TECHNICAL TRAINING 2008. Inverter Mini Chiller System and Control.
-
Upload
ethan-newman -
Category
Documents
-
view
234 -
download
3
Transcript of TECHNICAL TRAINING 2008. Inverter Mini Chiller System and Control.
Technical Training 2008Technical Training 2008
TECHNICAL TRAINING TECHNICAL TRAINING
20082008
Technical Training 2008Technical Training 2008
Inverter Mini Chiller Inverter Mini Chiller
System and ControlSystem and Control
Technical Training 2008Technical Training 2008
1. Introduction1. Introduction
2. Basic Inverter Technology2. Basic Inverter Technology
3. Components3. Components
4. Control Algorithm4. Control Algorithm
5. Protection5. Protection
Content
Technical Training 2008Technical Training 2008
Introduction
Technical Training 2008Technical Training 2008
5ACV30 CR5ACV30 CR
5ACV55/75 CR5ACV55/75 CR
5ACV100/135/210 CR5ACV100/135/210 CR
Introduction
Technical Training 2008Technical Training 2008
ModelModelCapacity (kW)Capacity (kW)
Cooling Cooling HeatingHeating
5ACV030CR5ACV030CR 7.947.94 9.669.66
5ACV055CR5ACV055CR 14.6514.65 16.1216.12
5ACV075CR5ACV075CR 20.5220.52 21.9921.99
5ACV100CR5ACV100CR 27.8027.80 29.3029.30
5ACV135CR5ACV135CR 38.5438.54 41.4741.47
5ACV210CR5ACV210CR 58.6258.62 61.5561.55
Introduction
Technical Training 2008Technical Training 2008
Conventional Back to Back Circuits BPHE
Primary Circuit 1 Primary Circuit 2
Secondary Circuit
Primary Circuit 1 Primary Circuit 2
5ACV True Dual Circuits BPHE
New Technology BPHE- True Dual Circuits
Introduction
Technical Training 2008Technical Training 2008
Conventional System
Inverter System
Inverter Compressor
Introduction
Technical Training 2008Technical Training 2008
Inverter system provide constant Water Temperature band, or much lesser water temperature fluctuation. With this, water tank of mini chiller system can be eliminated
Elimination of Water Tank
A network up to 50 chillers in a system is possible. Control on the operation of chillers will be done through the microprocessor controller. The external water piping connection can be made either from the left or right side of the unit.
Modular Installation
• High & Low Pressure Switches • Anti Freeze Protection Sensor• Discharge Temperature Sensor• Over Pressure Relief Valve
Safety Protection• Water Pressure Differential Switch• Anti Freeze Heater on BPHE• Compressor, Water Pump Overload Protector
Introduction
Technical Training 2008Technical Training 2008
Basic Inverter Technology
Technical Training 2008Technical Training 2008
The system:-The system:-
Inverter
AC/DCRectifiert
u
t
Power supplyInput frequency50Hz t1
50 Hz 100 Hz 15 Hz
DC/ACInverter
(compressor motor input)
PWM
Basic Inverter Technology
Technical Training 2008Technical Training 2008
Three-phase inverter
PWM control
Power supply unit
Compressor
(Waveform formation)
AC Inverter Unit
Three-phase induction motor
AC ACDC
Temperature detection signal
Operating frequency signal
Basic Inverter Technology
Technical Training 2008Technical Training 2008
Inverter Basic StructureInverter Basic Structure
Inversion
PLC Control
Rectification
AC AC
DC Link Converter
PWM Signal
SMPS
M
Basic Inverter Technology
Technical Training 2008Technical Training 2008
Rectification CircuitRectification Circuit
• EMI filter to minimize emission effect (EMC) and raise EMI filter to minimize emission effect (EMC) and raise immunity level (EMS)immunity level (EMS)
• PTC to cushion start-up current to capacitorPTC to cushion start-up current to capacitor
• Diode bridge inverts AC to DCDiode bridge inverts AC to DC
EMI Filter
Rectifier Bridge
PTC Starter
Relay
Basic Inverter Technology
Technical Training 2008Technical Training 2008
DC StageDC Stage
• PFC capacitor acts to curb PF losses caused by DC voltage PFC capacitor acts to curb PF losses caused by DC voltage fluctuation in order to drive the asynchronous motorfluctuation in order to drive the asynchronous motor
Stabilizing Capacitor
Reactor
PFC Capacitor
Diode
Basic Inverter Technology
Technical Training 2008Technical Training 2008
Inversion CircuitInversion Circuit
• Consists of 6 IGBT (Insulated Gate Bipolar Transistor)Consists of 6 IGBT (Insulated Gate Bipolar Transistor)
• Controlling the ON/OF linkages, different frequency and voltage of 3-Controlling the ON/OF linkages, different frequency and voltage of 3-phase AC can be generatedphase AC can be generated
• IPM (Intelligent power module) encased the inversion circuitry together IPM (Intelligent power module) encased the inversion circuitry together with error detection and protection featureswith error detection and protection features
Basic Inverter Technology
Technical Training 2008Technical Training 2008
ItemItem Fixed Speed ACFixed Speed AC Inverter ACInverter AC
Energy SavingEnergy Saving NoNo Yes, by 30% - 40%Yes, by 30% - 40%
Temp. FluctuationTemp. Fluctuation ± 2°C± 2°C ± 0.5°C± 0.5°C
Adjust to LoadAdjust to Load NoNo YesYes
Start-upStart-up Current surge of 7-Current surge of 7-11x11x
Soft-start. No Soft-start. No current surgecurrent surge
Full Load Op.Full Load Op. NoNo Yes, operates at Yes, operates at high freq.high freq.
Speed of Cool/HeatSpeed of Cool/Heat SlowSlow FastFast
DefrostingDefrosting Less efficientLess efficient Accurate and fastAccurate and fast
Protection FeaturesProtection Features BasicBasic CompleteComplete
Auto-Mode FeaturesAuto-Mode Features BasicBasic CompleteComplete
Advantages of Inverter Air ConditionersAdvantages of Inverter Air Conditioners
Basic Inverter Technology
Technical Training 2008Technical Training 2008
Components
Technical Training 2008Technical Training 2008
fan motors
Heat exchangers with gold fin as standard
Water pump
True dual circuits BPHE (Brazed plate heat exchanger)
Expansion tank ( 8L)
Control box assembly
Coil guardsFan guards
Components
Technical Training 2008Technical Training 2008
Variable drive system compartment
Fixed drive system compartment
High pressure switch(NC) 600 psi – open, 480psi – close.
Low pressure switch(NC) 18 psi – open, 28 psi – close.
Pump OLP (overload protector)
Differential pressure switch
Over pressure relief valve
Anti freeze heater on BPHE
Compressor OLP (overload protector)
Chiller panel controller
Fixed speed scroll compressor (R410A)
Variable speed scroll compressor (R410A)
Components
Technical Training 2008Technical Training 2008
Control box assembly IPM board(Intelligent power module)
Main board Magneticcontactors
EMI filter
Capacitor board
PFC capacitor(Power factor correction)
Uni-directional bridge diode
3 phase rectifier bridge diode
Fan capacitors
Power board
Components
Technical Training 2008Technical Training 2008
Components
EMI Filter
Function• EMI Filter is a device placed between the power source and control device circuit.• Prevents external electromagnetic interference from getting into the controller.• Prevents internal electromagnetic emission from polluting the supply grid.
Technical Training 2008Technical Training 2008
Main Board
For Model 55, 75, 100 & 135 For Model 30
Components
Technical Training 2008Technical Training 2008
Power Board
- To convert rectified DC current +590VDC to respective desired voltages
- 12VDC relay- MCU +5VDC- IPM +15VDC
- Ensure stability of above voltages within power supply voltage fluctuation range (304-480 VAC)- Over voltage feedback- Output short circuit protection
Components
Technical Training 2008Technical Training 2008
Capacitor Board
Components
Technical Training 2008Technical Training 2008
IPM
Components
Function• Invert DC to AC current• Drive variable compressor
In-Built Protection• Low voltage lock-out• Over-heating, over-current and short-circuit protection.
Technical Training 2008Technical Training 2008
Schematic Diagram
Condenser Coil 1
Acc
Acc
Liq Rvr
Liq Rvr
BPHE FS
Condenser Coil 2
DischTemp 2
(Disch Comp 2)
DischTemp 1
(Disch Comp 1)
InvComp
StdComp
SuctTemp
(Suction)
HP1
HP2
LP2
LP1
Cond InTemp 1
(Condenser)
Cond OutTemp 1
(Def Comp 1)
BPHE OutTemp
(BPHE Out)
BPHE InTemp
(BPHE In)
EWT (Water In)
LWT (Water Out)
Pump
Cond OutTemp 2
(Def Comp 2)
FilterDrier
Heating Cap Tube
Check valve
Cooling Cap Tube
Check valve
FilterDrier
EXV
O/A Temp(Outdoor Air)
Summary Pages-Screen 3
Display Menu-Defrost Sensor
Display Menu-Inverter Chiller
Display Menu-Discharge Sensor
5ACV100CR
4WV
4WV
Components
Technical Training 2008Technical Training 2008
Control Algorithm
Technical Training 2008Technical Training 2008
General Control Flow ChartGeneral Control Flow Chart
Start
No
Stop Inverter Comp
Yes
Stop pump
60s
Clash between current & selected
mode of operation?
Cooling mode
No
Heating?No
YesYes
Heating mode
System On?
Yes
Cooling?No10s
Stop Fixed Comp
Control Algorithm
Technical Training 2008Technical Training 2008
Variable Drive Compressor ControlVariable Drive Compressor ControlCooling mode
Start up condition :
• Pump runs normally for 3 minutes *
• 2°C T water return – T set 4°C
• No irreversible errors in variable drive and the systems• Satisfy a delay of 3 minutes before restart #
Note : If fixed drive system starts first, the variable drive system should trail after 30 sec.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
For example :Return water temp.= 14 to 16 °CSet temp = 12°C T = 2 to 4°C
Control Algorithm
Technical Training 2008Technical Training 2008
Variable Drive Compressor ControlVariable Drive Compressor Control
Cooling mode selected water pump starts Outdoor fan starts variable drive compressor starts
Rated Freq.
55Hz
5Hz
t
3 min 5 sec 1 min
ONOFF
ONOFF
Variable drive comp
Outdoor fan
Outdoor fan will start 5 sec before compressor start
Inverter compressor will start from 5Hz to 55Hz and maintain this frequency for 1 min.
Increase to rated frequency with the rate of 1Hz/s5ACV100CR=75Hz
5ACV135CR=95Hz
Cooling mode
Control Algorithm
Technical Training 2008Technical Training 2008
Variable Drive Compressor ControlVariable Drive Compressor ControlCooling mode
Shut down condition :
• Cooling mode terminates, OR
• T water return – T set -2°C
• Variable drive system error occurs, OR
For example :Return water temp.= 10°CSet temp = 12°C T = -2°C
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlCooling mode
Start up condition :
• Pump runs normally for 3 minutes *
• T water return – T set > 4°C
• No irreversible errors in fixed drive and the systems• Satisfy a delay of 3 minutes before restart #
Note : If variable drive system starts first, the fixed drive system will only start after the frequency of variable drive drops to 50Hz.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
For example :Water return temp = 16°CSet temp = 12°CT = 4°C
Fixed drive starts first followed by variable drive
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlCooling mode
Cooling mode selected water pump starts Outdoor fan starts compressor starts
Outdoor fan will start 5 sec before compressor start
Fixed drive compressor starts
Fixed drive comp
Outdoor fan
1 min3 min 5 sec
ON
OFF
ON
OFF
Outdoor fan will stop after compressor has stopped for 1 min
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlCooling mode
Shut down condition :
• Cooling mode terminates, OR
• T set - T water return > 2°C and variable frequency drops pass 20Hz
• Fixed drive system error occurs, OR
For example :Set temp = 12°CWater return temp = 10°CT = 2°C
Control Algorithm
Technical Training 2008Technical Training 2008
Variable Drive Compressor ControlVariable Drive Compressor ControlHeating modeStart up condition :
• Pump runs normally for 3 minutes *
• 2°C T set - T water return 4°C
• No irreversible errors in variable drive and the systems• Satisfy a delay of 3 minutes before restart #
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
Note : If fixed drive system starts first, the variable drive system should trail after 30 sec.
For example :Set temp = 40°CReturn water temp.= 36 to 38 °C T = 2 to 4°C
Control Algorithm
Technical Training 2008Technical Training 2008
Rated Freq.
45Hz
5Hz
t
3 min 10 sec 1 min
ONOFF
ONOFF
Variable drive comp
Outdoor fan
ONOFFVariable 4WV
5 sec
Variable Drive Compressor ControlVariable Drive Compressor ControlHeating modeHeating mode selected water pump starts Variable drive 4WV engages Outdoor fan starts compressor starts
Outdoor fan will start 5 sec before compressor start
Variable drive 4WV start 10 sec before compressor start
Inverter compressor will start from 5Hz to 45Hz and maintain this frequency for 1 min.
Increase to rated frequency with the rate of 1Hz/s
5ACV100CR=65Hz5ACV135CR=90Hz
Control Algorithm
Technical Training 2008Technical Training 2008
Variable Drive Compressor ControlVariable Drive Compressor ControlHeating modeShut down condition :
• Heating mode terminates, OR
• T set - T water return -2°C
• Variable drive system error occurs, OR
For example :Set temp = 40°CWater return temp = 42°CT = -2°C
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlHeating modeStart up condition :
• Pump runs normally for 3 minutes *
• T set - T water return > 4°C
• No irreversible errors in fixed drive and the systems• Satisfy a delay of 3 minutes before restart #
Note : If variable drive system starts first, the fixed drive system will start after the variable drive frequency drops to 50Hz.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min 0s, max 199s, default 180s )# Depends on Parameter C2 (compressor min stop time. Min 0s, max 1990s, default 180s)
For example :Set temp = 40°CWater return temp = 36°CT = 4°C
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlHeating modeHeating mode selected water pump starts Fixed drive 4WV engages Outdoor fan starts compressor starts
Outdoor fan will start 5 sec before compressor start
Fixed drive 4WV start 10 sec before compressor start
3 min 10 sec 1 min
ON
OFF
ON
OFF
Fixed drive comp
Outdoor fan
ON
OFFVariable 4WV 5 sec
Fixed drive compressor starts
Outdoor fan and 4WV will stop after compressor has stopped for 1 min
Control Algorithm
Technical Training 2008Technical Training 2008
Fixed Drive Compressor ControlFixed Drive Compressor ControlHeating modeShut down condition :
• Heating mode terminates, OR
• T water return - T set > 2°C
• Fixed drive system error occurs, OR
For example :Water return temp = 42°CSet temp = 40°CT = 2°C
Control Algorithm
Technical Training 2008Technical Training 2008
Pump ControlPump Control
Pump start up
When starting the system, pump will run for 3 minutes * before proceeding to next step.
* Depends on Parameter P2 (flow switch alarm delay at pump start. Min = 0s, Max = 199s, default = 120s)
Pump shut down
After both compressors shut down for 1 minute, pump shuts down.
Control Algorithm
Technical Training 2008Technical Training 2008
Protection
Technical Training 2008Technical Training 2008
Compressor Over-Current ProtectionCompressor Over-Current Protection
Variable drive compressor • When variable drive compressor current reaches the Ib, over-current protection triggers and the compressor frequency will reduce.• When the compressor current drops into Ic to Ib, frequency will not increase. • When the compressor current drops below the Id, frequency variation resumes.• When compressor current increase rapidly and reaches the Ia, the system will be determined as compressor overload and stop the compressor.
Ia
Ic
Variable compressor stops
Maintain frequency
Normal Operation
Comp amp (A)
IbFrequency step down
Id
Protection
Technical Training 2008Technical Training 2008
Compressor Over-Current ProtectionCompressor Over-Current Protection
Variable drive compressor
Inv Inv Comp Comp
CurrentCurrent
M5ACVM5ACV030030
M5ACVM5ACV055055
M5ACVM5ACV075075
M5ACVM5ACV100100
M5ACVM5ACV135135
M5ACVM5ACV210210
IIaa 2929 20.520.5 20.520.5 20.520.5 20.520.5 20.520.5
IIbb 2727 1818 1818 1818 1818 1818
IIcc 2525 1717 1717 1717 1717 1717
IIdd 2525 1616 1616 1616 1616 1616
Protection
Technical Training 2008Technical Training 2008
Compressor Over-Current ProtectionCompressor Over-Current ProtectionFix drive compressor • When fixed compressor current > Ie. The compressor will stops and resumes after 3 minutes
Note: When either drive overload protection occurs more than 3 times within 30 minutes, system triggers irreversible error protection.
Fixed compressor stopsComp amp
(A)
Ie
Model Ie
5ACV30 NA5ACV55 NA5ACV75 NA
5ACV100 165ACV135 305ACV210 ?
Protection
Technical Training 2008Technical Training 2008
High Discharge Temperature ProtectionHigh Discharge Temperature ProtectionVariable drive system• When variable drive discharge temperature reaches 110°C, system stops.• When variable drive discharge temp. between 100°C and 110°C, frequency drops.• When variable drive discharge temperature is less than 97°C and more than 100°C, frequency increased restricted.• When discharge temperature falls below 94°C, normal operation resumes.
System shuts down
Frequency step down
Maintain frequency
Normal operation
Compressor dischargetemperature
110°C
100°C
97°C94°C
Protection
Technical Training 2008Technical Training 2008
High Discharge Temperature ProtectionHigh Discharge Temperature Protection
Fixed drive system• When fixed drive discharge temperature reaches 110°C, system stops.• When discharge temperature falls below 94°C for 3 minutes, system resumes.
Td = Compressor discharge temperature
110°C
94°CComp start
Comp Cut
3 min
Td
Protection
Technical Training 2008Technical Training 2008
Outdoor Coil High Temperature ProtectionOutdoor Coil High Temperature Protection
Variable drive system• During cooling, when Tcoil1 > 60 °C, frequency drops.• During cooling, when Tcoil1 < 55 °C, system resumes.
Fixed drive system• During cooling, when Tcoil2 > 64°C, compressor stops.• During cooling, when Tcoil2 < 51°C, system resumes.
Protection
Technical Training 2008Technical Training 2008
Low Pressure Switch ProtectionLow Pressure Switch Protection
• Alarm delayed at compressor startup : 30 sec depends on Parameter P3*.• No protection during defrosting.• If variable drive or fixed drive low pressure switch is activated for 5 seconds, alarm will be triggered.* Parameter P3 (Low pressure alarm delay at compressor start up. Min=0s, max=199s, default=30s)
Note : If low pressure alarm occur more than 3 times within 30 minutes, system shuts down to irreversible error.
Protection
Technical Training 2008Technical Training 2008
High Pressure Switch ProtectionHigh Pressure Switch Protection
• If fixed drive high pressure switch is activated for 30 sec, alarm will be triggered.• If variable drive high pressure switch is activated, frequency of variable drive compressor will decrease at 1Hz/s. If it is re-activated for 30 sec, alarm will be triggered.
Note : If high pressure alarm occur more than 3 times within 30 minutes, system shuts down to irreversible error.
Protection
Technical Training 2008Technical Training 2008
If 3 phase AC phase sequence is incorrectly connected, system will not start and controller will indicate error. System will resume after rectification. (except M5ACV030CR)
If phase missing happens, system will not operate. Controller will indicate error. System will resume after rectification.
3 Phase AC Phase Sequence Protection
3 Phase AC Phase Missing Protection
Protection
Technical Training 2008Technical Training 2008
Thank YouThank You