The Association for Specialist Fire Protection - ASFP & Wear Seminar 2013/6. PW Ducts.pdf · Fire...
Transcript of The Association for Specialist Fire Protection - ASFP & Wear Seminar 2013/6. PW Ducts.pdf · Fire...
Fire ducts and Dampers
Paul White
Managing Director
Advanced Smoke Group Ltd
The Association for Specialist Fire Protection
Pioneering fire protection through innovation and professionalism
Fire Dampers
Smoke Control Dampers
Fire Resisting Ductwork
Smoke Control Ductwork
January 2014
Paul White
Everyone knows what this is…
DUCTS PENETRATING COMPARTMENT WALLS 3
FIRE DOORS
Most people see one every day
DUCTS PENETRATING COMPARTMENT WALLS 4
STANDARD
DUCTWORK
But look up or go above the false ceiling
And you should find ordinary DW144 steel ductwork for ventilation air which will often pass
through the partition above doors, but will also go through at other points too..
And you should find things that are less well known
DUCTS PENETRATING COMPARTMENT WALLS 5
FIRE
DAMPERS
Where normal ventilation ductwork passes through compartment boundaries, the penetration and
compartment must be protected by a fire damper. It is a common misconception that fire dampers protect
ductwork, what they actually do is maintain the compartmentation which is why they must be installed
correctly
An alternative is
DUCTS PENETRATING COMPARTMENT WALLS 6
FIRE
RESISTING
DUCTWORK
In some instances fire resisting ductwork may be installed. This is also designed and tested to
maintain compartmentation, and consequently must be constructed and installed correctly at the
compartment wall
Installation
DUCTS PENETRATING COMPARTMENT WALLS 7
INSTALLATION
With installations it is often what is not seen that is important and must be got right during installation, support at the wall is critical for both dampers
and ducts, otherwise they might collapse at the wall and lose integrity
Penetration seals only tested with pipes and cables are not proven for use with dampers and ducts, unless they have been tested with dampers and ducts, so duct nand damper manufacturers cannot support this type
of installation unless thay have done specific testing. This situation is often overlooked on site, but may peove an issue if found after the event.
Test information
Fire dampers Fire dampers should be tested to BSEN1366-2.
Escape routes and areas with sleeping risk should be protected with ES
classified motorised fire dampers that respond to smoke alarms
Curtain fire dampers only have an E classification
Dampers tested ad hoc to BS 476 will be acceptable in older installations
but not really in new ones.
The Construction Products Regulation (CPR) now requires that fire
dampers are CE marked and installed in line with manufacturers'
instructions, which is generally as they have been tested.
CE marking is to EN15650 and requires testing to BS EN 1366-2 and third
party certification
DUCTS PENETRATING COMPARTMENT WALLS 8
TEST
INFORMATION
Test information
Fire resisting ducts Fire resisting ducts should be tested to BSEN1366-1 or BS476-24.
The latter is still allowed until such products have a standard published
that requires CE marking. The standard is well under way, but it is not
clear exactly when it will be published.
DUCTS PENETRATING COMPARTMENT WALLS 9
TEST
INFORMATION
Test information
Smoke control ducts Smoke control ducts should be tested to BSEN1366-8 for fire resistance for
multi compartment installations
Smoke control ducts should be tested to BSEN1366-9 for 600°C
performance (and below) for single compartment installations
CE marking is generally required under the requirements of BS EN12101-7
DUCTS PENETRATING COMPARTMENT WALLS 10
TEST
INFORMATION
Test information
Smoke control dampers Smoke control dampers should be tested to BSEN1366-10 for fire
resistance for multi compartment installations and 600°C performance (and
below) for single compartment installations
CE marking is generally required under the requirements of BS EN12101-8
They can be employed in smoke control ducts and in fire resisting ducts
and there are other applications where such dampers are required to be
open on a fire floor to allow smoke to be exhausted and closed in other
areas
DUCTS PENETRATING COMPARTMENT WALLS 11
TEST
INFORMATION
Regulatory Guidance
Approved Document B (ADB) – gives guidance to the building regulations
BS9999 – additional guidance referred to in ADB
HTM05-02 – additional information for hospitals
BB100 – additional information for schools and colleges
Regulatory Reform (Fire safety) Order (RRFSO) – requirements for fire safety in the running of buildings requiring information on how all the above are met, where items are installed and how they are to be maintained
Building Regulation 38 – requires that all information with regard to fire protection measures is passed over at handover.
DUCTS PENETRATING COMPARTMENT WALLS 12
REGULATORY
REFERENCES
Additional Guidance
ASFP Grey Book – Fire dampers
ASFP Blue Book – Fire Resisting and Smoke Control Ductwork
DW/144 – Sheet metal ductwork
DW/145 – Fire damper installations
HTM05-02 – additional information for hospitals
DUCTS PENETRATING COMPARTMENT WALLS 13
ADDITIONAL
GUIDANCE
REFERENCES
Maintenance
Maintenance regime Does this exist for any fire dampers, fire resisting ducts, smoke control ductwork and smoke control dampers?
Is the responsible person aware of this requirement?
Do adequate records of testing and inspection exist?
Do the records note any and all remedial action to the fire dampers and ducts (etc.) and to the seal between them and the supporting constructions
Refer to Annex V and Annex W of BS9999
DUCTS PENETRATING COMPARTMENT WALLS 14
MAINTENANCE
WRONG
DUCTS PENETRATING COMPARTMENT WALLS 15
WRONG
-1-
The damper is not in the plane of the wall and the duct is not protected. Has the damper been tested in association with batt? If fire resisting, is the
duct supported around its outside at its joint with the wall
WRONG
DUCTS PENETRATING COMPARTMENT WALLS 16
WRONG
-2-
The dampers are not in the plane of the wall, the duct is not protected and it is unlikely that the dampers have been tested passing through a
hole in a steel beam
WRONG
DUCTS PENETRATING COMPARTMENT WALLS 17
WRONG
-3-
!
RIGHT
DUCTS PENETRATING COMPARTMENT WALLS 18
RIGHT
-1-
The damper is within the plane of the wall, the installation is complete and without any damage to the seal around the damper.
Note: However, it needs to be checked that damper has been tested in a batt installation, especially for ES requirements
THANK YOU FOR LISTENING
Fire Dampers
Smoke Control Dampers
Fire Resisting Ductwork
Smoke Control Ductwork
January 2014 Paul White