 TES T V OLTAGES FOR M V , HV  & EH V  C  ABLES  Test Voltages for Medium Voltage Cables 1 2 3 4 5 6 7 8 Rated  Voltage U Highest voltage for equipment Um  Value of  Uo for determination of test voltages Uo Routine test 3.5 Uo  Partial Discharge 1.5 U o Sample Test 4 U o Impulse Test  Voltage Test fo r 15 minutes kV kV kV kV KV KV kV kV 6 10 15 20 30 7.2 12 17.5 24 36 3.6 6 8.7 12 18 12.5 21 30.5 42 63 5.4 9 13 18 27 - 24 35 48 72 60 75 95 125 170 12.5 21 30.5 42 63 PDF created with pdfFactory Pro trial version www.pdffactory.com

Transcript of Test Voltages for Cables

Page 1: Test Voltages for Cables

8/8/2019 Test Voltages for Cables

http://slidepdf.com/reader/full/test-voltages-for-cables 1/3

 

TEST VOLTAGES FOR 

MV, HV &  EHV C ABLES 

Test Voltages for Medium Voltage Cables

1 2 3 4 5 6 7 8

Rated Voltage

U

Highestvoltage forequipment

Um 

 Value of Uo for

determinationof test

voltages

Uo 

Routinetest

3.5 Uo 

PartialDischarge

1.5 Uo 

SampleTest

4 U o 

ImpulseTest

 Voltage Testfo r

15 minutes

kV kV kV kV KV KV kV kV

6

10

15

20

30

7.2

12

17.5

24

36

3.6

6

8.7

12

18

12.5

21

30.5

42

63

5.4

9

13

18

27

-

24

35

48

72

60

75

95

125

170

12.5

21

30.5

42

63

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 2: Test Voltages for Cables

8/8/2019 Test Voltages for Cables

http://slidepdf.com/reader/full/test-voltages-for-cables 2/3

Page 3: Test Voltages for Cables

8/8/2019 Test Voltages for Cables

http://slidepdf.com/reader/full/test-voltages-for-cables 3/3

 

TEST VOLTAGES FOR 

MV, HV &  EHV C ABLES 

Test Voltage for Ext ra High Voltage cables

1 2 3 4 5 6 7 8 9Rated

 Voltage

U

Highestvoltage forequipment

Um

Value of Uo for

determination

of test voltages

Uo

 Voltage test

Volt-

 Dura-

 Age1) tion1)  

Partialdischarge

test

1.5 Uo

Heatingcycle

voltage test

2 Uo

Impulsevoltage test

Voltage test after

impulse voltage test

2Uo

Switchingimpulse Voltage

test

kV kV kV kV min kV kV kV KV K V

220 to 230 245 127 318 30 190 254 1050 254 -

275 to 287 300 160 400 30 240 320 1050 320 850

330 to 345 362 190 420 60 285 380 1175 380 950

380 to 400 420 220 440 60 330 440 1425 440 1050

500 550 290 580 60 435 580 1550 580 11751) A threshold limit of 27 MV/m to 30 MV/m should not be exceeded for some insulations (as specified by the supplier), in order

to avoid any possible weakening to the insulation prior to delivery which might later cause a failure in service . At the voltagetest of (4), for rated voltage 330 kV to 500 kV, the voltage is lowered, combined with a longer testing time in order to avoid

too high stresses. For insulations where a threshold limit is not a problem, the supplier may increase the test voltage and

reduce the testing time. However, the duration should be at least 30 min.