TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika...

8

Transcript of TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika...

Page 1: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...
Page 2: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

TELE-FONIKA CABLE AMERICAS (TF KABLE) is a US firm with corporate offices and main facility located in Bolingbrook, IL and is a wholly owned subsidiary of Tele-Fonika Kable SA. Tele-Fonika, one of the largest manufacturers of wire and cable in the world, is a fully integrated manufacturer recognized by the industry as a world class producer of quality wire and cable products. The company specializes in electrical wire and cable for MINING, HEAVY INDUSTRY, UTILITY and ENERGY applications utilizing materials to meet strict mechanical and electrical performance requirements.

TELE-FONIKA KABLE GROUP KEY STATISTICS n 1 billion USD in annual turnover n 3rd largest wire and cable

supplier in Europe and one of the TOP global producers

n No. 1 European POWER CABLE SUPPLIER

n 3000 Group Employees n 15 Global Facilities n 25,000 Different types of wire

and cable constructions n Sales & Distribution network

stretching 90 countries

TELE-FONIKA CABLE AMERICAS

Page 3: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

TELE-FONIKA KABLE SA, a privately held wire and cable manufacturer headquartered in Krakow, Poland, is one of the largest wire and cable companies in the world. TF operates 8 plants in Central and Eastern Europe with a distribution network stretching 90 countries. Formed through a series of acquisitions and mergers, TFK has developed world-class technology centers of excellence with state of the art manu-facturing operations. Founded in 1992, TF grew rapidly and the operations today are a result of internal development projects supported by strategic investments.

TF is the leading medium and high voltage cable manufacturer in Europe with significant market share in rubber insulated

portable power cables used by HEAVY INDUSTRY & MINING. Additionally, the company manufactures products for the TELECOMMUNICATION, SHIP BUILDING, ELECTRONIC and ENERGY sectors.

All manufacturing facilities are ISO 9001, ISO 2000, and ISO 14001 certified. All products are manufactured to public, utility and industrial standards including ICEA, IEEE, and ASTM. Tele-Fonika has over 380 individual certificates issued by more than 30 governing bodies which include UL, CSA, MSHA, SABS, VDE, CE, etc.

Tele-Fonika Kable S.A.

Page 4: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

ApplicationsINDUSTRIAL AND COMMERCIAL

Installationsn In Cable TraynConduit in Airn Aerial with Messenger SupportednDirect Buriedn Underground Ductn Wet and Dry Locations

Benefits and Featuresn Durable construction allows for installation in practically any environmentn 105ºC insulation rating allows for higher ampacity rating of a cablen Continuous Conductor Operating Temperature 105ºCn Emergency Overload Rating 140ºCn Short Circuit Rating 250ºCn UL listed as Type MV-105n Oil and sunlight resistantn Flame retardant PVC jacketn Listed for CT use for sizes 1/0 AWG and larger

100% Insulation Leveln Used for cables installed in grounded systems and systems equipped with a protective device that will clear ground faults within 1 minute

133% Insulation Leveln Used for cables installed in ungrounded systems where faults will be de-energized within 1 hour but not quicker than 1 minute

n Chemical Plantsn Petrochemical Plantsn Electrical Utility Plantsn Water Treatment Facilitiesn Textile Millsn Steel Mills

n Paper Millsn Airportsn Shopping Mallsn Military Basesn Medical Facilitiesn Sports Stadiums

Page 5: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

MV-105

Conductor ShieldSemiconducting thermoset layer

ConductorCompact or compressed stranded

class B per ASTM (Copper or Aluminum)

InsulationEPR (Ethylene Propylene Rubber)

Metallic Shield5 mil bare copper tape shield

with a 25% overlap

JacketSunlight resistant PVC

(Polyvinyl Chloride)

Standard ConstructionCONDUCTOR Class B compact stranded copper or compressed aluminum. Cable element that allows for the flow of electrical current.

CONDUCTOR SHIELD The semiconducting thermoset extruded layer equalizes electrical charge across the conductor surface. It also minimizes electrical stresses should the conductor surface become uneven due to voids between conductor and insulation. The semiconducting layer eliminates potential for corona discharge by reduction of air voids between the conductor and the insulation. This greatly improves insulation life expectancy.

INSULATION Thermoset extruded EPR layer whose main function is to contain electricity and resist leakage of electrical charges. Insulation also serves as a protective layer.

INSULATION SHIELD The semiconducting thermoset extruded layer transfers insulation charging current to the metallic shield. It provides symmetrical distribution of voltage stress within insulation. Its function is also to restrict the electric field within the insulation.

METALLIC SHIELD The bare copper tape reduces the risk of shock to personnel by safely carrying and transferring leaked current in case of a cable fault. The metallic shield provides additional mechanical damage protection for the cable core.

JACKET External layer of extruded thermoplastic PVC provides protection for all internal cable elements from any mechanical, chemical or thermal abuse it may experience during cable installation and operation.

555 Remington Blvd n Bolingbrook, IL 60440 n tel: 630-406-9000 n fax: 630-406-6574 n www.tfcable.com

Insulation ShieldSemiconducting thermoset layer

Page 6: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

MV-105 Tape Shielded Power Cable (Copper)

SPECIFICATIONS & STANDARDSUL 1072, ASTM B-496, ICEA S-93-639, ICEA S-97-682, AEIC CS8-2000, IEEE 383

CONSTRUCTION: Conductor: Class B compact annealed uncoated copper. Conductor Shield: Extruded layer of semiconducting compound applied under simultaneous triple extrusion process.Insulation: Extruded layer of 105˚C rated Ethylene Propylene Rubber (EPR).Insulation Shield: Extruded layer of semiconducting compound applied by triple extrusion process.Metallic Shield: 5 mil bare copper tape applied helically with a 25% overlap.Jacket: Extruded layer of black sunlight resistant Polyvinyl Chloride (PVC).

Conductor Size

Insulation Thickness

Dia. over insulation

Jacket Thickness

Outer Diameter

Cable Weight

Ampacities*Isolated in Air Direct Buried Underground Duct

AWG or kcmil mils inches mils inches lbs/kft Amps

2 AWG1 AWG

1/0 AWG2/0 AWG3/0 AWG4/0 AWG250 MCM350 MCM500 MCM750 MCM1000 MCM

115

0.550.600.650.690.750.800.850.951.101.301.40

6060608080808080808080

0.780.800.850.951.001.051.101.201.351.551.70

42551558067586098511301480200028703690

215250290330385445495615775

10001200

250280320365415465510615745910

1055

155180210235270310345410505630720

Conductor Size

Insulation Thickness

Dia. over insulation

Jacket Thickness

Outer Diameter

Cable Weight

Ampacities*Isolated in Air Direct Buried Underground Duct

AWG or kcmil mils inches mils inches lbs/kft Amps

2 AWG1 AWG

1/0 AWG2/0 AWG3/0 AWG4/0 AWG250 MCM350 MCM500 MCM750 MCM1000 MCM

220

0.750.790.820.860.920.971.021.121.261.411.97

808080808080808080110110

1.031.051.091.131.171.211.301.401.521.771.95

593700770865

1040116513201680220031154060

2152502903353854454956107659901185

225260295335380435475575700865

1005

165185215245275315345415500610690

5kV 133% / 8kV 100% INSULATION LEVEL

15kV 133% INSULATION LEVEL

555 Remington Blvd n Bolingbrook, IL 60440 n tel: 630-406-9000 n fax: 630-406-6574 n www.tfcable.com

* Ampacities in “Underground Duct” per NEC 2011 Table 310.60(C) (77). Ampacities “Isolated in Air” per NEC 2011 Table 310.60(C) (69). Ampacities “Direct Buried” per NEC 2011 Table 310.60(C) (81).

Page 7: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

555 Remington Blvd n Bolingbrook, IL 60440 n tel: 630-406-9000 n fax: 630-406-6574 n www.tfcable.com

MV-105 Tape Shielded Power Cable (Aluminum)

CONSTRUCTION: Conductor: Class B compressed concentric strand aluminum 1350. Conductor Shield: Extruded layer of semiconducting compound applied under simultaneous triple extrusion process.Insulation: Extruded layer of 105˚C rated Ethylene Propylene Rubber (EPR).Insulation Shield: Extruded layer of semiconducting compound applied by triple extrusion process.Metallic Shield: 5 mil bare copper tape applied helically with a 25% overlap.Jacket: Extruded layer of black sunlight resistant Polyvinyl Chloride (PVC).

SPECIFICATIONS & STANDARDSUL 1072, ASTM B-231, ICEA S-93-639, ICEA S-97-682, AEIC CS8-2000, IEEE 383

5kV 133% / 8kV 100% INSULATION LEVEL

15kV 133% INSULATION LEVEL

Conductor Size

Insulation Thickness

Dia. over insulation

Jacket Thickness

Outer Diameter

Cable Weight

Ampacities*Isolated in Air Direct Buried Underground Duct

AWG or kcmil mils inches mils inches lbs/kft Amps

2 AWG1 AWG

1/0 AWG2/0 AWG3/0 AWG4/0 AWG250 MCM350 MCM500 MCM750 MCM1000 MCM

115

0.540.580.610.660.700.770.820.921.051.241.40

6060608080808080808080

0.740.780.820.860.931.001.051.151.281.461.61

310342380425508580643786990

13211645

165195225260300350385480605790950

195220250285320365395480580720840

125140160185210245270325400505590

Conductor Size

Insulation Thickness

Dia. over insulation

Jacket Thickness

Outer Diameter

Cable Weight

Ampacities*Isolated in Air Direct Buried Underground Duct

AWG or kcmil mils inches mils inches lbs/kft Amps

2 AWG1 AWG

1/0 AWG2/0 AWG3/0 AWG4/0 AWG250 MCM350 MCM500 MCM750 MCM1000 MCM

220

0.750.790.820.860.910.971.031.131.251.431.59

808080808080808080110110

0.971.011.041.091.131.191.251.351.471.651.86

487525570625685762836995

122015802035

170195225260300350385480600780940

175200230260295340370450545680795

130145165190215245270330400490565

TELE-FONIKA CABLE AMERICAS

* Ampacities in “Underground Duct” per NEC 2011 Table 310.60(C) (78). Ampacities “Isolated in Air” per NEC 2011 Table 310.60(C) (70). Ampacities “Direct Buried” per NEC 2011 Table 310.60(C) (82).

Page 8: TELE-FONIKA CABLE AMERICAS (TF KABLE) · tele-fonika cable americas (tf kable) ... tele-fonika cable americas. tele-fonika kable sa, ... 836 995 1220 1580 2035 170 195 ...

555 Remington Blvd, Bolingbrook, IL 60440tel: 630-406-9000 fax: 630-406-6574www.tfcable.com