TEST REPORT Report No.: B8572.02‐201‐47

57
TEST REPORT Report No.: B8572.02‐201‐47 Rendered to: ANDERSEN CORPORATION Bayport, Minnesota PRODUCT TYPE: Mullion SERIES/MODEL: 100 Series LVL Mullion SPECIFICATION: AAMA 450‐10, Voluntary Performance Rating Method for Mulled Fenestration Assemblies Title Summary of Results Air Infiltration 0.20 L/s/m 2 (0.04 cfm/ft 2 ) Water Resistance Test Pressure 220 Pa (4.5 psf) Uniform Load Deflection Test Pressure +1440/‐1680 Pa (+30/‐35 psf) Uniform Load Structural Test Pressure +2160/‐2520 Pa (+45.0/‐52.5 psf) Reference must be made to Report No. B8572.02‐201‐47, dated 05/11/12 for complete test specimen description and detailed test results. Architectural Testing

Transcript of TEST REPORT Report No.: B8572.02‐201‐47

TEST REPORT  

Report No.:  B8572.02‐201‐47  

Rendered to:  

ANDERSEN CORPORATION Bayport, Minnesota 

 PRODUCT TYPE:  Mullion 

SERIES/MODEL:  100 Series LVL Mullion  

SPECIFICATION:  AAMA 450‐10, Voluntary Performance Rating Method for Mulled Fenestration Assemblies 

 Title  Summary of Results 

Air Infiltration  0.20 L/s/m2 (0.04 cfm/ft2) Water Resistance Test Pressure  220 Pa (4.5 psf) 

Uniform Load Deflection Test Pressure  +1440/‐1680 Pa (+30/‐35 psf) Uniform Load Structural Test Pressure  +2160/‐2520 Pa (+45.0/‐52.5 psf) 

           Reference must  be made  to  Report  No.  B8572.02‐201‐47,  dated  05/11/12  for  complete test specimen description and detailed test results.  

Architectural Testing

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 1 of 8 

1.0 Report Issued To:  Andersen Corporation   100 Fourth Avenue North   Bayport, Minnesota 55003‐1096  2.0 Test Laboratory:  Architectural Testing, Inc.   849 Western Avenue North   St. Paul, Minnesota 55117   651‐636‐3835  3.0 Project Summary: 

3.1 Product Type:  Mullion 

3.2 Series/Model:  100 Series LVL Mullion 

3.3 Compliance Statement:   Results obtained are tested values and were secured by using  the designated  test methods.   The overall  design pressure assigned  to  this mulled assembly is +1440/‐1680 Pa (+30/‐35 psf) for a Class LC­PG+30/35 MA: Size Tested 95.5" Span/59.4 ft2 rating.  The rating was determined in accordance with AAMA 450‐10, Option (1).  The AAMA 450 rating options are shown below: 

AAMA 450­10 RATING OPTIONS 

Rating Options Option 1 Test Total 

Assembly Configuration 

Option 2 Testing Mullion Elements as Individual Components 

Option 3 Structural Calculations by P.E. 

Air and Water Test Required?  Yes  Yes  Yes 

Deflection Limit During Application of Design 

Pressure Load? 

No requirement for R and LC ratings. 

L/175 for CW and AW ratings.Yes  Yes 

Permanent Set Limit of Span After Application 

and Removal of Structural Test Pressure? 

0.4% for R and LC ratings. 0.3% for CW ratings 0.2% for AW ratings 

Yes  No 

Professional Engineer to Sign and Seal?  No  Yes  Yes 

Separate Anchorage Calculations Required?  No  Yes  Yes 

Product Grouping Permitted? 

Yes  Yes  Yes 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 2 of 8 

3.0 Project Summary:  (Continued) 

3.4 Test Date:  04/04/2012 

3.5 Test  Location:    Test  Location:    Andersen  Corporation  test  facility  in  Bayport, Minnesota.  Calibration of test equipment was performed by Architectural Testing in accordance with AAMA 205‐01 "In‐Plant Testing Guidelines  for Manufacturers and Independent Laboratories". 

3.6 Test  Sample  Source:    The  test  specimen  was  provided  by  the  client.  Representative  samples  of  the  test  specimen  will  be  retained  by  Architectural Testing for a minimum of four years from the test completion date. 

3.7 Drawing  Reference:    The  test  specimen  drawings  have  been  reviewed  by Architectural Testing and are representative of the test specimen reported herein.  Test specimen construction was verified by Architectural Testing per the drawings located in Appendix C.  Any deviations are documented herein or on the drawings. 

3.8 List of Official Observers: 

Name  Company 

Joe Brummer  Andersen Corporation Karl Lips‐Eakins  Architectural Testing, Inc. 

 4.0 Test Methods:  The test specimen was evaluated in accordance with the following: 

 AAMA  450‐10,  Voluntary  Performance  Rating  Method  for  Mulled  Fenestration Assemblies.  ASTM  E  283‐04,  Test  Method  for  Determining  Rate  of  Airflow  Through  Exterior Windows,  Curtain  Walls  and  Doors  Under  Specified  Pressure  Differences  Across  the Specimen.  ASTM E 330‐02, Test Method  for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference.  ASTM E 331‐00(2009), Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference.  ASTM E 547‐00(2009), Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Cyclic Static Air Pressure Difference. 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 3 of 8 

4.0  Test Methods:  (Continued)  

4.1 Mullion Grouping:   Grouping of mulled  fenestration assemblies  is allowed  for  the purpose  of  qualifying  multiple  designs  with  a  single  evaluation.    A  licensed professional  engineer  shall  review  all  mulled  fenestration  assemblies  within  the manufacturer's  specified  grouping  in  order  to  determine  the  weakest  and/or minimal performing product. 

 5.0 Test Specimen Description:  

5.1 Product Sizes:  

Width  Height Overall Area: 5.7 m² (59.4 ft2)  inches  millimeters  inches  millimeters Overall mulled fenestration assembly size 

95‐1/2  2524  89‐1/2  2273 

Mullion Size  1/2  13  89‐1/2  2273 Individual window size 

47‐1/2  1206  89‐1/2  2273 

 5.2 Mullion Construction:   Mullion Member 

Material  Description 

Center beam Pultruded fiberglass 

13 x 83 mm (1/2" x 3‐1/4") pultrusion beam. Mull side flange removed, frames put together, and fastened with #8 x 2‐3/4" screws through frame  into  mull  101  mm  (4")  from  ends  and 203‐254  mm  (8‐10")  on  center,  alternating sides.   A  gusset plate was utilized  at  the head and sill, sealed with a gasket and silicone, and was  attached with  twelve  #8  x  1"  PH  screws.  The  exterior  joint  was  sealed  full  length  with two  beads  of  silicone.  A  snap  in  PVC  trim covered both interior and exterior. 

 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 4 of 8 

 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 5 of 8 

5.0  Test Specimen Description:  (Continued)  5.3 Frame Construction:  

Frame Member  Material  Description 

Frame members  Composite  Co‐extruded  Fibrex  Composite  material  with white PVC capstock. 

   Joinery Type  Detail 

All corners  Mitered  Corner key held with hot melt adhesive.  5.4 Sash Construction:  Sash Member  Material  Description 

All members  Composite  Co‐extruded  Fibrex  Composite  material  with white PVC capstock. 

   Joinery Type  Detail 

All corners  Mitered  Corner key held with hot melt adhesive.  5.5 Weatherstripping:  

Description  Quantity  Location Poly‐pile w/ center and side fins 1 Row  Perimeter of operable sash. 

Poly‐pile w/ center and side fins 1 Row  Meeting rail of fixed sash.  5.6 Glazing:  Glass Type 

Spacer Type Interior Lite 

Exterior Lite 

Glazing Method 

19 mm (0.75") IG 

Desiccant filled metal 

3.1 mm annealed  

3.1 mm annealed 

The glass was set from the exterior against  silicone  backbedding  and stopped with a vinyl snap‐in, duo‐durometer glazing bead. 

 Daylight Opening 

Location  Quantity millimeters  inches 

Glass Bite 

Operable sash  2  1047 x 673  41‐1/4 x 26‐1/2  12.7 mm 

Fixed lite  2  1047 x 1381  41‐1/4 x 54‐3/8  12.7 mm 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 6 of 8 

5.0  Test Specimen Description:  (Continued)  5.7 Drainage: 

Drainage Method  Size  Quantity  Location 

Weep w/cover 

28 mm x 6 mm 

(1‐1/8" x 1/4") 

2 per unit 102  mm  (4")  from  frame  corner  on exterior sill face. 

Weep hole  13 mm (1/2") dia. 

2 per unit  102 mm (4") from frame corner in sill track to hollow below. 

5.8 Hardware: 

Description  Quantity  Location Latch‐type lock  1 per sash  Mid‐span of meeting rail. 

Spring balance  2 per unit  Side jambs.  5.9 Reinforcement: 

Drawing Number  Location  Material 1051A  Fixed meeting rail  Galvanized steel. 

 5.10 Screen Construction:  

Frame Material  Corner Construction  Mesh Type  Mesh Attachment Method Roll formed aluminum  Miter‐cut and keyed  Fiberglass 

mesh  Spline. 

6.0 Installation: 

The  specimen  was  installed  into  a  Spruce‐Pine‐Fir  wood  buck.    The  rough  opening allowed for a 3/8" shim space.  The exterior perimeter of the window was sealed with tape.  Location  Anchor Description  Anchor Location 

Nail flange  #6 x 1‐5/8" drywall screw At  corners  and  between  every hole spaced 89 mm (3‐1/2") on center. 

Gusset plate  #8 x 2" TH screw  Two  screws  through  gusset plate at head and sill. 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 7 of 8 

7.0 Test  Results:    The  temperature  during  testing  was  20C  (68°F).    The  results  are tabulated as follows: 

Title of Test  Results  Allowed  Note 

Initiate motion: 120 N (27 lbf)  Report Only   

Maintain motion: 134 N (30 lbf)  155 N (35 lbf) max.   

Latches: 18 N (4 lbf)  100 N (22.5 lbf) max.   

Operating Force, per ASTM E 2068 

Locks: 18 N (4 lbf)  100 N (22.5 lbf) max.   

Air Leakage, Infiltration per ASTM E 283 

at 75 Pa (1.6 psf) 0.20 L/s/m2 (0.04 cfm/ft2) 

1.5 L/s/m2 (0.3 cfm/ft2) max.  1 

     Water Penetration, per ASTM E 547 at  220 Pa (4.5 psf)  Pass  No leakage  2 

     Uniform Load Deflection,  

per ASTM E 330 taken at the mullion +1440 Pa (+30.0 psf) ‐1680 Pa (‐35.0 psf) 

23.6 mm (0.93") 28.4 mm (1.12")  Report Only   3, 4, 5 

     Uniform Load Structural, 

per ASTM E 330 taken at the mullion +2160 Pa (+45.0 psf) ‐2520 Pa (‐52.5 psf) 

0.5 mm (0.02") 2.5 mm (0.10") 

9.1 mm (0.36") max. 9.1 mm (0.36") max.  4, 5 

Note  1:    The  tested  specimen meets  (or  exceeds)  the  performance  levels  specified  in AAMA/WDMA/CSA 101/I.S.2/A440 for air leakage resistance.  Note 2:  With and without insect screen.  Note 3:   The deflections reported are not  limited by AAMA/WDMA/CSA 101/I.S.2/A440 for  this product designation.   The deflection data  is  recorded  in  this  report  for  special code compliance and information only.  Note 4:  Loads were held for 10 seconds.  Note 5:  Tape and film were used to seal against air leakage during structural testing.  In our opinion, the tape and film did not influence the results of the test. 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 Page 8 of 8 

The service life of this report will expire on the stated Test Record Retention End Date, at which  time such materials as drawings, data  sheets,  samples of  test  specimens,  copies of this  report,  and  any  other  pertinent  project  documentation,  shall  be  discarded  without notice.  If  test  specimen  contains  glazing,  no  conclusions  of  any  kind  regarding  the  adequacy  or inadequacy  of  the  glass  in  any  glazed  test  specimen  can  be made.    This  report  does  not constitute certification of this product nor an opinion or endorsement by this laboratory.  It is  the  exclusive property of  the  client  so named herein  and  relates only  to  the  specimen tested.  This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc.  For ARCHITECTURAL TESTING, Inc.     _________________________________________  _________________________________________ Karl A. Lips‐Eakins  Daniel A. Johnson Senior Technician  Director, Regional Operations  KLE/jb  Attachments (pages):  This report is complete only when all attachments listed are included.   Appendix‐A:  Alteration Addendum (1)   Appendix‐B:  WDMA Submittal forms (2)   Appendix‐C:  Drawings (32)   Appendix‐D:  Installation Guidelines (10)               This report produced from controlled document template ATI 00517, issued 03/02/11. 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 

  

Appendix A  

Alteration Addendum  

Note:  No alterations were required. 

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 

  

Appendix B  

WDMA Submittal Forms 

www.archtest.com

WDMA HALLMARK CERTIFICATION PROGRAM REPORT SUBMISSION FORM THIS FORM IS TO BE COMPLETED BY THE MANUFACTURER AND SUBMITTED TO AMS ALONG WITH SUBMISSION OF EACH NEW OR REVISED TEST REPORT FOR CERTIFICATION TO THE HALLMARK PROGRAM. ANY QUESTIONS PLEASE CONTACT AMS AT 315-646-2234 OR [email protected].

Manufacturer: Andersen Corporation Contact: Alan Barstad Plant Location(s) (list all plants where product is made):

Phone: 651-264-5308

3801 Regency Crest Drive Garland, TX 75041

Test Report Number: B8572.02-201-47 Email: [email protected]

Product Relationship:

Extension of Currently certified product? yes no If yes, what CCL

Extension of currently pending product? yes no If yes, what test report #?

Difference from Certified Product:

Does this report require a Gateway Report #? yes no Report #:

Impact Report:

If this is not a impact report check here: no

AWS Report # Impact Report #

Test Plan #? yes no

Installation Instructions submitted? yes no

Additional Information:

WDMA HALLMARK CERTIFICATION PROGRAM REPORT SUBMISSION FORM

Product Name: (As to be listed on CCL – must match test report)

100 Series LVL Mullion

Product Type: Mullion Additional Manufacturer ID #: 129-4 n/a Check here for Individual listing yes no Check here for full CCL listing yes no

Hallmark CCL Standard Rating

ANSI/AAMA/NWWDA 101/I.S. 2 97

101/I.S.2/NAFS-02

AAMA/WDMA/CSA/101/I.S.2/A440-05

AAMA/WDMA/CSA/101/I.S.2/A440-08

ASTM E 1996 99 / E1886-97

ASTM E 1996 01 / E1886-97

ASTM E 1996 02 / E1886-02

ASTM E 1996 03 / E1886-02

ASTM E 1996 04 / E1886-04

ASTM E 1996 05 / E1886-05

ASTM E330 02

TAS 201-94

TAS 202-94

TAS 203-94

AAMA 450-10 Class LC-PG+30/35 MA: Size Tested 95.5” Span/59.4ft2

Other:

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 

  

Appendix C  

Drawings  

www.archtest.com

Test Report No.:  B8572.02‐201‐47 Report Date:  05/11/12 

Test Record Retention End Date:  04/04/16 

  

Appendix D  

Installation Guidelines  

www.archtest.com