Ref. No.: m83/om/403 Issue No.: 19

masibus

Operators Manual

S C A NNE R - 85 X X

Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India. Ph: 91-079-23287275--79 Fax: 91-079-23287281/82 Email: support@masibus.com Web: www.masibus.com

Page 1 of 52 Operators manual Date: 18/12/2009

Ref. No.: m83/om/403

masibusIssue No.: 19

CONTENTS1. TECHNICAL DETAILS. 2. SPECIFICATIONS. 3. KEY OPERATION. 4. CONNECTIONS DETAILS. 5. USER GUIDE. 6. MODE OF OPERATION. 7. RELAY TABLE. 8. AUXILLAY OPTIONS TABLE. 9. TROUBLE SHOOTING. 10. MODBUS DETAIL (OPTIONAL). 11. OPEN COLLECTOR PIN DETAILS.

Page 2 of 52

Operator Manual Date: 18/12/2009

Ref. No.: m83/om/403 Issue No.: 19

masibusif group mode is selected as 1rELy, then Relay action type ( ON or OFF ) for alarm limit 1 is only programmable. Latching for LED Status of alarm limit 1 and alarm limit 2 is programmable. Scan time is programmable up to 99 seconds. Provision for zero and span setting is made to restrict range of usage and programming. This restricts accidental wrong setting of set point beyond the range of interest. Outside this range the unit will indicate data as 'OVER' towards span side up to 5% more than programmed span and UNDR towards zero side up to 5% less then programmed zero. This zero and span setting is more useful for linear inputs for setting the range between 1999 to 9999 counts. Digital input is mapped on 0-5V input and printing output and display is as ON if input voltage is less than 2.5v DC and OFF if input voltage is greater than 2.5v DC. The reverse feature can be obtained on using UPSCALE/DOWN SCALE of open sensor. There is no relay or any output action for digital input. Number of optional features provided including Relay output, Open collector output, Isolated Retransmission output, Serial printer output or Centronics printer output which can be easily set through front panel keys under Auxiliary Slot1 and Slot2 configuration. Full relay mapping possible. Any channel can be assigned to any group. For each group two relays are given for one alarm limit 1 and second alarm limit 2 if relay group mode is selected as 2rELy. For each group one relay is given for alarm limit 1 if relay group mode is selected as 1rELy. Isolated Retransmission output (420mA) can be configured for either Minimum or Maximum of channels selected in a group. Serial Communication with RS 232 / RS 485 is also provided for using the scanner as backend for Supervisory Control or for P.C. connectivity. Standard protocol for communication used is MODBUS-RTU.Page 3 of 52

1. TECHNICAL DETAILSThis is a versatile micro-controller based Scanner with a very high performance to price ratio. The features offered in this product are better than any other Scanner available in similar price range. The instrument is made in 96x192x208 mm size with standard cut out of 92x188 mm. Front is sealed membrane type to withstand dusty environment. On back plate PCB soldered flat terminals of very good quality are used. The programming, calibration and operation of the instrument are by nine simple keys with two independent displays for channel no. and data value for that channel. Channel display is of two digits to differentiate it from data display of four digits, each of 0.56" seven segments LED. Status of Run/ Program/Verify mode, Fault, Auto/Manual mode and status of each channel for programmed set point limits are displayed by 3 mm red LEDs. Operation of the instrument is menu driven with user understandable prompts. Provision for PASS WORD is kept for unauthorized access to critical configuration and program parameters. The product is made to accept all 7 standard thermocouple, PT100 RTD, CU-53, PT46, Linear voltage and current inputs and digital input. The type of input can be changed in field also. The calibration of the unit is done without trim-pots. The unit can be calibrated in installed condition itself by front panel keys at any given point i.e. user do not required to feed a fixed signal. RTD inputs are linear for 0.1 deg. as well as 1 deg. resolution. Also incorporating Self check feature for stand alone verification of hardware of the device of input section. Set point type (LL, HL or HH), abnormal status (Alarm or Trip) for alarm limit1 and alarm limit 2 as well as Relay action type (ON or OFF) for alarm limit 1 and alarm limit 2 are programmable if group mode is selected as 2rELy. Relay action type (ON or OFF) for alarm limit 1 are programmable if group mode is selected as 2rELy.

Operators manual Date: 18/12/2009

Ref. No.: m83/om/403

masibusIssue No.: 19 Serial or parallel printer interface is also provided for online Data printing application with Real Time Clock in built. Print time is settable from 0-99 minutes. Also PC based configuration software is available for configuration of data through PC. NMRR NMRR > 40 db @ 50Hz.

2.3. RANGEE -200 to 1000 Deg C J -200 to 1200 Deg C K -200 to 1372 Deg C T -200 to 400 Deg C B 400 to 1820 Deg C R 0 to 1768 Deg C S 0 to 1768 Deg C Cu-53 -210 to 210 Deg C PT46 -200 to 600 Deg. C PT100(RTD 1) -199 to 850 Deg. C PT100 (RTD 0) -199.9 to 200.0 Deg C 4-20mA- Field scaleable-1999 to 9999 0-5 V - Field scaleable -1999 to 9999

2. SPECIFICATIONS2.1. DISPLAY2 digit 0.56" Red seven segment LEDs for channel no. 4 digit 0.56" Red seven segment LEDs for data of current channel. Power ON and Mode Selection discrete Red LEDs. Individual discrete Red LEDs to indicate channel status.

2.4. CALIBRATIONAmbient, Zero and span adjusted by digital calibration through front panel keys. No trim- pots. Zero Span Calibration of output through front panel keys. One shot Calibration of both input and output.

2.2. INPUTUniversal Input. No. of inputs 8,16 or 24. Thermocouple type E, J, K, T, B, R, S (ANSI Standard). RTD Pt 100, Pt-46, CU-53 3-wire. 4-20 mA* / 1-5 V DC / 0-20 mA* / 05 V DC (*250 ohm/0.1% external Resistor required). Digital I/P wetted internally. Digital input is mapped on 0-5V input and display is as ON if input voltage is less than 2.5v DC and OFF if input voltage is greater than 2.5v DC. The reverse feature can be obtained on using UPSCALE/DOWN SCALE of open sensor. There is no relay or any output action for digital input. Cold junction compensation automatic for thermocouple types. Three wire cancellation for RTD I/P automatic by software. Accuracy: +/- 0.1% of full span +/- 1 Count Sampling Speed 250 msec per channel for T/C & Linear Input. 450 msec per channel for RTD Input. Display Scan Rate Settable 1 to 99 seconds. CMRR CMRR > 120 db @ 50Hz.

2.5. CONTROLSVfy, Increase, Decrease, Auto/Man, Next/Group Check, Skip/Self Check, Al1/Al2, Scan Time/Print Time and Enter/ ACK keys for operation, programming & calibration.

2.6. Serial CommunicationIsolated RS232/485 Serial Communication Protocol Standard MODBUS RTU HEX. OR Standard Serial Printer Output.

Page 4 of 52

Operator Manual Date: 18/12/2009

Ref. No.: m83/om/403 Issue No.: 19

masibus

2.7. OPTIONS FOR AUXILLARY OUTPUTS (Maximum Two Auxiliary Outputs are possible under SLOT-1 and SLOT-2 Input):Relay card 2relay/1relay(per group) 3 groups(1 to 3 ) with 2 set points/ Slot 1 6 groups(1 to 6) with 1 set point Two Isolated Retransmission groups (Gr. No.: 1 and 2) 24 Open Collector Outputs Analog Card Output Open Card Collector Printer Card

3 groups(4 to 6) with 2 set points Slot 2 6 groups(7 to 12) with 1 set point 2A@230V A.C. with N.O./C/N.C. Relay Mapping possible with number of channels

Two Isolated Retransmission groups (Gr. No.: 3 and 4) Groups:- MAX or MIN Outputs:- 4-20mA Accuracy:- 0.25% of Range Load:- 250 Ohms

24 Open Collector Outputs

Centronics Printer Port interface

Common Description

24V D.C. @ 100mA externally wet Contacts

Parallel port

printer

NOTE: The possible combinations are explained in the operational manual in Topic no. 8. Parallel Printer Port: 1 No ( See Special Note 2) o Centronics Printer Port Interface Special note 1: If OR type Logic is selected or Scanner Type is 8508 and INDIVIDUAL logic is used, user can configure SLOT-2 for any other Output. (Refer to Operation manual for detail description of OR type and INDIVIDUAL type Logic). If INDIVIDUAL Logic is used and Scanner Type 8516 or 8524 both Slots require Open Collector Output by default. Special note 2: If serial Printer is selected then Parallel Printer Selected on Slot-1 and Slot-2 will not be active. If Parallel Printer is selected as Option on Both Slots, Parallel Printer on Slot-1 will only be active.

2.8. GENERALpower supply - selectable 85V to 265V AC 50 Hz and 125V to 280 VDC. 22V to 30V DC, (optional),90V to 135V DC(optional). Ambient - 0 to 55 deg C. Humidity - up to 95% RH (Noncondensing) Power consumption - Less than 20 VA Scanning time 1) For T/C and Linear - 250 mSec.Page 5 of 52

Operators manual Date: 18/12/2009

Ref. No.: m83/om/403

masibusIssue No.: 19 2) For Rtd - 450 mSec. Dimension560 (H) x 275 (W) x 210(D) Key 9 push button keys for front access.

2.9.

PHYSICAL

Case M.S. powder coated with ABS molded bezel Terminals Screw type, can accept up to 2.5 sq. mm wire Bezel size - 96 X 192 mm Depth behind panel - 208 mm / 250mm (with terminal plate) Panel cutout - 92 X 188 mm

2.11. OTHER OPTIONS1. Channel to channel online isolation up to 125V AC and 300V DC and off-line isolation up to 500VDC is available for Critical Applications. 2. Horizontal Scanner: Bezel size - 192 X 96 mm Depth behind panel -208 mm / 250mm (with terminal plate) Panel cutout - 188 X 92 mm

2.10. SPECIAL FEATURES:Real time RTC interface for Serial or parallel printer output. Print on Time and Hot