P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 220–230 © 2013 WIT Press, www.witpress.com ISSN: 2041-9031 (paper format), ISSN: 2041-904X (online), http://journals.witpress.com DOI: 10.2495/SAFE-V3-N3-220-230 TEMPERATURE ASSESSMENT ON FIRE RESISTANCE EXPERIMENTS OF PARTIALLY ENCASED BEAMS P.A.G. PILOTO 1 , A.B.R. GAVILÁN 2 & L.M.R. MESQUITA 1 1 Department of Applied Mechanics, Polytechnic Institute of Bragança, Bragança, Portugal. 2 Department of Mechanical Engineering, University of Salamanca, Zamora, Spain. ABSTRACT Twelve fire resistance tests, grouped in four series, were developed using partially encased beams (PEBs) without concrete slab, for different load levels and shear condition. PEBs were built with stan- dard hot rolled IPE100 profile and reinforced concrete between flanges. Fire resistance was determined for standard ISO834 nominal fire curve, using small fire resistance furnace and portal frame. Tem- perature was measured in three different sections along PEB length (S1, S2, S3), for three different materials (steel, concrete and reinforcement). Average temperature in each section and material was compared with the average temperature over length. Each series presented similar results, with good reproducibility. Special focus was given to critical temperature. The maximum temperature difference between sections and the average temperature of element length is smaller than 3.2%, 5.1%, 6.3% and 11.2%, for test series 1, 2, 3 and 4, respectively. Temperature is not uniform in cross-section. After the initial heating stage, temperature revealed a constant difference of approximately 150°C between temperatures measured inside and outside, defining two main temperature evolutions. Temperatures measured outside revealed always higher temperature level. Keywords: Critical temperature, fire resistance, partially encased beams 1 INTRODUCTION Partially encased beams (PEBs) are elements in which the web of the steel section is encased by reinforced concrete. They are usually built-up with I-Shape or H-shape steel sections; however, they can also be constructed from thin-walled built-up sections. These elements are casted in the floor, and once the concrete cured, section behaves with composite action. Con- crete between flanges provides several advantages over a steel beam, increasing fire-resistance, load bearing and stiffness, without enlarging the overall size of the cross-section. The increasing weight and cost represent two main disadvantages. PEBs have been widely tested at room temperature, but only a small number of experi- ments under fire conditions are reported. Kindmann et al. [1] performed 13 tests on PEB with and without concrete slabs. Elements were built with HEAA400, showing the importance of the reinforced concrete between flanges in determining the ultimate bending moment. This research caused the revision of Eurocode 4 (pre-standard) for the design of partially encased composite beams, to include the effect of the encased material for load bearing resistance and deflection. Hosser et al. [2] carried out four experimental tests on simply supported composite PEB, connected to reinforced concrete slabs, under fire conditions. The research developed three-dimensional analytical model, sufficiently reliable in accuracy, to estimate the effective slab width. In 1995, Plumier et al. [3] performed 12 full sized test joint specimens under cyclic loading, consisting of PEC connected to PEB. Authors concluded that neither the connection type (welded, bolted) nor the web thickness affected the performance of the specimen. Authors have also observed that yielding took place in the beams and that beam flanges always buckled outward due to the presence of concrete.

Transcript of TEMPERATURE ASSESSMENT ON FIRE … 4 (pre-standard) for the design of partially encased ... and...

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 220–230

© 2013 WIT Press, www.witpress.comISSN: 2041-9031 (paper format), ISSN: 2041-904X (online), http://journals.witpress.comDOI: 10.2495/SAFE-V3-N3-220-230

TEMPERATURE ASSESSMENT ON FIRE RESISTANCE EXPERIMENTS OF PARTIALLY ENCASED BEAMS

P.A.G. PILOTO1, A.B.R. GAVILÁN2 & L.M.R. MESQUITA1

1Department of Applied Mechanics, Polytechnic Institute of Bragança, Bragança, Portugal.2Department of Mechanical Engineering, University of Salamanca, Zamora, Spain.

ABSTRACTTwelve fi re resistance tests, grouped in four series, were developed using partially encased beams (PEBs) without concrete slab, for different load levels and shear condition. PEBs were built with stan-dard hot rolled IPE100 profi le and reinforced concrete between fl anges. Fire resistance was determined for standard ISO834 nominal fi re curve, using small fi re resistance furnace and portal frame. Tem-perature was measured in three different sections along PEB length (S1, S2, S3), for three different materials (steel, concrete and reinforcement). Average temperature in each section and material was compared with the average temperature over length. Each series presented similar results, with good reproducibility. Special focus was given to critical temperature. The maximum temperature difference between sections and the average temperature of element length is smaller than 3.2%, 5.1%, 6.3% and 11.2%, for test series 1, 2, 3 and 4, respectively. Temperature is not uniform in cross-section. After the initial heating stage, temperature revealed a constant difference of approximately 150°C between temperatures measured inside and outside, defi ning two main temperature evolutions. Temperatures measured outside revealed always higher temperature level.Keywords: Critical temperature, fi re resistance, partially encased beams

1 INTRODUCTIONPartially encased beams (PEBs) are elements in which the web of the steel section is encased by reinforced concrete. They are usually built-up with I-Shape or H-shape steel sections; however, they can also be constructed from thin-walled built-up sections. These elements are casted in the fl oor, and once the concrete cured, section behaves with composite action. Con-crete between fl anges provides several advantages over a steel beam, increasing fi re-resistance, load bearing and stiffness, without enlarging the overall size of the cross-section. The increasing weight and cost represent two main disadvantages.

PEBs have been widely tested at room temperature, but only a small number of experi-ments under fi re conditions are reported.

Kindmann et al. [1] performed 13 tests on PEB with and without concrete slabs. Elements were built with HEAA400, showing the importance of the reinforced concrete between fl anges in determining the ultimate bending moment. This research caused the revision of Eurocode 4 (pre-standard) for the design of partially encased composite beams, to include the effect of the encased material for load bearing resistance and defl ection.

Hosser et al. [2] carried out four experimental tests on simply supported composite PEB, connected to reinforced concrete slabs, under fi re conditions. The research developed three-dimensional analytical model, suffi ciently reliable in accuracy, to estimate the effective slab width.

In 1995, Plumier et al. [3] performed 12 full sized test joint specimens under cyclic loading, consisting of PEC connected to PEB. Authors concluded that neither the connection type (welded, bolted) nor the web thickness affected the performance of the specimen. Authors have also observed that yielding took place in the beams and that beam fl anges always buckled outward due to the presence of concrete.

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 221

Lateral instability was investigated at room temperature by Lindner and Budassis [4], using 22 full-scale PEB with two different steel sections. A new design proposal for lateral torsional buckling was proposed, taking into account the torsional stiffness of concrete.

Maquoi et al. [5] improved and implemented the knowledge on lateral torsional buckling of beams, including PEB, and prepared design rules that were not satisfactory covered by the existing standards. The elastic critical moment and the ultimate lateral torsional buckling moment resistance were revised and improved.

Assi et al. [6] developed a theoretical and experimental study on the ultimate moment capacity of PEB. Authors performed 12 tests to investigate the contribution of different types of concrete. According to authors, normal concrete showed insignifi cant enhancement to fl exural strength, when compared with lightweight concrete.

More recently, Kodaira et al. [7] decide to determine the fi re resistance of eight PEB. Authors demonstrate that reinforcement is effective during fi re. The numerical method did not well predicted experimental temperature, even though the global thermo-mechanical behaviour seemed to present results broadly in agreement with each other. The perfor-mance criteria are not in accordance to the European standard [8], because authors decided to use either deformation criterion or rate of deformation criterion to determine fi re resistance.

In 2008, Elghazouli and Treadway [9] performed 10 full-scale tests. The experimental analysis was focused on the inelastic performance or partially encased members. Authors discussed several parameters (strain hardening of steel, concrete confi nement, extension of section yielding) related with capacity and ductility with relevance to design and assessment procedures.

de Nardin and El Debs [10] studied the static behaviour of three composite PEBs under fl exural loading at room temperature, testing some alternative positions for shear studs, using mono-symmetric steel section. Experimental results confi rmed that studs are responsible for composite action and increase bending strength, especially when the studs are vertically welded on the bottom fl ange. The authors also developed an analytical method to estimate the bending capacity of PEB, according to experimental results.

The purpose of this study is to analyse temperature in three different sections of each PEB during fi re resistance tests and evaluate the uniformity of heating inside furnace. The temper-ature of furnace environment was already been tested and numerically validated in a previous work [11], using 16 plate thermocouples.

2 PARTIALLY ENCASED BEAMSPEBs are made of a steel profi le laterally fi lled of plain or reinforced concrete. Partially encased sections can achieve higher fi re resistance performance compared to bare steel sections. The increase in fi re resistance is due to the reduction of exposed steel surface area and the concrete cover, which has a low thermal conductivity. Fire resistance can also be increased by reinforcement as reported in a previous work [12]. The fi re resistance is smaller than 30 minutes, according to Eurocode 4 part 1–2 [13].

PEBs were designed according to Fig. 1, with welded stirrups (W) and not welded stirrups (NW) to the web of profi le.

PEBs were built with IPE100 steel S275 JR, using C20/25 encased concrete, with four longitudinal steel B500 rebars having a diameter of 8 mm. Stirrups were designed and built with B500 rebars having a diameter of 6 mm, distributed through the length, at a distance of 167 mm. PEBs were casted in laboratory, without the need of formwork and tested after

222 P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013)

more than 60 days, with respect to the fi rst casting phase. The second casting phase was performed 1 week after the fi rst. The surface of the materials had not special treatment and were considered as delivered by manufactures. Steel elements were cut from long steel bars, using traditional machinery. Stirrups were welded (W) to the web of steel profi le and not welded (NW). Reinforcement was welded to stirrups for the W case and tied with wire rope for the other case (NW).

3 FIRE RESISTANCE TESTSPEBs were tested using European standards [8], grouped into four series, see Table 1. Three series were used to analyse the contribution of the load level (40%, 60% and 80% of plastic moment at room temperature, Mpl,Rd = 13,844 Nm) and the fourth was used to analyse

Table 1: Series of fi re resistance tests.

SeriesSpecimen

identifi cationStirrups(W/NW)

Thermalload

Load level(%Mpl)

B/1.2–01 W ISO834 401 B/1.2–02 W ISO834 40

B/1.2–03 W ISO834 40B/1.2–04 W ISO834 80

2 B/1.2–05 W ISO834 80B/1.2–06 W ISO834 80B/1.2–07 NW ISO834 80

3 B/1.2–08 NW ISO834 80B/1.2–09 NW ISO834 80B/1.2–10 W ISO834 60

4 B/1.2–11 W ISO834 60B/1.2–12 W ISO834 60

Figure 1: Cross-section dimensions for PEBs.

55

5,7

Ø8

Ø6

R7

4,1

44,3

22,3

20

66

Y

Zh=

100 Y

Z

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 223

the effect of shear conditions between stirrups and the web, comparing the thermal and mechanical behaviour of PEB without welded stirrups (NW). Table 1 refers to the conditions of each test.

Each element was positioned inside the furnace for loading and heating, as represented in Fig. 2. Tests were performed with constant mechanical load and increasing temperature according to the standard fi re ISO834 curve.

The distance between supports of each PEB was ‘Ls’ = 1.210 m. Two different supports were applied; the top support restrained Z/Y displacements and X rotation, whereas the bot-tom support restrained Z/Y displacement and Z/X rotations. The latest was built with a shaft suited into drilled web. The length exposed to fi re ‘Lf’ was equal to 1.0 m, whereas the total length ‘Lt’ of each specimen was defi ned to 1.37 m.

Three different cross-sections were defi ned to measure temperature (S1–S2–S3).The objective of determining fi re resistance is to assess the behaviour of PEB when sub-

mitted to heating and load fi re conditions. The method is able to quantify the ability of an element to withstand load when exposure to high temperatures, using appropriate perfor-mance criteria. Fire resistance may be expressed as the time or in temperature (critical) for which the appropriate criteria have been satisfi ed.

3.1 Instrumentation

Thermocouples type K were positioned along the length of each PEB, according to Fig. 3, using the spot welding machine. For concrete temperature readings in positions Si-IC and Si-OC, thermocouples were welded to a small steel washer, wrapped in concrete.

Temperatures in materials were acquired with frequency of 2 Hz, using MGCPlus multi-channel electronic measurement unit.

Temperature in furnace was acquired with 0.5 Hz, with a plate thermocouple, which com-prise an assembly of a folded steel plate. The plate thermometer has the ability to measure the correct ratio of convective and radiative heat transfer for a fl at surface.

Figure 2: Testing conditions and main cross-sections.

Ls=

121

0

Lt=

137

0

Lf=

100

0

Load

S3

S2

S1

Z

X

xf=

441

xf=

107

xf=

942

224 P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013)

3.2 Material properties

The mechanical properties were determined by tensile testing, according to international standards for hot rolled and cold formed steel, see Table 2. Three samples were collected from the web of steel hot rolled profi le and two more samples were collected from steel reinforcement material. Table 2 accounts for the modulus of elasticity ‘E’, the proof strength ‘Rp.0.2%’, maxi-mum value of stress prior to the fi rst decrease in force ‘REh’, lowest value of stress during plastic yielding ‘ReL’, tensile strength ‘Rm’ and percentage of total extension at fracture ‘At’.

The thermal properties were not measured but were assumed from EN1992–1.2 [14] and from EN1993–1-2 [15]. Particular attention was dedicated to thermal resistance of interface between both materials. Authors verifi ed that thermal conductance equals to 80 kW/m2 was acceptable for validation of experiments [16].

3.3 Performance criteria

The performance criteria used for load bearing (rating R) are independent of the ultimate limit state attained by each PEB. Fire resistance time was defi ned by the elapsed time between the start of heating and the failure of load bearing capacity.

The load bearing criteria or performance criteria were defi ned according to testing stand-ards [8], using the displacement parameter “D” and rate of displacement parameter “dD/dt” criteria. The ultimate limit state was considered when both parameters exceeded limits

D = L2/400 d (mm) dD/dt = L2/9000 d (mm/min) (if D3 L/30) (1)

Figure 3: Thermocouples positions at three different cross-sections.

S1/S2/S3-OC

S1/S2/S3-RS

S1/S2/S3-WS

S1/S2/S3-OS

S1/S2/S3-IC

S2-FS

Table 2: Tensile tests for hot rolled and cold formed steel.

Properties

Steel profi le Steel reinforcement

Average Std. deviation Average Std. deviation

E (GPa) 197.901 2.948 203.294 2.110Rp.0.2% (MPa) 300.738 6.720 524.993 3.521ReH (MPa) (fy) 302.466 5.749 531.508 7.908ReL (MPa) 300.856 4.028 520.825 4.068Rm (MPa) (fu) 431.252 5.020 626.574 11.539At (%) 41.584 0.231 25.155 0.495

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 225

The performance criteria were used to determine critical temperature ‘θcr,d’ and fi re resistance time. This is the time in completed minutes for which the test specimen was able to support the test load.

3.4 Temperature measurements

The nominal fi re heating curve ISO834 was used for heating PEB elements. Temperature was registered in three different sections, S1, S2 and S3, to verify the homogeneity of heating produced by fi re resistance furnace. The maximum temperature difference between sections S1, S2, S3 and the average element temperature is smaller than 3.2% for test series 1. For test series 2, 3 and 4, the maximum temperature difference is smaller than 5.1%, 6.3% and 11.2%, respectively.

Figure 4: Temperature in section S2, for series 1.

Figure 5: Temperature in section S2, for series 2.

226 P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013)

Temperature is not uniform over the cross-section; after the initial heating stage, tempera-ture evolution revealed a constant difference of approximately 150°C between temperatures measured inside and outside each section, defi ning two main temperature evolutions. Temperatures measured outside revealed always higher temperature levels. The initial oscil-lation in temperature was due to the moisture effect in concrete. Figures 4–7 represent temperature evolution in section S2 for each tests series.

Test B/1.2–09 presented higher cracks when compared with other tests, reason why tem-perature increased inside concrete, in comparison with previous tests series 2.

Test B/1.2–10, from series 4, missed temperature readings inside concrete in section S2.Figures 8–11 represent the temperature distribution in each element according to each

series. Critical temperature was determined for each material by weighted average based on temperature readings and the area contribution for each reading. ‘Tis’, ‘Tic’ and ‘Tir’ refer to

Figure 6: Temperature in section S2, for series 3.

Figure 7: Temperature in section S2, for series 4.

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 227

steel, concrete and reinforcement critical temperatures, determined for section ‘Si’ (i = 1,2,3), respectively, according to the following expressions:

Tis = (2Af(SiOS) + Aw(SiWS)/(2Af + Aw)Tic = [1/4 Ac(SiIC) + 3/8 Ac(SiIC + SiOC) + 3/8 Ac(SiIC + SiOS)]/(Ac)

Tir = SiRS (2)

wehre ‘Af’ is the area of the fl ange, ‘Aw’ is the area of the web, ‘Ac’ is the concrete area, ‘Ar’ is the reinforcement area and ‘At’ is the total cross-section area. Critical temperature ‘TSi’ was determined for each section ‘Si’, based on area weighted average temperature, according to the following equation:

Figure 9: Temperature on exposed fi re length for test series 2.

Figure 8: Temperature on exposed fi re length for test series 1.

228 P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013)

TSi = [Tis(AW + 2Af) + TiC(Ac) + Tir(Ar)]/At (3)

Critical temperature ‘θcr,d’ for each PEB was determined using the critical temperature of each section, eqn (4), based on weighted temperature of each section TSi.

θcr,d = [TS1 + 2TS2 + TS3]/4 (4)

Temperatures are represented up to the critical temperature by increments of 5 minutes.The deformation mode shape was the same for all three tests on series 1. Ultimate limit

state was attained by plastic hinge formation; after 20 minutes, the rate of displacement ‘dD/dt’ exceeded the limit criterion but did not verify the condition. Fire resistance time agrees very well, for all tests in 25 minutes. Temperature distribution is almost constant over each element.

Figure 10: Temperature on exposed fi re length for test series 3.

Figure 11: Temperature on exposed fi re length for test series 4.

P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013) 229

The ultimate limit state for test series 2 was attained by instability (lateral torsional buck-ling); after 13 minutes, the rate of displacement was exceeded as well. Fire resistance time did not agree for all tests. Eighteen minutes were determined for tests B/1.2–04 and B/1.2–05, whereas 19 minutes was determined for test B/1.2–06. Temperature distribution is almost constant for each test, but different levels were determined for each registered time.

Fire resistance was also determined for different stirrup conditions. Series 3 differed from series 2, because stirrups were not welded to the web of profi le. Ultimate limit state was attained by lateral torsional buckling; after 13 minutes, the rate of displacement was exceeded, as well. Fire resistance time equals 18 minutes for all tests in this series, although temperature distribution is not the same for each test.

Test series 4 was performed using 60% load level, with stirrups welded to the web. The ultimate limit state was attained by the formation of a plastic hinge; after 16 minutes the rate of displacement was exceeded. Fire resistance time of 20 and 21 minutes were determined for tests on this series. Temperature distribution was almost equal for every tested beam.

Progressive damage of concrete was verifi ed for each fi re resistance test due to excessive deformation for longer fi re exposure. Flexural cracking and debonding of concrete were observed at mid-span. Encased concrete blocks presented expressive displacement outward of encasement (Y direction), as expected during tests series 3.

4 CONCLUSIONSTwelve bending tests were performed under fi re standard ISO834 conditions to evaluate fi re resistance and to determine the behaviour of partially encased elements. Three different load levels were considered (40%, 60% and 80%) and two different bond conditions were tested (welded and not welded).

Fire resistance depends on load level, as expected. Fire resistance decreased from 25 to 21 and 18 minutes, as load ratio increased from 40% to 60% and 80%, respectively. The results are in accordance with Eurocode 4 part 1–2 [13].

There was no evidence of shear bond effect. Tests in series 3 presented higher outward movement of concrete that was responsible for higher temperature inside cross-section, but fi re resistance was the same determined on series 2.

Differences between temperatures along each element length were smaller than 10%, with respect to the element average critical temperature. Temperature of reinforcement represented the lowest value in all sections. Two different temperature evolutions were recorded for experi-ments, proofi ng that temperature was not uniform. Temperature distribution along each exposed PEB was almost constant proofi ng the uniformity of heating and the insulation at the supports.

Results provide essential data to the calibration and validation of new simplifi ed design methods, tabulated data and advanced numerical methods.

REFERENCES [1] Kindmann, R., Bergmann, R., Cajot, L.-G. & Scleich, J.B., Effect of reinforced

concrete between the fl anges of the steel profi le of partially encased composite beam. Journal of Constructional Steel Research, 27, pp. 107–122, 1993. doi: http://dx.doi.org/10.1016/0143-974X(93)90009-H

[2] Hosser, D., Dorn, T. & El-Nesr, O., Experimental and numerical studies of compos-ite beams exposed to fi re. Journal of Structural Engineering, 120(10), pp. 2871–2892, 1994. doi: http://dx.doi.org/10.1061/(ASCE)0733-9445(1994)120:10(2871)

230 P.A.G. Piloto, et al., Int. J. of Safety and Security Eng., Vol. 3, No. 3 (2013)

[3] Plumier, A., Abed, A. & Tiliouine, B., Increase of buckling resistance and ductility of H-sections by encased concrete. Behaviour of Steel Structures in Seismic Areas, E & FN Spon: London, ISBN: 0419 198903, 1995.

[4] Lindner, J. & Budassis, N., Lateral torsional buckling of partially encased composite beams without concrete slab. Composite Construction in Steel and Concrete IV, confer-ence proceedings, May 28th to June 2nd, Banff, Alberta, Canada, pp. 117–128, 2000.

[5] Maquoi, R., Heck, C. & Ville de Goyet, V., et al., (European commission), Lateral tor-sional buckling in steel and composite beams. ISBN 92–894-6414–3; Book 1,2 and 3; Technical steel research fi nal report EUR 20888 EN; August 2002.

[6] Assi, I.M., Abed, S.M. & Hunaiti, Y.M., Flexural strength of composite beams par-tially encased in lightweight concrete. Pakistan Journal of Applied Sciences, 2(3), pp. 320–323, 2002.

[7] Kodaira, A., Fujinaka, H., Ohashi, H. & Nishimura, T., Fire resistance of composite beams composed of rolled steel profi le concreted between fl anges. Fire Science and Technology, 23(3), pp. 192–208, 2004.

[8] CEN, EN 1363–1, Fire resistance tests, part 1 – General requirements.English version, European Standard, 1999.

[9] Elghazouli, A.Y. & Treadway, J., Inelastic behaviour of composite members under combined bending and axial loading. Journal of Constructional Steel Research, 64, pp. 1008–1019, 2008. doi: http://dx.doi.org/10.1016/j.jcsr.2007.12.016

[10] de Nardin, S. & El Debs, A.L.H.C., Study of partially encased composite beams with innovative position of stud bolts. Journal of Constructional Steel Research, 65(2), pp. 342–350, 2009. doi: http://dx.doi.org/10.1016/j.jcsr.2008.03.021

[11] Piloto, P.A.G., Mesquita, L.M.R. & Pereira, A.,Thermal analysis in fi re-resistance fur-nace. International Workshop on Fire Protection and Life Safety in Buildings and Trans-portation Systems, proceedings ISBN 978–84-8102–559-0, pp. 103–111, GIDAI – University of Cantabria, 15–17 October 2009.

[12] Piloto, P.A.G., Gavilán, A.R. & Mesquita, L.M.R., Advanced numerical method for estimate fi re resistance of partially encased beams. Proceedings of the International Congress in Fire Safety in Tall Buildings, ISBN 84–8102-415–5, pp. 79–91; 19th October 2006, University of Cantabria, Santander, Spain.

[13] CEN-EN 1994-1-2, Eurocode 4: Design of composite steel and concrete structures - Part 1-2: General rules - Structural fi re design, European Standards, Brussels, August 2005.

[14] CEN-EN 1992–1-2, Eurocode 2: Design of concrete structures – Part 1–2: General rules – Structural fi re design, European Standards, Brussels, December 2004.

[15] CEN-EN 1993–1-2, Eurocode 3: Design of steel structures – Part 1–2: General rules – Structural fi re design, European Standards; Brussels, April 2005.

[16] Piloto, P.A.G., Ramos Gavilán, A.B. & Mesquita, L.M.R., Numerical analysis for ther-mal conductance of the interface between steel and concrete to composite structures at elevated temperatures. Proceedings of the 2nd Portuguese Conference on Numerical Methods Applied to Thermodynamics and Fluid Mechanics (in Portuguese), University of Aveiro, 8–9 May de 2008.

This paper has been selected for this special issue but fi rst appeared in WIT Transactions on the Built Environment, Vol 117, © 2011 WIT Press, www.witpress .com, ISSN 1743-3509 (on-line), doi:10.2495/SAFE110281.