Page 1: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

Technology & Resilience

Page 2: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

The Scalpel is designed with best-in-class technology. It is future ready, with changing occupier needs in mind.

the scalpel

// 1

Page 3: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

Mobile Phone Enhancement and WIFI

Mobile Phone An Opencell mobile enhancement system provides in-building mobile phone continuity of service in the common areas of the building, including main reception, common lift lobbies and cycle/shower facilities.

The system provides ‘‘plug in’’ capability so tenants can extend coverage into their premises as required at their own cost.

The Opencell system connects directly to the operator networks via a hard wired system, providing a resilient ‘‘cell’’ within the building, unaffected by external traffic or interruptions to the external cellular service.

Further information:

opencell.co.uk/technology/

WIFIHigh speed Wi-Fi is available throughout the building’s common areas including main reception, common lift lobbies, passenger lift cars and cycle/shower facilities.

the scalpel

// 2

Page 4: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

KEY

SEC

TCA

4 Bore Primary BFT

4 Bore Secondary BFT

3837363534333231302928272625242322212019181716151413121110090807060504030201

MezzGB1B2

Tenant West 2 Riser

(Tray Only)

Tenant West 1 Riser

Tenant East Riser

Landlord Riser

MER

POP2

POP1

BTS

Telecoms and ICTCurrent telecommunication providers within the Scalpel include BT Openreach, COLT and Vorboss, with connections at B1 and B2 POP rooms. Other major providers including Virgin and Level 3 have fibre infrastructure nearby and are able to provide service upon request through ‘meet me’ chambers on Leadenhall Street and Billiter Street.

The landlord has a standard wayleave agreement to streamline future installations for additional providers.

The building has a diversely routed blown fibre backbone to enable rapid deployment and resilient telecommunications and ICT pathways.

A copper backbone provides connectivity for copper based phone systems from MER & POP rooms in the basement.

WiredScore PlatinumThe Scalpel achieved a Wired Certified Platinum rating for Developments and Redevelopments; the best available.

For more information:

wiredscore.com/uk/

the scalpel

// 3

Page 5: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

Transformer 4Transformer 3

Connection to 33kVnetwork ring betweenBack Hill and Finsbury

Market C UKPN Grid Substations

LV switchroom 3

GROUND LEVEL

Tenant and Landlord Busbars(Landlord busbars are dual fed)

LV switchroom 4

Transformer 2Transformer 1

Transformer 6Transformer 5

Generator 1 Generator 2 Generator 3

LV switchroom 1

Tenant and Landlord Busbars(Landlord busbars are dual fed)

LV switchroom 2

Generator switchroom

UKPN Substation UKPN Substation(Leadenhall St) (Billiter St)

Billiter St. Annex

Connection to 33kVnetwork ring betweenBack Hill and FinsburyMarket C UKPN Grid Substations

HV switchroom 1 HV switchroom 2

Power SuppliesPower to the building is supplied by two 33kV independent UK Power Network (UKPN) substations located in the building, which are fed from a 33 kV ring from two UKPN Grid Substations (Back Hill and Finsbury Market). These incomers feed two main HV switchboards and can cross-feed to support the whole building on a single incomer.

There is a resilient control system to monitor all HV and LV switchboards.

In addition, three 2.2 MVA standby diesel generators are provided both for life safety and tenant business continuity. These will be operated and maintained by the landlord as a building service.

The standby generators are sized to support the building’s full predicted load and with fuel storage sufficient to enable the generators to operate for 24 hours.

The generators are located in the low rise Billiter Street annex section of the building.

the scalpel

// 4

Page 6: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

LEVEL 39

Level 37 SEC

1:32 SPLITTERS

Levels 26 to 35 shall have 2Termination Units per level in the Tenant East Riser

Levels Ground to 25 shall have 1Termination Unit in the Tenant EastRiser and 1 Termination Unit in theTenant West 1 Riser per level.

LEVEL 37

TENANT RISER WEST 1 TENANT RISER EAST

LEVELS 26-35

LEVELS GROUND-25

Fibre Patch Panel

Fibre Patch Panel

BREAKOUT BREAKOUT

BREAKOUT

BREAKOUT

Fibre Patch Panel Fibre Patch Panel

DTT Filter

DTT/DAB/FMRadio antennas

Satellite TV SystemsDedicated fibre-optic network cabling distributes satellite and terrestrial TV services from the roof throughout the building via tenant risers.

Four satellite dishes provide satellite TV services and three antennas provide digital terrestrial TV, FM radio and digital audio broadcasting services.

Tenant connections can be made on request and supply costs settled with the service providers.

the scalpel

// 5

Page 7: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

The building provides chilled water from four water-cooled chillers working in conjunction with four forced draft cooling towers. Supplementary cooling (for communications rooms etc.) is provided via 24/7 chilled water circuits providing a total building additional capacity of 350kW.

Tenant communications rooms and communications room plant benefit from the building’s diverse power feeds and standby generator support, minimising the risk of power failure.

Communications Room Resilience

the scalpel

// 6

Page 8: Technology & Resilience - Scalpel Building · Technology & Resilience. The Scalpel is designed with best-in-class technology. It is future ... operator networks via a hard wired system,

thescalpelec3.co.uk

Tom Meijer T: +44 (0) 20 7182 2778 E: [email protected]

Chris VydraT: +44 (0) 20 7182 3143 E: [email protected]

David PerowneT: +44 (0) 20 7182 3235 E: [email protected]

Important notice relating to the Misrepresentation Act 1967 and the Property Misdescriptions Act 1991: (i) the particulars are set out as a general outline only for guidance of intending purchasers or lessees and do not constitute, nor constitute part of, an offer or contract (ii) all descriptions, dimensions, references to condition and necessary permission for use and occupation, and other details are given in good faith and are believed to be correct, but any intending purchasers or occupiers should not rely on them as statements or representations of fact, but must satisfy themselves by inspection or otherwise as to the correctness of each of them. March 2019.

Tim PlumbeT: +44 (0) 20 3296 2005 E: [email protected]

James Campbell T: +44 (0) 20 3296 2074 E: [email protected]

Eleanor Reed T: +44 (0) 20 3296 2080 E: [email protected]

cushmanwakefield.co.ukcbre.co.uk

scalpellondon

Contact

the scalpel

// 7