TE/XGA Series & XTE/XGA Series
Surge Protective Device (SPD)Installation, Operation & Maintenance Manual
Advanced Protection Technologies14550 58th St. N.Clearwater, FL 33760
(800) 237-4567, (727) 535-6339Fax (727) 539-8955
www.aptspd.com
WARNING – IMPORTANT – PLEASE READ – WARNING
Safety First – Hazardous Voltage & Shock Hazard
• OnlyqualifiedlicensedelectriciansshouldinstallorserviceSPDs• HazardousvoltagesexistwithinSPDs• SPDsshouldneverbeinstalledorservicedwhenenergized• Use appropriate safety precautions including Personal Protection Equipment• Failure to follow these instructions can result in death, serious injury, and/or equipment damage.• Thismanualshallbereadinentiretypriortoinstalling
Bonding and Grounding Hazard
VerifythattheneutralconductorintheserviceentranceequipmentisbondedtogroundinaccordancewiththeNationalElectricCode(NEC®)andallapplicablecodes.
Verifythattheneutralterminal(XO)onthesecondarysideofdistributiontransformersaregroundedtothesystemgroundinaccordancewiththeNEC®andallapplicablecodes.
During installation intoanelectricalsystem theSPDmustnotbeenergizeduntil theelectricalsystem iscompletelyinstalled,inspectedandtested.Allconductorsmustbeconnectedandfunctionalincludingtheneutral(ifrequired).ThevoltageratingoftheSPDandsystemmustbeverifiedbeforeenergizingtheSPD.
FailuretofollowtheseguidelinescanleadtoabnormallyhighvoltagesattheSPD.ThismaycausetheSPDtofail.ThewarrantyisvoidediftheSPDisincorrectlyinstalledand/oriftheneutralconductorintheserviceentranceequipmentordownstreamofseparatelyderivedsystemsisnotbondedtogroundinaccordancewiththeNEC®.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potentialinsulationtesting,oranyothertestswherethesuppressioncomponentswillbesubjectedtohighervoltagethantheirratedMaximumContinuousOperatingVoltage(MCOV)mustbeconductedwiththeSPDdisconnectedfromthepowersource.For4-wiresystems,theneutralconnectionattheSPDmustalsobedisconnectedpriortoperforminghigh-potential testing and then reconnected after test completion.
FailuretodisconnectSPDandassociatedcomponentsduringelevatedvoltagetestingwilldamagetheSPDandwillvoid the warranty.
FiGurES2008 NEC Art 285 & UL 1449-3 ...................................................................................................................................... 1Flush Mount front view .................................................................................................................................................... 3Flush Mount Side View ................................................................................................................................................... 3NEMA Type 1, 4, and 4X Stainless Steel ........................................................................................................................ 6NEMA Type 3R ................................................................................................................................................................ 6NEMA Type 4X Plastic .................................................................................................................................................... 6Typical Panel Installation................................................................................................................................................. 7ModuleLED .................................................................................................................................................................. 10PinoutDiagramforDryContactsofSPD ..................................................................................................................... 10TroubleShootingFlowchart ...........................................................................................................................................11
TABlESTable1:VoltageRatingandServiceType ..................................................................................................................... 4Table2:ModelNumberDecoder ................................................................................................................................... 5Table3:ReplacementParts ......................................................................................................................................... 12
TABlE oF CoNTENTSINTRODUCTION ................................................................................................................................................................ 1
Major Industry Nomenclature Changes Effective 2008-2009 .......................................................................................... 1SimplifiedExplanationofOperation ................................................................................................................................ 1Parallel Connection ......................................................................................................................................................... 1PrecautionaryStatementRegardingSPDsonUngroundedSystems ............................................................................ 1Unpacking & Preliminary Inspection ............................................................................................................................... 1Storage Environment ...................................................................................................................................................... 2
PRE-INSTALLATION & PLANNING ................................................................................................................................... 2Operating Environment ................................................................................................................................................... 2AudibleNoise ................................................................................................................................................................. 2Mounting,Dimensions,andWeight ................................................................................................................................ 2Service Clearance ........................................................................................................................................................... 2MaximizingSPDPerformance ........................................................................................................................................ 2Cascade Surge Protection .............................................................................................................................................. 2Overcurrent Protection .................................................................................................................................................... 2CircuitBreakerandDisconnectSwitch ........................................................................................................................... 2WireSizeandInstallationTorque .................................................................................................................................... 2ShortestLeadsPossible ................................................................................................................................................. 3Special Enclosure Considerations .................................................................................................................................. 3RemovingandReconnectingtheRibbonCables ........................................................................................................... 3NEMA Type 4X Enclosure ............................................................................................................................................... 3Flush Mount Option ......................................................................................................................................................... 3Terminals ......................................................................................................................................................................... 3ConfigurationManagement&PartNumberingSystem .................................................................................................. 4Voltage Rating ................................................................................................................................................................. 4System Grounding .......................................................................................................................................................... 4UL 1283 required language concerning the installation of EMI Filters ............................................................................ 5
INSTALLATION .................................................................................................................................................................. 7CommonProblemstoAvoid ............................................................................................................................................ 7Pre-Plan your installation. .............................................................................................................................................. 7ElectricalConnectionDiagrams ...................................................................................................................................... 8Surge Counter Options ................................................................................................................................................... 9
OPERATION ....................................................................................................................................................................... 9SupplementalLEDindicatorsonModules .................................................................................................................... 10DryContactOption........................................................................................................................................................ 10
MAINTENANCE ................................................................................................................................................................11Module Removal and Replacement ...............................................................................................................................11Display/DiagnosticBoardRemovalandReplacement...................................................................................................11Preventive Maintenance (Inspection and Cleaning) ..................................................................................................... 12Corrective Maintenance (Repair) .................................................................................................................................. 12LimitedWarranty ........................................................................................................................................................... 12
Page 1
iNTroDuCTioNThankyouforchoosinganAPTSurgeProtectiveDevice(SPD).Thisisahighquality,highenergysurgesuppressordesigned to protect sensitive equipment from damaging transient overvoltages.
Proper installation is important to maximize performance. Please follow steps outlined herein.
ThisentireOperation&MaintenanceManualshouldbereadpriortobeginninginstallation.Theseinstructionsarenot intended to replace national or local codes. Follow all applicable electrical codes to ensure compliance.Installation of this SPD should only be performed byqualifiedelectricalpersonnel.
APTSPDs are extensively tested in accordancewithindustry standards such as ANSI/IEEE C62.41.1, C62.41.2, C62.45, C62.62, C62.72, UL 1449, UL 1283, IEC 61643, etc. This SPD is a single-port parallel-connected deviceintendedforserviceentrance,panelboardordownstreaminstallation for IEEE Category C, B or A applications
Major industry Nomenclature Changes Effective 2008-2009Be aware that UL 1449 Third Edition and 2008 NEC® Article 285generatedsubstantialchanges.
• ThetermTVSSchangedtoSPD• Types1,2,3&4SPDsarecreated• UL 1449 clamping voltage performance testing changed
from 500A to 3,000A• UL 1449 added new I nominal testing (In), which
consists of more rigorous duty-cycle testing
ThisSPDcomplieswiththelatestregulatoryactionsandis UL Listed as such.
For further information, please review latest editions of NEC® Art. 285, UL 1449 or contact APT Tech Support at (800) 237-4567
GENErAl iNForMATioNThisisaType2SPD.Itincludesinternalovercurrentprotection.Type2SPDsaresuitableforinstallationontheloadsideoftheservice disconnect overcurrent device.
This device features internal overcurrent and overtemperature protection that will disconnect effected surge suppression componentsattheendoftheirusefullife,butwillmaintainpowertotheload–nowunprotected.Ifthissituationisundesirablefor the application, follow these instructions for servicing or replacing the device.
Service of this unit consists of replacing internal modules and/ordisplayassembly.
There are no user-serviceable parts inside the replaceablemodules.Donotattempttodisassemblethemoduleasitstorescharge and is potted.
Simplified Explanation of OperationSPDssenseovervoltageandcreateamomentaryshortcircuitto redirect harmful surge energy to earth ground. Then they reset automatically and wait for the next surge. This is similar tothepressurereliefvalveonawaterheater:pressuregoesup, valve opens to relieve pressure and then resets. In an electricalsystem,anSPDsensesovervoltage,shortstemporarilysendingenergytogroundandthenresets.SPDsarecapableof repeating this function thousands of times.
Parallel ConnectionThisisaParallelconnectedSPD–notseriesconnected.Asoutlinedabove,anSPD‘drainsoff’excessivevoltagefromanelectrical system. Because of parallel connection, installation oftheSPDneartheequipmenttobeprotectedissatisfactory.Thiseffectissimilartoflushinganytoiletinahouse;pressurein the shower goes down. In an electrical system, a parallel connectedSPDwill removeexcessive voltageoff the entiresystem(assumingreasonableproximity).
Tip: It is critically important that wiring leads beconfiguredasshort&straightaspossible.Avoidlongleads.Avoidsharpbends.RouteSPDconductorsinthesameconduit.Leadsdonothavetobesizedfortheentireload–thisSPDisparallelconnected,notseriesconnected.Asageneralization,6AWGworksfine.
Precautionary Statement regarding SPDs on ungrounded SystemsCaution–Ungroundedsystemsareinherentlyunstableandcanproduct excessively high line-to-ground voltages during certain fault conditions. During these fault conditions,anyelectricalequipment including anSPD,maybe subjected to voltageswhichexceedtheirdesignedratings.Thisinformationisbeingprovidedtotheusersothataninformeddecisioncanbemadebefore installinganyelectrical equipment onanungroundedpower system.
unpacking & Preliminary inspectionInspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect theunitforanyobviousshippingdamages.
2008 NEC ArT 285 & ul 1449-3SPDTypes:Types1,2,3,&4
BasedonLocationwithinelectricaldistributionsystem(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B & A)
Figure 1
Page 2
If any damage was found and is a result of shipping or handling, immediatelyfileaclaimwiththeshippingcompanyandforwarda copy to APT.
Storage EnvironmentThisSPDshouldbestoredinaclean,dryenvironment.Storagetemperature range is -40°C (-40°F) to +60°C (+140°F). Avoid exposure to high condensation.
PrE-iNSTAllATioN & PlANNiNGoperating EnvironmentThe standard unit is in a Type 1 enclosure. Other enclosure typesareavailableasoptions.Beforeinstalling,ensurethatyour enclosure type and application are appropriate per NEMA 250withregardtomoisture,dirt,excessivedust,flammablematerials or atmospheres, corrosive vapors, etc.
ThisSPDisdesignedinanambienttemperaturerangeof-40°C(-40°F) to +60°C (+140°F) with a relative humidity of 0% to 95% (non-condensing). Excessive temperature may inadvertently operate internal thermal overtemperature protectors.
Audible Noise SPDbackgroundnoiseisnegligibleornon-existent,anddoesnot restrict the location of installation.
Mounting, Dimensions, and WeightThis SPD is designed to bewallmounted.The standardenclosure is: 12” x 12” x 6” (L/W/D), and the weight is 25lbs.TheXTESeriesisdesignedforinternalmountingintheelectricaldistributionequipment.Standardbackplanesize is:10.75”x10.88”x4.5”,andtheweightis15lbs.
Service ClearanceService clearance is needed at the front of the TE Series unit only, 36 inches minimum is the required distance for clearance pursuant to the NEC®.
Maximizing SPD PerformanceSPD’smust be located as close to the circuit as possibleto minimize parasitic losses. Surges are high current, high frequencyeventsthatcausesubstantialvoltagedropsacrossconductors.ThishurtsSPDperformance.Usetheshortest&straightestpossibleleads.Pre-Planinstallationsandensurethatnearestbreakerpositionsareused.Ifnewconstruction,adjustbreakerlocationsasappropriate.
Tip: Voltage drops for normal 120V or 277V linesmightbe2-3Vperhundredfeet.Insurgeapplications,voltage dropsmight be 100-150Vper foot. Thesevoltage drops add to clamping voltage, thus hurting performance. Make every effort to keep leads short and straight.
Asdistributiongearbecomeslarger,shorter leadsaremoredifficult toaccomplish.Whenlonger leadsareunavoidable,gently twist leads together (one to two twists per foot), or tie-wrap leads together.
Tip: surges createmagnetic fields per the ‘right-handrule’.Whencurrentgoesindirectionofthumb,magneticfieldisindirectionofcurloffingers.Assurge
current goes toSPD, fields are created in onedirection.WhentheSPDsendsthosecurrentstoneutral and/or ground, current goes in the opposite direction.If‘coming&going’areonthesameaxis,themagneticfieldscanbecancelled,thusavoidingperformancedecrease.Gentletwists,bundling&tie-wraps accomplish this.
Cascade Surge ProtectionFor optimum surge protection, cascade or staged surge suppressionshouldbeimplementedattheserviceentranceand downstream locations as appropriate. Known or expected surge sources, as well as sensitive loads, should also have localized surge suppression. For interconnected electronicloads(datacabling),SPDsshouldalsobeutilizedto protect the devices on either end of the interconnecting datacables.
overcurrent ProtectionSPDsdrawverylittlecurrentundernormalconditionsandconductforabriefdurationuponencounteringatransientsurgecurrent.ThisSPDcontaininternalovercurrentandovertemperature protection to protect against abnormalvoltage conditions.
Supplemental overcurrent protection is not required to protectthisSPD.However,connectingconductorsrequireprotectioninType2or4applications.Followapplicablecodes.
Circuit Breaker and Disconnect SwitchThisXGAfamilySPDistestedandqualifiedasaType2SPDperUL1449ThirdEditionand2008NEC®.ThisSPDcanbeinstalledontheloadsideoftheserviceovercurrentdevice per 2008 NEC® Article 285. When connected on load side ofmain disconnect, wesuggestconnectingviaa60Acircuitbreaker.Thecircuitbreaker is the intendeddisconnect switch and providesshort circuit protection to the connecting conductors. The XGA Series has internal overload protection elements withintheproduct.Abreakerordisconnectisnotrequiredfor theSPD’s overcurrent protection. XGASPD’s havedemonstrated 200kA Short Circuit Current Ratings (SCCR). Confertolabelonunit.
Wire Size and installation TorqueThisisaparallel-connectedSPD;itisnotseries-connected.ThesizeoftheSPDwiringisindependentoftheampererating of the protected circuit. Recommended wire is 6 AWGforphase,neutralandgroundconnections.Torqueconnections to 18 inch-pounds. Conductor length should beasshortaspossible.
If other wire sizes are used, we recommend that all conductorsbethesamegauge.Notethatlargerconductormightappeartobebeneficial;however,ittendstohavethesameinductanceassmallerconductorandismoredifficultto work with.
Terminalsaccept14-2AWGconductorwith6AWGbeingpreferred. Coordinate conductor size and overcurrent protectionperapplicablecodes.
Page 3
Special Enclosure Considerations
removing and reconnecting the ribbon CablesThe ribbon cables aremarked withmatching phaseconnections.Ifanyofthecablesareremoved,reconnectthecablesasmarked.
NEMA Type 4X EnclosureOn rare occasions in high temperature climates, XGA's inside clear-cover polycarbonate enclosures haveexperienced internal temperatures exceeding 200oF. This inadvertently operates the overtemperature safety disconnectorsinsidetheSPD.Werecommendpositioningthe unit so that the clear front avoids direct summer sunlight byshadingornotfacingwest.
The NEMA Type 4X enclosure is shipped with its mounting bracketsandinstallationscrewspackagedinsideit.Usethe enclosed 1/4-20 x 1/2 in. slotted screws to secure the bracketstotheenclosurebeforeinstallingtheXGASPDdevice.Torque these screws to amaximumof 50lb-in.(6N·m).When installing the cover for theNEMAType4X enclosure, torque the cover screws to a maximum of 25lbs-in.(3N·m).
Flush Mount optionRemovethedisplaypanelandbarrierbeforemakinganyelectrical connections.Replace the barrier and displaypanelbeforeenergizingthedevice.
The XGA is approximately 5.25 in. (133 mm) deep. The XGAwillnotflushmountunlessthereisatleast5.25in.(133mm)ofclearance.TheXGAisnotdesignedtoflushmount on a typical 2 x 4 stud wall.
Followsteps1-5toflushmounttheXGA.1. Beforeremovingthetrim,disconnecttheribboncables
and ground wire from the modules. 2. Mountthedeviceascloseaspossibletothepanelbeing
protected. Create a wall opening slightly larger than 12 in.highby12in.wide(305mmhighby305mmwide).Seefigure2.
3. Install abackingplate inside thewall cavity5.25 in.(133mm)fromthewallfacesuchthattheXGAwillbesupportedfromitsback.Seefigure3.Notethemountingholesonthebackoftheenclosure.AlsonotethattheXGAweighs25lb(12kg)maximum.
4. Configuretheelectricalconductorandconduitconnectionsconsistentwiththewiringinstructionsbeginningonpage7.
5. Carefullyreattachtheribboncablesandthegroundwireto the modules and reattach the display panel/cover beforeenergizingandtestingthedevice.
TerminalsTerminals will accept 14 - 2AWG conductor and areprovided for line (phase), neutral (if used), and equipment safety ground connections. 8AWG is theminimumrecommendedwiresizebecauseULtestingandevaluationwasperformedusing8AWG.
Figure 2
Figure 3
Shortest leads Possible• leads must be as short and straight as possible - See
NEC® Art. 285.12• Pretend wire is $1000 per foot coming out of your pocket• No long leads• No sharp bends• No wire nuts• How short is short enough? As short as you can make it• How long is too long? if anyone else can make it shorter
FluSH MouNT FroNT viEW
FluSH MouNT SiDE viEW
Page 4
tobecomeunstableincertainsituations.Suchinstabilitycan cause line to ground voltage fluctuations thatmayprematurelyfailSPDs.Forthisreason,theNEC®Article285hasplacedSPDrestrictionsonungroundedsystems.Asgeneralizations,SPDsforungroundedsystemscanbeinstalled on grounded systems with a clamping performance penalty. However,SPDs forgroundedsystems installedon ungrounded systems are almost certainly destined for premature failure. Call APT Tech Support at (800) 237-4567 for further information.
TABlE 1: volTAGE rATiNG AND SErviCE TyPE
TE & XTE / 1XGA 120/240SinglePhase,3Wire,"Grounded"
TE & XTE / 11XGA 120SinglePhase,2Wire,"Grounded"
TE & XTE / 12XGA 240SinglePhase,2Wire,"Grounded"
TE & XTE / 2XGA 120/208ThreePhase,4Wire,"Grounded",WYE
TE & XTE / 3XGA 120/240ThreePhase,4Wire,"High-Leg",DELTA
TE & XTE / 4XGA 277/480ThreePhase,4Wire,"Grounded",WYE
TE & XTE / 5XGA 480ThreePhase,3Wire,DELTA
TE & XTE / 51XGA 480ThreePhase,"CornerGrounded",DELTA
TE & XTE / 6XGA 240ThreePhase,3Wire,DELTA
TE & XTE / 61XGA 240ThreePhase,"CornerGrounded",DELTA
TE & XTE / 7XGA 220/380ThreePhase,4Wire,"Grounded",WYE
TE & XTE / 8XGA 347/600ThreePhase,4Wire,"Grounded",WYE
TE & XTE / 9XGA 600ThreePhase,3Wire,DELTA
TE & XTE / 91XGA 600ThreePhase,"CornerGrounded"DELTA
System GroundingAnequipmentgroundingconductormustbeusedonallelectricalcircuitsconnectedtotheSPD.
Forthebestperformance,useasinglepointgroundsystemwhere the service entrance grounding electrode system is connectedtoandbondedtoallotheravailableelectrodes,building steel,metalwater pipes, driven rods, etc. (forreferencesee:IEEEStd142-2007).
For sensitive electronics and computer systems, we recommendthatthegroundimpedancemeasurementbeaslowaspossible.Whenmetallicracewayisusedasanadditional grounding conductor, an insulated grounding conductor should be run inside the raceway and sizedper theNEC®.Adequate electrical continuitymust bemaintainedatallracewayconnections.Donotuseisolatingbushingstointerruptametallicracewayrun.
AseparateisolatedgroundfortheSPDisNOTrecommended.Proper equipment connections to grounding system and groundgrid continuity shouldbe verified via inspectionsandtestingonaregularbasisaspartofacomprehensiveelectrical maintenance program.
On4-WirePowerSystems,neutraltogroundbonding(MainBondingJumper)mustbeinstalledpertheNEC®. Failure todosoWILLdamageSPDs.
Configuration Management & Part Numbering SystemTE series correct installation orientation is such that the door will hinge from the left. (XTE has no enclosure or door and is typically factory installed)
Locatetheunit'sprintedidentificationnameplateontheinsideof the hinged door, although options may dictate placing it in aconspicuouslocationelsewhere.Themodelnumbercanbedecodedasfollows:
• TE identifies an external mount Transient Eliminator® followedbyaslash(/).XTEidentifiesanenclosure-lessmodelfollowedbyaslash(/).
• AoneortwodigitnumberwillprecedethelettersXGA.Thisnumber indicates the voltageandwiring configurationofthedevice.Refertopage5toidentifyandconfirmcorrectapplication.
• XGAidentifiestheXGASeries,followedbyaslash(/)• Followingthesecondslashmaybea/240.Thesenumbers
identify optional per phase Surge Current Ratings. (Please note: TheStandard160kARatingdoesnothavea /160identifier.)
OptionsareidentifiedaftertheSurgeCurrentRatingandareindividuallyseparatedbyaslash.(Optionsaredetailedlaterin this manual.)
Example: TE/2XGA/240/DC/RM/4X identifies aTransientEliminator® XGASeriesSPD(externalmount),208Y/120V,3Phase,4Wire(plusGround),witha240kAperphaseSurgeCurrentRatingwith:DryContact,RemoteMonitor,andaNEMA4X Enclosure.
voltage ratingBefore installingSPD, verify that it has the same voltageratingasthepowerdistributionsystem.ComparetheSPD’snameplate voltage ormodel number and ensure thatSPDconfigurationmatchestheintendedpowersource.SeeTable1.
ThespecifierortheuserofthedeviceshouldbefamiliarwiththeconfigurationandarrangementofthepowerdistributionsysteminwhichanySPDistobeinstalled.Thesystemconfigurationofanypowerdistributionsystemisbasedstrictlyonhowthesecondary windings of the transformer supplying the service entrancemainorloadareconfigured.Thisincludeswhetheror not the transformer windings are referenced to earth via a groundingconductor.Thesystemconfigurationisnotbasedonhowanyspecificloadorequipmentisconnectedtoaparticularpowerdistributionsystem.
480VSystemExample: SPDs should be installed per theelectricalsystem,notperaloadormotor’swiringconnection.Forexample,a480Vthreephasemotormightappeartobeconnectedasa480VDelta.Inactuality,theservingdistributionsystemmightbea480Y/277VgroundedWye,withorwithouta neutral pulled to the motor or MCC. The system is still a 480Y/277VWye, even though the load is connected as aDelta. AgroundedWyehasadefined reference toground(i.e.,neutralisbondedtoground).SomeDeltasystemsareungrounded, which have no reference to ground and are known
Page 5
TE = Transient Eliminator, listed Type 2 SPD in NEMA 1 enclosure
XTE = Transient Eliminator, recognized Type 4 SPD on backplane for installation within gear in Type 2 installation (display on 6’ cable)
voltage Code for Electrical System
Model Family Option Suffixes (Seperated by slashes -/)
ll / ll / XGA / lll / lll ...
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6
SPLIT2 Hots, 1 Neu, 1 Grnd
HI-LEGDELTA(BHigh)3 Hots, (B HIGH), 1 Neu, 1 Grnd
SINGLE POLE1 Hot, 1 Neu, 1 Grnd
WYE3 Hots, 1 Neu, 1 Grnd
DELTA&HRGWYE3 Hots, 1 Grnd
CORNERGROUNDDELTA(Bgrounded)2 Hots, 1 Grnd
Hot (BLK)
Hot (BLK)
Neutral (WHT)V
V
}}
Ground (GRN)}
Phase A (BLK)Phase B (BLK)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
A
C
N
V
B
Phase A (BLK)Phase B (ORNG)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
}V V}Neutral (WHT)
Hot (BLK)
Ground (GRN)
Phase A (BLK)
Phase C (BLK)
Phase B (BLK)
Ground (GRN)
}V Phase A (BLK)
Phase C (BLK)
Ground (GRN)
V}
/240 = 240kA Option
/090 = 090kASADoption(120/240V&208Y/120)
/130 = 130kASADoption(120/240V&208Y/120)
/170 = 170kASADoption(120/240V&208Y/120)
/DC = DryContacts
Two sets Form C (24V, 1A)
/SC = SurgeCounter,sixdigitLCD/2S = DualSurgeCounter
/12 = NEMA12Enclosure(12”x12”x6”)
/3R = NEMA3REnclosure(12”x12”x6”- display inside door)
/04 = NEMA4Enclosure(12”x12”x6”- display inside door)
/FM = Flush Mount enclosure, NEMA 1 only
(wallcavitysize:12”x12”x6”deep)
/4X = NEMA4XNon-metallicenclosure(polycabonate,14”x12”x6”- display inside door)
/4S = NEMA 4S Stainless Steel enclosure
(12”x12”x6”-displayinsidedoor)
/TN = NEMA1/12/3R/4Enclosure(10”x10”x6”)
(Note:Enclosure-lessversionforOEMusesXTEprefix)
AvailableAccessory(orderseperately):RM = Remote Monitor
Other Available Systems - Confirmation encouraged:15 = 254/127VSplitPhase-1Ø3W+Grnd(Fig1)18 = 480/240VSplitPhase,orTwolegsofWye(Call)21 = 220Y/127VWye-3Ø4W+Grnd(Fig2)41 = 520Y/300VWye-3Ø4W+Grnd(Fig2)42 = 415Y/240VWye-3Ø4W+Grnd(Fig2)43 = 400Y/230VWye-3Ø4W+Grnd(Fig2)44 = 440Y/250VWye-3Ø4W+Grnd(Fig2)51 = 480VBCornerGrndDelta,3Ø3W+Grnd(Fig6)06 = 240VDelta-3Ø3W+Grnd(Fig4)61 = 240VBCornerGrndDelta,3Ø3W+Grnd(Fig6)07 = 380Y/220VWye-3Ø4W+Grnd(Fig2)09 = 600VDelta-3Ø3W+Grnd(Fig4)&HRGWye91 = 600VBCornerGrndDelta,3Ø3W+Grnd(Fig6)
XGA = XGA Family160kA rating standard
Common North American Systems:01 = 240/120v Split Phase - 1Ø 3W+Grnd (Fig 1)02 = 208y/120v Wye - 3Ø 4W+Grnd (Fig 2)03 = 240/120v High leg Delta (B High) (Fig 3)04 = 480y/277v Wye - 3Ø 4W+Grnd (Fig 2)05 = 480v Delta - 3Ø 3W+Grnd (Fig 4) & HrG Wye08 = 600y/347v Wye - 3Ø 4W+Grnd (Fig 2)
TABlE 2: MoDEl NuMBEr DECoDErDonotcreatemodelnumbersfromthischartasallfeaturesarenotavailableonallmodels
ul 1283 required language concerning the installation of EMi Filtersa) An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green withorwithoutoneormoreyellowstripes,istobeinstalledaspartofthecircuitthatsuppliesthefilter.ReferenceshouldbemadetoTable250-122oftheNationalElectricalCoderegarding the appropriate size of the grounding conductor.
b) The grounding conductor mentioned in item a is to begrounded toearthat theserviceequipmentorotheracceptablebuildingearthgroundsuchasthebuildingframein the case of a high-rise steel-frame structure.
c) Any attachment-plug receptacles in the vicinity of the filter are to be of a grounding type, and the groundingconductorsservingthesereceptaclesaretobeconnectedtoearthgroundattheserviceequipmentorotheracceptablebuildingearthgroundsuchasthebuildingframeinthecaseof a high-rise steel-frame structure.
d) Pressure terminal or pressure splicing connectors and solderinglugsusedintheinstallationofthefiltershallbeidentifiedasbeingsuitableforthematerialoftheconductors.Conductorsofdissimilarmetalsshallnotbeintermixedinaterminal or splicing connector where physical contact occurs betweendissimilarconductorsunlessthedeviceisidentifiedfor the purpose and conditions of use.
Page 6
Figure 4
SPD DiMENSioNSNEMA TyPE 3rFigure 5
SPD DiMENSioNS NEMA TyPE 4X PlASTiC
Figure 6
SPD DiMENSioNSNEMA TyPE 1, 4, AND 4X STAiNlESS STEEl
Page 7
iNSTAllATioNCommon Problems to Avoid• ConfirmSystemvoltagetoSPDvoltage(120VSPDwillfailinstantlyon240V,277V,etc.)• LocateSPDclosesoleadsareshort&straightaspossible(orwillseriouslyhurtperformance)• MakesureN-GorXObondingmeetsNEC®(orwillprematurelyfailSPD)• EnergizeSPDAFTERsystemisstabilized&checked(inadvertentsystemproblemmayfailSPD)• SPDsareregulatedbyNEC®Article285andUL1449• NeverHi-PottestanySPD(willprematurelyfailSPD)
Pre-Plan your installation. Youwillneedtoaccomplishthefollowing:• Meet all National and Local codes (NEC®Article285addressesSPDs)• MountSPDasclosetopanelorequipmentaspossibletokeepleadsshort• Ensureleadsareasshortandstraightaspossible,includingneutralandground.ConsiderabreakerpositionthatisclosesttotheSPDandthepanel’sneutral&ground
• Suggestedbreaker&conductorsizeis60A-30Awith6AWG(60Apreferred)• Make sure system is grounded per NEC®andclearoffaultsbeforeenergizingSPD.
1. UseavoltmetertocheckallvoltagestoensurecorrectSPD2. IfSPDhasDryContact,RemoteMonitoringorRemoteDisplay,pre-plantheirinstallation3. Removepowerforpanel.Confirmpanelisdeenergized.4. IdentifybreakerlocationandSPDlocation.5. Make sure leads are short! Reducing inches matters! Pretend that connector leads cost you $1000 per foot!6. Removeanappropriatelysizedknockoutfrompanel.CreateanappropriatelysizedholeintheSPDenclosure.7. MountSPD8. Connectconductorsasappropriate–shortandstraightaspossible(NotethatHi-LegsarePhaseB)9. Labelormarkconductorsasappropriate(neutral:white,ground:green,energized:black,hi-leg:orange)10. MakesuresystemisbondedperNEC®andisclearofhazardsorfaultsbeforeenergizing(N-Gbondingnotper
NEC®willfailSPDs:#1causeofSPDfailures)11. Energizeandconfirmproperoperationofindicatorsand/oroptions.
A B C
GN
BREAKER
Phase C
Service
Phase B
Phase ASurge Counter
Advanced Protection Technologies
SilenceTest Count Reset
TyPiCAl PANEl iNSTAllATioN
• UseclosestbreakertoSPD• LocateSPDclosetointendedbreaker
• KeepLeadsShortasPossible• Avoid Sharp Bends
• TE/XGA
• Outdoor insta l la t ion requi res appropriate weather sealing at nipple (o-ring, sealing condulet, etc.)
Figure 7
To Protected Loads
Page 8
Figure 13
CORNERGROUNDDELTA(Bgrounded)2 Hots, 1 Grnd
Phase A (BLK)
Phase C (BLK)
Ground (GRN)
V}
Figure 9
WYE3 Hots, 1 Neu, 1 Grnd
}
Phase A (BLK)Phase B (BLK)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
A
C
N
V
B
Figure 11
DELTA3 Hots, 1 Grnd
Phase A (BLK)
Phase C (BLK)
Phase B (BLK)
Ground (GRN)
}V
Figure 8
SPLIT2 Hots, 1 Neu, 1 Grnd
Hot (BLK)
Hot (BLK)
Neutral (WHT)V
V
}}
Ground (GRN)
Figure 10
HI-LEGDELTA(BHigh)3 Hots, (B HIGH), 1 Neu, 1 Grnd
Phase A (BLK)Phase B (ORNG)
Neutral (WHT)
Phase C (BLK)
Ground (GRN)
}V
Figure 12
Electrical Connection Diagrams
SINGLE POLE1 Hot, 1 Neu, 1 Grnd
V}Neutral (WHT)
Hot (BLK)
Ground (GRN)
Page 9
Service lED and the Audible AlarmDiagnosticswill indicate a failure upon loss of voltage orsignificant drop in voltage. Be aware that ground faults onungrounded or resistive ground systems will trigger a failure alarmonthisSPD.
IfLEDsareilluminatedinamannerthatsuggestscontradictoryinformation,theremaybeaninternallogicproblemandtheunitneedsreplaced.IfnoneoftheLEDsareilluminated,theunitmaynotbeinstalledcorrectly.Fortroubleshootingassistance,please contact APT Technical Support at (800) 237-4567.
Surge Counter optionsThesurgecounterregistersthenumberoftransientovervoltageson all L-N and L-G modes since the counter was last reset. The counter is inductively coupled from each mode of protection. It incrementsuponsignificantcurrentchangeinashorttimeperiod(large di/dt).
The surge counter includes Test and Reset buttons on thetouchpad display. Pressing Test adds one count. Pressing Resetclearsthecounter’smemoryandsetsthedisplaytozero.
The counter option includes a SuperCap internal storage capacitor thatprovidesbackuppowerforuptofourdaysintheeventofapoweroutage. Thiseliminates themaintenanceof batterybackups. There isa10-15minutechargingcyclebefore thecounter(s) operate.
Single Counter – Totals the surges through the L-N and L-G
DualCounters– Isused todistinguishbetweenL-NandL-Gsurges. Two separate counters are used, with common Resetand Testtabs.
Control and Diagnostic Panel All indicators and controls are located on the front diagnosticpanel.GreenLEDsindicatecorrectoperation.
Phase A, B & C:Tri-ColorLEDstatus indicators–oneper phaseGreen – Full ProtectionAmber – Partial Protectionred – No Protection
Service lED (red): LED illuminates in the event ofproblem.Thisindicatorislogic-connectedtothePhaseLEDs.ShouldaPhaseLEDgoout,theredServiceLEDwillilluminateandtheAudibleAlarmwillsound.
Test: TestsredServiceLEDandAudibleAlarmregardlessofAlarmSilencestatus;doesnotcycleoptionaldrycontacts
Alarm Silence: TurnsAudibleAlarmoff(AudibleAlarmisdeactivatedwhenLEDisilluminated)
Surge Counter Count: (if equipped) Increments optional surgecounterbyone(+1)
Surge Counter Reset: (if equipped) Resets optional surge counter to zero (0)
If an inoperative conditionwhere to occur, the built-inaudible alarmwill soundand the redService LEDwillilluminate. This indicates that the unit needs evaluation byaqualifiedelectricianor technician. Untilaqualifiedperson evaluates the unit, press Alarm Silence to silence thealarm.(TheLEDaboveAlarmSilenceilluminateswhenthe alarm is deactivated. Normal operation occurs with the AlarmSilenceLEDextinguished.)TheredServiceLEDwillremainilluminatedeventhoughtheAudibleAlarmhasbeensilenced.Testteststhered.
oPErATioN
XGA Control and Diagnostics
PanelWith Dual
Surge Counter option
XGA Control and Diagnostics
Panel
Figure 14
Page 10
Dry Contact optionTheXGASeriesisavailablewithoptionalDryContactswhichutilize aDB-9 connector.This feature provides two sets ofnormally open (N.O.) and normally closed (N.C.) contacts throughtheDB-9connector.TheserelaycontactscanbeusedforremoteindicationoftheSPD’soperatingstatus.Examplescould include a computer interface board, an emergencymanagement system, etc. The relay contact pin arrangement isoutlinedinTable2.(Pleasenotethejumperedconnections.Pins 7, 8 & 9 were used to drive an earlier version of the Remote Monitor option. Pins 7, 8 & 9 do not represent a third set of contacts. Pin pairs 4 & 7, 5 & 8, and 6 & 9, are connected via jumperinternally.Thecombinedcurrentofeachpinpairmaynot exceed 1 Ampere).
Supplemental lED indicators on ModulesEachmoduleincludesthreeLEDsperFigure15.ThecentergreenLEDindicatespowerison.ThisgreenLEDshouldbeilluminated during normal operation.
WhentheupperleftredLEDisilluminated,themodule’sL-Gprotection is lost.
WhentheupperrightredLEDisilluminated,themodule’sL-Nprotection is lost.
AnoptionalRemoteMonitor accessory is available thatwill provide visual and audible indication of an alarmcondition.TheRemoteMonitorrequirestheDryContactoptionasitcollectsinformationthroughtheDryContact’sDB-9 connection.Please note that theDB-9 connectoris completely utilized by theoptional remotemonitoringaccessory.IftheRemoteMonitorisused,therewillbenomeans to interface with another device. For customapplicationsusing theDryContacts, pleasenotethefollowinginformation:• TheDryContacts are designed for low voltage or
control signals only.• Maximum switching current is 1 amp.• Maximumswitchingvoltageis24volts,DCorAC.
Higher energy application may require additional relay implementationoutsidetheSPD.DamagetotheSPD’relaycausedby implementationwithenergy levels in excessofthosediscussedinthismanualwillnotbecoveredbywarranty. If you have design questions, please contact APT TechnicalSupportat:1.800.237.4567.
remote Monitor Accessory optionARemoteMonitor is available for remoteannunciation.It requires a standalone 120V power source (wall plug transformer) and uses one set of Form C dry contacts. The RemoteMonitorcanbeconfiguredtomonitorseveralAPTSPDssimultaneously.Installationisdetailedinaseparatedocument. Contact factory as appropriate.
Figure 9Green LED lit: power on
Red LED lit: loss of surge suppression from line to neutral
Red LED lit:loss of surgesuppressionfrom line toground
Figure 15
PiNouT DiAGrAM For Dry CoNTACTS oF SPD
UsingDB-9SyleConnector:
1 Normally Closed2 Common3 Normally Open4 Normally Closed5 Common6 Normally Open7 Connected to Pin 48 Connected to Pin 59 Connected to Pin 6
12345
6789
Form C Set #2
Form C Set #1
Figure 16
MoDulE lEDs
Page 11
MAiNTENANCESPDs requireminimalmaintenance. We recommendperiodic inspection of diagnostic indicators to ensure properoperation.WealsorecommendkeepingtheSPDclean as appropriate.
Troubleshooting & ServicePleasecontactusforanyservicerelatedissues.Wewanttotakecareofanyproblems.
Quality SPDs are designed and tested to withstandsevere duty. However, there are various electrical anomalies that SPDs cannot protect against. Theseare generally Sustained Overvoltages also known as Temporary Overvoltages (TOVs). In this context, Sustained Overvoltagesmaybeonlyafewcycles.FailedSPDstendtobesymptoms,notrootcauses.AfailedSPDshouldbetreatedasa ‘canary in thecoalmine’suggesting furtherinvestigation as theremay be a larger issue at play.Regardlessofcause,SPDsattempttoprotecttheirloaduntil failure.
As noted above, the single largest ‘killer’ of SPDs isreferencetogroundissues.IftheSPDshowsproblemsonstartup,thereisreasonablechanceofbonding/grounding/misapplication issue. This permanently damages the unit. If not corrected, it will happen again.
Tip:VisuallyconfirmN-Gbonding.BeawarethatavoltmetermeasuringN-Gcanbemisleading. Forexample,N-Gvoltagecouldread0Vbecauseneutral and ground are at the same potential purely byhappenstance, not because theyarebonded.Visuallyconfirmbonding.
Tip:Experience indicates that regulation-challengedgenerators can cause Sustained Overvoltages, as well as ungrounded generators, and/or unusual load transfer systems.
Note:PriortoreturningpowerorservicingtheSPD,inspecttheentireSPDforanyotherdamagedcomponents.AnydamagedcomponentsshouldbereplacedpriortoreturningtheSPDtoservice.
Module removal and replacementDisconnect power to the SPD. DISCHARGE INTERNALCAPACITORSBYGROUNDING.Unplug the 10 pin connector fromtheXGAmodule.Usinga7/16"socketwrench,removetheboltsonbothendsofthemodule,andpullthemoduleout.Makenote of the location andpart number of eachmoduleremoved,asthispartnumberisnotreferencedanywhereelseon theSPD.Themodule(s) should only be replacedwith anewmodulebearingthesamepartnumberasthemodule(s)previouslyremoved.Replacewithanewmodulebyreversingtheprocedure.Torqueboltsto65inch-pounds,poweruptheSPDandverifythegreenmoduleLEDislitandallalarmshavebeencleared.
Display/Diagnostic Board removal and replacementDisconnect power to the SPD.Remove the nuts from theswitchesthatsecuretheboardtothepanel,thenremovetheboard.Removetheconnectorsoneatatimefromtheexistingboardandinsertthemintotheappropriateconnectoronthereplacementboard.Installthereplacementboardintothepaneland install the nuts onto the switches and tighten securely.
Notethatasealinggasketbetweenthedisplayandtheenclosureis a key component ensuring weather resistance. Replace the gasket whenever the display is removed.
No Yes
No
No
Yes
No
Yes Yes
No
No
No Yes
Yes
Figure 17 TrouBlE SHooTiNG FloWCHArT
Page 12
TABlE 3: rEPlACEMENT PArTSORDER# DESCRIPTION USEDIN
MA120V090K Module 120VACwithLED90kA
MA220V090K Module 220VACwithLED90kA
MA277V090K Module 277VACwithLED90kA
MA120V130K Module 120VACwithLED130kA
MA220V130K Module 220VACwithLED130kA
MA277V130K Module 277VACwithLED130kA
MA120V160K Module 120VACwithLED160kA
MA220V160K Module 220VACwithLED160kA
MA240V160K Module 240VACwithLED160kA
MA277V160K Module 277VACwithLED160kA
MA347V160K Module 347VACwithLED160kA
MA480V160K Module 480VACwithLED160kA
MA600V160K Module 600VACwithLED160kA
MA120V170K Module 120VACwithLED170kA
MA220V170K Module 220VACwithLED170kA
MA277V170K Module 277VACwithLED170kA
MA120V240K Module 120VACwithLED240kA
MA220V240K Module 220VACwithLED240kA
MA220V240K Module 240VACwithLED240kA
MA277V240K Module 277VACwithLED240kA
MA347V240K Module 347VACwithLED240kA
MA480V240K Module 480VACwithLED240kA
MA600V240K Module 600VACwithLED240kA
ForOrderingFrontDisplayPanel,contactAPTforpartnumber
Corrective Maintenance (repair)APT’sSurgeProtectiveDevices are designed for yearsofreliable,trouble-freeoperation.Unfortunately,eventhemost reliable equipment can become inoperative.On-linediagnosticsarean integral part of theSPDandwillaid in isolating which of the protection module(s) have become inoperative.TokeeptheSPDoperatingatpeakperformance, replacement of any inoperative module(s) should be performedaccording tomodule removal andreplacement instructions at the earliest service opportunity.
Troubleshooting procedures should be used to isolateotherproblemsnotassociatedwithinoperativemodule(s).SeeFigure17,TroubleshootingFlowChartonpage10forassistance. Be sure to replace components with identically ratedpartstocontinueproperoperationandsafety.Table3 lists typical replacement parts.
limited WarrantyAdvancedProtectionTechnologies, Inc.warrants it’sACpanel protection products against defective workmanship andmaterials for 10 years (Optionalwarranty available)fromthedateoforiginalpurchase.TheunitmusthavebeeninstalledbyaqualifiedandlicensedelectricianinordertoqualityforWarrantycoverage.
Liability is limited to the replacement of the defectiveproduct.AReturnAuthorization (RA#) numbermust begivenby thecompanyprior to thereturnofanyproduct.Returned productsmust be sent to the factorywith thetransportation charges prepaid. In addition, the company also warrants unlimited replacement of modular and component parts within the warranty periods previously described. APTspecificallydisclaimsallotherwarranties,expressedorimplied.Additionally,thecompanywillnotberesponsiblefor incidental or consequential damages resulting from any defect in any product or component thereof.
CoNTACT uS
Advanced Protection Technologies14550 58th St. N.
Clearwater, FL 33760
(800) 237-4567(727) 535-6339
Fax (727) 539-8955
www.aptspd.com
AnyreturnsneedaReturnAuthorizationnumber.
UL is a registered trademark of Underwriters Laboratories, NEC® and National Electrical Code are registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002, C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
Preventive Maintenance (inspection and Cleaning)Inspection of theSPDshould be performedperiodically tomaintainreliablesystemperformanceandcontinuedtransientvoltage surge protection.While it is difficult to establish apreventivemaintenanceschedulebecauseconditionsvaryfromlocation to location, inspections for inoperative modules and othersignsoftroubleutilizingthebuilt-indiagnosticsshouldbeperformedonaroutinebasis(weeklyormonthly).
14550 58th Street North · Clearwater, Florida 33760
EuropeanAuthorizedRepresentative:ObelisS.A.
BoulevardGénéralWahis,53B-1030 Brussels
BelgiumTel.:+32.2.732.59.54·Fax:+32.2.732.60.02
Email:[email protected]
8.24.11jb