The Emergi-Fire Sensa control panel operatingwith Apollo Alarmsense devices is an advancedand cost-effective 2-wire fire system for small tomedium-sized buildings. System flexibilityenables use in applications such as ‘dwellingsand in houses of multiple occupation’ (HMO)and distributed buildings using a proven andextensive networking capability.
In summary this is a flexible, reliable and costeffective fire detection system that is easy to installand extend.
Eurofire Sensa panelsEurofire Sensa panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.
Panels are available in 4, 8, 12 or 16 zones of firedetection cover, with powerful and flexible setup,control and display capabilities.
AlarmSense devicesAlarmSense devices (detectors, manual call points,sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair ofzone wires from the panel. A key feature is that alarmsounders can be programmed to operate as so-called‘priority’ or ‘non-priority’ devices.
The principle of priority andnon-priority responseIn a Sensa system, the nominal operating voltage is12 volts, which enables AlarmSense detectors andmanual call points (MCPs) to operate. Sounders andbeacons operate at 24 volts, so remain dormant at thisstage. When a detector or MCP is activated, the panelwill register a change and will take the zone voltageup to 24 volts, which will switch the sounders on.
A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.
AlarmSense sounder and sounder beacon bases arechangeable between ‘priority’ and ‘non-priority’ modes.
‘Non-priority’ devices are intended for use in HMOtype applications where there are a number ofindividual dwellings. The operating method isintended to help reduce the instances of unwantedalarms and give a local warning before the fullalarm/evacuation.
A sounder-beacon base (with a detector on the baseseat) when set to ‘non-priority’, will sound a local alertfor 2 minutes at that locality. People in the vicinity oroccupants in the dwelling will be the first warned of apossible fire situation or false alarm. They will have2 minutes to investigate and rectify a false alarm,
(i.e. heat or fumes from cooking). After 2 minutes, ifthe detector is still activated, the Eurofire panel willgo into a full fire situation. At any time during thealert period, if another device is activated, the systemgoes into a full fire situation.
Eurofire can be programmed to react to ‘non-priority’signals in one of two ways:
The panel sends out a ‘non-priority’ pattern to thezone, which causes only the sounder on theactivated detector to sound, or
The panel sends out a ‘non-priority’ pattern to allzones, which have been set to include ‘non-priority’ devices. This will cause any local response(LR) devices set as ‘non-priority’ to also sound –no other ‘non-priority’ devices will sound.
If another device of any type or a ‘priority/non-priority’ is activated during the alert period, thesystem goes into a full fire alarm condition.
A ‘non-priority’ alert cannot be generated if thesystem is already in a fire alarm condition.
When a heat detector is attached on a sounder orsounder beacon base, we recommend that thesounder be set as a ‘priority’ device.
www.emergi-lite.co.uk
Emergi-Fire Sensa with Alarmsense
Conventional | Emergi-Fire Sensa with Alarmsense
36
Programming non-priority detectorsfor local alarm operationThe diagram below illustrates a 2-storey block containing3 flats and an entrance lobby. A Eurofire panel controlsthe fire alarm system for all 3 flats. Manual call points aresituated in the lobby and along the corridors. Sounderdetector bases are situated throughout with a separatesounder adjacent to the fire panel.
Scenario 1 – ‘Non-priority’ detector in Flat 1activates owing to fumes from cooking
The base sounder above the detector will sound for 2minutes (alerting the occupants in flat 1).
The sounder beacon (Zone 8) next to the panelactivates, if it is programmed for local response (LR).The occupant has time to expel the smoke from thedetector vicinity.
During this period, the panel indicates ‘Zone 1 LocalAlert’, and sounds the buzzer in the control panel. Theresponsible person has time to investigate the alertand act accordingly. If any detector or MCP activatesduring the alert, the system goes into a full firesituation and sounds the alarm.
After the alert period, with fumes dispersed, the panelwill return to the quiescent state. If the detectorremains activated after the alert period, the panel willgo into a full fire alarm condition.
Scenario 2 – Non-priority detector in Flat 1 isactivated as a real fire condition
The sequence is the same as in the first scenario, untilthe 2-minute alert period is over. After the alertperiod, with a real fire, the detector remains activatedand the panel will go into a full fire alarm condition.
Scenario 3 – Detector or MCP is activated as a fire
The panel goes into a full fire situation. If a ‘non-priority’ detector is activated afterwards – the paneltreats this as a normal detector being activated in afire situation.
www.emergi-lite.co.uk
37
Emergi-Fire Sensa with Alarmsense | Conventional
CIE
Up
Up
Zn3Zn2
Zn1Zn8
Zn4
Zn5
Zn6Zn7
Zone 7
Zone 5
Zone 3Zone 2
Zone 1
# = Set as non-priority detector
#
##
Flat 2
Flat 1
Flat 3
Apartment building with a floor plan of 2 floors: Illustration ofdetector programming for local alarm operation
Floor 1
Floor 2
Zone 6
Zone 4
Key:
Manual call point
Combined sounder-detectorbase (priority set)
Combined sounder-detectorbase (non-priority set)
Sounder-beacon base
Standalone smoke alarm
Conventional | Eurofire Sensa 2-wire panels
Eurofire Sensa 2-wire panels
www.emergi-lite.co.uk
38
Eurofire Sensa 2-wire fire panels Benefits and featuresComprehensive zone coverage:Available in 4, 8, 12 or 16 zonemodels.
Zone capacity:Nominally 30 devices per zone.
Soft select:Non-latching or latching zones:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This preventslockout and allows panels to bereset more readily (the panelbeing connected to must have aspare zone and auxiliary contactswith a volt-free pair). Short circuitfire or fault for older systems.
Output wiring:2-wire configuration to the zones,giving reduced wiring cost.
Outputs:4 alarm outputs and auxiliary volt-free contacts, which areprogrammable for continuous,pulsing or delayed operation.Fault volt-free relay contacts.
Sounder delay activation:Eurofire includes a sounder ‘delay-on’ facility. This allows the user toprogramme chosen sounders orbeacons to activate at a latermoment. This is suited toapplications where it is beneficialnot to have undue panic, such asin bars or Soft Play centres.
2-wire and 4-wire systemintegration:The Eurofire system has the abilityto recognise and operate a 4-wirezone, which can potentially save onwiring when a refurbishment isundertaken. For example in a smallhotel or guesthouse where nosounders or sounder-beacons arefitted in bedrooms, a bedroom zonecan be the 2-wire format, withdetectors and alarms wired on thesame pair. Other existing 4-wirezones in the building can remain ifdesired (it will be necessary to checkfor sounder tone compatibility).
Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits, or save on fieldwiring.
Eurofire Sensa is a range of conventional (non-addressable) firedetection panels with extensive safety, technical and practicalfeatures for the installer and user. Eurofire Sensa panels aredesigned to comply with the European Standard EN54 Parts 2 and 4and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.
Panels are available in 4, 8, 12 or 16 zones of fire detection cover, withpowerful and flexible setup, control and display capabilities and areconfigured to operate with Apollo AlarmSense devices.
The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.
Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.
Eurofire Sensa 2-wire panels | Conventional
Panel DisplayThe Eurofire Sensa panel includes an easy to reference display with LCD screen allowing for up to four lines of text,with text programmable for each zone. 6 buttons are included on the front of the panel which can be used to accessthe following functions:
Lamp test, silence alarms, silence buzzer
User zone, sounder and 2-wire sounder isolation
Walk and alarm test facility with mute option
99-event history log that stores any events withtime and date stamp, for the user to scroll
Configurable system message for the user withnormal time and date displayed
The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.
Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.
Eurofire Sensa 2-wire panels
www.emergi-lite.co.uk
39
Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:
Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.
Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).
CAN network
IsolatedCAN
network
CA
NN
ETC
AR
D
CAN network
IsolatedCAN
network
CA
NN
ETC
AR
D
To nextpanel
Illustration: Network of Eurofire panels, in star format[wired to the CAN network facility]
Eurofire c-net
Eurofire c-net Eurofire c-net
Eurofire Sensa 2-wire panels
Conventional | Eurofire Sensa 2-wire panels www.emergi-lite.co.uk
40
Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points, with settings forboth ‘priority’ and non-priority’.
Eurofire 2-wirezonal layoutThe illustration belowshows a potential schemelayout for a Eurofire panel,over 5 active zones, with1 additional alarm circuit.
Additonal alarmcircuits
Auxiliary relaycontacts
NC C NO +AL2-+AL1-
Aux 1 Aux 2
+Z1- +Z2-
Cla
ssch
ang
e
TTL
fau
lt
GN
D
- 24v +
+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO
Co
mm
on
fau
lt
Pro
gi/p
Bo
mb
aler
t+AL3- +AL4-
Isolated CAN network
HI LO SCR HI LO SCRHI LO SCR HI LO SCR
CAN network
- 24v +- 12v +
Auxoutputs
Auxi/p
- +AC AC
Batt
+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-
Eurofire Sensa 2 wire: Illustration of zonal wiring
Fault 1 Fault 2
2- wire zones; 2 & 4 to 8,wired as priority or non-
priority EOL diode to unused zones [cathode to zone,+ve end]
EOLresistor inunused
alarm ccts
No spurs
EOL diode on last detector[cathode to zone +ve end]
No spurs
o
o
o o
o
Call point -2wKey:
Optical 2wdetector
Priority 2wsounder
2w Sounder, setas non-priority
Standardsounder
o
o
Z1: Priority zone
Z3: Non-priority zone
Key:
o
EOL
Call point
Optical smoke detector
Heat detector
Beamdetector set
End of line device-detector circuit
Sounder (priority)
Sounder-beacon (priority)
Zone: detection circuitwiring
Alarm circuit wiring
SEOLEnd of line device -alarm circuit
RA1
Programmablesounder circuitsfrom the panel
Zone circuits toEurofire 2wSensa panel
Kitchen
Fire exit
Fire exit
Fire exit
Apex roof
o
A1R
o o
oo
o
o
o
o
o
A1R
o
o
o
ROOFWINDOWCONTROL
o
Auxiliarycircuits
Motorisedwindowvents
EOL
EOL
EOL
EO
L
EO
L
SEOL
A1R
Detectors per zone 30 per zone, maximum
Sounders per zone [1] 30 per zone, maximum
Sounder-Beacons per zone [2] 15 per zone, maximum
Zone Sounder Current (panel total) 1.25A max (see notes 1 & 2)
Sounder current 5mA at either low (70dBA) or high (87dBA) output
Sounders per panel 250
Sounder-Beacon Current 9mA at either low (70dBA) or high (87dBA) output
Sounder-Beacons per panel 135
Inputs Class change, Bomb Alert, Programmable
Display 4 x 20 character LCD + zone fire & fault LEDs and system LEDs
Mains input voltage 230Vac +10% –6% 50Hz
Output auxiliary voltage, DC 24Vdc @ 250mA 12Vdc @ 250mA
Battery size 12V 7AH x 2 (connected in series)
Battery standby Minimum 24 hours (please contact technical sales for further information.)
Construction: Metal back box with moulded polycarbonate front panel in cool grey
Panel dimensions hwd (mm) 469 x 373 x 103
Detector & call point compatibility Sensa – Alarmsense detectors, call points and alarm devices.
Programmable features Extensive via buttons and LCD display
CAN Network Panel and repeater combinations via CAN 2.0b link
Outputs:
Alarm Lines 4
Alarm current total 1.25A- zone sounder current, see note 3
Auxiliary outputs 2 sets of volt free contacts, rated @ 2A 30Vdc
Fault outputs 2 sets of volt free contacts, rated @ 2A 30Vdc
Notes:[1] – Version 2 sounders only[2] – Using version 2 sounder-beacons only[3] – Total Panel Alarm Current is 1.25A. The total zone sounder current must be taken into account when deciding how much load is available for alarm lines
AL1 – 4For example: a maximum of 250 sounders (5mA each) or 135 sounder beacons (9mA each) can be loaded onto the system.
Warning: do not use FAP6 detectors on Alarmsense systems. Although they would appear to work initially, using them could cause severe system malfunction in the longer term. Also beaware that if used with the Sounder/Sounder Beacon Bases the non-priority function will not operate correctly.
Eurofire Repeater panel
PRODUCT ORDER CODE FEUN-RP
Connections 2-core for data from the main panel and 2-core for 24 Vdc power
Display 4 x 20 character LCD with Zone, Fire and Fault LEDs
Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)
Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)
Construction Metal back box with moulded polycarbonate front panel in cool grey
Dimensions hwd (mm) 469 x 373 x 103
Eurofire Sensa 2-wire panels | Conventional
Eurofire Sensa 2-wire panels
www.emergi-lite.co.uk
41
STANDARD ORDER CODE DESCRIPTION
FEWN-4 Eurofire 4 Zone Panel
FEWN-8 Eurofire 8 Zone Panel
FEWN-12 Eurofire 12 Zone Panel
FEWN-16 Eurofire 16 Zone Panel
OPTIONS
Suffix LD Lockable door option for Eurofire Panel
FEUN-RP Eurofire Repeater Panel
ACCESSORIES
F4ALMB 4 way Alarm Extender
F4COB Relay Unit, 4 pole
FEUN-EOL-KIT End of Line Component Kit
FEUN-NETCAN CAN Isolator Assembly
FEUR-BG Semi-recessing bezel grey
FEUN-SPARES Eurofire Spares Pack
To Order
PRODUCT ORDER CODE FEWN-4 FEWN-8 FEWN-12 FEWN-16
No. of zones 4 Zone 8 Zone 12 Zone 16 Zone
Eurofire Sensa, 2-wire panel technical specification
Conventional | Firetec Sensa 2-wire panels
Firetec Sensa 2-wire panels
www.emergi-lite.co.uk
42
Firetec Sensa 2-wire fire panels Benefits and featuresThe panel is easy to install andcomes with a wide range offeatures for the user andmaintenance engineer.
The panel enclosure is shapedwith gentle curves and clean linesto fit in with surrounding décor.
Comprehensive zone coverage:Available in 2, 4 or 8 zone models.
Zone capacity:Nominally 25 devices per zone.
Output wiring:2-wire, giving reduced wiring cost.
Standby duration:48 hours
Walk test:1 man operation
Security coded push button entry:Status can be checked via level 1.Subsequent levels are passwordprotected for the authorised userand engineer respectively
Programmability:Several features such as ‘priority –non priority setting’, ‘delays toalarms’, ‘day mode’ are availableto tailor the function of the panelto local requirements.
Details are listed in thespecification table.
Outputs:Output facilities for Alarm,Volt-free alarm and TTL Fault.
Note: Firetec Sensa 2-wire panelavailable soon. Please contactEmergi-Lite Sales Team for furtherdetails.
STANDARD DESCRIPTIONORDER CODE
FTEW2 Firetec 2 Zone Panel
FTEW4 Firetec 4 Zone Panel
FTEW8 Firetec 8 Zone Panel
Firetec Sensa is a range of conventional (non-addressable) firedetection panels offering a practical, cost effective fire safetysolution for smaller to medium sized premises. Firetec Sensa panelsare designed to comply with the European Standard EN54 Parts 2and 4 and are suitable for BS 5839-1:2002 and BS 5839-6:2004installations.
Firetec Sensa is now more versatile than ever with the ability of handlingdetection and alarm in up to 8 separate zones. Panels are available in2, 4 and 8 zones of fire cover, with flexible setup, control and displaycapabilities, and are configured to operate with ‘2-wire’ Sensa: Alarmsensedetection and alarm devices.
The 2-wire convention uses one pair of wires for the connection of Sensa-compatible devices (detectors, manual call points and alarm sounders). Thisgives the scheme designer a greater flexibility of choice, whilst retainingcompliance with the relevant standards. Benefits can be seen in havingreduced field wiring costs and time saving with ease of installation.
Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.
Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.
OPTION
Suffix KS Optional security keyswitch for Firetec panels
Firetec Sensa 2-wire panels | Conventional
Firetec Sensa 2-wire panels
www.emergi-lite.co.uk
43
Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.
Display & user interfaceThe Firetec Sensa panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:
Silence alarms or enable/disable zones
Silence buzzer
User zone and 2-wire sounder isolation
Lamp test
Walk and alarm test facility
Reset function
Alarm circuits
NC C NO
Auxiliary relaycontacts
NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-
Ena
ble
dela
y
Cla
ssch
ange
Mon
inpu
t
TT
Lfa
ult
GN
D
C - Classchange switch
End of line resistor10K, on last
sounder
Enable alarmdelay switch
+Aux-24v
Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-
Zones 2,4,5 wired butnot shown
EOL diode to unusedzones [cathode to
zone, +ve end]EOL
resistor inunused
alarm cct
No spurs
Call point
Detector Standard alarm device
C
EOL diode on lastdetector [cathodeto zone +ve end]
No spurs
o
o
o
o
Z1: Priority zoneo
o
Z3: Non-priority zone
o
Priority alarm device
Non-prioity alarm device
Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.
Conventional | Firetec Sensa 2-wire panels
Firetec Sensa 2-wire panels
www.emergi-lite.co.uk
44
Notes:
1 Total panel alarm current, is total zone alarm current + total sounder current on AL1 & AL2. Total should not exceed 1A.
2 Ensure that maximum number of sounders/sounder-beacon devices does not exceed total current allowed for zones.30 sounders on a zone = 5mA * 30 = 0.15A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on zone.16 sounder-beacons on a zone = 9mA * 16 = 0.144A. Zone supplying maximum current, no more sounders/sounder-beacons should be placed on the zone.Sounders and sounder-beacon devices can be used together on a zone but should not exceed the maximum alarm current per zone.
3 Current available for alarm lines AL1 & AL2 = 1A - Total zone alarm current being used.
Detection Circuits Compatible with Emergi-Lite Sensa sounders, manual call points, smoke and heat detectors, Emergi-Lite Sensa zonesounders & zone sounder-beacon bases, Emergi-Lite Sensa priority/non priority devices
Detectors per Zone 25 Detectors per zone
Total Alarm Current (panel total) 1A, see note 1
Maximum Alarm Current Per Zone 0.15A
Sounders Per Zone(Low70dB(A) 5mAHigh87dB(A) 5mA)
25
Sounder-Beacons Per Zone(Low70dB(A) 9mAHigh87dB(A) 9mA)
16
Alarm Lines [AL1 & AL2] 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max, panel total is 1A. Each sounder circuit protected by a resettablefuse - resets when fault is removed. Expandable to 8 circuits in groups of 4 with 4 way alarm extender board
Auxiliary Relay Contacts 2 Sets of volt-free contacts rated 30Vdc @2A - activated during a fire condition when the alarm circuits are activated
Auxiliary Output 24Vdc rated 250mA protected by resettable fuse - resets when fault is removed.
Class Change Connect CC to Gnd terminal to activate sounders.
Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line device
Alarm: Short circuit & open circuit using end of line resistor
Mains Input Voltage 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)
Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery. Temperature compensated charger. Deep discharge protected withcut off at approx. 10.5V. Protected by a resettable fuse - resets when fault is removed.
Battery Standby 48 hours. For more details refer to technical sales for standby calculations.
Supply Fault Monitoring Mains missing - battery missing - battery charger fault
Controls 5 push buttons with coded entry access
Construction Moulded polycarbonate plastic fascia and back box in cool grey
Dimensions hwd (mm) 263 x 337 x 90
Fault Output TTL fault output: Active (5Vdc) when no faults are present - fail safe to off
Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as Priority or Non Priority
Class change can be programmed to illuminate 'general fire' led when activated.Delay of 1-10 mins to alarms activating in a fire condition - this works in conjunction with
Enable delay' input. 'Enable delay' can also be used as a 'day switch/input.'
PRODUCT ORDER CODE FTEW2 FTEW4 FTEW8
No. of Zones 2 Zone 4 Zone 8 Zone
Firetec Sensa, 2-wire panel technical specification
AlarmSense devices | Conventional
AlarmSense devices
AlarmSense devices (detectors, manual call points, sounders, sounder beacons and alarm relays) aredesigned to operate normally on the same pair of zone wires from the panel. A key feature is thatalarm sounders can be programmed to operate as so-called ‘priority’ or ‘non-priority’ devices.
A ‘priority’ set device reacts as a normal sounder instandard use and sounds a full alarm. A ‘non-priority’set device will give an initial local alert prior to goinginto full alarm.
‘Non-priority’ devices are intended for use in HMO typeapplications where there are a number of individualdwellings. The operating method is intended to helpreduce the instances of unwanted alarms and give alocal warning before the full alarm/evacuation.
When a heat detector is attached on a sounder orsounder beacon base, we recommend that the sounderbe set as a ‘priority’ device.
For more information about priority/non-prioritydevices, please refer to pages 36 – 37.
Detector base FAPW2-ASB
The Sensa detector base is specific for the Sensa detector range. Electroniccircuitry is included, which monitors the presence of the detector and willsignal a fault if a device is removed.
SPECIFICATION
Quiescent current at 15V <30µA
Load shown to the zone withhead removed
47Ω for 10ms every 4 seconds
Wiring & polarity 2 wire supply, polarity insensitive
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100
Weight g 55
www.emergi-lite.co.uk
45
FAPW2-ASB
Device benefits and featuresThe table below highlights the key features of the sounder bases and sounder-beacon bases available as part of ourconventional 2-wire range.
PRODUCT CODE DESCRIPTION
FAPW2-BS24W Sounder base W
FAPW2-BSB24W Sounder base beacon C W
FAPW2-CBSW Sounder base cap W
FAPW2-CBSR Sounder base cap R
Feat
ure
s:
Beac
on
Soun
der
Am
ber,
Cle
aror
Red
lens
Red
orW
hite
body
Apo
lloA
lert
/Ev
acto
ne
Inte
grat
edba
se
Con
vent
iona
l
Acc
esso
ries
www.emergi-lite.co.uk
46
Sounder base unit FAPW2-BS24W
A compact low profile device fitted with a base seat for fitting compatiblesmoke or heat detectors. For standalone use, optional caps in red or whiteare available. The sounder has a volume control (DIL switch selection forhigh or low output) and can operate within the ‘priority/non-priority’signalling regime.
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 5mA
Sound output dBA, high volume 87
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate/ABS
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap
Conventional | AlarmSense devices
AlarmSense devices
Sounder beacon base FAPW2-BSB24W
A compact low profile device with visual and sound warning indication.The unit is fitted with an integral base seat for fitting compatible smoke orheat detectors. For standalone use, optional caps in red or white areavailable. The sounder has a volume control (DIL switch selection for highor low output) and can operate within the ‘priority/non-priority’ signallingregime.
Suited to premises where visual warning indication is needed for the hardof hearing.
Enables the user to comply with the Disability Discrimination Act (DDA).
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 12V <20µA
Sounder active current @ 24V 9mA
Sound output dBA, high volume 87
Low volume dBA 70 nominal
Operating temperature –20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Construction Polycarbonate
Dimensions ø d (mm) 115 x 40
Weight g 150
Standards EN54-3
OPTIONS
FAPW2-CBSW White cap
FAPW2-CBSR Red cap
FAPW2-BS24W
FAPW2-BSB24W
Application
Owing the level of sound these devices can produce; they are effective forlocal use. For example, in situations where there is a corridor with anumber of adjoining rooms, closed doors can reduce the sound levelsomewhat. Consequently, it is recommended that this type of soundershould be placed in both the room and the corridor.
www.emergi-lite.co.uk
47
AlarmSense devices | Conventional
AlarmSense devices
Optical smoke detector FAPW2-OP
The optical detector measures the level of smoke particles using lightscatter, then going to alarm at a pre-set threshold.
Integrating optical smoke detector FAPW2-OP-INT
This detector is available for spaces in buildings where smoke particles(cigarette smoke for example) might be present normally, to help avoidfalse alarms.
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V10.5 – 15V
<1.5mA25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-7: 2000
Rate of rise device, grade A1R FAPW2-R6
The detector monitors the rate of temperature rise in the vicinity and willalso trigger when a fixed upper threshold of 50°C is reached.
Fixed temperature detector, grade CS FAPW2-F84
The static heat detector will signify fire, when a preset temperature isreached. The CS device will trigger at 80°C.
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 12V24V
<1.5mA25 +/- 2mA
Grades A1R & CS
Wiring & polarity 2 wire supply, polarity insensitive
Construction Polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000
FAPW2-OP
FAPW2-R6
FAPW2-F84
Surface mount unit FMFW2-800
The Sensa call point is fitted with frangible element. A key test facility issituated underside, which is fully reset when the key is removed. The deviceis detected as an operated call point by the Sensa system.
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 15V <50µA
Alarm current at 2 – 8.5V10.5 – 15V
<1.5mA25 +/- 2mA
Wiring & polarity 2 wire supply, polarity insensitive
Reset time 1 second
LED indicator Red
Construction Polycarbonate/ABS
Dimensions ø d (mm) 87 x 87 x 52
Weight g 170
Standards EN54-11: 2000
ACCESSORY
RSL800 Fire call point notice sticker
Conventional | AlarmSense devices
AlarmSense devices
www.emergi-lite.co.uk
48
FMFW2-800
Protective covers for manual call pointsA tough protective cover is available to help prevent accidental operationof call points, or prevent unauthorised use by those with malicious intent.The cover is suitable for use in educational buildings, hospitals, nursinghomes or places where the threat of false alarm is prevalent.
STANDARD ORDER CODE DESCRIPTION
FMC-ST30 Surface mount protective cover, with 30mm spacer
FMC-ST50WP Surface mount weatherproof cover, with 50mm spacer
For further options, please contact technical sales.
FMC-ST30
FMC-ST50WP
RSL800
AlarmSense devices | Conventional
AlarmSense devices
Standard remote indicator unit FAP6-P10
(standard base)A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space.
Remote indicator unit FMFW2-PBD20
(sounder base or sounder beacon base)The PBD version is designed to show indication from a detector fitted to asounder base or sounder beacon base in premises such as an HMO.
SPECIFICATION
LED indicator Red
Construction Polycarbonate/ABS
Termination Terminal block
Dimensions ø d (mm) 85 x 85 x 5
Weight g 38.2
Alarm relay FAPW2-ALR
This ancillary unit allows external items, including paging devices andmagnetic door closers to be connected to the 2-wire fire detection system.The relay can be configured to provide two sets of volt-free contacts foruse by external devices.
Selectable DIL switch features:
A relay-reset delay of 2 seconds is selectable by DIL switch.
Non-priority signals from the fire panel can be recognised at the relayaccording to a DIL switch setting, which could enable the relay to beused as a stand-alone alarm indicator or activate an external functionlike a staff alarm.
SPECIFICATION
Voltage range 9 – 33Vdc
Relay operating voltage >18V
Quiescent current at 12V <20µA
Surge current at relay set voltage 15mA for 20ms
Relay contact ratings 1A at 30Vdc
Wiring & polarity 2 wire supply, polarity sensitive
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 65 x 45 x 25
Weight g 35
Standards EN54
Commissioning note: At commissioning the relay should be reset prior touse. During operation the relay will reset if there is a power loss on the firealarm circuit.
www.emergi-lite.co.uk
49
FAP6-P10
FAPW2-ALR
o o
Remote indicator
Closed roomspace
Normaldetection:
Indicator visible
Corridor
Vision panel in doorSolid door
-ve+
ve-R
Zone
Zone
Zone inZone out
L1 zone +ve
L2 zone -ve
Rem
oteLE
Dboard
R5
Connection of remote LED unit to Sensasounder or sounder-beacon bases
Eurofire 4-wire panels
Conventional | Eurofire 4-wire panels www.emergi-lite.co.uk
50
Eurofire 4-wire fire panels
Traditionally, conventional fire systems have been wired as ‘4-wire’installations, where the detection and alarm devices are wiredseparately from the panel. This does give some integral protectionwhere the alarm circuit would not be affected by a fault on thedetection side.
Eurofire EN54 is a conventional (non-addressable) fire detection systemwith enhanced safety, technical and practical features for the installer anduser. Eurofire EN54 panels are designed to comply with the EuropeanStandard EN54 Parts 2 and 4 and are suitable for BS 5839-1:2002 andBS 5839-6:2004 installations.
Panels are configured to operate with ‘4-wire’ detection and alarm devicesand are available as a standalone panel for 4, 8, 12 or 16 zones of firecover, ideal for medium sized premises. Alternatively, for larger installationsEurofire can be networked with sister Eurofire panels and repeaters forcomplete cover over the site.
Panels are supplied as a complete package, with all end of line devices,batteries and a logbook included.
Benefits and featuresThe panel has an extensive arrayof useful tools and featuresdesigned to help both the installerto set up the system easily and theuser to manage the systemeffectively.
Standby duration:48 hours
Zone capacity:Up to 30 devices per zone.
Soft select:Non-latching or latching on fire:The non-latching zone featureallows a better integrityconnection to existing systems(other manufacture). This methodwill monitor the interconnectionbetween panels and allow panelsto be reset more readily (thepanel being connected to, musthave a spare zone and alarm lineor auxiliary contacts with avolt-free pair). Short circuit fire orfault for older systems.
Security control:Coded push button entry:The status viewer has quick entry atlevel 1. Levels 2 and 3 are passwordprotected for the authorised userand Engineer respectively.
Outputs:4 Programmable Alarm outputs.Fire auxiliary volt-free relaycontacts, which are programmablefor continuous, pulsing anddelayed operation. Fault volt-freerelay contacts.
Output wiring:Conventional 4-wire to the zones.
2-wire zone selection:In instances, where it is desired torun a zone of 2-wire devices, thepanel can be programmed toachieve this by a trainedcommissioning engineer.
Sounder delay activation:A sounder ‘delay-on’ facilityallows the user to programmechosen sounders or beacons toactivate at a later moment. Idealwhere it is beneficial not to haveundue panic, such as in bars orSoft Play centres.
Networking capability:Coverage in larger buildingcomplexes can be achieved bylinking Eurofire EN54 panels andrepeaters together via a ‘CANConnect’ link. It is also possible tomake more power available forsounder circuits or save on fieldwiring.
Eurofire 4-wire panels
Eurofire 4-wire panels | Conventionalwww.emergi-lite.co.uk
51
Panel DisplayThe Eurofire panel includes an easy to reference display with LCD screen allowing for up to four lines of text, withtext programmable for each zone. 6 buttons are included on the front of the panel which can be used to access thefollowing functions:
Lamp test, silence alarms, silence buzzer
User zone and sounder isolation
Walk and alarm test facility with mute option
99-event history log that stores any events withtime and date stamp, for the user to scroll
Configurable system message for the user withnormal time and date displayed
The panel also features indicator LEDs which advisethe current state of the fire detection system, and givea clear signal of fire or fault in any particular zone.
Further functionality includes the facility to reviewevent logs, to override any pre-set alarm delays, andto enable sounding the evacuation to all zones.
Networking capabilityFire detection coverage in a larger building complex can be achieved by linking Eurofire EN54 panels and repeaterstogether via a ‘CAN Connect’ link. (‘CAN Connect’ is a readily available communications protocol.) It is also possibleto make more power available for sounder circuits (additional 4), or save on field wiring:
Indicator detailsThe panel includes indicators for information, fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.
Scenario: In abuilding, one panelmight be sited in theoffice area and onein the warehousearea. The zones foreach area are wiredto their respectivepanels. Network thepanels and theoffice unit has fullvisibility of thebuilding. It may benecessary to use ahigher rated cableand the Emergi-Litenetwork card (pleasecontact Technicalsales for furtherguidance).
A1 R
c s
o
o
oo
o EO
L
o
EO
L
o
o
EOL
SEOL
SEOL
Network
Zone 8
Eurofire c-net
Zone 1
Zone 7
Zone 2
Illustration: 8 zone Eurofirewith network panel connected
4 sounder circuits, 2shown connected
EO
L
www.emergi-lite.co.uk
52
Eurofire 4-wire panels
Conventional | Eurofire 4-wire panels
Connection diagramThe diagram below illustrates a Eurofire panel connected to detectors, sounders, and call points.
Eurofire 4-wire zonal layoutThe illustration below shows a potential scheme layout for a Eurofire panel, over 5 active zones, with 4 alarm circuits.
Alarm circuits
Auxiliary relaycontacts
NC C NO +AL2-+AL1-
Aux 1 Aux 2
+Z1- +Z2-
Cla
ssch
ang
e
TTL
fau
lt
GN
D
- 24v +
+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-NC C NONC C NO NC C NO
Co
mm
on
fau
lt
Pro
gi/p
Bo
mb
aler
t+AL3- +AL4-
Isolated CAN network
HI LO SCR HI LO SCRHI LO SCR HI LO SCR
CAN network
- 24v +- 12v +
Auxoutputs
Auxi/p
- +AC AC
Batt
+Z10-+Z9- +Z11- +Z12- +Z13- +Z14- +Z15- +Z16-
o
o
o
Fault 1 Fault 2
Zones 2-8 wired as Z1
EOL diode to unusedzones [cathode to
zone, +ve end]
EOLresistor in
unusedalarm ccts
No spurs
EOL diode on lastdetector [cathodeto zone +ve end]
o
No spurs
o
c s
o
o
o
o o
oo
o
o
o
o
o
o
o
o
EO
L
EOL
EOL
Programmablesounder circuits from
the panel
Zone circuits toEurofire 4wpanel
Illustration:Scheme layout using aEurofire panel [5 zones active,with four alarm circuits]
EOL
Kitchen
Fire exit
Fire exit
Fireexit
Apex roof
SEOL
SEO
L
SEOL
SEOL
EOL
Key:
o
c s
EOL
Call point
Opticalsmokedetector
Heat detector
Beam detector set
End of line device -detector circuit
Sounder
Sounder-beacon
Zone: detection circuitwiring
Alarm circuit wiring
SEOL End of line device -alarm circuit
53
www.emergi-lite.co.uk
PRODUCT ORDER CODE FEUN-4 FEUN-8 FEUN-12 FEUN-16
No. of zones 4 Zone 8 Zone 12 Zone 16 Zone
Detectors per zone 30 per zone maximum
No. of alarm lines 4 (expandable to 16 programmed in groups of 4, with card extenders)
Maximum alarm load Total = 1.25A. Maximum per line or circuit = 1A
Inputs Class change. Bomb Alert and Programmable input
Display 4 x 20 character LCD, plus zone fire and fault LEDs
Mains input voltage 230Vac +10%, –6% 50Hz
Output auxiliary voltage, DC 24Vdc & 12Vdc @ 250mA
Battery size 12V 7AH x 2 (connected in series)
Battery standby 24 hours minimum (please contact technical sales for further information.)
Construction: Metal back box with moulded polycarbonate front panel in cool grey
Dimensions hwd (mm) 469 x 373 x 103
Detector & call point compatibility ‘Emergi-Lite Orbis’ and FAP6 smoke and heat with diode base. Manual call points with 220-680 ohm resistor
Outputs:
Auxiliary outputs Two sets of volt-free aux. programmable contacts (rated 2A @ 30Vdc)
Fault outputs Two sets of volt-free fault contacts (rated 2A @ 30Vdc)
Additional options:
FEUN-BG Semi-recessing trim bezel finished in grey
Networking Panels networked using ‘CAN’ Network terminals. An ‘isolated CAN network driver’ is available for isolated networks.Please contact technical sales for particular need
Zone upgrade Where a user expects to expand coverage in the future a special upgradeable version can be supplied.Please specify the requirement when requesting a quotation
Eurofire Repeater panel
PRODUCT ORDER CODE FEUN-RP
Connections 2-core for data from the main panel and 2-core for 24Vdc power
Display 4 x 20 character LCD with Zone, Fire and Fault LEDs
Inputs Data and DC supply inputs from the main panel (repeater loading must be included when calculating load at the main panel)
Outputs 4 programmable alarm outputs (load to be included in main panel alarm load)
Battery size 12V 7AH x 2 (connected in series)
Construction Metal back box with moulded polycarbonate front panel in cool qrey
Dimensions hwd (mm) 469 x 373 x 103
Eurofire 4-wire panels
Eurofire 4-wire panels | Conventional
STANDARD ORDER CODE DESCRIPTION
FEUN-4 Eurofire 4 Zone Panel
FEUN-8 Eurofire 8 Zone Panel
FEUN-12 Eurofire 12 Zone Panel
FEUN-16 Eurofire 16 Zone Panel
OPTIONS
Suffix LD Lockable door option for Eurofire Panels
FEUN-RP Eurofire Repeater Panel
ACCESSORIES
F4ALMB 4 way Alarm Extender
F4COB Relay Unit, 4 pole
FEUN-EOL-KIT End of Line Component Kit
FEUN-NETCAN CAN Isolator Assembly
FEUR-BG Semi-recessing bezel grey
FEUN-SPARES Eurofire Spares Pack
To Order
Eurofire conventional, 4-wire panel technical specification
Firetec 4-wire panels
Conventional | Firetec 4-wire panels
STANDARD ORDER CODE DESCRIPTION
FTEP1 Firetec 1 Zone Panel
FTEP2 Firetec 2 Zone Panel
FTEP4 Firetec 4 Zone Panel
FTEP8 Firetec 8 Zone Panel
ACCESSORIES
FTE-EOL-KIT End of Line Component Kit
FTE-BG Semi-recessing bezel grey
FTE-SPARES Firetec Spares Pack
www.emergi-lite.co.uk
54
Firetec 4-wire fire panels Benefits and featuresThe panel is easy to install and comes with a widerange of features for the user and maintenanceengineer.
The panel enclosure is shaped with gentle curves andclean lines to fit in with surrounding décor.
Comprehensive zone coverage:Available in 1, 2, 4 or 8 zone models.
Zone capacity:Nominally 25 devices per zone.
Standby duration:48 hours
Walk test:1 man operation
Display and user interface:Indicators for information, fire, fault and ‘fire & fault’
Security coded push button entry:Status can be checked via level 1. Subsequent levelsare password protected for the authorised user andengineer respectively
Programmability:A number of features are available including‘latching/unlatching zones’, ‘delays to alarmactivation’, ‘monitored input’ (which can be on or off).Programmability is detailed in the specification table.
Outputs:A set of output facilities for Alarm, Volt-free alarmand TTL fault
Traditionally, conventional fire systems havebeen wired as ‘4-wire’ installations, where thedetection and alarm devices are wiredseparately from the panel. This does give someintegral protection where the alarm circuitwould not be affected by a fault on thedetection side.
Firetec is a conventional (non-addressable) firedetection panel that is suited for fire detectioncoverage in smaller premises, such as offices andshops. The panel is configured to operate with ‘4-wire’detection and alarm devices and is available as astandalone panel for 1, 2, 4 or 8 zones of fire cover.
Firetec panels are designed to comply with theEuropean Standard EN54 Parts 2 and 4 and aresuitable for BS 5839-1:2002 and BS 5839-6:2004installations.
Panels are supplied as a complete package, with allend of line devices, batteries and a logbook included.
Secure panel operation:Key switch activation optionFor installations where it is necessary to secure the panel from interference,a key switch option is available, which enables or disables the controlbuttons on the front fascia. To order this option a suffix KS should beadded to the standard product code.
OPTION
Suffix KS Optional security keyswitch for Firetec panels
Firetec 4-wire panels
Firetec 4-wire panels | Conventionalwww.emergi-lite.co.uk
55
Connection diagramThe diagram below illustrates an 8 zone Firetec panel connected to detectors, alarms, and call points.
Display & user interfaceThe Firetec 4-wire panel includes a clear, easy toreference push button and LED display capable ofproviding the user with all the necessary informationto determine fire, fault or ‘fire and fault’ within aparticular zone. 5 buttons are included on the front ofthe panel which can be used to access the followingfunctions:
Silence alarms or enable/disable zones
Silence buzzer
User zone and sounder isolation
Lamp test
Walk and alarm test facility
Reset function
Alarm circuits
NC C NO
Auxiliary relaycontacts
NC C NO+AL2- +AL1- Aux 1 Aux 2+Z1- +Z2-
o
o
o
Enab
led
elay
Cla
ssch
ang
e
Mo
nin
pu
t
TTL
fau
lt
GN
D
C - Classchange switch
End of line resistor10K, on last
sounder
Enable alarmdelay switch
+Aux-24v
Lo Hi+Z5-+Z4-+Z3- +Z6- +Z7- +Z8-
Zones 2-5 wired as Z1 EOL diode to unusedzones [cathode to
zone, +ve end]
Firetec 8 zone: wiring illustration -zones & alarms
EOL diode on lastdetector [cathodeto zone +ve end]
EOLresistor –unused
alarm cct
No spurs
o
No spurs
o
Call point
Detector
Alarm device
C
Indicator detailsThe panel includes an LED system to indicate fault, fire and ‘fire & fault’, whereby specific panel LEDs will illuminateor flash to establish the zone affected.
The panel also features indicator LEDs which advise the current state of the fire detection system, to highlightsystem, earth, or supply faults, system disabled or test status, and alarm silenced mode.
www.emergi-lite.co.uk
56
Auxiliary output 24Vdc rated 250mA protected by resettable fuse – resets when fault is removed
Auxiliary relay 2 Sets of volt-free contacts rated 30Vdc @2A – activated during a fire condition when the alarm circuits are activated
Panel controls & indicators:
Controls 5 push buttons (with coded entry access)
Indicators 27 LED indicators for fire, fault or fire and fault
Construction: Moulded polycarbonate plastic fascia and back box in cool grey
Dimensions hwd (mm) 263 x 337 x 90
Weight (Kg), without battery 2.55
Cable requirements To comply with the recommendations of BS 5839-1:2002, section 26 for cables, wiring and other interconnections
Detector & call point compatibility * Compatible with Emergi-Lite Orbis smoke and heat detectors with diode base.* Compatible with FAP6 smoke and heat detectors with diode base.
* Compatible with 220 – 680 Ohm Manual Call Points (MCP).
Programmability Zones individually programmed as latching or unlatching fire conditionsZones individually programmed as 470 Ohm or short circuit fire detection
Class change can be programmed to illuminate ‘general fire’ led when activated.Delay of 1-10 mins to alarms activating in a fire condition – this works in congunction with
Enable delay’ input. ‘Enable delay’ can also be used as a ‘day switch/input.’
Class Change Connect CC to Gnd terminal to activate sounders
Fault Monitoring Zone: Short circuit & open circuit/detector removed monitoring using end of line deviceAlarm: Short circuit & open circuit using end of line resistor
Fault Output TTL fault output: Active (5Vdc) when no faults are present – fail safe to off
Additional options:
FTEP-BG Recessing bezel kit
Alarm Lines 2 Alarm circuits per panel each rated @ 24Vdc 0.5A max. 2 Alarm circuits per panel each rated @ 24Vdc 1A max.
Panel total is 0.5A Panel total is 1A
Each sounder circuit protected by a resettable fuse – resets when fault is removed
Expandable to 8 circuits in groups of 4 with 4 way alarm extender board
Power supply:
Supply Fault Monitoring 230Vac +10% -6%, 50Hz (mains fuse: 20mm, 240Vac 1A High rupture capacity)
Supply Fault Monitoring Mains missing – battery missing – battery charger fault
Battery 1 x 12V 7AH VRLA (valve regulated lead acid) battery
Battery charger Battery charger is temperature compensated
Battery deep discharge protection Battery is deep discharge protected (cut off at approx. 10.5V)
Battery fuse protection Battery protected by resettable fuse – resets when fault is removed
Battery Standby [up to 4z, then 8z] 72 hours with 20 detectors per zone and 30 mins of0.75A alarm load
48 hours with 20 detectorsper zone and 30 mins of
1A alarm
For more details refer to technical sales for standby calculations
Firetec 4-wire panels
Conventional | Firetec 4-wire panels
PRODUCT ORDER CODE FTEP1 FTEP2 FTEP4 FTEP8
Zones of Fire Protection 1 2 4 8
Detectors per zone 25
Firetec conventional, 4-wire panel technical specification
www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional
Emergi-Lite Orbis detectors
Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofiresystems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within agiven zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.
Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,complemented by operational and maintenance enhancements.
Features:
StartUp: Correct installation – a flashing red LED
Continuity link: Zone wiring can be voltagetested before commissioning
Wide-angle optics: Responsive to fires with blackor white smoke
Drift Compensation: Calibrated sensitivity levelsare maintained despite contamination
DustDefy: Dust ingress prevented while airflow isunimpeded
Transient Rejection: Abnormal readings arefiltered out to reduce false alarms
DirtAlert: A flashing yellow LED will indicatewhen the drift compensation limit has beenreached
SensAlert: A flashing yellow LED indicatesincorrect sensor operation
Fast Test: A 4 second test confirms correct detector operation
E-Z Fit slots: Remove and refit the base without dismounting the fixing screws
Detector base with diode FAPO-TDB
The standard detector base has a diode fitted beneath the connectors. Alink feature enables voltage testing of zone wiring before commissioning.
The base is a five terminal unit – positive IN, positive OUT, Negative IN &OUT, remote LED negative and functional earth (screen) wire. Two fixingcentre positions are provided at 51 and 60mm.
SPECIFICATION
Construction White moulded polycarbonate
Termination Connectors accept up to 2.5mm2 cables
Dimensions ø d (mm) 100 x 15
Weight g 60
Detector relay base FAPO-TRB
The relay base has a single pole voltage free changeover contact for use toswitch ancillary equipment. When the detector goes to alarm the relay isenergised and changes state.
Contacts rated at 30Vdc, 1A.
SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 15
Weight g 60
FAPO-TDB
FAPO-TRB
57
www.emergi-lite.co.ukConventional | Emergi-Lite Orbis detectors
58
Optical smoke detector FAPO-OPT
The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.
Recommended for general purpose use to give early warning of fire.
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V24V
20mA40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)
Weight g 75, 135 with base
Standards EN54-7: 2000
Optical smoke and thermally FAPO-MUS
enhanced detectorThe detector uses optical and heat sensing technology in deciding when totrigger an alarm condition. The unit is designed as a smoke detector andcannot be switched from smoke to heat detection.
This detector is more sensitive to fast burning, flaming fires than theoptical model. Ideal for where heat is prevalent at an early stage inthe fire.
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V24V
20mA40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)
Weight g 80, 140 with base
Standards EN54-7: 2000
Emergi-Lite Orbis detectors
FAPO-OPT
FAPO-MUS
59
www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional
Emergi-Lite Orbis detectors
Heat detectors – FAPO-HR1, FAPO-HR2, FAPO-HR3
Fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.
Classification – maximum application temperature: HR1 = 50ºC, HR2 = 65ºC,HR3 = 80ºC
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V24V
20mA40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42
Weight g 100
Standards EN54-5: 2000
STANDARD ORDER CODE DESCRIPTION
FAPO-HR1 Heat detector – Fixed upper threshold 50ºC, A2S
FAPO-HR2 Heat detector – Fixed upper threshold 65ºC, BS
FAPO-HR3 Heat detector – Fixed upper threshold 80ºC, CS
Heat detectors – FAPO-RR1, FAPO-RR2 , FAPO-RR3
Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.
Readings are taken every 2 seconds, the stored values are compared againsta preset value to decide if an alarm level has been reached.
Classification – maximum application temperature: RR1= 50ºC, RR2 = 65ºC,RR3 = 80ºC
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V24V
20mA40mA
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 97 x 36 (100 x 51 inc base)
Weight g 70, 130 with base
Standards EN54-7: 2000
STANDARD ORDER CODE DESCRIPTION
FAPO-RR1 Heat detector -Rate of rise with fixed upper threshold 50ºC, A1R
FAPO-RR2 Heat detector -Rate of rise with fixed upper threshold 65ºC, BR
FAPO-RR3 Heat detector -Rate of rise with fixed upper threshold 80ºC, CR
FAPO-HR1
FAPO-RR1
Conventional 4-wire detectors
www.emergi-lite.co.ukConventional | Conventional 4-wire detectors
60
Detector base with diode FAP6-STB
The standard detector base has a diode fitted beneath the connectors.
SPECIFICATION
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 15
Weight g 60
Relay base FAP6-RLB
The relay base incorporates a set of volt-free changeover contacts, whichwill latch when the detector registers an alarm.
FAP6-STB
FAP6-RLB
Conventional 4-wire detection: The FAP6 rangeIntroducing the FAP6 range of detectors, for use with the Firetec and Eurofire 4-wire panels. FAP6provides proven technology in a slim package, the concise range comprises optical and heat detectors(fixed and rate of rise temperature). In conjunction with Firetec the range is suited to small to mediumsized buildings.
FAP6 is based on series 65technology from Apollo FireDetectors Ltd
SPECIFICATION
Voltage range 9 – 33Vdc
Relay base alarm current at 24V 17mA
Modes Latching
Operating temperature -20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100, 25
Weight g 100
61
www.emergi-lite.co.uk Conventional 4-wire detectors | Conventional
Conventional 4-wire detectors
Relay base, 12 volt FAP6-RLB12
The low voltage relay base incorporates a set of volt-free changeovercontacts that can be used for either latching or non-latching (securitysystem) purposes. To enable control of an automatic door closer,for example.
SPECIFICATION
Voltage range 9 – 15Vdc
Average quiescent current at 12V <10µA
Relay base alarm current, at 12V 20mA
Modes Latching or non-latching
Operating temperature –20 to +70ºC
Termination Connectors accept up to 2.5mm2 cables
Construction White moulded polycarbonate
Dimensions ø d (mm) 100, 25
Weight g 100
Optical smoke detector FAP6-OPT
The optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.
Recommended for general purpose use to give early warning of fire.
SPECIFICATION
Voltage range 8.5 – 33Vdc
Average quiescent current at 24V 65µA
Alarm current at 12V24V
20mA40mA
Alarm indication Clear LED, red on alarm
Operating temperature -20 to +60ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 99, 150 with base
Standards EN54-7: 2000
FAP6-RLB12
FAP6-OPT
www.emergi-lite.co.uk
62
Conventional 4-wire detectors
Conventional | Conventional 4-wire detectors
Heat detector – FAP6-RR6, FAP6-RR75, FAP6-RR90
Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.
Classification – maximum application temperature: RR6= 50ºC, RR75 = 65ºC,RR90 = 80ºC
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 24V <50µA
Alarm current at 9V24V
17mA52mA
Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-7: 2000
STANDARD ORDER CODE DESCRIPTION
FAP6-RR6 Heat detector – Rate of rise with fixed upper threshold 50ºC, A1R
FAP6-RR75 Heat detector – Rate of rise with fixed upper threshold 65ºC, BR
FAP6-RR90 Heat detector – Rate of rise with fixed upper threshold 80ºC, CR
FAP6-RR6
Heat detector – FAP6-FT8
fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.
SPECIFICATION
Voltage range 9 – 33Vdc
Quiescent current at 24V <50µA
Alarm current at 9V24V
17mA52mA
Alarm indication Red LED
Operating temperature –20 to +90ºC
Wiring & polarity 2 wire supply, polarity sensitive
Construction White moulded polycarbonate
Dimensions ø d (mm) 100 x 42 (100 x 50 inc base)
Weight g 80, 131 with base
Standards EN54-5: 2000
FAP6-FT8
63
www.emergi-lite.co.uk Conventional 4-wire call points | Conventional
Conventional 4-wire call points
Call point FMC-200R
Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:
Secure clip-fix front cover
A single key for test, reset and removal of cover
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature -25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTIONS
FMC-200RS Call point with re-settable plastic element
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
Weatherproof call point FMC-200RWP
Surface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:
Secure clip-fix front cover
One key for test, reset and removal of cover
Weatherproof to IP67
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Alarm indication Red LED
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-200RSWP Weatherproof call point with re-settable plastic element
ACCESSORIES FOR FMC CALL POINTS
FMC-KEY Spare test key (pack of 10)
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
FMC-PC Polycarbonate cover
FMC-PCS Polycarbonate cover with security tie
RSL800 Fire call point notice sticker
SPARES FOR FMC INDOOR CALL POINTS
FMC-BBR Back box in red
FMC-BBW Back box in green
FMC-200R
FMC-200RWP
For standard and weatherproofprotective call point covers, seepage 88.
RSL800
www.emergi-lite.co.uk
64
Conventional 4-wire call points
Conventional | Conventional 4-wire call points
Call point FMC-800R
Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:
Secure clip-fix front cover
A single key for test, reset and removal of cover
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP42
Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)
Weight g 190
Standards EN54-11
OPTION
FMC-800RS Call point with re-settable plastic element
Weather resistant call point FMC-800RWP
Surface mounted manually operated call point, providing a switch closureto the panel when operated. Features:
Secure clip-fix front cover
One key for test, reset and removal of cover
Weatherproof to IP67
SPECIFICATION
Voltage range 24Vdc
Impedance 470R series resistor
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Construction ABS plastic in red
Ingress rating IP67
Dimensions lwd (mm) 110 x 110 x 65
Weight g 290
Standards EN54-11
OPTION
FMC-800RSWP Weatherproof call point with re-settable plastic element
ACCESSORIES FOR FMC CALL POINTS
FMC-KEY Spare test key (pack of 10)
FMC-10G Spare glass (pack of 10)
FMC-10GRS Spare re-settable element (pack of 10)
FMC-PC Polycarbonate cover
FMC-PCS Polycarbonate cover with security tie
RSL800 Fire call point notice sticker
SPARES FOR FMC INDOOR CALL POINTS
FMC-BBR Back box in red
FMC-BBW Back box in green
FMC-800R
FMC-800RWP
For standard and weatherproofprotective call point covers, seepage 88.
RSL800
65
www.emergi-lite.co.uk Conventional 4-wire call points/ancillary | Conventional
Conventional 4-wirecall points/ancillary
Key-switch operated call point FMC-2KSW
A key-switch operated call point for use in secure premises where restrictedaccess is needed.
Suitable for use with 230Vac systems
SPECIFICATION
Voltage range 24Vdc
Operation 2 position keyswitch with 1 NO contact and 1 NC contact
Switch rating 10A, 24Vdc 2A, 230Vac
Operating temperature –25 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Flying lead connections
Construction ABS plastic in red
Ingress rating IP42, when fitted to a standard back box
Dimensions lwd (mm) 87 x 87 x 20
Weight g 190
Standards EN54-11
Fitting The 2KSW can be used with either a standard or a weatherresistant back box.
FMC-2KSW
Remote Indicator unit FAP6-P10
A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space. Features:
Fire detector operated text
SPECIFICATION
LED indicator Red
Termination Terminal block
IP rating IP42
Dimensions lwd (mm) 86.5 x 86.5 x 9
Weight g 38
Ceiling tile mounting box FAP-MBCT
The fixture is used to fit a detector or sounder into a false ceiling matrix.The devices can be pre-wired and tested before the ceiling is fitted. Withthe ceiling tiles in place, the MBCT assemblies can be slotted into place.
FAP6-P10
FAP-MBCT-FD
STANDARD ORDER CODE DESCRIPTION
FAP-MBCT-FD Ceiling tile mounting box for detectors
FAP-MBCT-SO Ceiling tile mounting box for sounders
o o
Remote indicator
Closed roomspace
Normaldetection:
Indicator visible
Illustration: Use of remote indicatorin conventional fire system
Corridor
Vision panel in doorSolid door
L1 in
L1 out
- RZone+
Zone -
End of linedevice
Example: Connecting a remote indicator to anFAP6 detector base (shown common across
two detectors) in a zone
L2Earth
L1 in
L1 out
L2
- R
Note: A diode is normallyfitted between L1 in & L1 out
LED-
COM-
IN+
OUT+LED-
COM-
IN+
OUT+
Connection of remote LED unitto FAPO Orbis detector
EO
L
Zone
Zone -ve
Zone +ve
Note: A diode is normallyfitted between IN+ & OUT-
Remote LEDindicator
66
www.emergi-lite.co.uk
Conventional 4-wire alarms
Conventional | Conventional 4-wire alarms
FACS Conventional 4-wire sounders,beacons and alarm bellsEmergi-Lite Safety Systems offers a range of sounderand alarm options, for use with Firetec and Eurofire4-wire panels.
The table below highlights the key features ofindividual alarms to assist with planning and selection,when preparing a fire detection and evacuationsystem.
PRODUCT CODE DESCRIPTION
FACS-5W Sounder base W 67
FACS-5TPR Sounder base cap R 67
FACS-5TPW Sounder base cap W 67
FACS-1R Sounder R 67
FACS-1RL Sounder R 67
FACS-1W Sounder W 67
FACS-1WL Sounder W 67
FACS-BBR Back box for FACS1R R 67
FACS-BBW Back box for FACS1W W 67
FACS-4R Sounder R 68
FACS-4RDB Sounder R 65 68
FACS-4W Sounder W 68
FACS-4WDB Sounder W 65 68
FACS-8R Sounder-beacon R R 68
FACS-8RDB Sounder-beacon R R 65 68
FACS-8RDB-A Sounder-beacon A R 65 68
FACS-8W Sounder-beacon R W 68
FACS-8WDB Sounder-beacon R W 65 68
FACS-BEA-R Beacon R R 69
FACS-BEA-RDB Beacon R R 65 69
FACB-624 Bell R 69
FACB-624-G Bell G 69
FAAB-624-WP Bell R 55 70
Feat
ure
s:
Bell
6in
diam
Beac
on
Soun
der
Soun
der:
room
/be
dhea
d
Soun
der
beac
on
Am
ber,
Cle
aror
Red
lens
Red.
Whi
teor
Gre
ybo
dy
Vis
ualL
ED
IPra
ting
100
dB(A
)
Inte
grat
edba
se
Acc
esso
ries
32To
nera
nge
Page
refe
renc
e
67
www.emergi-lite.co.uk
Conventional 4-wire alarms
Conventional 4-wire alarms | Conventional
Low profile sounder FACS-5W
A low height sounder that can be used standalone with an optional coveror as a platform for a smoke/heat detector with a detector base. Features:
Four selectable tones including warble, pips and sweep
SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
Sound output, at 1m (dBA) 91 (94 with cover plate)
No. of tones 4
Operating frequency 800Hz to 1Khz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear
Construction ABS plastic
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 106 x 25 (35 with cover)
Weight g 121
OPTIONS
FACS-5TPW White cover
FACS-5TPR Red cover
Room sounder FACS-1R
A room sounder, suitable for bedroom and passageway use. Features:
Low profile with a small footprint
Audio/visual version with flashing LEDs on alarm
Four selectable tones including warble, pips and sweep
SPECIFICATION
Voltage range 8 – 35Vdc
Current draw @ 24Vdc 11mA
Sound output, at 1m (dBA) 97
No. of tones 4
Volume control -50dBA
Operating frequency 800Hz to 1Khz
Operating temperature -20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (or side entry with surface box)
Construction ABS plastic
Ingress rating IP43
Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)
Weight g 103
OPTIONS
FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs
FACS-1W Room sounder, white
FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs
FACS-BBR Back box for FACS-1R
FACS-BBW Back fox for FACS-1W
FACS-5W
FACS-5TPW
FACS-1R
www.emergi-lite.co.uk
68
Conventional 4-wire alarms
Conventional | Conventional 4-wire alarms
Open area sounder FACS-4R
A multi-tone sounder for open area use, operating across a range offrequencies. Features:
Quick fit installation
32 tones, selectable by DIL switch
High, medium and low outputs can be selected to fit in with a localsound pattern requirement
Side grub screw for security locking
SPECIFICATION
Voltage range 15 – 35Vdc
Sound level Low Med Hi
Current draw @ 24Vdc <9mA <18mA <36mA
Sound output, at 1m, 1st tone (dBA) 91 106 111
No. of tones 32
Operating frequency 440 to 2900Hz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (DB rear or side entry [with cover plate])
Construction ABS plastic
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 84.3 (DB-101.6)
Weight g 220 (DB-250)
OPTIONS
FACS-4RDB Open area sounder, red, deep base
FACS-4W Open area sounder, white, shallow base
FACS-4WDB Open area sounder, white, deep base
Open area sounder beacon FACS-8R
A multi tone sounder-beacon, for open area use. Features:
LED cluster beacon light
32 tones, selectable by DIL switch
Enables compliance with the Disability Discrimination Act (DDA)
Side grub screw for security locking
SPECIFICATION
Voltage range 15 – 35Vdc
Sound level Low Med Hi
Current draw @ 24Vdc <14mA <20mA <41mA
Sound output, at 1m, 1st tone (dBA) 88 103 109
No. of tones 32
Operating frequency 440 to 2900Hz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination Terminal block
Cable entry Rear (DB rear or side entry [with cover plate])
Construction ABS plastic, with red lens
Ingress rating IP43 (DB version – IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 89.6 (DB-106.9)
Weight g 233 (DB-258)
OPTIONS
FACS-8RDB Open area sounder, red, deep base
FACS-8W Open area sounder, white, shallow base
FACS-8WDB Open area sounder, white, deep base
FACS-8RDB-A Open area sounder, red, deep base with amber cover
FACS-4R
FACS-4RDB
FACS-8R
FACS-8RDB
69
www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional
Conventional 4-wire alarms
Alarm beacon FACS-BEA-R
A bright output flashing beacon to augment sounders, particularly in areasof higher ambient noise. LED light source with low power requirement.
SPECIFICATION
Voltage range 20 – 35Vdc
Set up Standard Low
Current draw @ 24Vdc 5mA 3mA
Light output (equiv) @24Vdc 0.7w 0.4w
Operating frequency 1Hz
Operating temperature –20 to +70ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 6 way angled terminal block
Cable entry Rear (DB - rear or side entry)
Construction ABS plastic in red
Ingress rating IP43 (DB version - IP65)
Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)
Weight g 145
OPTION
FACS-BEA-RDB Alarm beacon, deep base
FACS-BEA-R
FACS-BEA-RDB
Alarm fire bell FACB-624
A wall mountable motorised fire bell for fire alarm or class change.The gong is secured by a tamper resistant bolt.
SPECIFICATION
Voltage range 18 – 28Vdc
Current draw @ 24Vdc 25mA
Sound output, at 1m (dBA) 96
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red
Ingress rating IP42
Dimensions ø h (mm) 150 x 54
Weight g 527
OPTION
FACB-624-G Alarm fire bell with grey gong
FACB-624
www.emergi-lite.co.uk
70
Conventional 4-wire alarms
Conventional | Conventional 4-wire alarms
Alarm fire bell FAAB-624-WP
A wall mountable fire bell for fire alarm or class change applications.Weather resistant rating achieved with a rubber gasket.
SPECIFICATION
Voltage range 18 – 30Vdc
Current draw @ 24Vdc 30mA
Sound output, at 1m (dBA) 93 – 95
Operating temperature –10 to +55ºC
Wiring & polarity 2 wire supply, polarity sensitive
Termination 4 way terminal block
Cable entry Rear (or side entry with surface box)
Construction Metal gong in red, base in polycarbonate
Ingress rating IP55
Dimensions ø h (mm) 150 x 85
Weight g 1,100
FAAB-624-WP