The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

43
The Building Science Fight Club Roars ASHRAE 62.2 vs. Building Science Corpora?on’s New Ven?la?on Standard 24 February 2014 RESNET Conference

Transcript of The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Page 1: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

The  Building  Science  Fight  Club  Roars      

ASHRAE  62.2  vs.  Building  Science  Corpora?on’s  New  Ven?la?on  Standard    

24  February  2014  RESNET  Conference  

Page 2: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

High  Performance  Homes      –  Knowledge  +  Service  

Training  

HVAC  Design  HERS  Provider  

The  Energy  Vanguard  Blog  

Page 3: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

 Posi:ve  Energy  

• Building  Science  Consul:ng  &  Training  • High  Performance  HVAC  Design    • Energy  Modeling  &  Monitoring  • Building  Performance  Tes:ng  • Program  Compliance  &  Cx  • Net  Zero  Design  • IAQ  Tes:ng  

Page 4: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

The  Bones  

•  Why  we  need  ven:la:on  •  Ven:la:on  methods  •  Ven:la:on  rates  –  62.2  –  BSC-­‐01  

•  Dr.  Joe’s  beef  with  62.2  •  Where  will  this  lead?  •  Q&A  

Page 5: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Why  We  Need  Ven:la:on  

Air:ght  enclosures  

Page 6: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Infiltra:on  Doesn’t  Cut  It     ATTIC

Insulation fibers, dust, rodent scat

CRAWLSPACE

Mold, dust, lead, radon, moisture, termiticide

OUTSIDE

Pollen, auto fumes, dust

GARAGE

Carbon monoxide, pesticides, gasoline, fertilizers

Page 7: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Bad  Stuff  in  the  Air  

Water  vapor  CO2  

VOCs  Formaldehyde  NOx  

Radon  …and  more!    

Page 8: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Pathways  

People  

Pollutants  

Connec:ons  

Page 9: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

2  Ways  to  Achieve  Good  IAQ  

Source  control  Mechanical  Ven:la:on  

Page 10: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

“Build  Tight.    Ven:late  Right.”  

Page 11: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

3  Types  of  People  

1.  Those  who  can  do  math  

2.  and  those  who  can’t.  

Page 12: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

3  Types  of  Ven:la:on  

1.  Whole  house  2.  Local  3.  Buffer  space  

Page 13: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Posi:ve  Pressure  

Page 14: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Posi:ve  Pressure  

Page 15: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Central  Fan  Integrated  Supply  (CFIS)  

Image  courtesy  of  Building  Science  Corpora?on  

Page 16: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Neutral  Pressure  

Page 17: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Neutral  Pressure  

•  HRV  •  ERV  •  Balanced  

without  recovery  

Page 18: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Nega:ve  Pressure  

Page 19: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Whole  House  Ven:la:on  

Exhaust-­‐only  

Page 20: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Local  Ven:la:on  

•  Bathrooms  •  Kitchens  

Page 21: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Buffer  Space  Ven:la:on  

•  Radon  •  Crawl  space  •  Garage  •  Acc  

Page 22: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

How  Much  to  Ven:late?  

•  ASHRAE  62-­‐1989?  •  ASHRAE  62.2-­‐2010?  •  ASHRAE  62.2-­‐2013?  •  BSC-­‐01?  •  Something  else?  

Whole-­‐House  Ven?la?on  

Page 23: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

62.2  Ven:la:on  Rates  

62.2-­‐2010    Qv  =  0.01  Afloor  +  7.5  (Nbr  +  1)    62.2-­‐2013    Qv  =  0.03  Afloor  +  7.5  (Nbr  +  1)  

   Afloor  =  cond.  floor  area,    Nbr  =  #  of  bedrooms  

Page 24: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

“ASHRAE  62  is  the  only  na?onal  consensus  standard  document  there  is.  Follow  62.2.  Resistance  is  fu?le.”    

 ~  Dr.  Max  Sherman  

Page 25: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

“Game  on.”    

 ~  Dr.  Joseph  Ls?burek  

Page 26: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

BSC-­‐01  Ven:la:on  Rates  

BSC-­‐01    Qv  =  0.01  Afloor  +  7.5  (Nbr  +  1)      

Afloor  =  cond.  floor  area,    Nbr  =  #  of  bedrooms    But  wait…there’s  more!  

Page 27: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

BSC-­‐01  Ven:la:on  Rates  

Page 28: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Real  Numbers  

•  2000  sf,  3  bedroom  house  •  3  BR  è  4  people  

Method   Rate  (cfm)  62.2-­‐2010   50    62.2-­‐2013   90  BSC-­‐01   50,  63,  or  75  (w/o  mixing)  

38,  47,  or  56  (w/  mixing)  

Page 29: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Why  Dr.  Joe  Went  Rogue  

•  Comfort  •  Humidity  •  Energy  consump:on  •  System  effec:veness  •  Lack  of  data  on  health  impacts  

Page 30: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Ven:la:on  Effec:veness  Study  •  Rudd  &  Bergey,  Building  America  study,  BA-­‐1309,  March  2013  

•  2  iden:cal  houses  in  Tyler,  Texas  •  Slab,  aoached  garage  •  1  with  sealed  acc,  1  vented  acc  •  Tracer  gas,  par:culates,  VOCs  

Page 31: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Ven:la:on  Effec:veness  Study  

•  CFIS  had  47%  lower  VOC  level  than  EO  •  ERV  had  57%  lower  VOC  level  than  EO  •  EO  had  37%  higher  VOC  level  than  baseline  for  vented  acc  home  

•  EO  had  18%  higher  VOC  level  than  baseline  for  sealed  acc  home  

•  EO  drew  34%  of  ven:la:on  air  from  vented  acc    

Page 32: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Ven:la:on  Effec:veness  

Page 33: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Where  Do  These  Rates  Come  From?  

•  Odor  control  –  15  cfm/person,  C.P.  Yaglou  research,  1936  

•  0.35  ACH  for  residen:al  since  62-­‐89  –  ‘expert  judgment,’  not  health  data  

•  Long  history,  mostly  commercial  and  ins:tu:onal  

 

Page 34: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

What  Level  of  Pollutants  Is  Safe?  

•  Who’s  living  in  the  house?  •  Which  pollutant?  •  Where  in  the  house?  •  We  don’t  really  know  

Page 35: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Related  Ques:ons  

•  What  sources  of  indoor  pollutants  does  the  house  have?  – Aoached  garage?  – Moldy  crawl  space?  – Household  chemicals?  

•  How  bad  is  the  outdoor  air?  –  Including  underground  

Page 36: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

“If  there  is  a  pile  of  manure  in  a  space,  do  not  try  to  remove  the  odor  by  ven?la?on.  Remove  the  

pile  of  manure.”    

 ~  Max  von  PeVenkofer,  1858    

Page 37: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Source  Control  

•  Best  to  prevent  pollutants  from  gecng  into  air  

•  Ven:la:on  doesn’t  always  work  

Page 38: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Formaldehyde  and  Ven:la:on  Rates  

Offerman  study,  2009  -­‐  Ven?la?on  and  Indoor  Air  Quality  in  New  Homes    

Page 39: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

A  Lesson  in  Source  Strengths  

•  Formaldehyde  emission  from  materials  increases  when  you  ven:late  more.  

•  Materials  that  emit  formaldehyde  at  lower  levels  result  in  less  formaldehyde  in  home’s  air.  

Page 40: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

What  Should  Happen  Next?  

•  62.2  commioee  needs  to  address  the  issues  Joe  raised  –  System  effec:veness  –  Humidity  –  Source  control  –  Science  behind  ven:la:on  rates  

•  Make  the  standard  simpler!  •  Add  design  flexibility  

Thanks  to  Eric  Werling  for  making  these  great  sugges?ons  first!  

Page 41: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

“On  a  long  enough  ?meline,  the  survival  rate  for  everyone  drops  to  zero.”    

 ~  Fight  Club  narrator  

Page 42: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Other  Ven:la:on  Talks  Ven?la?on:  Effec?ve  Strategies  &  Lessons  Learned  

Tue,  10:30.  Doug  McCleery,  MaGrann  Associates  IAQ,  Ven?la?on,  and  Air?ghtness  in  High  Performance  New  and  Exis?ng  Homes  

 Tue,  3:30.  Brennan  Less  &  Iain  Walker,  Lawrence  Berkeley  Na:onal  Laboratory  

The  “V”  in  HVAC:  Mechanical  Ven?la?on  in  ENERGY  STAR  Cer?fied  Homes  

Wed,  8:30.  Dean  Gamble,  U.S.  EPA;  Ashley  Fowler,  ICF  Interna:onal  

Page 43: The Building Science Fight Club Roars – ASHRAE 62.2 vs. Building ...

Contact  Info  

Allison  Bailes        Energy  Vanguard  Decatur,  GA  [email protected]  energyvanguard.com  

Kristof  Irwin        Posi:ve  Energy  Aus:n,  TX  kristof@posi:veenergy.pro  posi:veenergy.pro