TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions 1302 Goshen Parkway West Chester, PA 19380 Phone: 610-692-9100 800-888-2323 Fax: 610-692-9192 Web: www.zeks.com Form: TM 1000-1600HSF-DPC-0513 DPC Patent No.: 6,186,223 NOTICE Those operating the machine or performing maintenance should read and understand the decals positioned on the machine and contents of this Technical Manual. Ensure that this Technical Manual is not removed permanently from the machine. TM

Transcript of TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling...

Page 1: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

TECHNICAL MANUAL

HeatSinkTrue-Cycling RefrigeratedCompressed Air Dryers

HSF Models1000-1600 SCFM

ZEKS Compressed Air Solutions1302 Goshen Parkway

West Chester, PA 19380Phone: 610-692-9100

800-888-2323Fax: 610-692-9192Web: www.zeks.com

Form: TM 1000-1600HSF-DPC-0513DPC

Patent No.: 6,186,223

NOTICEThose operating the machine or performingmaintenance should read and understand thedecals positioned on the machine andcontents of this Technical Manual.

Ensure that this Technical Manual is notremoved permanently from the machine.

TM

Page 2: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

TABLE OF CONTENTS PAGE

1. INTRODUCTION 22. ABBREVIATED WARRANTY 23. REFRIGERATED DRYER NOMENCLATURE 34. RECEIVING AND INSPECTION 45. SAFETY AND OPERATION PRECAUTIONS 56. PRINCIPLES OF OPERATION 67. INSTALLATION AND INITIAL START-UP 158. SCHEDULED MAINTENANCE 189. TECHNICIAN MODE 20

10. TROUBLESHOOTING 2311. WIRING DIAGRAMS 2512. GENERAL ARRANGEMENT 3113. PARTS IDENTIFICATION 3214. ENGINEERING SPECIFICATIONS 33

TECHNICAL MANUAL

HeatSinkTrue-Cycling Refrigerated Compressed Air Dryers

HSF Models1000-1600 SCFM

Patent No.: 6,186,223TM

ZEKS Compressed Air Solutions1302 Goshen Parkway

West Chester, PA 19380Phone: 610-692-9100

800-888-2323Fax: 610-692-9192Web: www.zeks.com

Page 3: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

2. ABBREVIATED WARRANTYZEKS refrigerated dryers are warranted to be free from defects in material and workman-ship for a period of 12 months from the original date of shipment from the factory. Toallow the warranty to be in effect for 12 months from the date of equipment start-up, theWarranty Registration Card must be completed and returned to ZEKS. Alternately, theWarranty Registration Card may be completed online at www.zeks.com. The totalwarranty period cannot exceed 18 months from the original date of shipment from thefactory.

Equipment must be installed and operated in accordance with ZEKS’ recommendations.ZEKS liability is limited to repair of, refund of purchase price paid for, or replacement inkind at ZEKS’ sole option, during the warranty time period stated above. IN NO EVENTSHALL ZEKS BE LIABLE OR RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIALDAMAGES, even if the possibility of such incidental or consequential damages has beenmade known to ZEKS Compressed Air Solutions. In addition, the usual maintenance andreplacement type products are not covered by this warranty.

REFRIGERANT COMPRESSORS A prorated warranty for the replacement of the refrigerant compressor will be extended toa maximum of 60 months (5 years) from the original date of shipment from the factory.Following the standard warranty terms, the available prorated compressor warranty is asstated below. This prorated warranty applies to replacement compressor only and doesnot cover any labor expenses.

Prorated coverage of price from date of shipment from the factory:19 to 24 months 70%25 to 36 months 50%37 to 48 months 30%49 to 60 months 10%

2

1. INTRODUCTION

The ZEKS HeatSink refrigerated air dryer removes moisture, oil vapor, and other contami-nants from compressed air. These contaminants are detrimental to pneumaticallyoperated appliances, controls, instruments, machinery and tools. This is accomplished bycooling the air with a refrigeration unit to a temperature at which moisture in the air iscondensed and separated from the airstream. The temperature the air is cooled to,normally between 36 and 40°F, is known as dew point. This dryer can be easily installedinto various pneumatic systems in which dry air is required or desired. Please refer toPrinciples of Operation for complete operating details.

Page 4: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

3

HEAT EXCHANGERS Dryers that utilize CFX heat exchanger technology (HSF, HSG, NCE & NCG) are coveredfor a total of 10 years from the original date of shipment from the factory. Following thestandard warranty terms the available warranty is as stated below. The exchangerwarranty applies to the replacement exchanger only and does not cover any laborexpenses.

Prorated coverage of prices from date of shipment from the factory:18 to 48 months 100%49 to 60 months 70%61 to 72 months 50%73 to 84 months 30%85 to 96 months 20%97 to 120 months 10%

Freight and labor coverage varies internationally. Refer to Distributor Warranty Guidelinesfor limitations and detailed explanation of warranty coverage.

The warranties expressed above are in lieu of and exclusive of all other warranties. Thereare no other warranties, expressed or implied, except as stated herein. There are no im-plied warranties of merchantability or fitness for a particular purpose, which are specificallydisclaimed.

3. REFRIGERATED DRYER NOMENCLATURE

NOMINALFLOW DESIGN CONDENSERSCFM TYPE SERIES TYPE POWER OPTIONS

1000, 1200 HS= HeatSink F A=Air Cooled 4=460-3-601600 W=Water Cooled 5=230-3-60

6=575-3-60

O = STANDARD O = STANDARDH = NEMA 4 Z = SPECIALW = WEATHERPROOF 8 = DPC-8 F = AMBIENT AIR FILTER

Page 5: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

4. RECEIVING AND INSPECTION

4.1 INSPECTIONUpon receiving your ZEKS air dryer, please inspect the unit closely. If rough handlinghas been detected, please note it on your delivery receipt, especially if the dryer willnot be immediately uncrated. Obtaining the delivery person’s signed agreement toany noted damages will facilitate any insurance claims

4.2 UNPACKING AND HANDLING

Under no circumstances should any person attempt to lift heavyobjects without proper lifting equipment (i.e., crane, hoist, slings orfork truck). Lifting any unit without proper lifting equipment, cancause serious injury.

All dryer packages have been mounted on a base which provides for forkliftingbetween the two base channels to facilitate handling during shipment. Forks shouldextend all the way through forklift channels to reduce unnecessary forces to the dryerduring moving. Slings can be used to lift the crates, but spreader bars must be usedto prevent the slings from exerting a force against the sides of the crates.

4

WARNING

Page 6: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

5

5. SAFETY AND OPERATION PRECAUTIONS

Because an air dryer is pressurized and contains rotating parts, the same precautionsshould be observed as with any piece of machinery of this type where carelessness inoperation or maintenance could be hazardous to personnel. In addition to obvious safetyrules that should be followed with this type of machinery, safety precautions as listedbelow must be observed:

OSHAHeading Descriptions

1. Only qualified personnel shall be permitted to adjust, perform maintenance or repair this air dryer.

2. Read all instructions completely before operating unit.

3. Pull main electrical disconnect switch and disconnectany separate control lines, if used, before attempting towork or perform maintenance on the unit.

4. Do not attempt to service any part while machine is inan operational mode.

5. Do not attempt to remove any parts without first relievingthe entire air system of pressure.

6. Do not attempt to remove any part of the refrigerationsystem without removing and containing refrigerant inaccordance with the EPA and local regulations.

7. Do not operate the dryer at pressures in excess of itsrating.

8. Do not operate the dryer without guards, shields andscreen in place.

9. Inspect unit daily to observe and correct any unsafeoperating conditions.

The user of any air dryer manufactured by ZEKS Compressed Air Solutions, is herebywarned that failure to follow the above Safety and Operation Precautions may result inpersonal injury or equipment damage. However, ZEKS Compressed Air Solutionsdoes not state as fact, nor does it mean to imply, that the preceding list of Safety andOperating Precautions is all inclusive, and further, that the observance of this list willprevent all personal injury or equipment damage.

“Warning” is used to indicate ahazardous situation which hassome probability of death orsevere injury. Warning shouldnot be considered for propertydamage accidents unlesspersonal injury risk is present.

“Notice” is used to indicate astatement of company policyas the message relates directlyor indirectly to the safety ofpersonnel or protection ofproperty. Notice should not beassociated directly with ahazard or hazardous situationand must not be used in placeof “Danger,” “Warning,” or“Caution.”

CAUTION

“Caution” is used to indicate ahazardous situation which mayresult in minor or moderateinjury.

NOTICE

NOTICE

WARNING

Page 7: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

6

6. PRINCIPLES OF OPERATION

6.1 INTRODUCTIONZEKS HEATSINK™ dryers remove moisture from compressed air by cooling the airtemperature to between 36° and 40°F (2 and 4°C). This causes vapors to condenseinto liquid droplets which can then be easily removed from the air. The majorsystems of the dryer which contribute to its operation are the Air System, the MoistureRemoval System, the Refrigeration System, the Thermal Mass Circulating Systemand the Controls. The following paragraphs describe each of the systems in greaterdetail.

6.2 AIR SYSTEMThe air system consists of the dryer components which are in contact with thecompressed air. Referring to Figure 1 and following the bold “AIR FLOW,” hot saturatedair from the compressor enters the precooler/reheater where the air temperature isreduced prior to entering the chiller by the cool air exiting the air/moisture separator.This precooling allows for the use of a smaller refrigeration system. The air thengoes into the chiller section where it is further cooled to the desired dew point by athermal mass fluid. The temperature of the thermal mass fluid is maintained by therefrigeration circuit and controls. The air continues to the separator where moisture isremoved, thereby, allowing the cool, dry air to return to the precooler/reheater to beheated by the incoming moist hot air. The air exiting the “reheater” portion of thedryer should be approximately 15°- 20°F lower than the inlet air temperature basedon standard conditions at full rated flow.

FIGURE 1FLOW DIAGRAM

DRAWING 500161

Page 8: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

7

6.3 MOISTURE REMOVAL SYSTEMLiquid droplets are removed from the air stream in the separator. As the air andliquid mixture passes through the separator it spins, slows down and then changesdirection. This causes the condensate to fall out of the air stream and collect in thebottom of the separator. The collected liquid is removed from the separator by asolenoid valve. The solenoid valve is controlled by the microprocessor controller asdescribed in Section 6. For adjustment please note the following:

• To obtain the optimum time values for operation of the solenoid drain valve, set the off-time to three minutes and the on-time ten seconds via the controller.

• After running the unit under full rated flow for approximately 30 minutes, verify thatwhen the solenoid drain opens, all of the accumulated liquid is discharged and thena small burst of air.

• If a small amount of liquid and a large amount of air is discharged, decrease the on-time setting or increase the off-time setting. If there is all liquid and no air has beendischarged, increase the on-time setting or decrease the off-time setting.

• The on/off time settings will vary according to seasonal operating conditions. Duringthe summer when more moisture is present in the air system a shorter on-time,increasing the valve opening frequency, is required. A longer valve off-time may beused during the winter months when moisture levels are lower.

6.4 REFRIGERATION SYSTEMThe Refrigeration System consists of all the components which handle refrigerant.This is a hermetically sealed closed-loop system. Referring to Figure 1 and followingthe phantom “REFRIGERANT FLOW,” refrigerant is shown leaving the evaporator sectionwhere, in the process of removing heat, it is changed from a low pressure liquid intoa low pressure gas. This gas enters the suction side of the compressor where it iscompressed into a high pressure gas. The high pressure gas is cooled in the aircooled or water cooled condenser section until it becomes a high pressure liquid. Itthen goes through a permanent filter dryer that ensures the refrigeration system isfree of contaminants. A thermostatic expansion valve meters the refrigerant forintroduction into the evaporator. The refrigerant pressure is reduced upon enteringthe evaporator where as it evaporates, heat is removed from the thermal mass fluid.A solenoid valve in the liquid line eliminates the possibility of flooded starts.

6.5 THERMAL MASS CIRCULATING SYSTEMThe thermal mass fluid in a ZEKS HEATSINK™ dryer is continuously circulated in aclosed pump loop system. Referring to Figure 1 and following the dashed “THERMALMASS FLUID” line, the heat is removed from the fluid in the evaporator by the refrigera-tion system. The thermal mass reservoir is sized to minimize refrigeration cyclesduring reduced air load periods. The thermal mass fluid is pulled from the bottom ofthe reservoir and pumped through the chiller, removing heat from the air and returnedto the evaporator. The pump utilized on ZEKS’ HEATSINK™ dryer is a maintenance-free, quiet cartridge circulator pump similar to those used in residential watersystems. While the refrigeration system cycles on and off based on loadingconditions, the circulating pump runs continuously to maintain flow through the chillerat all times.

Page 9: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

6.6 CONTROLS

ZEKS’ 1000-1600HSF Refrigerated Compressed Air Dryers are equipped with theDigital Performance Controller (DPC™). This advanced microprocessor-basedcontroller has been engineered by ZEKS exclusively for use with ZEKS’ CompressedAir Dryers.

The DPC™ cycles the refrigeration system based on the dryer's Chiller Temperature.A temperature sensor samples the thermal mass temperature as it enters the chillerexchanger. The Chiller Temperature Set point is a user adjustable set point that isused to set the Refrigeration Compressor Off temperature. Once the ChillerTemperature has fallen below the Chiller Temperature Set point, the refrigerationcompressor will de-energize. The Operating Temperature Differential is factory set at4°F above the Chiller Temperature Set point. Therefore, if a user adjusts the ChillerTemperature at 36°F, the Refrigeration Compressor On temperature will be 40°F.

In addition to the operation of the HeatSink™ dryers as described above, the DPC™permits monitoring of dryer parameters and enunciation of alarm conditions.

The list below summarize the features the DPC™:

• 2 X 16 Character Backlit LCD Display - Easy-to-read display provides continuousindication of dryer default parameter. Standard backlight permits viewing of criticalinformation in low light environments.

• Electronic Drain with On/Off Time Adjustment: Included with DPC™-equippedHeatSink™ and NonCycle dryers is a solenoid drain valve. Control of the open andclose time of the valve is set via the DPC™ Controller.

• Remote Start / Stop: DPC™-equipped dryers offer a unique remote start / stopfeature. This feature allows the dryer to be operated via a remote user-suppliedswitch.

• Remote Alarm Contact: DPC™-equipped dryers include a remote alarm contact toprovide indication of any of the dryers alarms described later in this manual.Contact rated for 2A / 120V max.

The DPC™ Controller features three levels of access. The default level CUSTOMERMODE permits adjustment of dryer parameters to address seasonal variations fordrain timing and pressure dew point temperature. A protected TECHNICIAN MODEpermits access to and manipulation of additional parameters to address the initialmachine set up. A password protected FACTORY MODE is also included for use withZEKS Service Personnel for troubleshooting the dryer.

8

Page 10: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

The DPC™ controller includes a digital readout for monitoring the discharge pressureof the refrigerant gas exiting the compressor. This reading will vary dependent uponcondenser type as indicated below:

• For air-cooled applications, condensing fans are cycled on and off by the DPCbased on the refrigerant discharge pressure. Primary fan(s) are cycled on at 235psig and off at 195 psig. Should the discharge pressure continue to climb above265 psig, the secondary condensing fans will cycle on. As discharge pressure isreduced below 210 psig, the secondary fan(s) will cycle off. On 1000 and1200HSF models, two condensing fans are utilized. The 1600HSF has threecondenser fans. For the 1600HSF, the center fan is the primary controlled fanthe outside fans are the secondary controlled fans.

• Water cooled condensers utilize a water regulating valve (Note Figure 2). Thewater regulating valve comes pre-adjusted from the factory at 250 psig dischargepressure. To compensate for water temperature variation, it may be necessary toadjust the water regulating valve to maintain a 250 psig discharge pressure.Adjustment can be done by rotating the adjusting screw counterclockwise for anincrease in discharge pressure. For conditions where low water temperatureand/or high water pressure are expected it is advisable to install a water pressureregulator ahead of the condenser.

ADJUSTMENT SCREW

FIGURE 2WATER REGULATING VALVE

Drawing 600562

9

Page 11: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

10

6.6.1 BASIC USER INTERFACEThe DPC™ display provides the user with the operating parameters and theircorresponding values. The following illustration summarizes the keypad functions.

BUTTONS

• ON Places the dryer "On Line"; Energizes glycol pump onHeatSink™ dryers. For HeatSink™ models, thecompressor will operate based on temperature;

• OFFPlaces the dryer "Off Line"; Stops all automatic functions,including circulating pump operation on HeatSink™ dryers.

• SELECT DISPLAYAllows the user to cycle through the available displays.The last display selected will remain displayed as thedefault display.

• + / -Allows user to increase set point values. Set point valuescycle through a fixed range. Also allows entering negativenumbers in FACTORY MODE.

• TESTAllows user to manually activate the drain solenoid valve.

• RESETPressing once clears the local alarm indication and de-energizes the remote alarm contact. Should the alarmcondition persist, the alarm will return after the alarminhibit time has expired.

• SETPermits the adjustment of parameters in TECHNICANand FACTORY MODES. In CUSTOMER MODE, allowsuser to back through displays,

• ENTERUsed to accept changed parameters and set pointvalues.

• iRestricted Level access for factory use only. Not usedfor basic dryer functions. Not to be used by customer orservice technician.

CHLLR TEMP: 37

Page 12: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

11

6.6.2 DISPLAY PARAMETERSThe DPC™ Controller is capable of displaying a number of system parameters.The following summarizes the parameters that can be accessed by the user fromthe DPC™ Controller:

• Chiller Temperature (CHLLR TEMP): For HeatSink Dryers, the ChillerTemperature is the temperature, in degrees Fahrenheit, of the thermal mass fluid.

• Compressor Status (CMPRSSR): Displays whether the refrigeration compressoris “ON” or “OFF”.

• Discharge Pressure (P disch): Displays the discharge pressure of the refrigerationsystem.

• Suction Temperature (T suction): Displays the suction temperature, in deg. F, ofthe refrigeration system. This value is useful in determining superheat of therefrigerant.

• Suction Pressure (P suction): Displays the suction pressure, in psig, of the refrig-eration system.

• Inlet Air Pressure and Temperature (P AIR IN / T AIR IN): Displays the tempera-ture, in °F and pressure, in psig, of the inlet compressed air. (DPC™-Plus Only)

• Outlet Air Pressure and Temperature (P AIR OUT / T AIR OUT): Displays thetemperature, in °F and pressure, in psig, of the outlet compressed air. (DPC™-Plus Only)

• Drain Interval (DRN INT): Displays the length of time, in minutes, betweenoperation of the solenoid drain.

• Drain On (DRN ON): Displays the length of time, in seconds, that the solenoiddrain is open.

• Percent Savings (% SVGS): Displays the length of time the compressor has beenoperating versus the length of time the dryer has been on.

• Cumulative Dryer Hours (CUM DRYER HR): Displays the length of time, in hours,that the dryer has been operational.

• Cumulative Compressor Operating Hours (CUM CMP HR): Displays the length oftime, in hours, that the refrigeration compressor has been energized.

Depressing the SELECT DISPLAY button repeatedly scrolls through the abovenon-adjustable displays. The Customer Set Points appear at the end of the listand may be adjusted by the end user to match seasonal refrigeration and drainoperation. These settings are as follows:

• Chiller Temperature (CHLLR TEMP)

• Drain Interval (DRN INT)

• Drain On (DRN ON)

Page 13: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

12

SELECTDISPLAY

Pressing SELECT DISPLAY will increment the displaythrough the available display parameters.

Depress “ + / -“ as required to change the DRN INT timeto 5 minutes.

Pressing “ENTER“ saves the set point.

6.6.4 ADJUSTING SET POINTSAccessing and manipulating each of the set points in the CUSTOMER MODE isaccomplished as follows. The parameter is selected using the SELECT DISPLAYbutton. After scrolling through the displays, the “Cust Set Points” screen isdisplayed. The parameters after this screen may be adjusted by the user. Oncethe desired parameter is displayed, depressing the “+/-” button changes the setpoint. Once the new set point is displayed, depressing ENTER saves the set point.Exiting the Customer Set Point routine is accomplished by depressing the SELECTDISPLAY button until the END CUST SET PTS screen is displayed. The followingexample illustrates the keystrokes required to change the Drain Closed Time fromthe default value of 3 Minutes to 5 Minutes:

6.6.3 DRYER SET POINTS AND ALARMSThe DPC™ Controller has several user adjustable set points that are displayed atthe end of the display parameter list. These set points allow the user to configurethe dryer to operate according to site conditions. The controller is shipped from thefactory with each parameter having its own default value. The following chartsummarizes the parameters that may be adjusted by the user:

Display Parameter SETPOINT Description Range HeatSink NonCycleDrain Interval Time DRN INT 3, 5, 10, 15, 20, 30, 60 min 3 MIN 3 MINDrain On Time DRN ON 3, 5, 7, 10, 12, 15 , 20, 30 sec. 10 SEC 10 SECChiller Off Temperature CHLLR TEMP 32°F - 50°F; 1 °F increments 34°F INACTIVE

Factory Setpoint

ENTER

DRN INT: 5 min

SELECTDISPLAY

Press SELECT DISPLAY as necessary to display the EndCustomer Set points Screen.End Cust Set Pts

DRN INT: 5 min

+-

CHLLR TEMP: 36

SELECTDISPLAY

Continue pressing SELECT DISPLAY until the CustomerSet point screen is displayed. The parameters that followare the User Adjustable Parameters for the controller.

Cust Set Points

SELECTDISPLAY

Press SELECT DISPLAY until “DRN INT” is displayed.DRN INT: 3 min

SELECTDISPLAY

Press SELECT DISPLAY as necessary to return the DPCto the desired display parameter.CHLLR TEMP: 36

Page 14: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

13

6.6.5 ALARMS AND THEIR FUNCTIONSThere are several alarms detected by the DPC™ to alert the user of an out oftolerance condition. Once each alarm is detected, a description of the alarm willappear in the screen and the remote alarm contact will close. Note that during thealarm condition, the SELECT DISPLAY button may be depressed to scroll throughthe available parameters. After approximately 30 seconds, the alarm screen willreappear, provided the alarm condition persists.

The alarm names and description of each are described in detail below. Note thatsome alarms will enunciate only after a prescribed alarm delay. Refer to theTECHNICIAN MODE section of this manual for factory default alarm delay periods.

HIGH TEMPERATURE ALARM (HITEMP ALARM)When the thermal mass (glycol) temperature in a HeatSink™ dryer (separatortemperature for NonCycle dryers) reaches the factory alarm set point, after analarm delay, the alarm will be activated. This alarm condition may not necessarilydamage the dryer when subjected to long-term exposure. It may, however, have asignificant impact on downstream processes and thus should be investigated upondetection. Note that this alarm will not shut down the dryer. This alarm will activatethe remote alarm contact and reset automatically once the alarm condition isrectified.

LOW TEMPERATURE SAFETY ALARM (LOWTEMP ALARM)If the dryer chiller temperature falls to or below the factory set point and remains ator below this set point for the factory delay time, the alarm routine will activate.This alarm condition may cause damage to the dryer when subjected to continuousor long-term exposure. Note that this alarm will shut down the dryer after aresponse time delay. This alarm will activate the remote alarm contact and resetautomatically once the alarm condition is rectified.

HIGH PRESSURE CUTOUT ALARM (HPCO ALARM)If the discharge pressure of the refrigerant is determined to be above the set point,the alarm routine will activate. This alarm condition may cause damage to thedryer when subjected to continuous or long-term exposure. Note that this alarm willshut down the dryer after a response time delay. The operator must depress theRESET button in order to clear the alarm and restart the refrigeration system.

LOW PRESSURE CUTOUT ALARM (LO PRESS CO)If the suction pressure of the refrigerant is determined to be below the set point ofthe LPCO alarm, the DPC alarm routine will activate. This alarm condition maycause damage to the dryer when subjected to continuous or long-term exposure.Note that once cleared, the compressor will restart automatically. However, if twosuccessive low-pressure conditions are determined, this alarm will shut down thedryer after a response time delay and will display the alarm condition. The operatormust depress the RESET button in order to reinstate the compressor.

Alarm Display Alarm Set PointHIGH PRESSURE CUTOUT HI PRESS CO See Table 1LOW PRESSURE CUTOUT LO PRESS CO See Table 1HIGH TEMPERATURE ALARM HITEMP ALRM 55 °FLOW TEMPERATURE ALARM LOTEMP ALRM 30 °FHIGH DRAIN LEVEL ALARM DRAIN LVL ALARM N/A

Page 15: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

HIGH DRAIN LEVEL ALARM - OPTIONAL (DRAIN LVL ALARM)On dryers equipped with the optional High Drain Level Alarm, should condensaterise to a predetermined level in the separator, a liquid level switch will signal theDPC and the High Drain Level Alarm will enunciate. In addition to indicating thealarm on the LCD and closing the remote alarm contact, the High Drain Level Alarmwill open the solenoid drain in an attempt to correct the problem. The condition willnot shut off the dryer. Once the source of the problem has been addressed, thealarm will automatically reset.

6.6.6 START MODESZEKS dryers are capable of starting in one of three start modes. Note that toprotect the refrigeration compressor from repeated rapid starts, the DPC™ isequipped with an an anti-short cycle (ASC) delay. The ASC delay will countdownfrom the factory set point (see TECHNICIAN MODE). Only after the ASC delayhas timed out will the refrigeration system operate. Below are brief descriptions ofthese various start modes.

6.6.6.1 Manual ModeZEKS dryers are shipped from the factory in the Manual Mode. After power issupplied to the dryer, the user will be presented with the ASC delay, followed by the“PRESS ON BUTTON” display. After the ASC delay has timed out, the dryer willonly start once the ON button is depressed. In this configuration, to restart thedryer, the user must manually depress the ON button on the dryer’s control panel.

6.6.6.2 Auto Restart ModeAfter power is applied to the dryer, and once an anti-short cycle delay has timedout, the dryer will start automatically. In addition, this mode of operation allowsmanual control of the dryer via the ON & OFF pushbuttons. This is useful forapplications where automatic restarting of the dryer is desired after a power failurehas occurred.

6.6.6.3 Remote Automatic ModeThis mode of operation allows the user to control the dryer remotely and requiresthe installation of a customer-supplied contact. With power applied to the dryerand once the anti-short cycle delay has timed out, the dryer will start automaticallyonce the switch is closed. In addition, this mode of operation still permits manualcontrol of the dryer via the ON & OFF pushbuttons. Note that the signal to theRemote Alarm Contact must be 24V.

TABLE - 1

14

Parameter R-404A R-407CFan 1 ON 275 psig 235 psigFan 1 OFF 195 psig 195 psigFan 2 ON 335 psig 265 psigFan 2 OFF 235 psig 210 psigHPCO (Air-Cooled) 450 psig 400 psigHPCO (Water-Cooled) 320 psig 320 psigLPCO 20 psig 20 psig

Page 16: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

Failure to comply to the above instructions may result in equipment malfunctionand will void warranty.

Always use a backup wrench when making any threaded connection to the dryer.Failure to use a backup wrench may result in damaged tubing and components internal to the cabinet.

7.2 PIPING AND VALVESInstall piping, fittings and accessories as required for specific site conditions andrequirements. Figure 3 indicates a typical piping arrangement for a refrigerated dryer,including dryer and filter bypasses. This figure can be used as a guide for valve andaccessory placement in the system.

ZEKS 1000 through 1600 HSF models come factory installed with a drain isolationvalve (D). The isolation valve permits maintenance of the automatic drain withoutisolating air flow to the dryer. To operate dryer, all valves shown in Figure 3 are to beclosed except valves (B), (C) and (D). Valve (A) is used for bypass purposes andvalve (E) is for test and manual drain purposes.

7. INSTALLATION AND INITIAL START-UP

7.1 LOCATION AND MOUNTINGThe dryer should not be located in an area where ambient temperature is likely to exceed 113°F (45°C) or be less than 50°F (10°C). The dryer must be located inan area that provides sufficient clearance from walls and other adjoining equipmentto allow easy access for servicing and maintenance requirements. A minimum of 30 inches is required to allow free flow of air to the condenser inlet and clearance forservicing the dryer.

On installations with a relatively steady flow rate, the dryer is normally connected afterthe air receiver. If loads fluctuate widely, the dryer should be positioned ahead of thereceiver and sufficient storage capacity downstream is necessary to prevent excessive air flow through the dryer.

When installed after any compressor that causes significant vibration or air pulsation,such as reciprocating compressors, proper vibration isolation and pulsation dampening devices should be added to protect the dryer.

NOTICE

Dryers equipped with the optional SDD200H drain are shipped with a foammaterial inside the drain housing to protect the internal components of the drainduring shipment of the dryer. The foam material must be removed and thesupplied 3/4” plug installed in the designated port prior to start-up.

NOTICE

NOTICE

15

Page 17: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

FIGURE 3TYPICAL PIPING ARRANGEMENT

AIRDRYER

OILSEPARATOR

DRAINVALVE

CHECKVALVE

CHECKVALVE

CHECKVALVE

DRAINVALVE

CHECKVALVE

PREFILTER

B

A

CAIR OUTAIR IN

DE

UNIT AS DELIVERED

OPTIONAL ACCESSORY ITEMS

NOTE: DRAIN TUBE MUST NOT RISE OR BE CONNECTED TOEXCESSIVELY LONG PIPE WHICH MAY CREATE BACK PRESSUREA CONNECTION TO OPEN FLOOR DRAIN IS REQUIRED

7.4 ELECTRICAL CONNECTIONEquipment is available in various electrical configurations. All customer connectionscan be made at the terminal connections located in the customer electrical connectionbox on the rear of the dryer. (Refer to General Arrangement and appropriate WiringDiagrams.)

A suitable fused disconnect switch or circuit breaker, in accordance with national andlocal code requirements, is recommended for all ZEKS equipment. Refer to theEngineering Specifications section for voltage requirements and load.

7.4.1 ZEKS dryers can be configured for three variations of start modes: Manual Mode,Automatic Mode and Remote Mode. The instructions below describe the methodsto configure the dryer for a particular Start Mode.

A) Manual Mode (Factory Default) - No modification required to operate dryer inManual Mode. Once power is applied, dryer can be started or stopped bydepressing the local ON / OFF pushbuttons located on the front panel.

Never wire directly or connect any additional wires to the compressorjunction box. This will cause severe system malfunction.

CAUTION

16

7.3 FILTRATIONTo protect the air dryer from gross contamination associated with compressor oil anddebris and ensure maximum dryer performance, a prefilter is recommended.Prefilters and afterfilters sized to your drying application can be provided by ZEKS andare available factory installed. Call your local distributor to select the filter that bestsuits your filtration requirements. In addition to air filtration, condensate dischargeoil/water separators are also available to address stringent EPA regulations.

Page 18: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

B) Auto Restart Mode - Auto Restart Mode permits the dryer to start after a briefdelay once power is applied to the dryer. In TECHNICIAN MODE, changing theAuto Restart parameter from the default “N” to “Y” using the SET button enablesthis mode of operation. Note that the dryer’s touch pad will still affect dryeroperation. Depressing the OFF button will de-energize the refrigerationcompressor and all other electrical components. After the OFF button has beendepressed, the user must depress the ON button to permit the dryer to operate.

C) Remote Mode - Remote Mode allows the dryer to be turned ON or OFF via aremote switch supplied by the customer. This mode will work regardless of thesetting for Auto Restart. The dryer must be powered on for this feature to takeeffect. To enable this feature:

• Install N.O. remote switch as indicated on the appropriate wiring diagram.

• Customer-supplied contact should be rated at 1A at 24V. To operate dryer,close switch or contact and allow dryer to start after an initial delay. Thelocal On / OFF pushbuttons may also be used at any time after contactclosure.

17

7.5 INITIAL START-UP

For water cooled models, the water valve must be manually openedto ensure that the condenser is full of water prior to start-up.

7.5.1 START- UP SEQUENCE

• Apply power to dryer. LCD Panel will illuminate. The Anti-Short Cycle delay willcommence counting down. Remaining time on the Crankcase heater will alsocountdown.

After installation or a prolonged shutdown, start the dryer with no air load (no air flow).This enables the dryer to reach its proper operating temperature in the shortest timepossible (typically within 30 minutes for HeatSink™ dryers).

NOTICE

NOTICE

Allow 8 hours of warm-up time for the crankcase heater prior to start up.Crankcase heater is connected directly to the incoming power and isenergized at all times.

CAUTION

Page 19: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

18

8.0 SCHEDULED MAINTENANCE

8.1 INTRODUCTIONZEKS HEATSINK™ refrigerated air dryers require little maintenance. These dryersutilize hermetically sealed compressors which do not require any lubrication. Fanmotors require lubrication at both oil ports every six months. ZEKS recommendscomponent inspection and service at regular intervals to obtain maximum perfor-mance from your dryer.

8.2 REFRIGERANT CONDENSERFor standard dryers, regular inspection and cleaning of the condenser isrecommended. ZEKS dryers may be equipped with an optional ambient air filterdesigned to protect the condenser from dirt and debris that can accumulate on thecondenser. For proper operation with this option, it is imperative that this filter beinspected and cleaned on a regular basis. Annual replacement of the filter isrecommended. For applications where excessive dirt, dust or debris is encountered,more frequent inspection and cleaning may be required.

• Start Dryer, using one of the following methods, depending on Start Mode setting:Manual Mode - Press the ON pushbutton.Auto Restart Mode - No additional action requiredRemote Automatic Mode - Close the remote contact.

• For HeatSink™ dryers, the circulating pump will be energized and will run continu-ously. Provided the CHILLER TEMPERATURE is greater than the CompressorOff Set point plus 4° F and the anti-short cycle delay and crankcase heater delayhave timed out, the refrigeration system will energize. As the system operatesand thermal mass temperature drops, the suction pressure will be lowered tobetween 30 and 50 psig.

After the alarm delay, provided the Chiller Temperature is greater than the HIGHTEMPERATURE ALARM set point, the dryer will go into HIGH TEMPERATUREALARM. The LCD panel will indicate the alarm and the refrigeration system willcontinue to operate. Pressing the SELECT DISPLAY button will permit viewing ofthe available dryer parameters during this alarm condition. Note that the alarmcondition screen will reappear after approximately 30 seconds until the alarmcondition is cleared.

The CHILLER TEMPERATURE will gradually drop as indicated on the display.Once the temperature falls below the HIGH TEMPERATURE ALARM set point, thealarm will reset and the LCD panel will return to its default display. After the refrig-eration system shuts off, air flow may be slowly introduced to the dryer.

• Drain settings should be checked as described earlier in this manual.

If power is removed from the dryer for less than two hours, the crackcase heater delaywill be automatically bypassed. If, however, the power is removed from the dryer formore than two hours, the full crankcase heater delay must be observed.

NOTICE

Page 20: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

19

8.3 CONDENSATE DISCHARGE SYSTEMOn a minimum of a monthly basis, the operation of the automatic drain should bechecked. The drain should be removed and cleaned as well to ensure no debrisfrom the system is trapped inside the strainer. Figure 4 illustrates the drainassembly. To clean the drain, turn the Isolation Valve to the off position. Be surethe valve is depressurized. Carefully remove the Strainer End Cap and remove theStrainer. Clean the Strainer and remove any debris that is evident in the valve.Replace the Strainer and reinstall the Strainer End Cap. Carefully open theisolation valve and inspect the Strainer End Cap for leaks. Tighten as required.

If your dryer is installed without a drain isolation valves (filter stop), failure to depres-surize the dryer may result in serious injury. Do not remove the drain valve withoutdepressurizing the unit.

WARNING

NOTE: Orientation of drain and strainer maybe different than shown above.

FIGURE 4DRAIN DETAILDRAWING 749830

Page 21: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

20

9.0 TECHNICIAN MODEThe DPC provides a protected TECHNICIAN MODE to manipulate several parameters notaccessible by the typical operator. This mode also permits viewing of the factory settingsto aid in troubleshooting of the dryer. Below is a list of parameters that can be accessedand manipulated by the technician when in TECHNICIAN MODE:

TECHNICIAN MODE should only be entered by qualified service personnel. Altering theset points in TECHNICIAN MODE will have a significant effect on the operation of thedryer. Incorrect set points may damage dryer and cause potential serious injury.

Parameter Display Set PointSOLENOID DRAIN ENABLE DRAIN ENABLE ON (or OFF)CRANKCASE HEATER DELAY CCH DLY 8 (or 0,2,4,12 hours)AUTO RESTART ENABLE AUTO RESTART N (or Y)

Parameter Display Set PointCONFIGURATION (# of sensors) CONFIG #: 1, 2, 4, 8OPERATING MODE OP MODE: HS or NCREFRIGERANT REFRIG: 22 or 404 or 407CONDENSER TYPE COND: AC OR WCOPERATING TEMPERATURE DIFFERENTIAL T OP DIFF: 4SHORT CYCLE DELAY SHT CYC DLY: 03HIGH PRESSURE CUTOUT HPCO: See Table-1HIGH PRESSURE CUTOUT DELAY HPCO DLY: 10LOW PRESSURE CUTOUT LPCO: See Table-1LOW PRESSURE CUTOUT DELAY LPCO DLY: 10HIGH TEMPERATURE ALARM HITEMP ALRM: 55LOW TEMPERATURE ALARM LOWTEMP ALRM: 30LOW TEMPERATURE ALARM DELAY LOTEMP DLY: 2:00FAN 1 ON PRESSURE FAN1 ON: See Table-1FAN 1 OFF PRESSURE FAN1 OFF: See Table-1FAN 2 ON PRESSURE FAN2 ON: See Table-1FAN 2 OFF PRESSURE FAN2 OFF: See Table-1ALARM LIST BEGIN ALARM LIST N/A

In TECHNICIAN MODE, the following parameters can be viewed but not changed:

9.1 ENTERING TECHNICIAN MODE

WARNING

Page 22: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

21

To enter the TECHNICIAN MODE, perform the following keystrokes:

Pressing the “2” and “3” buttons simultaneously entersthe TECHNICIAN MODE.TECH SET MODE

SELECTDISPLAY

Depressing SELECT DISPLAY scrolls through theavailable parameters. The first three parameters viewedare adjustable in TECHNICIAN MODE.

DRAIN ENABLE: ON

2 3

Depressing ENTER saves the selected set point.

Depressing the SELECT DISPLAY button advances tothe next adjustable parameter for the Crankcase HeaterDelay. This parameter must not be altered unlessinstructed by ZEKS Service personnel.

DRAIN ENABLE: OFF

CCH DELAY: 8

SETFor parameters with “ON / “OFF” or “Y” / “N” choices, theset point is changed using the SET button. Pressing theSET button changes the Drain Enable from ON to OFF.

DRAIN ENABLE: OFF

ENTER

SELECTDISPLAY

Depressing ENTER saves the selected set point.AUTO RESTART: Y

SETDepressing the SET button changes the AUTO RESTARTparameter from “N” to “Y”.AUTO RESTART: Y

ENTER

Depressing the SELECT DISPLAY button advances tothe next adjustable parameter for the Auto Restartfeature.

AUTO RESTART: N SELECTDISPLAY

The DRAIN ENABLE parameter determines whether the DPC shall control an electronicsolenoid drain valve. A value of “ON” will permit the DPC to control the drain valve. Avalue of “OFF” will disable this feature. This would be suitable for servicing the drainvalve or if an independent no air loss drain is to be used with the dryer. To change theDRAIN ENABLE set point from the displayed set point, perform the following. Otherwise,depress the SELECT DISPLAY button to advance to the next adjustable parameter:

The AUTO RESTART feature permits the dryer to operate once power is applied to thedryer without requiring operator intervention. This would be desirable should the userwish to have the dryer restart automatically after a power outage. Note that the dryer willenergize once the ASC or CCH delay times out. To change the AUTO RESTART set pointfrom “N” (NO) to “Y” (YES), perform the following. Otherwise, depress the SELECTDISPLAY button to advance to the next display:

The Crankcase Heater Delay set point must not be altered unless directed by ZEKSService Personnel. Improperly altering the set point may result in damage to the dryer.Contact ZEKS Compressed Air Solutions before altering the default set point.

NOTICE

Page 23: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

Depressing the SELECT DISPLAY button displays theEND TECH SET PTS display. END TECH SET PTS SELECT

DISPLAY

At the end of the list of parameters, depressing theSELECT DISPLAY button displays the beginning of theALARM LIST.

BEGIN ALARM LIST SELECTDISPLAY

Depressing the SELECT DISPLAY button displays thealarms that the dryer has experienced, with the mostrecent alarm displayed first. The actual display willdepend on the most recent alarm detected by the DPC.

HPCO ALARMSELECTDISPLAY

The list of alarms can be scrolled by depressing theSELECT DISPLAY button as needed. At the end of thealarm list, the END ALARM LIST screen is displayed.

END ALARM LIST SELECTDISPLAY

Depressing the SELECT DISPLAY list displays theALARM LIST screen at the top of the ALARM LIST. BEGIN ALARM LIST SELECT

DISPLAY

The Alarm List will repeat as long as the SELECT DISPLAY button is depressed.To EXIT the ALARM LIST, perform the following:

Depressing the BLANK button (located above the SETbutton) returns the controller to the top of the TECHNI-CIAN MODE.

TECH SET MODE

Depressing the BLANK button again returns the controllerto the default display of the CUSTOMER MODE.CHLLR TEMP: 37

Changing the AUTO RESTART feature to “Y” will permit the dryer to operate automati-cally once power is applied and after a brief delay. Proper warning signs should beaffixed to the dryer to alert users and service personnel that dryer may start withoutwarning. Failure to do so may result in serious injury.

The remaining non-adjustable parameters may be viewed by depressing the SELECTDISPLAY button as required to arrive at the desired display. .

To exit the TECHNICIAN MODE at any time, depress the “BLANK” button locatedabove the SET button to return to the CUSTOMER MODE.

9.2 ALARM LISTAt the end of the list of non-adjustable parameters, the DPC™ displays a list of themost recent 20 alarm conditions. This list can facilitate troubleshooting the dryer

NOTICE

22

WARNING

Page 24: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

10.2 PROBLEM / ACTION GUIDE

PROBLEM

Moisture down stream

SYMPTOM(S)

Dryer is properlycooling air stream(Check Chiller Temp oncontroller)

Inlet and outlet temper-atures are the same.

POSSIBLECAUSE

Drain failure or timeradjustment is required

Excessive flow

Dryer by-pass valvenot closedNo power to the dryer

High suction pressureRefrigerant leak

Compressor notrunning and fan isrunning

CORRECTIVE ACTION

Depress “TEST” button - if drainvalve operates then adjust timing(See Section 6.3)Depress “TEST” button - if DRAINTEST is displayed but valve doesnot open, ensure wiring connec-tions are secure and power is beingapplied to the solenoid coil. If valvecontinues not to open, clean asdescribed in Maintenance Sectionof this manual.Depress “TEST” button - if displaydoes not indicate DRAIN TEST,contact distributor.Check inlet and outlet pressuresand system design capacity.Correct cause of excessive flow.Close by-pass valveCheck power supply andfuses/circuit breakersCheck and clean ambient air filter.Check suction pressure gauge ifreading is 0 psig, turn dryer off andcontact your distributorCheck and clean ambient air filter.Check ambient temperature andreduce below 113°F

An air dryer always operates under pressure. Any maintenance procedure that involvesdisassembly of pipe fittings, valves or any other components requires the dryer beisolated from the compressed air stream and fully depressurized.

Prior to working on the unit, make sure that all circuit breakers or disconnected switchesare tagged “Out of Service.”

10. TROUBLESHOOTING

10.1 INTRODUCTIONZEKS HEATSINK™ dryers are designed for reliable, trouble-free operation. In theevent of any dryer malfunction, the guide below has been developed to facilitateproblem identification and corrective actions.

23

WARNING

WARNING

Page 25: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

24

PROBLEM

Moisture downstream

Apparent controllerdisplay malfunction

High pressure dropacross dryer

SYMPTOM(S)

Inlet and outlettemperatures are thesame.

Compressor and fanare running,exchanger temp high,pump not runningDisplay Blank

Unrealistic tempera-ture displayed

Erratic or inaccuratetemperature readings

Unrealistic pressuredisplayed

Outlet pressuresubstantially lowerthan inlet pressureSystem operatingtemperature is above32°FOutlet pressuresubstantially lowerthan inlet pressureSystem operatingtemperature is below32°F

POSSIBLE CAUSE

Compressor and fan notrunning.

Compressor and fan notrunning. Controller indicatescompressor is ON.

Defective Pump

Blown FuseBoard Failure

Probe loose,off connection ordefective probe

Probe not completely inthermal well

Defective probeTransducer loose, off connec-tion or defective transducer

Inlet and outlet valves notcompletely openInlet and outlet filters blockedup

Compressor relay / contactorstuck.DPC relay badProbe not completely inthermal well

Problem persists

CORRECTIVE ACTION

Check Chiller TemperatureCheck MAIN CONTROL fuse.

Compressor relay may be bad, replacerelayCheck for loose wire connections atcontactor or loss of power at controlboardDefective control board - replace asnecessaryContact your local distributor for furtherassistance.

Contact your local distributor for furtherassistance.

Check FusesContact your local distributor for furtherassistance.Inspect probe cable and terminalconnectionReplace probeInspect probe and check readingsagainst independent source (eg.temperature analyzer/pyrometer/icebath) both in temperature well and toambientReplace probeInspect transducer cable and terminalconnectionReplace transducerOpen valves

Change filter elements

Replace relay / contactor.

Replace relayInspect probe and check readingsagainst independent source (eg.temperature analyzer/pyrometer/icebath) both in exchanger well and toambientTurn dryer off and consult your localdistributor for further assistance

Page 26: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

25

11. WIRING DIAGRAMS

WIR

ING

DIA

GR

AM

1000

-160

0HS

FA&

W w

ith D

PC

™46

0V/3

/60H

Z10

00-1

200H

SFA

&W

with

DP

C™

230V

/3/6

0HZ

TM50

0162

V

Page 27: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

26

WIR

ING

DIA

GR

AM

1000

HS

FA&

W,1

200H

SFW

with

DP

C™

575V

/3/6

0HZ

TM

5005

10G

Page 28: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

27

WIR

ING

DIA

GR

AM

1200

HS

FA,1

600H

SFA

&W

with

DP

C™

575V

/3/6

0HZ

TM

5005

49G

Page 29: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

28

WIR

ING

DIA

GR

AM

1000

-160

0HS

FA&

W w

ith D

PC™

-PLU

S20

8, 2

30, 4

60V

/3/6

0HZ

200,

220

, 380

, 400

, 415

, 440

V/3

/50H

ZTM

5001

63Q

Page 30: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

29

WIR

ING

DIA

GR

AM

1000

HS

FA&

W, 1

200H

SFA

&W

with

DP

C™

-PLU

S57

5V/3

/60H

ZTM

5006

07B

Page 31: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

30

WIR

ING

DIA

GR

AM

1200

HS

FA, 1

600H

SFA

&W

with

DP

C™

-PLU

S57

5V/3

/60H

Zw

ith T

rans

form

ed 4

60V

Fan

sTM

5005

20F

Page 32: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

12. GENERAL ARRANGEMENT

GEN

ERA

LA

RR

AN

GEM

ENT

1000

-160

0HSF

TM50

0387

G

31

Page 33: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

13. SPARE PARTS

32

1000

HS

FA40

012

00H

SFA

400

1600

HS

FA40

010

00H

SFW

400

1200

HS

FW40

016

00H

SFW

400

Air-

Coo

led

Air-

Coo

led

Air-

Coo

led

Wat

er-C

oole

dW

ater

-Coo

led

Wat

er-C

oole

d46

0/3/

6046

0/3/

6046

0/3/

6046

0/3/

6046

0/3/

6046

0/3/

601

Com

pres

sor

6843

0068

2248

6823

4668

2578

6822

4568

2248

2C

onde

nser

6984

7868

4309

6843

2368

2403

6982

0269

8202

3Fa

n M

otor

6981

5269

8152

6843

25-

--

4Fa

n B

lade

6981

5669

8156

6843

24-

--

5P

ump

- Gly

col

6837

2468

3724

6837

2468

3724

6837

2468

3724

6Fi

lter D

ryer

6003

8660

0388

6003

8860

0388

6003

8760

0388

7E

xpan

sion

Val

ve68

4304

6843

0468

4304

6816

0068

1600

6004

018

Wat

er R

egul

atin

g Va

lve

--

-60

0563

6982

0469

8204

9C

onta

ctor

- S

ingl

e P

ole,

25A

6996

2169

9621

6996

21-

--

10C

onta

ctor

- Th

ree

Pol

e, 2

5A69

7290

6972

9069

7290

6972

9069

7290

6972

9011

Con

trol T

rans

form

er69

9640

6996

4069

9640

6996

4069

9640

6996

4012

Fuse

, 2A

, 1/4

”68

2646

6826

4668

2646

6826

4668

2646

6826

4613

Fuse

, 3A

, 13/

32”

6987

7069

8770

6987

7069

8770

6987

7069

8770

14Fu

se, .

75A

, 13/

32”

6826

5168

2651

6826

5168

2651

6826

5168

2651

15P

ower

Sup

ply

Fuse

6839

7668

3976

6839

7668

3976

6839

7668

3976

16D

igita

l Con

trolle

r DP

C80

0087

8000

8780

0087

8000

8780

0087

8000

8717

Pow

er S

uppl

y68

3956

SP

6839

56S

P68

3956

SP

6839

56S

P68

3956

SP

6839

56S

P18

Tem

pera

ture

Pro

be68

2955

6829

5568

2955

6829

5568

2955

6829

5519

Pre

ssur

e Tr

ansd

ucer

, Dis

char

ge, 0

-500

PS

I68

2943

6829

4368

2943

6829

4368

2943

6829

4320

Pre

ssur

e Tr

ansd

ucer

, Inl

et/O

utle

t Air

& S

uctio

n, 0

-300

PS

I68

2942

6829

4268

2942

6829

4268

2942

6829

4221

Tran

sduc

er C

able

, ref

rig. D

isch

arge

& S

uctio

n - 5

ft.

6829

4568

2945

6829

4568

2945

6829

4568

2945

22Tr

ansd

ucer

Cab

le, I

nlet

& O

utle

t Air

- 10

ft. (D

PC

-8 o

nly)

6829

4668

2946

6829

4668

2946

6829

4668

2946

23D

igita

l Con

trolle

r Bat

tery

6839

7568

3975

6839

7568

3975

6839

7568

3975

24

Con

dens

ate

Dra

in68

2657

SP

6826

57S

P68

2657

SP

6826

57S

P68

2657

SP

6826

57S

P25

C

rank

case

Hea

ter

6846

0568

4595

6845

9568

2245

6822

4568

4595

Page 34: TECHNICAL MANUAL HeatSink - ZEKS Compressed Air … · TECHNICAL MANUAL HeatSink True-Cycling Refrigerated Compressed Air Dryers HSF Models 1000-1600 SCFM ZEKS Compressed Air Solutions

Spec

ifica

tion

info

rmat

ion

abov

e ac

cura

te a

t tim

e of

pub

licat

ion.

Ref

er to

equ

ip-

men

t ser

ial l

abel

for a

ctua

l ref

riger

ant c

harg

es a

nd s

peci

ficat

ions

for u

nits

.

14.

EN

GIN

EE

RIN

G S

PE

CIF

ICAT

ION

S

33

Max

imum

Allo

wab

le W

orki

ng P

ress

ure:

220

psi

g

For d

ryer

s m

anuf

actu

red

with

a re

frige

rant

oth

er th

an R

404A

, ref

er to

the

seria

lla

bel o

n th

e dr

yer f

or re

frige

rat t

ype

and

char

ge.

NO

TIC

E

NO

TIC

E

RE

FRIG

ER

AN

TR

404A

MA

XM

IN C

IRC

UIT

CO

MP

RE

SS

OR

RAT

ING

SFA

N R

ATIN

GS

MO

DE

LN

O.

VO

LTS

/PH

/HZ

WE

IGH

TLB

SO

ZFU

SE

AM

PAC

ITY

HP

RLA

LRA

QTY

HP

RLA

LRA

1000

HS

FA40

046

0/3/

6020

0011

030

18.4

712

.880

.02

1/4

0.95

2.4

1200

HS

FA40

046

0/3/

6023

0015

035

23.0

915

.778

.53

1/4

0.95

2.4

1600

HS

FA40

046

0/3/

6022

0013

040

29.4

10.5

19.3

105.

03

1/2

1.6

4.0

RE

FRIG

ER

AN

TR

404A

MA

XM

IN C

IRC

UIT

CO

MP

RE

SS

OR

RAT

ING

SM

OD

EL

NO

.V

OLT

S/P

H/H

ZW

EIG

HT

LBS

OZ

FUS

EA

MPA

CIT

YH

PR

LALR

A

1000

HS

FW40

046

0/3/

6020

006

815

11.3

58.

660

.0

1200

HS

FW40

046

0/3/

6023

008

025

14.4

611

.168

.0

1600

HS

FW40

046

0/3/

6023

0011

035

20.2

915

.778

.5