperature –20 to +70ºC

Termination Connectors accept up to 2.5mm2 cables

Construction White moulded polycarbonate

Dimensions ø d (mm) 100, 25

Weight g 100

Optical smoke detector FAP6-OPT

The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.

Recommended for general purpose use to give early warning of fire.

SPECIFICATION

Voltage range 8.5 – 33Vdc

Average quiescent current at 24V 65µA

Alarm current at 12V24V

20mA40mA

Alarm indication Clear LED, red on alarm

Operating temperature -20 to +60ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 99, 150 with base

Standards EN54-7: 2000

FAP6-RLB12

FAP6-OPT

BaxteCE
Rectangle

www.emergi-lite.co.uk

62

Conventional 4-wire detectors

Conventional | Conventional 4-wire detectors

Heat detector – FAP6-RR6, FAP6-RR75, FAP6-RR90

Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

Classification – maximum application temperature: RR6= 50ºC, RR75 = 65ºC,RR90 = 80ºC

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 24V <50µA

Alarm current at 9V24V

17mA52mA

Alarm indication Red LED

Operating temperature –20 to +90ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 80, 131 with base

Standards EN54-7: 2000

STANDARD ORDER CODE DESCRIPTION

FAP6-RR6 Heat detector – Rate of rise with fixed upper threshold 50ºC, A1R

FAP6-RR75 Heat detector – Rate of rise with fixed upper threshold 65ºC, BR

FAP6-RR90 Heat detector – Rate of rise with fixed upper threshold 80ºC, CR

FAP6-RR6

Heat detector – FAP6-FT8

fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.

SPECIFICATION

Voltage range 9 – 33Vdc

Quiescent current at 24V <50µA

Alarm current at 9V24V

17mA52mA

Alarm indication Red LED

Operating temperature –20 to +90ºC

Wiring & polarity 2 wire supply, polarity sensitive

Construction White moulded polycarbonate

Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)

Weight g 80, 131 with base

Standards EN54-5: 2000

FAP6-FT8

BaxteCE
Rectangle

63

www.emergi-lite.co.uk Conventional 4-wire call points | Conventional

Conventional 4-wire call points

Call point FMC-200R

Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

Secure clip-fix front cover

A single key for test, reset and removal of cover

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Alarm indication Red LED

Operating temperature -25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP42

Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

Weight g 190

Standards EN54-11

OPTIONS

FMC-200RS Call point with re-settable plastic element

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

Weatherproof call point FMC-200RWP

Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

Secure clip-fix front cover

One key for test, reset and removal of cover

Weatherproof to IP67

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Alarm indication Red LED

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP67

Dimensions lwd (mm) 110 x 110 x 65

Weight g 290

Standards EN54-11

OPTION

FMC-200RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS

FMC-KEY Spare test key (pack of 10)

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

FMC-PC Polycarbonate cover

FMC-PCS Polycarbonate cover with security tie

RSL800 Fire call point notice sticker

SPARES FOR FMC INDOOR CALL POINTS

FMC-BBR Back box in red

FMC-BBW Back box in green

FMC-200R

FMC-200RWP

For standard and weatherproofprotective call point covers, seepage 88.

RSL800

BaxteCE
Rectangle

www.emergi-lite.co.uk

64

Conventional 4-wire call points

Conventional | Conventional 4-wire call points

Call point FMC-800R

Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

Secure clip-fix front cover

A single key for test, reset and removal of cover

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP42

Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

Weight g 190

Standards EN54-11

OPTION

FMC-800RS Call point with re-settable plastic element

Weather resistant call point FMC-800RWP

Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

Secure clip-fix front cover

One key for test, reset and removal of cover

Weatherproof to IP67

SPECIFICATION

Voltage range 24Vdc

Impedance 470R series resistor

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Construction ABS plastic in red

Ingress rating IP67

Dimensions lwd (mm) 110 x 110 x 65

Weight g 290

Standards EN54-11

OPTION

FMC-800RSWP Weatherproof call point with re-settable plastic element

ACCESSORIES FOR FMC CALL POINTS

FMC-KEY Spare test key (pack of 10)

FMC-10G Spare glass (pack of 10)

FMC-10GRS Spare re-settable element (pack of 10)

FMC-PC Polycarbonate cover

FMC-PCS Polycarbonate cover with security tie

RSL800 Fire call point notice sticker

SPARES FOR FMC INDOOR CALL POINTS

FMC-BBR Back box in red

FMC-BBW Back box in green

FMC-800R

FMC-800RWP

For standard and weatherproofprotective call point covers, seepage 88.

RSL800

BaxteCE
Rectangle
BaxteCE
Rectangle
BaxteCE
Rectangle

65

www.emergi-lite.co.uk Conventional 4-wire call points/ancillary | Conventional

Conventional 4-wirecall points/ancillary

Key-switch operated call point FMC-2KSW

A key-switch operated call point for use in secure premises where restrictedaccess is needed.

Suitable for use with 230Vac systems

SPECIFICATION

Voltage range 24Vdc

Operation 2 position keyswitch with 1 NO contact and 1 NC contact

Switch rating 10A, 24Vdc 2A, 230Vac

Operating temperature –25 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Flying lead connections

Construction ABS plastic in red

Ingress rating IP42, when fitted to a standard back box

Dimensions lwd (mm) 87 x 87 x 20

Weight g 190

Standards EN54-11

Fitting The 2KSW can be used with either a standard or a weatherresistant back box.

FMC-2KSW

Remote Indicator unit FAP6-P10

A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space. Features:

Fire detector operated text

SPECIFICATION

LED indicator Red

Termination Terminal block

IP rating IP42

Dimensions lwd (mm) 86.5 x 86.5 x 9

Weight g 38

Ceiling tile mounting box FAP-MBCT

The fixture is used to fit a detector or sounder into a false ceiling matrix.The devices can be pre-wired and tested before the ceiling is fitted. Withthe ceiling tiles in place, the MBCT assemblies can be slotted into place.

FAP6-P10

FAP-MBCT-FD

STANDARD ORDER CODE DESCRIPTION

FAP-MBCT-FD Ceiling tile mounting box for detectors

FAP-MBCT-SO Ceiling tile mounting box for sounders

o o

Remote indicator

Closed roomspace

Normaldetection:

Indicator visible

Illustration: Use of remote indicatorin conventional fire system

Corridor

Vision panel in doorSolid door

L1 in

L1 out

- RZone+

Zone -

End of linedevice

Example: Connecting a remote indicator to anFAP6 detector base (shown common across

two detectors) in a zone

L2Earth

L1 in

L1 out

L2

- R

Note: A diode is normallyfitted between L1 in & L1 out

LED-

COM-

IN+

OUT+LED-

COM-

IN+

OUT+

Connection of remote LED unitto FAPO Orbis detector

EO

L

Zone

Zone -ve

Zone +ve

Note: A diode is normallyfitted between IN+ & OUT-

Remote LEDindicator

BaxteCE
Rectangle

66

www.emergi-lite.co.uk

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

FACS Conventional 4-wire sounders,beacons and alarm bellsEmergi-Lite Safety Systems offers a range of sounderand alarm options, for use with Firetec and Eurofire4-wire panels.

The table below highlights the key features ofindividual alarms to assist with planning and selection,when preparing a fire detection and evacuationsystem.

PRODUCT CODE DESCRIPTION

FACS-5W Sounder base W 67

FACS-5TPR Sounder base cap R 67

FACS-5TPW Sounder base cap W 67

FACS-1R Sounder R 67

FACS-1RL Sounder R 67

FACS-1W Sounder W 67

FACS-1WL Sounder W 67

FACS-BBR Back box for FACS1R R 67

FACS-BBW Back box for FACS1W W 67

FACS-4R Sounder R 68

FACS-4RDB Sounder R 65 68

FACS-4W Sounder W 68

FACS-4WDB Sounder W 65 68

FACS-8R Sounder-beacon R R 68

FACS-8RDB Sounder-beacon R R 65 68

FACS-8RDB-A Sounder-beacon A R 65 68

FACS-8W Sounder-beacon R W 68

FACS-8WDB Sounder-beacon R W 65 68

FACS-BEA-R Beacon R R 69

FACS-BEA-RDB Beacon R R 65 69

FACB-624 Bell R 69

FACB-624-G Bell G 69

FAAB-624-WP Bell R 55 70

Feat

ure

s:

Bell

6in

diam

Beac

on

Soun

der

Soun

der:

room

/be

dhea

d

Soun

der

beac

on

Am

ber,

Cle

aror

Red

lens

Red.

Whi

teor

Gre

ybo

dy

Vis

ualL

ED

IPra

ting

100

dB(A

)

Inte

grat

edba

se

Acc

esso

ries

32To

nera

nge

Page

refe

renc

e

BaxteCE
Rectangle

67

www.emergi-lite.co.uk

Conventional 4-wire alarms

Conventional 4-wire alarms | Conventional

Low profile sounder FACS-5W

A low height sounder that can be used standalone with an optional coveror as a platform for a smoke/heat detector with a detector base. Features:

Four selectable tones including warble, pips and sweep

SPECIFICATION

Voltage range 8 – 35Vdc

Current draw @ 24Vdc 11mA

Sound output, at 1m (dBA) 91 (94 with cover plate)

No. of tones 4

Operating frequency 800Hz to 1Khz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear

Construction ABS plastic

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 106 x 25 (35 with cover)

Weight g 121

OPTIONS

FACS-5TPW White cover

FACS-5TPR Red cover

Room sounder FACS-1R

A room sounder, suitable for bedroom and passageway use. Features:

Low profile with a small footprint

Audio/visual version with flashing LEDs on alarm

Four selectable tones including warble, pips and sweep

SPECIFICATION

Voltage range 8 – 35Vdc

Current draw @ 24Vdc 11mA

Sound output, at 1m (dBA) 97

No. of tones 4

Volume control -50dBA

Operating frequency 800Hz to 1Khz

Operating temperature -20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (or side entry with surface box)

Construction ABS plastic

Ingress rating IP43

Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)

Weight g 103

OPTIONS

FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs

FACS-1W Room sounder, white

FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs

FACS-BBR Back box for FACS-1R

FACS-BBW Back fox for FACS-1W

FACS-5W

FACS-5TPW

FACS-1R

BaxteCE
Rectangle

www.emergi-lite.co.uk

68

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

Open area sounder FACS-4R

A multi-tone sounder for open area use, operating across a range offrequencies. Features:

Quick fit installation

32 tones, selectable by DIL switch

High, medium and low outputs can be selected to fit in with a localsound pattern requirement

Side grub screw for security locking

SPECIFICATION

Voltage range 15 – 35Vdc

Sound level Low Med Hi

Current draw @ 24Vdc <9mA <18mA <36mA

Sound output, at 1m, 1st tone (dBA) 91 106 111

No. of tones 32

Operating frequency 440 to 2900Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (DB rear or side entry [with cover plate])

Construction ABS plastic

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 84.3 (DB-101.6)

Weight g 220 (DB-250)

OPTIONS

FACS-4RDB Open area sounder, red, deep base

FACS-4W Open area sounder, white, shallow base

FACS-4WDB Open area sounder, white, deep base

Open area sounder beacon FACS-8R

A multi tone sounder-beacon, for open area use. Features:

LED cluster beacon light

32 tones, selectable by DIL switch

Enables compliance with the Disability Discrimination Act (DDA)

Side grub screw for security locking

SPECIFICATION

Voltage range 15 – 35Vdc

Sound level Low Med Hi

Current draw @ 24Vdc <14mA <20mA <41mA

Sound output, at 1m, 1st tone (dBA) 88 103 109

No. of tones 32

Operating frequency 440 to 2900Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination Terminal block

Cable entry Rear (DB rear or side entry [with cover plate])

Construction ABS plastic, with red lens

Ingress rating IP43 (DB version – IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 89.6 (DB-106.9)

Weight g 233 (DB-258)

OPTIONS

FACS-8RDB Open area sounder, red, deep base

FACS-8W Open area sounder, white, shallow base

FACS-8WDB Open area sounder, white, deep base

FACS-8RDB-A Open area sounder, red, deep base with amber cover

FACS-4R

FACS-4RDB

FACS-8R

FACS-8RDB

BaxteCE
Rectangle

69

www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional

Conventional 4-wire alarms

Alarm beacon FACS-BEA-R

A bright output flashing beacon to augment sounders, particularly in areasof higher ambient noise. LED light source with low power requirement.

SPECIFICATION

Voltage range 20 – 35Vdc

Set up Standard Low

Current draw @ 24Vdc 5mA 3mA

Light output (equiv) @24Vdc 0.7w 0.4w

Operating frequency 1Hz

Operating temperature –20 to +70ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 6 way angled terminal block

Cable entry Rear (DB - rear or side entry)

Construction ABS plastic in red

Ingress rating IP43 (DB version - IP65)

Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)

Weight g 145

OPTION

FACS-BEA-RDB Alarm beacon, deep base

FACS-BEA-R

FACS-BEA-RDB

Alarm fire bell FACB-624

A wall mountable motorised fire bell for fire alarm or class change.The gong is secured by a tamper resistant bolt.

SPECIFICATION

Voltage range 18 – 28Vdc

Current draw @ 24Vdc 25mA

Sound output, at 1m (dBA) 96

Operating temperature –10 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Cable entry Rear (or side entry with surface box)

Construction Metal gong in red

Ingress rating IP42

Dimensions ø h (mm) 150 x 54

Weight g 527

OPTION

FACB-624-G Alarm fire bell with grey gong

FACB-624

BaxteCE
Rectangle

www.emergi-lite.co.uk

70

Conventional 4-wire alarms

Conventional | Conventional 4-wire alarms

Alarm fire bell FAAB-624-WP

A wall mountable fire bell for fire alarm or class change applications.Weather resistant rating achieved with a rubber gasket.

SPECIFICATION

Voltage range 18 – 30Vdc

Current draw @ 24Vdc 30mA

Sound output, at 1m (dBA) 93 – 95

Operating temperature –10 to +55ºC

Wiring & polarity 2 wire supply, polarity sensitive

Termination 4 way terminal block

Cable entry Rear (or side entry with surface box)

Construction Metal gong in red, base in polycarbonate

Ingress rating IP55

Dimensions ø h (mm) 150 x 85

Weight g 1,100