TECHNICAL DATA SHEET FIXED BACK TO SFS

10
TECHNICAL DATA SHEET 25/15 FrameFix™ For Mineral Wool Insulation Technical Data ACS FrameFix Ultra™ is designed to allow an outer leaf of a cavity wall constructed from masonry to be tied to a light steel frame or another structural element through mineral wool using a suitable fixing. Composite, high compressive capacity sleeves are used at every fixing position to provide a rigid, high capacity fixing detail. The sleeves have a Class 2 fire resistance to BS476 Part 6. The channel is fixed back to the structure via the pre-punched holes in the channel which are spaced at close centres to allow the fixing point to be selected depending on the application. Once fixed, ACS 4000 range ties can be positioned at any point along the channel to suit the coursing of the masonry panel. System Performance Table 1.0 below provides the wall tie type performance values from PD6697 based on the standard stud centres of 600mm. Panel Required Type (PD 6697) Wall Tie Vertical CTRS (mm) Fixing Vertical CTRS (mm) Panel Design Resistance (kN/m 2 ) Type 1 300 337.5 2.27 Type 2 450 337.5 1.51 Type 3 450 450 0.88 For alternative performance requirements or spacing’s please contact the ACS Technical Department for further information. Installation The channel is typically fixed back to the SFS/Studwork through mineral wool insulation and CP board. Each fixing requires a compression sleeve to be pushed through the insulation to bear onto the CP board and stud work behind. Fixings can then be installed through the channel (small hole only) and sleeves, then driven into the SFS studs. Studs are normally set at 600mm horizontal centres. Ties can then be positioned at any point along the channel length to suit the bed joint coursing at the required vertical centres (refer to Table 1.0). Installing through large holes in the channel is not permitted and as such will invalidate any system performance. Table 1.0 - Channel Tie / Fixing Centres FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected] LEEDS . LONDON . GLASGOW . TAUNTON Austentic Stainless Steel (Grade 1.4301) CE Marked (EN 845-1) Lucideon Tested Masonry - Channel Tie 2.7m Standard Lengths Standoff Sleeves FIXED BACK TO SFS Low Thermal Conductivity High Compressive Strength • Stabilises Channel Class 2 Fire Resistance to BS 476 Prevents Compression of Insulation • Aids Installation Compression Sleeves The Framefix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system are both achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation, and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.300 W/mK. Table 1.1 - Tech Screw Lengths NHBC Technical Specification Meets the Requirment of the BS EN 845 - 1 Insulation Thickness (mm) Screw Length (mm) 40-70 105 71-95 130 96-115 150 116-145 180 146-175 210

Transcript of TECHNICAL DATA SHEET FIXED BACK TO SFS

Page 1: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Mineral Wool Insulation

Technical DataACS FrameFix Ultra™ is designed to allow an outer leaf of a cavity wall constructed from masonry to be tied to a light steel frame or another structural element through mineral wool using a suitable fixing. Composite, high compressive capacity sleeves are used at every fixing position to provide a rigid, high capacity fixing detail. The sleeves have a Class 2 fire resistance to BS476 Part 6. The channel is fixed back to the structure via the pre-punched holes in the channel which are spaced at close centres to allow the fixing point to be selected depending on the application. Once fixed, ACS 4000 range ties can be positioned at any point along the channel to suit the coursing of the masonry panel.

System PerformanceTable 1.0 below provides the wall tie type performance values from PD6697 based on the standard stud centres of 600mm.

Panel RequiredType

(PD 6697)

Wall Tie Vertical

CTRS(mm)

Fixing Vertical

CTRS(mm)

Panel Design

Resistance(kN/m2)

Type 1 300 337.5 2.27

Type 2 450 337.5 1.51

Type 3 450 450 0.88

For alternative performance requirements or spacing’s please contact the ACS Technical Department for further information.

InstallationThe channel is typically fixed back to the SFS/Studwork through mineral wool insulation and CP board. Each fixing requires a compression sleeve to be pushed through the insulation to bear onto the CP board and stud work behind. Fixings can then be installed through the channel (small hole only) and sleeves, then driven into the SFS studs. Studs are normally set at 600mm horizontal centres. Ties can then be positioned at any point along the channel length to suit the bed joint coursing at the required vertical centres (refer to Table 1.0). Installing through large holes in the channel is not permitted and as such will invalidate any system performance.

Table 1.0 - Channel Tie / Fixing Centres

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

Austentic Stainless Steel (Grade 1.4301)

CE Marked (EN 845-1)

Lucideon Tested

Masonry - Channel Tie

2.7m Standard Lengths

Standoff Sleeves

FIXED BACK TO SFS

• Low Thermal Conductivity

• High Compressive Strength

• Stabilises Channel

• Class 2 Fire Resistance to BS 476

• Prevents Compression of Insulation

• Aids Installation

Compression SleevesThe Framefix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system are both achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation, and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.300 W/mK.

Table 1.1 - Tech Screw Lengths

NHBC Technical SpecificationMeets the Requirment of the

BS EN 845 - 1

Insulation Thickness(mm)

Screw Length(mm)

40-70 105

71-95 130

96-115 150

116-145 180

146-175 210

Page 2: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Mineral Wool Insulation

System WarrantyThe ACS SFS Framefix system comes with a full warranty and CE marking. If used in an inland environment and not within an environment where chlorine may be present the system can be offered with a 60-year warranty.

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO SFS

Brick

4000 Range Tie

25/15 FrameFixChannel

SFS

ACS Hi Thread

Tech Screw

CompressionSleeve

Insulation

CP Board

Socket and Fixing

ACS Self Drilling & Tapping Hi-Thread Screw

5/16ths Drive Unit

Scan the QR code (left) to see how best to install Framefix to

SFS with self-drilling screws.

Page 3: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Mineral Wool Insulation

Austentic Stainless Steel (Grade 1.4301)

CE Marked (EN 845-1)

Lucideon Tested

Masonry - Channel Tie

2.7m Standard Lengths

Standoff Sleeves

Technical DataACS Concrete Frame Fix is designed to allow an outer leaf of a cavity wall constructed from masonry to be tied to a concrete frame through insulation using a suitable fixing. Composite, high compressive capacity sleeves are used at every fixing position to provide a rigid, high capacity fixing detail. The sleeves have Class 2 fire resistance to BS476 Part 6. The channel is fixed back to the structure via the pre-punched holes in the channel which are spaced at close centres to allow the fixing point to be selected depending on the application. Once fixed, ACS 4000 range ties can be positioned at any point along the channel to suit the coursing of the masonry panel.

System PerformanceTable 1.0 below provides the wall tie type performance values from PD6697 based on the standard stud centres of 600mm.

Compression SleevesThe Concrete Framefix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system are both achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation, and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.300 W/mK.

For alternative performance requirements or spacing’s please contact the ACS Technical Department for further information.

InstallationEach fixing point will need marking out and a 5mm pilot hole should be drilled with a 5mm SDS+ drill. Compression sleeves can then be installed through the insulation and sat against the concrete behind. The fixing can then be installed through the channel (small hole only) and compression sleeve, then into the concrete behind with an embedment of between 30mm and 50mm. Channels are normally set at 600mm horizontal centres. Ties can then be positioned at any point along the channel length to suit the bed joint coursing at the required vertical centres. (Refer to Table 1.0). Installing through large holes in the channel is not permitted and as such will invalidate any system performance.

Table 1.0 - Channel Tie / Fixing Centres

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO CONCRETE

• Low Thermal Conductivity

• High Compressive Strength

• Stabilises Channel

• Class 2 Fire Resistant (BS 476)

• Prevents Compression of Insulation

• Aids Installation

Panel RequiredType

(PD 6697)

Wall Tie Vertical

CTRS(mm)

Fixing Ver-ticalCTRS(mm)

Panel Design

Resistance(kN/m2)

Type 1 300 337.5 2.27

Type 2 450 337.5 1.51

Type 3 450 450 0.88

Table 1.1 - Abite Screw Lengths

Screw Length (mm) Insulation Range (mm)

100 50-69

120 70-89

140 90-109

160 110-129

180 130-149

200 150-169

220 170-189

240 190-209

260 210-229

NHBC Technical SpecificationMeets the Requirment of the

BS EN 845 - 1

Page 4: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Mineral Wool Insulation

System WarrantyThe ACS Concrete Framefix system comes with a full warranty and CE marking. If used in an inland environment and not within an environment where chlorine may be present the system can be offered with a 25 year warranty. Care must be taken to ensure that the fixing and channel hole wall do not come into contact once the fixing is tightened. If this cannot be guaranteed, the two components should be isolated.

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO CONCRETE

Brick

4000 Range Tie

25/15 FrameFixChannel

Minimum C20/25 Concrete

ACS Abite Screw

CompressionSleeve

Insulation

Page 5: TECHNICAL DATA SHEET FIXED BACK TO SFS

Tie Reference Tie Length (mm) Clear Cavity Range (mm)

ACS4000/100 100 40-65

ACS4000/125 125 66-90

ACS4000/150 150 91-115

ACS4000/175 175 116-140

ACS4000/200 200 141-165

ACS4000/225 225 166-190

ACS4000/250 250 191-215

ACS4000/275 275 216-240

ACS4000/300 300 241-265

ACS4000/325 325 266-290

ACS4000/350 350 291-315

ACS4000/375 375 316-340

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

TECHNICAL DATA SHEET4000 Range Tie Lengths

Tie LengthsAn ACS 4000 Range Channel Tie length should be selected to ensure a minimum of 50mm and a maximum of 75mm embedment is achieved. ACS recommends that ties should be selected to an embedment (Eb) of 62.5mm

NEW Sizesfor 2019

Table 1.2- Tie Lengths

L Tie Length Eb + CC - 15

Eb Embedment 62.5mm (min 50mm)

CC Clear Cavity C - MW

C Structural Cavity Varies

IB Insulation Board Varies

Standoff SleevesThe mineral wool FrameFix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system is achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.3W/mK

Page 6: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Rigid Insulation

Austentic Stainless Steel (Grade 1.4301)

CE Marked (EN 845-1)

Lucideon Tested

Masonry - Channel Tie

2.7m Standard Lengths

Technical DataACS FrameFix Ultra™ is designed to allow an outer leaf of a cavity wall constructed from masonry to be tied to a light steel frame or another structural element. This is most commonly, but not exclusively through rigid insulation board using a suitable fixing. The channel is fixed back to the structure via the pre-punched holes in the channel which are spaced at close centres to allow the fixing point to be selected depending on the application. Once fixed, ACS 4000 range ties can be positioned at any point along the channel to suit the coursing of the masonry panel. Maximum spacing values must be adhered to as per Table 1.0 below.

System PerformanceTable 1.0 below provides the wall tie type performance values from PD6697 based on the standard stud centres of 600mm.

Fixing ScrewsThe ACS FrameFix™ channel standard configuration is designed to fix back to the stud work at 450mm vertical centres. The pre-punched holes in the rear of the channel are spaced at 112.5mm centres so a fixing can always be positioned near to the end of the channel and the fixing centres can be varied to increase or reduce the load capacity as required. Self-tapping screws can be supplied to accommodate fixing through the insulation. ACS recommends the use of stainless steel screw for fixing the channel back to the stud work.

Panel RequiredType

(PD 6697)

Wall Tie Vertical

CTRS(mm)

Fixing Vertical

CTRS(mm)

PanelDesign

Resistance(kN/m2)

Type 1 300 450 2.72

Type 2 450 450 1.81

Type 3 450 450 1.81

For alternative performance requirements or spacing’s please contact the ACS Technical Department for further information.

InstallationThe ACS FrameFix™ channel standard configuration is designed to fix back to the stud work at 450mm vertical centres. The pre-punched holes in the rear of the channel are spaced at 112.5mm centres so a fixing can always be positioned near to the end of the channel and the fixing centres can be varied to increase or reduce the load capacity as required (using the small hole only). Self-tapping screws can be supplied to accommodate fixing through the insulation. Installing through large holes in the channel is not permitted and as such will invalidate any system performance. ACS recommends the use of stainless steel screw for fixing the channel back to the stud work.

Table 1.1 - Tech Screw Lengths

Insulation Thickness(mm)

Screw Length(mm)

40-70 105

71-95 130

96-115 150

116-145 180

146-175 210

NHBC Technical SpecificationMeets the Requirment of the

BS EN 845 - 1

Table 1.0 - Channel Tie / Fixing Centres

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO SFS

Page 7: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Rigid Insulation

System WarrantyThe ACS SFS FrameFix system comes with a full warranty and CE marking. If used in an inland environment and not within an environment where chlorine may be present the system can be offered with a 60-year warranty.

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO SFS

Brick

4000 Range Tie

25/15 FrameFixChannel

SFS

Rigid Insulation

CP Board

ACS Hi Thread

Tech Screw

Socket and Fixing

ACS Self Drilling & Tapping Hi-Thread Screw

5/16ths Drive Unit

Scan the QR code (left) to see how best to install Framefix to

SFS with self-drilling screws.

Page 8: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Rigid Insulation

Austentic Stainless Steel (Grade 1.4301)

CE Marked (EN 845-1)

Lucideon Tested

Masonry - Channel Tie

2.7m Standard Lengths

Standoff Sleeves

Technical DataACS Concrete Frame Fix is designed to allow an outer leaf of a cavity wall constructed from masonry to be tied to a concrete frame through insulation using a suitable fixing. Composite, high compressive capacity sleeves are used at every fixing position to provide a rigid, high capacity fixing detail. The sleeves have a Class 2 fire resistance to BS476 Part 6. The channel is fixed back to the structure via the pre-punched holes in the channel which are spaced at close centres to allow the fixing point to be selected depending on the application. Once fixed, ACS 4000 range ties can be positioned at any point along the channel to suit the coursing of the masonry panel.

System PerformanceTable 1.0 below provides the wall tie type performance values from PD6697 based on the standard stud centres of 600mm.

Compression SleevesThe Concrete Framefix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system are both achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation, and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.300 W/mK.

Panel RequiredType

(PD 6697)

Wall Tie Vertical

CTRS(mm)

Fixing Vertical

CTRS(mm)

PanelDesign

Resistance(kN/m2)

Type 1 300 337.5 2.27

Type 2 450 337.5 1.51

Type 3 450 450 0.91

For alternative performance requirements or spacings please contact the ACS Technical Department for further information.

InstallationEach fixing point will need marking out and a 5mm pilot hole should be drilled with a 5mm SDS+ drill. Compression sleeves can then be installed through the insulation and sat against the concrete behind. The fixing can then be installed through the channel (small hole), compression sleeve and then into the concrete behind with an embedment of between 30mm and 50mm. Channels are normally set at 600mm horizontal centres. Ties can then be positioned at any point along the channel length to suit the bed joint coursing at the required vertical centres. (Refer to Table 1.0) Installing through large holes in the channel is not permitted and as such will invalidate any system performance.

Table 1.1 - Abite Screw Lengths

Screw Length (mm) Insulation Range (mm)

100 50-69

120 70-89

140 90-109

160 110-129

180 130-149

200 150-169

220 170-189

240 190-209

260 210-229

Table 1.0 - Channel Tie / Fixing Centres

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO CONCRETE

• Low Thermal Conductivity

• High Compressive Strength

• Stabilises Channel

• Class 2 Fire Resistant (BS 476)

• Prevents Compression of Insulation

• Aids Installation

NHBC Technical SpecificationMeets the Requirment of the

BS EN 845 - 1

Page 9: TECHNICAL DATA SHEET FIXED BACK TO SFS

TECHNICAL DATA SHEET25/15 FrameFix™ For Rigid Insulation

System WarrantyThe ACS Concrete Framefix system comes with a full warranty and CE marking. If used in an inland environment and not within an environment where chlorine may be present the system can be offered with a 25-year warranty. Care must be taken to ensure that the fixing and channel hole wall do not come into contact once the fixing is tightened. If this cannot be guaranteed, the two components should be isolated.

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

FIXED BACK TO CONCRETE

Brick

4000 Range Tie

25/15 FrameFixChannel

Minimum C20/25 Concrete

ACS Abite

Screw

CompressionSleeve

Insulation

Page 10: TECHNICAL DATA SHEET FIXED BACK TO SFS

FOR FURTHER INFORMATION OR TECHNICAL ASSISTANCE PLEASE CONTACT US 0844 850 0860 OR EMAIL [email protected]

LEEDS . LONDON . GLASGOW . TAUNTON

TECHNICAL DATA SHEET4000 Range Tie Lengths

Tie LengthsAn ACS 4000 Range Channel Tie length should be selected to ensure a minimum of 50mm and a maximum of 75mm embedment is achieved. ACS recommends that ties should be selected to an embedment (Eb) of 62.5mm

Tie Reference Tie Length (mm) Clear Cavity Range (mm)

ACS4000/100 100 40-65

ACS4000/125 125 66-90

ACS4000/150 150 91-115

ACS4000/175 175 116-140

ACS4000/200 200 141-165

ACS4000/225 225 166-190

ACS4000/250 250 191-215

ACS4000/275 275 216-240

ACS4000/300 300 241-265

ACS4000/325 325 266-290

ACS4000/350 350 291-315

ACS4000/375 375 316-340

NEW Sizesfor 2019

Table 1.2- Tie Lengths

L Tie Length Eb + CC - 15

Eb Embedment 62.5mm (min 50mm)

CC Clear Cavity C - MW

C Structural Cavity Varies

IB Insulation Board Varies

Standoff SleevesThe mineral wool FrameFix system is supplied with standoff tubes which correspond to the thickness of the insulation specified. The tubes are designed to ensure that the compressive strength and stability of the channel tie system is achieved and maintained by preventing the channel deflecting into and compressing the insulation during installation and whilst under normal load. The tubes are manufactured from a fire-resistant composite material with thermal conductivity of 0.3W/mK