CONFIDENTIAL CLB21103 BACHELOR IN CHEMICAL ENGINEERING TECHNOLOGY TEST 1 SEPTEMBER SEMESTER 2014 16 OCTOBER 2014 COURSE CODE : CLB 21103 COURSE : PROCESS INSTRUMENTATION DURATION : 1 HOUR NAME : ……………………………………………………………… ID NUMBER : ……………………………………………………………… SPECIALIZATION : ……………………………………………………………… INSTRUCTIONS TO CANDIDATES: 1. Answer ALL questions. THIS QUESTION SHEET CONSISTS OF 3 PRINTED PAGES INCLUDING THIS PAGE. ATTENTION: DO NOT OPEN THIS BOOKLET UNTIL PERMISSION IS GIVEN TO DO SO. UNIVERSITI KUALA LUMPUR MALAYSIAN INSTITUTE OF CHEMICAL & BIOENGINEERING TECHNOLOGY

description

21120

Transcript of TEST 1

  • CONFIDENTIAL CLB21103

    BACHELOR IN CHEMICAL ENGINEERING TECHNOLOGY

    TEST 1

    SEPTEMBER SEMESTER 2014 16 OCTOBER 2014

    COURSE CODE : CLB 21103

    COURSE : PROCESS INSTRUMENTATION

    DURATION : 1 HOUR

    NAME :

    ID NUMBER :

    SPECIALIZATION :

    INSTRUCTIONS TO CANDIDATES:

    1. Answer ALL questions.

    THIS QUESTION SHEET CONSISTS OF 3 PRINTED PAGES INCLUDING THIS PAGE. ATTENTION: DO NOT OPEN THIS BOOKLET UNTIL PERMISSIO N IS GIVEN TO DO SO.

    UNIVERSITI KUALA LUMPUR

    MALAYSIAN INSTITUTE OF CHEMICAL & BIOENGINEERING TECHNOLOGY

  • CONFIDENTIAL CLB21103

    1

    QUESTION 1

    a) What is the pressure 35.0 m below the surface of a lake? Atmospheric pressure (the

    pressure at the surface is 10.4 m H2O, and the density of water is 1000.0 kg/m3 (Assume

    that g is 9.807m/s2).

    (2 marks)

    b) Define each term below:

    i. Sensitivity

    ii. Instrument

    iii. Repeatability

    iv. Accuracy

    (4 marks)

    c) Given the lowest value of measurement in pressure sensor transmitter is 35 psig

    meanwhile the highest value is 60 psig. By referring to the statement, define and

    determine the value of

    i. Range of instrument

    ii. Span of instrument

    iii. Zero of instrument

    (6 marks)

    d) Label the following P & ID:

    (5 marks)

    (i)

    (ii) (iii)

    (iv)

    (v)

  • CONFIDENTIAL CLB21103

    2

    QUESTION 2 Both transducers and transmitters convert energy from one form to another and give an output

    signal. The signal is directed to any device that interprets it and uses it to display record or alter

    the pressure in a system.

    (a) Give 3 examples of transducer signal.

    (3 marks)

    (b) Data in Table 1 are obtained from calibration table of a pressure transmitter. By

    using the theoretical output as the reference, determine the accuracy (E) and

    deviation (F), followed by determining either the calibration are passed or failed (H).

    A B C D E F G H

    Input Pressure

    Applied (psig at

    % of Calibration

    Range)

    Output

    Pressure

    (psig)

    Measured

    Output

    (mA)

    Theoritical

    Output

    (mA)

    % Accuracy

    ( 100 % Deviation

    ( 20 4 100 Dev.

    Limit

    Remarks

    (Pass /

    Fail)

    7.50 at 25.0% 7.50 8.01 8.00 (i) (ii)

    0.075 (iii)

    15.00 at 50.00% 15.00 12.01 12.00 (iv) (v)

    0.075 (vi)

    22.50 at 22.5% 22.50 16.02 16.00 (vii) (viii)

    0.075 (ix)

    (9 marks) (c) Explain THREE (3) methods of pressure measurement maintenance.

    (6 marks)

    End of question paper