Test Report PV n°79_12 Performed by : A.BOINON Signature of approving officer: Date : 04/12/2012 Page n°1/ 5 TYPE TEST REPORT Mechanical test – Tensile test ACCC AMSTERDAM IEC 61284 Clause 11.5.1 I Product reference Project: Cable ACCC AMSTERDAM Cable: Cable ACCC AMSTERDAM Ø 23.55mm, RTS 122.8 Designation and reference of the product: Compression deadend: CCTC ACCC AMSTERDAM Compression midspan joint: JXFK ACCC AMSTERDAM Drawing reference: Compression deadend: CCTC ACCC AMSTERDAMa Compression midspan joint: JXFK ACCC AMSTERDAMa II Test purpose Type test are intended to prove conformance of fittings to applicable standards and/or specific requirementstechnical specifications. Mechanical tensile test to validate mechanical properties of fittings. III Standard reference IEC 61284 (199709): Standard Overhead Line Requirements and tests for fittings WI750031: Specification for Qualifying ACCC Accessory Manufacturers IV Conclusion The test results are satisfactory and meet the requirements of the applicable standard and technical specification for all the fittings mentioned previously. Tensile test results: the failure occurs at 122.1kN, 99.4% of the RTS (above 95% of the RTS)

Transcript of Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐...

Page 1: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

 

Test Report PV n°79_12

Performed by : 

A.BOINON 

Signature of approving officer:   Date :  

04/12/2012 Page n°1/ 5 

 

TYPE TEST REPORT Mechanical test – Tensile test

ACCC AMSTERDAM IEC 61284 Clause 11.5.1

 

I Product reference Project:  Cable ACCC AMSTERDAM  

Cable:    Cable ACCC AMSTERDAM Ø 23.55mm, RTS 122.8 

Designation and reference of the product:  

‐ Compression dead‐end:    CCTC ACCC AMSTERDAM 

‐ Compression mid‐span joint:  JXFK ACCC AMSTERDAM 

Drawing reference: 

‐ Compression dead‐end:    CCTC ACCC AMSTERDAM‐a  

‐ Compression mid‐span joint:  JXFK ACCC AMSTERDAM‐a  

 

II Test purpose Type  test  are  intended  to  prove  conformance  of  fittings  to  applicable  standards  and/or 

specific requirements‐technical specifications. 

‐ Mechanical tensile test to validate mechanical properties of fittings. 

 

III Standard reference ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI‐750‐031: Specification for Qualifying ACCC Accessory Manufacturers  

IV Conclusion The test results are satisfactory and meet the requirements of the applicable standard and 

technical specification for all the fittings mentioned previously.  

Tensile test results:   the failure occurs at 122.1kN, 99.4% of the RTS (above 95% of the RTS) 

Page 2: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

 

Test Report PV n°79_12

Performed by : 

A.BOINON 

Signature of approving officer:   Date :  

04/12/2012 Page n°2/ 5 

 

V Test procedures

1. Characteristic of the sample Characteristic: ACCC AMSTERDAM, Ø23.55, RTS 122.8kN, 15m. 

Ambient temperature: 22°C 

 

2. Measuring device Tensile test machine 1000kN, checked 05/06/2012, with report n°1204166‐6 

 

3. Mechanical tensile test - IEC 61284 Clause 11.5.1  

Guarantee:  Breakage above 95% of the RTS    

Comment:  The  sample  is  installed  in  the  tensile  test machine,  the  load  shall be  raised 

gradually until 20% of  the RTS of  the conductor, and a mark  is made on  the conductor  to 

detect the movement. Then the load is raised gradually until 60% of the RTS. And finally the 

load shall be increases until failure occurs. 

 

VI Results  

Installation of the sample in the tensile test machine.

The load is raised until 20% of the RTS, and a mark is made on the conductor to detect the movement. 

 

 

 

Compression Dead‐end

Compression Mid‐span

Page 3: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

 

Test Report PV n°79_12

Performed by : 

A.BOINON 

Signature of approving officer:   Date :  

04/12/2012 Page n°3/ 5 

 

The load is raised until 60% of the RTS, no slippage occurs.

 

 

The  load  is raised until the failure which occurs at 122.1kN (99.4% of the RTS). Breaking of the  composite  core,  between  the  dead  end  and  the  Mid‐span,  in  the  middle  of  the conductor. 

 

 

 

 

 

 

Page 4: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

 

Test Report PV n°79_12

Performed by : 

A.BOINON 

Signature of approving officer:   Date :  

04/12/2012 Page n°4/ 5 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ANNEX  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 5: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

 

Test Report PV n°79_12

Performed by : 

A.BOINON 

Signature of approving officer:   Date :  

04/12/2012 Page n°5/ 5 

 

1. Mechanical tensile test

 

Page 6: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

20

Alliage alu Jonc rond

23.55 mm 418.47 mm² 122.8 KNAMSTERDAM

RéférenceConducteur

Diamètreextérieur

SectionTotal

CompositionRésistanceMécanique

UltimateStrength

Stranding

ConductorName

OverallDiameter

TotalAera DiaNb Nb

812

4.86T4.87T

Alu Alloy Core round

Dia eq

Courant permanentadmissible maxi

Température maxi

Ampacity maxi

Temperature maxi

1405 A

180 °C1 7.75

Rep. Qty Désignation MaterialMatièreDescription1 1 CHAPE FORGED GALVA STEELACIER FORGE GALVACLEVIS BOLT

2 1 TUBE ALUMINIUM ALLOYALLIAGE ALUMINIUMOUTER SLEEVE

3 1 HOUSING & COLLET HOUSING & COLLET

4 1 PLAGE ALUMINIUM ALLOYALLIAGE ALUMINIUMPAD

5 1 FOURRURE ALUMINIUM ALLOYALLIAGE ALUMINIUMINNER SLEEVE

6 1 CABLE CABLE

50

Grease PROXALU HT MELT POINT >300°

95%U.T.S.Résistance du conducteur

of the conductor

MarkingMarquage DERVAUX ACCC AMSTERDAM

H50.5U PROXALUHT

Dead end clamps are delivered with grease.Les manchons sont livrés avec pot de graisse.

Die to useMatrice à utiliser

03/

10/2

012

b aLB P

arD

ate

Mo

dific

atio

nR

ev

- Cré

atio

n du

pla

n.

--

1 2 3 4 5 6

56

.5

34

.0

26

.0

50

.5

7 9 0

THIS DOCUMENT INCLUDING ALL INTELLECTUAL PROPERTY RIGHTS CONNECTED THEREWITH ARE OUR OWNERSHIP.IT IS GIVEN TO YOU ON A CONFIDENTIAL BASIS AND CANNOT BE USED, REPRODUCED, COMMUNICATED AND/OR MODIFIED (etc.)WITHOUT OUR PRIOR WRITTEN APPROVAL.

DEAD ENDCLAMP

C CTC ACCC AMSTERDAM

ORIGINELAYOUT

DATE :

DATE :EXECUTED BY :

CHECKED BY :

MODIFY BY :

SCALE :

ALL DIMENSIONS IN MM

L B 03/10/2012

CCTCACCCAMSTERDAM a

MANCHOND'ANCRAGE

Allee Ampere Z.I. Le Bec - 42501 LE CHAMBON FEUGEROLLES

Page 7: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

03/

10/2

012

b aLB P

arD

ate

Mo

dific

atio

nR

ev

- Cré

atio

n du

pla

n.

--

MarkingMarquage DERVAUX ACCC AMSTERDAM

H50.5U PROXALUHT

Dead end clamps are delivered with grease.Les manchons sont livrés avec pot de graisse.

95%U.T.S.Résistance du conducteur

of the conductor

6 1234

1 4 3 5

56

.5 34

26

Rep. Qty Désignation MaterialMatièreDescription1 1 FOURRURE ALUMINIUM ALLOYALLIAGE ALUMINIUMINNER SLEEVE

2 1 TUBE ALUMINIUM ALLOYALLIAGE ALUMINIUMOUTER SLEEVE

3 1 HOUSING & COLLET HOUSING & COLLET

4 1 HOUSING+COUPLER ASSEMBLY HOUSING+COUPLER ASSEMBLY

6 1 CABLE CABLE

Die to useMatrice à utiliser

50

.5

Alliage alu Jonc rond

23.55 mm 418.47 mm² 122.8 KNAMSTERDAM

RéférenceConducteur

Diamètreextérieur

SectionTotal

CompositionRésistanceMécanique

UltimateStrength

Stranding

ConductorName

OverallDiameter

TotalAera DiaNb Nb

812

4.86T4.87T

Alu Alloy Core round

Dia eq

Courant permanentadmissible maxi

Température maxi

Ampacity maxi

Temperature maxi

1405 A

180 °C1 7.75

THIS DOCUMENT INCLUDING ALL INTELLECTUAL PROPERTY RIGHTS CONNECTED THEREWITH ARE OUR OWNERSHIP.IT IS GIVEN TO YOU ON A CONFIDENTIAL BASIS AND CANNOT BE USED, REPRODUCED, COMMUNICATED AND/OR MODIFIED (etc.)WITHOUT OUR PRIOR WRITTEN APPROVAL.

MIDSPANJOINT

JXFKACCCAMSTERDAM

ORIGINELAYOUT

DATE :

DATE :EXECUTED BY :

CHECKED BY :

MODIFY BY :

SCALE :

ALL DIMENSIONS IN MM

L B 03/10/2012

JXFKACCCAMSTERDAM a

MANCHON DEJONCTION

Allee Ampere Z.I. Le Bec - 42501 LE CHAMBON FEUGEROLLES

Page 8: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...

DATA SHEET:

AMSTERDAM

Version 1, 10/10/'08

Conductor Type

Code Name

Conductor values:

Nominal aluminium equivalent area mm²

Nominal Cross-sectional area of aluminium mm²

Nominal Cross-sectional area of Core mm²

Number, diameter and type of Core #, mm 1 7,75 R CC

Number, (eq.) diameter and type of wire in layer 1 #, mm 8 4,86 T Al

Number, (eq.) diameter and type of wire in layer 2 #, mm 12 4,87 T Al

Minimum filling factor of the aluminium cross section %

Lay ratio of inner layer(s)

Lay ratio of outer layer

Overall diameter mm

Diameter of Core mm

Diameter tolerance of Core mm

Rated Tensile Strength of Conductor (RTS as per ASTM B 857) * kN

Extreme Load Safety Strength of Conductor (with 40% of the aluminium strength) ** kN

Rated Tensile Strength of Core kN

Nominal Mass per unit length - Total kg/km

Nominal Mass per unit length - Aluminium kg/kmNominal Mass per unit length - Core kg/km

DC resistance at 20 °C (nominal) Ohm/km

DC resistance at 20 °C (maximum) Ohm/km

DC current rating at maximum continuous surface Operating Temperature ***(calculated with maximum DC resistance at 20°C)

A, °C

Maximum allowable continuous operating temperature (surface) °CMaximum allowable continuous operating temperature (core) °C

Coefficient of linear expansion above thermal kneepoint / KCoefficient of linear expansion below thermal kneepoint / K

Modulus of elasticity above thermal kneepoint GPa

Modulus of elasticity below thermal kneepoint GPa

Individual wires:

Resistivity of aluminium at 20 °C (maximum) nohmm

Minimum tensile strength, aluminium wire MPa

Standard applied for conductor manufacturer: EN50182

* Note ASTM calculates aluminium strength at 96% of the minimum Tensile Strength of the aluminium wire

** This safety strength is recommended where sustained loads of over 80% of the RTS are expected forprolonged periods. For further information, please see the ACCC Conductor Technical Note TN-750-001.

*** Conditions: Wind : 0,6m/s; emissivity=abs.Coef.=0,5; sun radiation : 1000W/m²; Ambient temperature: 25°C

LF ACCC 380

122,8

0,00000161

1405 175

10-14

7,75

175

101,9

0,0769

AMSTERDAM

384

371,3

87,0

0,0754

± 0,06

93

23,55

110,6

1113,0

1026,0

47,2

10-16

0,0000185

58,6

118,6

63,6

27,35

180

Page 9: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 10: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 11: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 12: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 13: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 14: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 15: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...
Page 16: Test Report PV n°79 12 - CTC Global · ‐ IEC 61284 (1997‐09): Standard ‐ Overhead Line ‐ Requirements and tests for fittings ‐ WI ...