    ManualTC-9

    Ventilation controllerVersion V2.11March 25, 2008

    Aerotech Europe BVPostbus 512

    3233 ZK, Oostvoorne

    The Netherlands

    Tel. +31 (0)181 - 48 97 00 Fax. +31 (0)181 - 48 55 69

    www.abbisun.com

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    2/56

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    3/56

    TC-9 Version V2.11 March 25, 2008Manual Page 1

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Dear customer,

    This manual contains all the necessary information to master the operational characteristics of the TC-9. Carefullyread this manual before you start working with the TC-9. It makes it a lot easier to familiarize oneself with thecontroller. Keep this manual at hand, so that you can use it as a reference book at all times.

    As our products are subject to continuous development and updating, Abbi-sun is entitled to revise or modify its

    products without prior notice.

    IMPORTANT!

    In case any inductive loads are connected to the TC-9, such as field break switches and the like, aproper anti-interference device (RC-network, 100 Ohms + 100nF) should be applied.

    All weak current wiring should be shielded. Shield connected as shown in the wiring diagram.

    It is really important to provide the installation of a reliable alarm mechanism. Abbi-sun advisesnext to the application of the computer alarm signaling, a minimum/maximum thermostat that isnot dependent on the computer.

    Abbi-sun recommends checking its proper functioning regularly (at least 1x a day).

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    4/56

    TC-9 Version V2.11 March 25, 2008Manual Page 2

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Table of contents

    Table of contents ..............................................................................................................................................................2Features of the TC-9 ventilation controller .......................................................................................................................4Operation of the controller ................................................................................................................................................4

    Indicators ......................................................................................................................................................................4Zone 1 en 2 temperature ..................................................................................................................................................5Separate zone 1 regulation...............................................................................................................................................5

    Activating the separate zone 1 regulation....................................................................................................................5Blocking of user functions.................................................................................................................................................6

    Activating the blocking function ....................................................................................................................................6Special texts......................................................................................................................................................................6General .............................................................................................................................................................................6

    Menu GENERAL ..........................................................................................................................................................6Cooling..............................................................................................................................................................................9

    Cooling stages connection/ disconnection pattern.......................................................................................................9Changing connection/ disconnection pattern of cooling stages...................................................................................9Cascade regulation.......................................................................................................................................................9Stage 1 timer ................................................................................................................................................................9Activating cascade regulation without natural ventilation...........................................................................................10Natural ventilation.......................................................................................................................................................10Activating cascade regulation with natural ventilation................................................................................................11Step regulation ...........................................................................................................................................................11Activating step regulation ...........................................................................................................................................11Menu COOLING (CASCADE) ....................................................................................................................................12Menu COOLING (STEP) ............................................................................................................................................13

    Heating............................................................................................................................................................................13 Activating cascade or zone regulation........................................................................................................................14Activating separate zone 1 regulation ........................................................................................................................14Menu HEATING (CASCADE/ ZONED) ......................................................................................................................15Menu HEATING (SEPARATE ZONE 1).....................................................................................................................16

    Flap .................................................................................................................................................................................16Flap by means of bandwidth.......................................................................................................................................16Activating the flap by means of temperature (bandwidth)..........................................................................................17Flap by means of highest active cooling stage ..........................................................................................................17Activating the flap by means of highest active cooling stage .....................................................................................17Flap by means of pressure.........................................................................................................................................17Activating the flap by means of pressure ...................................................................................................................18Menu FLAP 1 (bandwidth)..........................................................................................................................................18Menu FLAP 1 (Highest cooling stage)........................................................................................................................19Menu FLAP 1 (pressure) ............................................................................................................................................19

    Analog output..................................................................................................................................................................20Analog 1 and 2 used by natural ventilation ................................................................................................................20Analog 4 used for misting output................................................................................................................................20Analog outputs as cooling/ heating regulation (bandwidth)........................................................................................20Activating the analog outputs as cooling/ heating regulation (bandwidth) .................................................................20Analog outputs by means of highest active cooling stage .........................................................................................21Activating the analog outputs by means of highest active cooling stage ...................................................................21Analog outputs as step regulation ..............................................................................................................................22Activating the analog outputs as step regulation........................................................................................................22Menu ANALOG 1 (heating/ cooling)...........................................................................................................................23Menu ANALOG 2 to 4 (heating/ cooling)....................................................................................................................23Menu ANALOG 1 (Highest cooling stage or step) .....................................................................................................24Menu ANALOG 2 to 4 (Highest cooling stage or step) ..............................................................................................24

    Fault messages...............................................................................................................................................................24Menu ROOM FAULT..................................................................................................................................................26

    Curves.............................................................................................................................................................................27 Menu CURVE (ROOM) ..............................................................................................................................................27

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    5/56

    TC-9 Version V2.11 March 25, 2008Manual Page 3

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Menu CURVE (SEPARATE ZONE 1) ........................................................................................................................31Humidity compensation...................................................................................................................................................31

    Activating the humidity compensation........................................................................................................................32Menu HUMIDITY ........................................................................................................................................................32

    Misting.............................................................................................................................................................................33 Activating the misting..................................................................................................................................................33Misting stage or analog output 4 by humidity, temperature and bandwidth...............................................................34Misting stage or analog output 4 by humidity and bandwidth ....................................................................................35

    Menu MISTING (mode 1 to 3) ....................................................................................................................................35

    Installers general.............................................................................................................................................................37Menu: ADJUST GENERAL ........................................................................................................................................37Menu: ADJUST STAGES...........................................................................................................................................37Menu: ADJUST HEATING..........................................................................................................................................39Menu: ADJUST MISTING...........................................................................................................................................39Menu: ADJUST FLAP (flap control without pressure)................................................................................................40Menu: ADJUST FLAP (flap control with pressure).....................................................................................................40Menu: ADJUST ANALOG 1........................................................................................................................................41Menu: ADJUST ANALOG 2 to 4 ................................................................................................................................41Menu: ADJUST ROOM FAULT..................................................................................................................................41

    Installers special .............................................................................................................................................................42Menu: SPECIAL GENERAL .......................................................................................................................................42Menu: SPECIAL FLAP (flap control without pressure sensor)...................................................................................43

    Menu: SPECIAL FLAP (flap control with pressure sensor)........................................................................................44Menu: SPECIAL ANALOG .........................................................................................................................................44Menu: SPECIAL SENSORS.......................................................................................................................................45Menu: TEST INDICATORS ........................................................................................................................................46Menu: TEST RELAYS ................................................................................................................................................46

    Installation instructions....................................................................................................................................................47Wiring diagram TC-9.......................................................................................................................................................48Wiring data TC-9.............................................................................................................................................................49Wiring diagram EX8T4O (flap control without pressure sensor) ....................................................................................50Wiring data EX8T4O (flap control without pressure sensor) ..........................................................................................50Wiring diagram EX8T4O (flap control with pressure sensor) .........................................................................................52Wiring data EX8T4O (flap control with pressure sensor) ...............................................................................................52Wiring diagram EX1RL (mist control on analog output 4) ..............................................................................................53Wiring data EX1RL (mist control on analog output 4) ....................................................................................................53Specifications..................................................................................................................................................................54

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    6/56

    TC-9 Version V2.11 March 25, 2008Manual Page 4

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Features of the TC-9 ventilation controller

    The TC-9 is specially developed for climate control in sectional production houses. The sections are temperature-controlled by means of flap, cooling and heating stages and a number of analog outputs (to control in- and outlets).

    After a reset, all the functions are put on hold for 8 seconds. This gives the controller time to read all the temperaturesensors.

    The controller has the following features:- Measurement of room temperature (by a maximum of 7 temperature sensors).- Measurement of outside temperature.- Timer function for cooling stage 1.- Up to 9 heating or cooling stages (each max. 5Amp. ON/ OFF).- Misting function on last cooling stage or analog output 4.- Heating to be set for cascade or zone (max. 2 stages) heating.- One flap controls (max. 4Amp.).

    Control by means of: 1 feedback by means of a potentiometer between 500 ohm and 10Kohm or bypressure sensor (0-10V signal).

    - Separate zone 1 regulation.

    - Curve controls.- Fault output.- Minimum compensation at excessive humidity.- Reduction of controls at falling outside temperature.- Fault message in case of faulty sensors.- Fault message at relative minimum en maximum room temperature.- Fault message at relative minimum en maximum separate zone 1 temperature.- Fault message at absolute room and separate zone 1 temperature.- Display option Fahrenheit or Celsius.- Blocking of the user functions.

    Note: The TC-9 can also be extended for communication. Ask your distributor for further information.

    Operation of the controller

    The front panel of the TC-9 ventilation controller is provided with 7 keys and LCD-display built up of 4 lines. The firstline indicates the menu you have accessed. The and keys can be used to go to a following menu. The otherthree lines display measurements and/ or settings. The cursor (the < sign at the end of the line indicates thepossibility of making a setting. Using the left and keys the cursor can be moved and used to point out aparticular function. Provided the function pointed out by the cursor is a setting, the and keys on the right can beused to adjust the value. After its entry the value can be stored into the computers memory by pressing the SET-key.Do not forget that last action! From then onwards the system will control on the newly entered values.

    Indicators

    The indicators represent the following symbols:Stage 1 relay active

    According for stage 2 till 9, the number 1 is replaced by number 2 till 9.

    Next is only for cooling stage 1, when timer function is activated.Out = Turned offBlinking = Timer off-timeContinue = Timer on-time

    Flap 1 control activatedOut = StopBlinking = ClosingContinue = Opening

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    7/56

    TC-9 Version V2.11 March 25, 2008Manual Page 5

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Curve control activate

    Curve separate zone 1 control activate

    Mist period activateOut = Turned offBlinking = Timer off-timeContinue = Timer on-time

    Adjustments and temperature displayed in Fahrenheit

    Fault indicationBlinking = sensor faultContinue = remaining fault (like temperature ranges, flap fault, memory fault)

    Installers- general/ special.Continue = Installers general active

    Blinking = Installers special active

    Zone 1 en 2 temperature

    Zone 1 temperature reads standard the measured temperature of sensor 1. In case the additional sensor 3 isactivated, the zone 1 temperature reading is calculated from the average reading of sensor 1 and sensor 3.

    Note: If sensor 1 and 3 are activated and one of them gets defective, zone 1 temperature takes over the overalltemperature reading from the remaining sensor.

    As for the zone 2 temperature the same applies as for zone 1 temperature, but now for sensor 2 and the additionalsensor 4.

    Separate zone 1 regulation

    With the TC-9 it is possible to make a separate regulation with its own:- Temperature (Zone 1 temperature).- Set temperature.- Minimum and maximum relative fault temperature settings.- Absolute fault temperature setting.- Curve control.

    Normally the room temperature is the average of all activated sensors without the outside temperature. With thesetting separate zone 1 it is possible to exclude the zone 1 temperature from the room temperature. Now you can

    make a separate regulation.Note I: Analog outputs, when activated and controlled by the zone 1 temperature are automatic connected toseparate zone 1 regulation.

    Note II: The separate zone 1 regulation and all connected regulations, make no use of humidity. Therefore theminimum compensation will not be used (see chapter humidity compensation).

    Activating the separate zone 1 regulation

    The function total heating has to be set to 1 or higher (Installer general menu 21, F2).The function natural ventilation has to be set to 0 (Installers general menu 21, F15).The function separate zone1 has to be set to 1 (Installers general menu 21, F13).The function heating has to be set to ZONED (Installers general menu 22, F1).

  • 8/12/2019 TC-9 V2.11 LCD#ENG#25032008

    8/56

    TC-9 Version V2.11 March 25, 2008Manual Page 6

    Aerotech Europe BV Postbus 512 Tel.+31(0)181 48 97 003233 ZK Oostvoorne Fax.+31(0)181 48 55 69

    Blocking of user functions

    The installer has the possibility to block all the user functions. The user can look at all the menus and functions, butcan not change them. The only functions that can be changed are: Set temperature, set temperature (separate zone1), current time and minimum/ maximum measured room temperature.

    Activating the blocking function

    - The function block has to be set to 1 (Installers general menu 20, F1).

    Special texts

    The installer has the opportunity to change several texts in the user menus and fault messages.The installer is able to change the next menu texts (13 characters):

    - Flap 1 (These text shall also being used by fault messages).- Analog output 1 to 4.

    The installer is able to change the next function texts (7 characters):- Flap 1.- Analog output 1to 4.- Zone 1 en 2 (Zone 1 text shall also be used in the menu text of curve separate zone 1).

    Note: Ask your distributor for further information.

    General

    Menu GENERAL

    This menu can be used to enter the set temperature, clock and to view a number of temperature readings. The menualso offers the possibility to read or restart the minimum and maximum measured temperature values.Note: A defective sensor will be displayed by '---.-'.

    1 GENERAL F 1time hh:mm 12:00