The development of the new generation ground wire for lightning protection of overhead transmission...

26
The development of the new The development of the new generation ground wire for generation ground wire for lightning protection lightning protection of overhead transmission of overhead transmission lines lines

Transcript of The development of the new generation ground wire for lightning protection of overhead transmission...

Page 1: The development of the new generation ground wire for lightning protection of overhead transmission lines.

The development of the new generation The development of the new generation ground wire for lightning protectionground wire for lightning protection

of overhead transmissionof overhead transmission lineslines

Page 2: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Motivation of new productMotivation of new product creation creation

Market demand in production, close to lifetime to the core elements of the overhead transmission lines, both current and prospective without substantial rise in price products.

Provision of ground wires life duration not less than 40 years, guarantee period on overhead transmission lines not less than 4 years.

Provision of ground wire’s operability under the condition of its factual exploitation: operations of all spectrum of the main types of loads.

Ground wire creation,which provides an effective lightning protection of overhead transmission from maximum true power

lightning strokes

Page 3: The development of the new generation ground wire for lightning protection of overhead transmission lines.

1 1 STAGESTAGE

The estimation of the basic technical features of steel-wire The estimation of the basic technical features of steel-wire robes according to the GOST 3062-3064, which were used robes according to the GOST 3062-3064, which were used

on theon the overhead transmission lines as ground wires. overhead transmission lines as ground wires.

Methods

Weather exposure test of lightning stroke

Aging test

Estimation of consumer’s requests

Estimation of strength characteristics

Engineering Centre FGC UES,ORGRES, Production and Commercial Firm “Eletroservice”, MPEI and other organizations.

To realize all system researches, were involved:

Page 4: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Testing technique of lightning stroke • Researches were conducted on the bench tester “Current generator of lightning –

quaternary(GTM-4), which is certified by the High voltage electrical equipment test center of the State unitary enterprise (accreditation certificate № ROSS RU.0001.21MB07 - 09.06.1999 ). Certificate № 7-03-07 - 15.03.2007. Generator «GTM-4» is capable of generating 4 current components with the following parameters:

• Component А (current impulse of the first back discharge)height to 200 10 % кА ,with action integral (∫ί2dt) - 2·10620%А2·с and exposure time to 500 MKS.

• Component В (transitory amperage) with average amplitude 2 10% кА width to 5 мс and transferred charge 10 10% C.

• Component С (DC current) amplitude from 200 to 800 А width from 0,25 to1c and with transferred charge to 200 20% C.

• Component D (recharge current)with amplitude 100 10% кА, action integral 0,25·10620%А2·с and exposure time to 500 MKS.

• Description of the generator component corresponds to the IEC 60794-4-1:1999 requisitions, appendix F.

• Measure of the impulse signal were certified and tested according to the repetitive metrological testing: shunt ШРТ-1 №002 C.t. 1,5, Rш = 1,16 мОм, attack time no more than 200 ns,was checked 22.05.2007.,digital-readout oscilloscope Tektronix TDS-2012,accuracy class. 2,0, was checked 30.05.2007.

• Registration of testing results were made by digital camera (comes with a CD supplement).

Page 5: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Tests results of ground wire №1 JSC “BMK” production.

Discharge№1,charge 55C Discharge №2,charge 55C

Discharge№3,charge 55C Discharge №4,charge 70C

Discharge №5,charge70CDischarge №6,charge 70C

Page 6: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Discharge №7,charge85CDischarge№8,charge 85C

Discharge№9,charge 85CDischarge№10,charge 110C

Discharge№11,charge110C

Page 7: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Tests results of ground wire №2,JSC “Silur” production

Discharge№1,charge 55C Discharge№2,charge 55C

Discharge№3,charge 55C Discharge№4,charge 70C

Discharge№5,charge70CDischarge№6,charge70C

Page 8: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Discharge№13,charge130C

Tests results of ground wires №2, CoLtd “VolgoMetiz” production

Discharge №1,charge55C Discharge №2,charge55C

Discharge№3,charge55CDischarge №4,charge 70C

Page 9: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Discharge№11,charge 110C

Page 10: The development of the new generation ground wire for lightning protection of overhead transmission lines.

General regimes of aging tests, equipment set and run time within one cyclic process (Testing laboratory “Khotkovo-

Test”,25.05.2006.).

OutfitTests schedule The duration of samples

exposure in one cycle, h Temperature, о С Relative humidity, %

Moisture chamber 40±2 97±3 2

Sulfur dioxide gas chamber (concentration SO2 - 5±1mg/m3)

40±2 97±3 2

Heating and freeze cabinet

Minus (30±3) Not normalized 6

Artificial weather apparatus: irrigation regime 3 min, without irrigation 17 min.

60±3 Not normalized 5

Freeze chamber Minus(60±3) Not normalized 3

Exposure to air 15-30 No more than 80 6

Total 24

Page 11: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Aging tests results (Testing laboratory “Khotkovo-Test”,25.05.2006.)

Samples Number of cycles Corrosion damage area, %

Lesion,point (GOST 9.311-87)

Steel rope GOST3063, JSC «Silur» -application technique zinc covering: HD galvanizing

40 0,34 А38

50 6,3 А34

60 28 А32Steel rope GOST 3063,JSC «Volgometiz»- application technique zinc covering: galvanization

40 No lesion No corrosion attack

50 No lesion No corrosion attack

60 No lesion No corrosion attack

Page 12: The development of the new generation ground wire for lightning protection of overhead transmission lines.
Page 13: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Basic conclusions about the study of steel Basic conclusions about the study of steel ropes according toropes according to GOSTGOST 3062 -3064 3062 -3064

The increase of working time in the process of galvanization (JSC «Sevestal-metiz» technology).

The increase of lightning stroke durability in the process of the increase of preformation degree (JSC «Severstal-Metiz»technology).

Total loss of service outage in the process of cumulative effect of discharge within the range 40-85 C.

The reduction of the aggregate breaking tension after the lightning exposure of all represented steel ropes.

Page 14: The development of the new generation ground wire for lightning protection of overhead transmission lines.
Page 15: The development of the new generation ground wire for lightning protection of overhead transmission lines.

The development of ground wires for overhead The development of ground wires for overhead transmission lines according to thetransmission lines according to the STO (Standards of STO (Standards of organization)organization) 71915393– 71915393–TU (Specifications)TU (Specifications) 062–2008 062–2008

Development peculiarityNovelty design of the ground wire according to 71915393–TU (Specifications)

062–2008(ground wire)for the electric power transmission protection from direct lightning strokes consists in the lay consolidation technology, provision of line contact wires and line contact of wires provision, use of the wires outer layer of the plastic straining to enlarge contact area between outer and inner armor wires. This construction provides the reduction of linear extension (confirmation patent of the R.F.).

Galvanical method application of coating to a tolerance of +5% prevents zinc layer at increases current and elevated temperature (short circuit), (it increases service life, this product is different from the previous one).

Utilize technology of the lay has no parallel in the Russian Federation, the technology of application of zinc coating is comparable to the technique, which is used by Volgograd plant - JSC Severstal-Metiz in a process of production cable and wire bridges.

Constructive result 40 years of service life and 20 years of exploitation under the influence of all types of loads.

22 StageStage

Page 16: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Cherepovetsplant

The plant was found in 1965. It produces more than 26000 types of production.

Orel plant

The plant was found in 1967. it produces more than 11000 types of production.

Volgograd plant

The plant was found in 1954. It produces more than 1500 types of steel ropes and wires.

Producer – Severstal-Metiz (Russia)

Authorized provider and developer of the rope and wire production:

Co Ltd «Energoservice».

Page 17: The development of the new generation ground wire for lightning protection of overhead transmission lines.
Page 18: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Basic conclusions about the researches of Basic conclusions about the researches of lightning stroke. lightning stroke.

)

Charge, C (Coulomb)

Tension reduction, kgf (kilogram-force)

Result of effect

110 no Surface fusion in the discharge zone in zone in area ~ 10х15 mm

147 no Surface fusion in the discharge zone in zone in area ~ 10х15 mm

55 no Electrode touched the surface of pattern during the process of discharge

55 no Surface fusion in the discharge zone in zone in area ~ 10х10 mm

Conclusion The ground wire’s patterns are stable to lightning stroke (with

transferred charge 55C and 110C) and also have high stable to a lightning current effect (with transferred charge 147 C),which has total occurrence probability 1,2 %, in negative and positive lightning. It ought to be noted, that such a high lightning resistance of the proved ground wires is connected with it’s improved construction, which is different from the ground wire’s construction and is used today in overhead transmission lines.

There is no strength reduction after stoke.

Page 19: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Basic results of the ground wires approval tests according to STO Basic results of the ground wires approval tests according to STO (Standards of organizations) (Standards of organizations) 71915393–71915393–TU (Specifications)TU (Specifications) 062–2008 062–2008 for for

the overhead transmission lines. the overhead transmission lines.

List of testing: full testing:lightning stroke, mechanical (disruption, after the lightning stroke) eolian vibration ,an attack of wind load, and stableness to short-circuit current. New ground wire’s construction was developed especially for the protection of

overhead transmission lines from lightning strokes, it was made with the use of current rope technologies and it has following peculiarities:

• Total resistance to lightning stroke in the load range 98,8%. • High corrosion resistance at the expense of galvanic coating with +5% tolerance and

reduction of the total contact area of the ground wire’s surface with environment. • Increased breaking strength (against ropes) - (180kg/mm2 – 200kg/mm2), it provides

reliability growth, it is especially important for the anchor poles and during the glaze formation.

• Extended service life almost in 2 and 5 times is a guaranteed service, in comparison with the standard rope.

• Applied technology, in the process of production of the ground wire’s lay according to the STO (Standards of organization) 71915393–TU (Specifications) provides reduction of the extension strain, which decreases sagging in the process of exploitation.

• There is no strength reduction, no disruptions or melting wires to base metal, after lightning strokes 147 C (coulomb). .

Page 20: The development of the new generation ground wire for lightning protection of overhead transmission lines.
Page 21: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Main points of specifications to the ground wire МЗ-В-OЖ- Н-Р* STO (Standards of organization) 71915393-TU (Specifications) 062-

2008, which realization is guaranteed by plant JSC «Severstal-Metiz»Ground wires should be up to quality of the standard and STO

(Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC “FGC UES”.

•Ground wires ( marking groups 1770n/mm2 (180kgf/mm2), 1870n/mm2 (190kgf/mm2), 1970n/mm2 (200kgf/mm2)) are made from galvanized wire, according to the GOST 7372-79, gauge of zinc covering should correspond to the “ОЖ”(extra hard) group with the positive tolerance 5%.

• Ground wires are made length at least 500 meters. • Ground wire should be resistant to impulse of the lightning discharge,

which size (in Coulombs) is defined by the ground wire suspension, according to the consumer requirements and is installed by manufacturer (if it has an appendix – tensile load, according to the STO (Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC «FGC UES» , at least 85C.

•Ground wire should be resistant to the thermal influence of short circuit current,appearing in the process of the ground wire’s exploitation with single and double phase to earth fault, which size and time is installed by manufacturer according to the STO (Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC «FGC UES».

(Lightning protection – premium quality – extra hard – nonspinning – straighten)*

Page 22: The development of the new generation ground wire for lightning protection of overhead transmission lines.

•Ground wire should be resistant to the eolian vibration at least 100 million cycles, which frequency should correspond to resonating frequency with wind speed from 4 to 8 ms (Frequency = 830/diameter of the ground wire in mm ± 10 Hz),with appendix of the tension load, which is installed by manufacturer, according to the STO (Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC «FGC UES».

•Ground wire should be resistant to the pitching (eolian vibration), in the process of its exploitation and under the influence of crosscut wind flow, alternate aerodynamic lift is appeared, which can create self-sustained oscillations, with the correlation of parallel and torsion motions of rope, STO (Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC «FGC UES».

• All others technical requirements should correspond to the GOST requirements 3241-91 and STO (Standards of organization) 56947007-29.060.50.015-2008 Technical requirements JSC «FGC UES».

•In accordance with article13.2, Technical requirements JSC «FGC UES» guarantee service life of the ground wires should form at least 20 years, from the moment of commencement of operation.

Page 23: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Overhead transmission lines

Ground wires (Lightning protection),which were made in accordance with the technical requirements STO (Standards of organization) 71915393-TU (Specifications) 062-2008, are meant for the overhead transmission lines protection from lightning strokes, diameters of which from 8 to 22,5mm and resistance from 1770 n/mm2 to 1970 n/mm2, are galvanized according to the “ОЖ”(extra hard) group with a tolerance of +5%. The advantages of lightning protection (except high density and better corrosive resistance) is a heightened sturdiness to the lightning pulse influence from 85C and higher. Lightning protection (in contrast to steel ropes) survive even in the zones with heightened probability value of lightning discharges, during the guaranteed service life – 20 years.

Sole manufacturer and patent holder : JSC «Severstal-Metiz».Dealer and developer : Co Ltd «Energoservice». Sign of implementation : Lightning protection.Agency output: minimum 350 tons monthly.Standard-size spectrum: 8,0-22,5mm

Page 24: The development of the new generation ground wire for lightning protection of overhead transmission lines.

Diameter,mm

Projected area of sectional

view of all wires in lightning protection

, mm2

Estimated weigh 1000 m of oiled

lightning protection , kg

Marking group 1770 n/mm2

Marking group 1870 n/mm2

Marking group 1970 n/mm2

Actual aggregate breaking strength of all wires - g, n (not less than)

8,0 44,54 366 78400 82300 87200

9,2 59,06 490 103800 109700 115600

10,0 69,67 575 122500 129300 136200

11,0 83,59 695 147000 154800 163600

12,5 107,97 886 190100 200900 210700

13,0 118,55 974 208700 220500 232200

14 135,88 1125 239100 252800 265500

15 157,79 1295 278300 293000 308700

16 180,61 1480 318500 336100 353700

17 201,59 1660 354700 375300 394900

18,5 240,72 1980 424300 447800 471300

21 309,35 2540 544800 575200 605600

22,5 354,29 2910 624200 659500 693800

Ground wires for the overhead transmission lines and lightning strokes protection

STO (Standards of organization) 71915393 TU (Specifications) 062-2008

Construction 1 х 36 (1+ 7 + 7/7 + 14)

Page 25: The development of the new generation ground wire for lightning protection of overhead transmission lines.
Page 26: The development of the new generation ground wire for lightning protection of overhead transmission lines.

“Severstal-Metiz” and “Energoservice” express gratitude for kind attention! We are always glad to cooperate!