Approved Discharge DevicesFor Use With AnsulFoam Concentrates
Technical Serv ices : Tel: (800) 381-9312 / Fax: (800) 791-5500
Page of 6 AUGUST, 2007 TFP2005
GeneralDescription
Foam liquid concentrates are suitableor use on fres involving ordinary hy-drocarbon petroleum products, and
some oam liquid concentrates mayalso be suitable or use on fres involv-ing polar solvent uels. The fre pro-tection system designer frst identifesthe uel load and selects the oam liq-uid concentrate according to its abilityto be used or a given uel load. Uponselecting the oam liquid concentrate,the designer then selects equipment,including discharge devices, basedon listing/approval compatibility o theequipment with the concentrate.
Discharge devices all into one o ourcategories:
Foam-Water Sprinklers
Foam-Water Spray Nozzles
Non-Aspirating Spray Nozzles
Standard Sprinklers
TFBP (Tyco Fire and Building Prod-ucts) provides a number o standardspray sprinklers and oam-water sprin-klers that can be used with oam liq-uid concentrates. The data provided inthis technical data sheet is intended toprovide compatibility inormation withthe ollowing Aqueous Film FormingFoams (AFFF) manuactured by Ansul:
Ansulite 1% AFFF (1609-95CG)
Ansulite 3x3 Low Viscosity
(3%) AR-AFFF Ansulite 3% AFFF (AFC-3A)
WARNINGSThe TFBP Sprinklers reerenced here-
in must be installed and maintainedin compliance with this document, aswell as with the applicable standardso the National Fire Protection Asso-ciation, in addition to the standards o
any other authorities having jurisdic-tion.Fair d s ma impair hprfrman f hs prds.
The owner is responsible or maintain-ing their fre protection system and de-vices in proper operating condition.The installing contractor or sprinkler
manuacturer should be contactedwith any questions.
Technical DataApprovalsUL Listed and FM Approved. Reer toTables 1, 2, and 3, as applicable.
Minimum Application RateThe Minimum Application Rate is aunction o oam liquid concentrate,uel load, and approval agency. Reerto Tables 1, 2, and 3, as applicable.
Minimum Inlet PressureThe Minimum Inlet Pressure is theminimum starting pressure or the dis-charge device or purposes o pro-ducing oam. Reer to Tables 1, 2, and3, as applicable. The Minimum InletPressure may need to be increased tomeet the Minimum Application Rate asa unction o sprinkler spacing. For ex-ample a Minimum Inlet Pressure o 7psi or a discharge K-actor o 5.6 pro-
duces 14.8 GPM. Assuming a sprinklerspacing o 10 t. x 10 t. (100 t2.), thetheoretical application rate would thenbe 0.148 GPM/t2. However, i the re-quired Minimum Application rate is0.16 GPM/t2, The Minimum Inlet Pres-sure would need to be increased to8.2 psi. or the sprinkler spacing wouldneed to be decreased to a maximum o92 t2. In all cases the Minimum Appli-cation Rate requirements override theMinimum Inlet Pressure requirements.
-
8/2/2019 TFP2005_08_2007
2/6
ANSULITE1% AFFF (1609-95CG)
Fuel
Minimum(1)Application Rate
GPM/Sq Ft(mm/min)
Minimum(2 )Inlet Pressure
psi(bar)
AgencyApproval
Description SIN / ModelTFP Data
Sheet
K-Factor 2.8Upright
TY1131
TY1151
TFP171
TFP151Hydrocarbons
0.16(6,52)
30.0(2,07)
UL
K-Factor 2.8Pendent
TY1231
TY1251
TFP171
TFP151Hydrocarbons
0.16(6,52)
30.0(2,07)
UL
K-Factor 4.2Upright
TY2131 TFP171 Hydrocarbons0.16
(6,52)13.0
(0,90)UL
K-Factor 4.2Pendent
TY2231 TFP171 Hydrocarbons0.16
(6,52)13.0
(0,90)UL
K-Factor 5.6Upright
TY3121
TY3131
TY3151
TFP130
TFP171
TFP151
Hydrocarbons0.16
(6,52)7.0
(0,48)UL
K-Factor 5.6Pendent
TY3231
TY3251
TFP171
TFP151Hydrocarbons
0.16(6,52)
7.0(0,48)
UL
(1) Minimum Application Rate required per UL 162 Foam Equipment and Liquid Concentrate Standard.
(2) Minimum Inlet Pressure is the minimum starting pressure required for the sprinkler. However, the Minimum Application Rate
overrides the Minimum Inlet Pressure (depending on sprinkler spacing).
tAble 1ANSulIte1% AFFF (1609-95CG)
Page 2 of 6 TFP2005
-
8/2/2019 TFP2005_08_2007
3/6
ANSULITE3x3 Low Viscosity (3%) AR-AFFF
Fuel
Minimum(1)Application Rate
GPM/Sq Ft(mm/min)
Minimum(2 )Inlet Pressure
psi(bar)
AgencyApproval
Description SIN / ModelTFP Data
Sheet
K-Factor 5.6Upright
TY3131
TY3151
TFP171
TFP151
Hydrocarbons 0.16 (6,52) 7.0 (0,48)
UL / FMAlcohols 0.22 (8,96) 14.5 (1,00)
Denatured Ethanol 0.16 (6,52) 7.0 (0,48)
E-85 Blend* 0.16 (6,52) 7.0 (0,48)
K-Factor 5.6Pendent
TY3231
TY3251
TFP171
TFP151
Hydrocarbons 0.16 (6,52) 7.0 (0,48)
UL / FMAlcohols 0.22 (8,96) 14.5 (1,00)
Denatured Ethanol 0.16 (6,52) 7.0 (0,48)
E-85 Blend* 0.18 (7,33) 9.0 (0,62)
K-Factor 8.0Upright
TY4131
TY4151
TFP171
TFP151
Hydrocarbons 0.22 (8,96) 7.0 (0,48) UL / FM
Alcohols 0.25 (10,19) 9.0 (0,62) UL
Alcohols 0.28 (11,41) 12.0 (0,83) FM
Denatured Ethanol 0.22 (8,96) 7.0 (0,48) UL / FM
K-Factor 8.0Pendent
TY4231
TY4251
TFP171
TFP151
Hydrocarbons 0.22 (8,96) 7.0 (0,48) UL / FM
Alcohols 0.27 (11,00) 11.0 (0,76) UL
Alcohols 0.28 (11,41) 12.0 (0,83) FM
Denatured Ethanol 0.22 (8,96) 7.0 (0,48) UL / FM
K-Factor 11.2Upright
TY5111
TY5131
TY5151
TFP340
TFP344
TFP342
Hydrocarbons 0.32 (13,04) 7.0 (0,48)
UL / FMAlcohols 0.36 (14,67) 9.5 (0,66)
Denatured Ethanol 0.32 (13,04) 7.0 (0,48)
K-Factor 11.2Pendent
TY5211
TY5231
TY5251
TFP340
TFP344
TFP342
Hydrocarbons 0.32 (13,04) 7.0 (0,48)
UL / FMAlcohols 0.36 (14,67) 9.5 (0,66)
Denatured Ethanol 0.32 (13,04) 7.0 (0,48)
Foam/WaterSprinkler
K-Factor 3.0,Pendent orUpright
Model B-1 TFP840
Hydrocarbons 0.16 (6,52) 30.0 (2,07)
UL
Alcohols 0.16 (6,52) 30.0 (2,07)
Denatured Ethanol 0.16 (6,52) 30.0 (2,07)
E-85 Blend* 0.16 (6,52) 30.0 (2,07)
* E-85 Blend based on 75% Denatured Ethanol / 25% Heptane
(1) Minimum Application Rate required per UL 162 Foam Equipment and Liquid Concentrate Standard.
(2) Minimum Inlet Pressure is the minimum starting pressure required for the sprinkler. However, the Minimum Application Rate
overrides the Minimum Inlet Pressure (depending on sprinkler spacing).
tAble 2ANSulIte 3x3 loW VIScoSIty (3%) AR-AFFF
TFP2005 Page of 6
-
8/2/2019 TFP2005_08_2007
4/6
ANSULITE 3% AFFF(AFC-3A)
Fuel
Minimum(1)Application Rate
GPM/Sq Ft(mm/min)
Minimum(2 )Inlet Pressure
psi(bar)
AgencyApproval
Description SIN / ModelTFP Data
Sheet
K-Factor 5.6Upright
TY3131
TY3151
TFP171
TFP151Hydrocarbons 0.16 (6,52)
7.0(0,48)
UL / FM
K-Factor 5.6Pendent
TY3231
TY3251
TFP171
TFP151Hydrocarbons 0.16 (6,52)
7.0(0,48)
UL / FM
K-Factor 8.0
Upright
TY4131
TY4151
TFP171
TFP151
Hydrocarbons 0.22 (8,96)7.0
(0,48)
UL / FM
K-Factor 8.0Pendent
TY4231
TY4251
TFP171
TFP151Hydrocarbons 0.22 (8,96)
7.0(0,48)
UL / FM
K-Factor 11.2Upright
TY5111
TY5131
TY5151
TFP340
TFP344
TFP342
Hydrocarbons 0.32 (13,0)7.0
(0,48)UL / FM
K-Factor 11.2Pendent
TY5211
TY5231
TY5251
TFP340
TFP344
TFP342
Hydrocarbons 0.32 (13,0)7.0
(0,48)UL / FM
Foam/WaterSprinklerK-Factor 3.0,Pendent orUpright
Model B-1 TFP840 Hydrocarbons 0.16 (6,52)30.0(2,07)
UL
(1) Minimum Application Rate required per UL 162 Foam Equipment and Liquid Concentrate Standard.
(2) Minimum Inlet Pressure is the minimum starting pressure required for the sprinkler. However, the Minimum Application Rate
overrides the Minimum Inlet Pressure (depending on sprinkler spacing).
tAble 3ANSULITE 3% AFFF (AFC-3A)
Page of 6 TFP2005
-
8/2/2019 TFP2005_08_2007
5/6
InstallationDepending on the nature o the haz-ard, oam water sprinkler systems mayuse automatic (closed) sprinklers ornon-automatic (open) sprinklers. Inthe case o non-automatic sprinkler in-
stallations, usually automatic (closed)sprinklers are frst installed with theirprovided usible link or rangible bulbheat sensitive element. This procedurewill provide or the ability to hydrostati-cally test the system. Ater successul-ly meeting the system hydrostatic testrequirements, the usible link or ran-gible bulb heat sensitive element canthen be removed to provide a non-au-tomatic (open) discharge device.
LimitedWarrantyProducts manuactured by Tyco Fire& Building Products (TFBP) are war-ranted solely to the original Buyer or
ten (10) years against deects in mate-rial and workmanship when paid orand properly installed and maintainedunder normal use and service. Thiswarranty will expire ten (10) years romdate o shipment by TFBP. No warran-ty is given or products or componentsmanuactured by companies not a-fliated by ownership with TFBP or orproducts and components which havebeen subject to misuse, improper in-stallation, corrosion, or which have notbeen installed, maintained, modifed orrepaired in accordance with applicableStandards o the National Fire Protec-tion Association, and/or the standards
o any other Authorities Having Juris-diction. Materials ound by TFBP to bedeective shall be either repaired or re-placed, at TFBPs sole option. TFBPneither assumes, nor authorizes anyperson to assume or it, any other ob-ligation in connection with the sale oproducts or parts o products. TFBPshall not be responsible or sprinklersystem design errors or inaccurate orincomplete inormation supplied byBuyer or Buyers representatives.
In no event shall TFBP be liable, incontract, tort, strict liability or underany other legal theory, or incidental,indirect, special or consequential dam-
ages, including but not limited to laborcharges, regardless o whether TFBPwas inormed about the possibility osuch damages, and in no event shallTFBPs liability exceed an amountequal to the sales price.
The oregoing warranty is made in lieuo any and all other warranties, ex-press or implied, including warrantieso merchantability and ftness or aparticular purpose.
This limited warranty sets orth the ex-clusive remedy or claims based onailure o or deect in products, materi-als or components, whether the claim
is made in contract, tort, strict liabilityor any other legal theory.
This warranty will apply to the ull ex-tent permitted by law. The invalidity,in whole or part, o any portion o thiswarranty will not aect the remainder.
OrderingProcedure
Reer to the TFP Data Sheet reer-enced in Tables 1, 2 or 3 or inorma-tion on ordering standard spray sprin-
klers and oam-water sprinklers.
cAutIoNExtreme care is to be used when re-
moving usible link or rangible bulbheat sensitive elements to avoidpersonal injury. Wear saety glasses.Contain the element within a dispos-
able cotton rag or several layers opaper towels beore prying a usiblelink or snapping a rangible bulb. Thesize and thickness o the cotton ragor the layers o paper towels must
be sufcient to completely envelopthe usible link or rangible bulb el-ement so as to cushion the releaseo the usible element or breaking o
glass, as well as be able to avoid re-lease o any parts or ragments. Dis-card protective rag or towels with-out unwrapping the captured pieceso the usible link or rangible bulb
heat sensitive element.
TFP2005 Page 5 of 6
-
8/2/2019 TFP2005_08_2007
6/6
Page 6 of 6 TFP2005
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale Pennsylvania 19446