TABLE -13 - V-marc (Asian Galaxy Private Limited...

12
Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS Al Cu (mm) (mm) 4 ----- 1/7 1.8 8 6 1 1/7 1.8 9 10 1 6 1.8 10 16 6 6 1.8 11 25 6 6 1.8 12 35 6 6 1.8 13 50 6 6 1.8 15 70 12 12 1.8 16 95 15 15 1.8 18 120 15 18 1.8 20 150 15 18 2.0 22 185 30 30 2.0 24 240 30 34 2.0 27 300 30 34 2.0 30 400 53 53 2.2 33 500 53 53 2.2 36 630 53 53 2.2 40 800 53 53 2.4 47 1000 53 53 2.6 51 ELECTRICAL PARAMETERS Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.136 0.29 --- --- --- 48 47 45 0.376 0.572 6 4.61 3.08 5.900 3.94 0.128 0.34 48 45 45 60 59 57 0.564 0.858 10 3.08 1.83 3.940 2.34 0.118 0.42 62 62 61 80 78 77 0.940 1.430 16 1.91 1.15 2.440 1.47 0.108 0.50 81 80 83 104 102 106 1.504 2.288 25 1.20 0.727 1.540 0.931 0.102 0.52 99 90 115 130 115 145 2.350 3.575 35 0.868 0.524 1.110 0.671 0.097 0.60 117 110 135 155 140 175 3.290 5.005 50 0.641 0.387 0.820 0.495 0.092 0.63 138 125 170 185 165 215 4.700 7.150 70 0.443 0.268 0.567 0.343 0.088 0.68 168 155 210 225 200 270 6.580 10.010 95 0.320 0.193 0.411 0.248 0.085 0.79 204 185 255 265 235 330 8.930 13.590 120 0.253 0.153 0.325 0.197 0.082 0.79 230 210 300 300 265 380 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.082 0.79 265 230 342 335 300 430 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.082 0.79 295 260 385 380 335 495 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.079 0.84 340 300 450 435 385 590 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.078 0.86 390 335 519 490 430 670 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.077 0.88 450 380 605 550 480 780 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.076 0.90 500 480 700 610 530 900 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.075 0.94 555 485 809 680 590 1020 59.220 90.090 800 0.0367 0.0221 0.0503 0.0319 0.075 0.97 625 530 935 740 630 1140 75.200 114.400 1000 0.0291 0.0176 0.0444 0.0268 0.068 1.01 690 570 1065 780 660 1250 94.000 143.000 SIZE cross- sectional area(Sq MM) Max. Cond.D.C. Resistance at 20°C in Ohm/km Approx. Cond. AC Resistaance at 90°C in Ohm/Km App. Reactance at 50HZ in ohms/km App. Capecitance of cable in micro F/KM 2995 Short Circuit Current Rating for 1 sec . duration in K. Amps 3030 3990 4985 6290 7630 9945 3740 1195 1540 1890 2375 Air Duct Air 225 330 990 1540 1945 2485 530 615 605 790 1035 1285 810 175 2.2 2.4 430 220 380 360 440 1.6 1.7 1.8 2.0 With Copper Conductor 2XY Approx. Weight of cable in kg /Km 65 75 95 90 115 155 Ground 1.4 (mm) 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 2.8 With Al Conductor A2XY 120 Duct 2.6 Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor TABLE -13 TECHNICAL DETAIL FOR V-MARC-1.1 KV SINGLE CORE AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted circular Ground SIZE Cross Sectional Area (Sq MM) Minimum No of Strand in Conductor Nominal Thickness of outer Sheath Approx. Over all Diameter Nominal Thickness of Insulation With Aluminium cond With Copper cond Normal *Current Rating in Amps

Transcript of TABLE -13 - V-marc (Asian Galaxy Private Limited...

Page 1: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Al Cu (mm) (mm) 4 ----- 1/7 1.8 8 6 1 1/7 1.8 9 10 1 6 1.8 10 16 6 6 1.8 11 25 6 6 1.8 12 35 6 6 1.8 13 50 6 6 1.8 15 70 12 12 1.8 16 95 15 15 1.8 18 120 15 18 1.8 20 150 15 18 2.0 22 185 30 30 2.0 24 240 30 34 2.0 27 300 30 34 2.0 30 400 53 53 2.2 33 500 53 53 2.2 36 630 53 53 2.2 40 800 53 53 2.4 47 1000 53 53 2.6 51

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.136 0.29 --- --- --- 48 47 45 0.376 0.572 6 4.61 3.08 5.900 3.94 0.128 0.34 48 45 45 60 59 57 0.564 0.858 10 3.08 1.83 3.940 2.34 0.118 0.42 62 62 61 80 78 77 0.940 1.430 16 1.91 1.15 2.440 1.47 0.108 0.50 81 80 83 104 102 106 1.504 2.288 25 1.20 0.727 1.540 0.931 0.102 0.52 99 90 115 130 115 145 2.350 3.575 35 0.868 0.524 1.110 0.671 0.097 0.60 117 110 135 155 140 175 3.290 5.005 50 0.641 0.387 0.820 0.495 0.092 0.63 138 125 170 185 165 215 4.700 7.150 70 0.443 0.268 0.567 0.343 0.088 0.68 168 155 210 225 200 270 6.580 10.010 95 0.320 0.193 0.411 0.248 0.085 0.79 204 185 255 265 235 330 8.930 13.590 120 0.253 0.153 0.325 0.197 0.082 0.79 230 210 300 300 265 380 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.082 0.79 265 230 342 335 300 430 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.082 0.79 295 260 385 380 335 495 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.079 0.84 340 300 450 435 385 590 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.078 0.86 390 335 519 490 430 670 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.077 0.88 450 380 605 550 480 780 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.076 0.90 500 480 700 610 530 900 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.075 0.94 555 485 809 680 590 1020 59.220 90.090 800 0.0367 0.0221 0.0503 0.0319 0.075 0.97 625 530 935 740 630 1140 75.200 114.400 1000 0.0291 0.0176 0.0444 0.0268 0.068 1.01 690 570 1065 780 660 1250 94.000 143.000

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km

Approx. Cond. AC Resistaance at 90°C

in Ohm/Km

App. Reactance at

50HZ in ohms/km

App. Capecitance of cable in micro

F/KM

2995

Short Circuit Current Rating for 1 sec .

duration in K. Amps

3030 3990 4985 6290 7630 9945 3740

1195 1540 1890 2375

Air Duct Air

225 330

990

1540 1945 2485

530 615

605 790 1035 1285

810

175

2.2 2.4

430 220 380 360 440

1.6 1.7 1.8 2.0

With Copper Conductor 2XY

Approx. Weight of cable in kg /Km

65 75 95

90 115 155

Ground

1.4

(mm) 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2

2.8

With Al Conductor A2XY

120

Duct

2.6

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

TABLE -13 TECHNICAL DETAIL FOR V-MARC-1.1 KV SINGLE CORE

AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted circular

Ground

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Thickness of Insulation

With Aluminium cond With Copper cond Normal *Current Rating in Amps

Page 2: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 13 6 1 1/7 0.7 0.30 1.80 14 10 1 6 0.7 0.30 1.80 17 16 6 6 0.7 0.30 1.80 17 25 6 6 0.9 0.30 2.00 19 35 6 6 0.9 0.30 2.00 20 50 6 6 1.0 0.30 2.00 22 70 12 12 1.1 0.30 2.00 25 95 15 15 1.1 0.40 2.20 28 120 15 18 1.2 0.40 2.20 31 150 15 18 1.4 0.40 2.20 33 185 30 30 1.6 0.50 2.40 37 240 30 34 1.7 0.50 2.60 41 300 30 34 1.8 0.60 2.80 44 400 53 53 2.0 0.60 3.00 48 500 53 53 2.2 0.70 3.40 54 630 53 53 2.4 0.70 3.60 62

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.084 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 425 17.390 26.460 240 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 102 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Nominal Thickness of

Insulation

Minimum thickness of inner Sheath

Short Circuit Current Rating for 1 sec .

duration in K. Amps With Aluminium cond With Copper cond

Ground Duct Air Ground Duct Air

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance

at 90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro

F/KM

Normal *Current Rating in Amps

5285 12975

3330 8290 4195 10385

1990 4995 2675 6395

1380 3295 1740 3975

990 2190 1175 2675

580 1190 740 1620

395 690 475 880

345 460 365 495

With Copper Conductor 2XY

180 230 320 395

TABLE -14 TECHNICAL DETAIL FOR V-MARC-1.1 KV TWO CORES

AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

With Al Conductor A2XY

Page 3: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 14 6 1 1/7 0.7 0.30 1.80 16 10 1 6 0.7 0.30 1.80 18 16 6 6 0.7 0.30 1.80 18 25 6 6 0.9 0.30 2.00 21 35 6 6 0.9 0.30 2.00 22 50 6 6 1.0 0.30 2.00 25 70 12 12 1.1 0.40 2.20 30 95 15 15 1.1 0.40 2.20 32 120 15 18 1.2 0.40 2.20 35 150 15 18 1.4 0.50 2.40 39 185 30 30 1.6 0.50 2.60 43 240 30 34 1.7 0.60 2.80 49 300 30 34 1.8 0.60 3.00 53 400 53 53 2.0 0.70 3.20 59 500 53 53 2.2 0.70 3.60 66 630 53 53 2.4 0.70 3.80 73

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090

Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .

duration in K. Amps With Aluminium cond With Copper cond

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Ground Duct Air Ground Duct Air

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance

at 90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro

F/KM

6095 14975 7630 18990

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

3145 7580 3830 9395 4845 11990

1630 3780 2040 4790 2475 5935

775 1685 1090 2380 1340 3095

410 675 520 995 630 1290

220 280 315 415 395 560

TABLE -15 TECHNICAL DETAIL FOR V-MARC-1.1 KV

THREE CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness of

Insulation

Minimum thickness of inner Sheath

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

With Al Conductor A2XY

With Copper Conductor 2XY

Page 4: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: 3.5Core A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Phase Al

Neutral Cu (mm) (mm) (mm) (mm)

3x25+16 6/6 6/6 0.90/0.70 0.30 2.00 22 3x35+16 6/6 6/6 0.90/0.70 0.30 2.00 24 3x50+25 6/6 6/6 1.00/0.90 0.30 2.00 27 3x70+35 12/6 12/6 1.10/0.90 0.40 2.20 31 3x95+50 15/6 15/6 1.10/1.00 0.40 2.20 34 3x120+70 15/12 18/12 1.20/1.10 0.40 2.20 38 3x150+70 15/12 18/12 1.40/1.10 0.50 2.40 43 3x185+95 30/15 30/15 1.60/1.10 0.50 2.60 46 3x240+120 30/15 34/18 1.70/1.20 0.60 2.80 52 3x300+150 30/15 34/18 1.80/1.40 0.60 3.00 57 3x400+185 53/30 53/30 2.00/1.60 0.70 3.40 65 3x500+240 53/30 53/34 2.20/1.70 0.70 3.60 73 3x630+300 53/30 53/34 2.40/1.80 0.70 4.00 82

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 3x25+16 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58 3x35+16 0.868 0.524 1.11 0.67 0.080 0.23 116 94 117 145 120 155 3.29 5.01 3x50+25 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15 3x70+35 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01 3x95+50 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59 3x120+70 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16 3x150+70 0.206 0.124 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45 3x185+95 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46 3x240+120 0.125 0.0754 0.162 0.0980 0.072 0.31 325 270 402 410 350 510 22.56 34.32 3x300+150 0.100 0.0601 0.130 0.0780 0.071 0.33 370 305 461 460 390 590 28.20 42.90 3x400+185 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20 3x500+240 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50 3x630+300 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Ground Duct Air Ground Duct Air

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance

at 90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro

F/KM

Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .

duration in K. Amps With Aluminium cond With Copper cond

8880 21990

3595 8680 4390 10780 5580 13990

2275 5490 2790 6775

6990 17490

1195 2675 1475 3580 1890 4490

590 1130 675 1435 880 1990

TABLE -16 TECHNICAL DETAIL FOR V-MARC-1.1 KV

THREE & HALF CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness of

Insulation

Minimum thickness of inner Sheath

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

With Al Conductor A2XY

With Copper Conductor 2XY

Page 5: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XY/2XY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Al Cu (mm) (mm) (mm) (mm) 4 ----- 1/7 0.7 0.30 1.80 17 6 1 1/7 0.7 0.30 1.80 18 10 1 6 0.7 0.30 1.80 20 16 6 6 0.7 0.30 1.80 20 25 6 6 0.9 0.30 2.00 24 35 6 6 0.9 0.30 2.00 26 50 6 6 1.0 0.30 2.00 29 70 12 12 1.1 0.40 2.20 34 95 15 15 1.1 0.40 2.20 37 120 15 18 1.2 0.50 2.40 41 150 15 18 1.4 0.50 2.60 45 185 30 30 1.6 0.50 2.80 50 240 30 34 1.7 0.60 3.00 56 300 30 34 1.8 0.70 3.20 63 400 53 53 2.0 0.70 3.60 70 500 53 53 2.2 0.70 3.80 79 630 53 53 2.4 0.70 4.00 88

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 5.900 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 3.940 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 2.440 1.47 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 1.540 0.931 0.08 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 1.110 0.671 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.072 0.29 255 210 394 315 270 375 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.220 90.090

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

Normal *Current Rating in Amps Short Circuit Current Rating for 1 sec .

duration in K. Amps With Aluminium cond With Copper cond

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Ground Duct Air Ground Duct Air

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance

at 90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro

F/KM

7990 19960 9975 25990

4095 9995 5040 12035 6375 15975

2140 5140 2530 6330 3240 7840

990 2190 1375 3095 1690 3985

440 840 655 1295 785 1680

245 340 340 495 395 630

TABLE -17 TECHNICAL DETAIL FOR V-MARC-1.1 KV

FOUR CORES ,AL/COPPER COND. XLPE INSULATED, UN-ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness of

Insulation

Minimum thickness of inner Sheath

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

With Al Conductor A2XY

With Copper Conductor 2XY

Page 6: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XFaY/2XFaY,A2XWaY/2XWaY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nominal Thickness of armour

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Diameter of wire

Minimum Thickeness of outer sheath.

Approx. Over all Diameter

Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFaY

Cu. Cond. 2XFaY (mm) (mm) (mm) Cu. Cond.

2XWaY 4 ----- 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 10 125 6 1 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 11 165 10 1 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 12 215 16 6 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 13 290 25 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 14 445 35 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 15 540 50 6 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 17 710 70 12 12 1.4 N/A N/A N/A N/A N/A 1.40 1.24 19 925 95 15 15 1.4 0.80 1.40 21 590 1175 1.60 1.40 22 1225 120 15 18 1.5 0.80 1.40 23 685 1440 1.60 1.40 24 1480 150 15 18 1.7 0.80 1.40 24 790 1715 1.60 1.40 25 1765 185 30 30 1.9 0.80 1.40 26 940 2095 1.60 1.40 28 2125 240 30 34 2.0 0.80 1.40 30 1190 2670 1.60 1.40 30 2770 300 30 34 2.1 0.80 1.56 32 1375 3260 1.60 1.56 33 3340 400 53 53 2.4 0.80 1.56 36 1730 4220 2.00 1.56 38 4360 500 53 53 2.6 0.80 1.56 39 2140 5230 2.00 1.56 41 5440 630 53 53 2.8 0.80 1.72 44 2675 6605 2.00 1.72 46 6795 800 53 53 3.1 0.80 1.72 48 3330 8310 2.00 1.88 51 8640 1000 53 53 3.3 0.80 1.88 54 4090 10290 2.50 2.04 56 10780

ELECTRICAL PARAMETERS

Al Cu Al Cu. Al Cu. 4 ----- 4.61 ---- 5.90 0.152 0.22 --- --- --- 48 47 45 0.376 0.572 6 4.61 3.08 5.900 3.94 0.144 0.26 45 45 40 60 59 57 0.564 0.858 10 3.08 1.83 3.940 2.34 0.133 0.31 59 62 53 80 78 77 0.940 1.430 16 1.91 1.15 2.440 1.47 0.122 0.40 76 80 73 104 102 106 1.504 2.288 25 1.20 0.727 1.540 0.931 0.116 0.40 99 90 115 130 115 145 2.350 3.575 35 0.868 0.524 1.110 0.671 0.110 0.47 117 110 140 155 140 175 3.290 5.005 50 0.641 0.387 0.820 0.495 0.103 0.50 138 125 170 185 165 215 4.700 7.150 70 0.443 0.268 0.567 0.343 0.099 0.55 168 155 210 225 200 270 6.580 10.010 95 0.320 0.193 0.411 0.248 0.097 0.64 204 185 255 265 235 330 8.930 13.590 120 0.253 0.153 0.325 0.197 0.093 0.67 230 210 300 300 265 380 11.280 17.160 150 0.206 0.1240 0.265 0.1590 0.091 0.67 265 230 342 335 300 430 14.100 21.450 185 0.164 0.0991 0.211 0.1270 0.090 0.67 295 260 385 380 335 495 17.390 26.460 240 0.125 0.0754 0.162 0.0976 0.086 0.72 340 300 450 435 385 590 22.590 34.320 300 0.100 0.0601 0.130 0.0778 0.085 0.75 390 335 519 490 430 670 28.200 42.900 400 0.0778 0.0470 0.1023 0.0618 0.085 0.75 450 380 605 550 480 780 37.600 57.200 500 0.0605 0.0366 0.0808 0.0489 0.083 0.77 500 430 700 610 530 900 47.000 71.500 630 0.0469 0.0283 0.6480 0.0391 0.082 0.81 555 485 809 680 590 1020 59.220 90.090 800 0.0367 0.0221 0.0503 0.0319 0.081 0.88 625 530 935 740 630 1140 75.200 114.400 1000 0.0291 0.0176 0.0444 0.0268 0.081 0.88 690 570 1065 780 660 1250 94.000 143.000

4590

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Nominal Thickness

of Insulation

Approx. Weight of cable in kg /Km

ARMOURING WITH FLATE STRIP(A2XFaY/2XFaY) ARMOURING WITH ROUND WIRES(A2XWaY/2XWaY)

Approx. Weight of cable in kg /Km

Al Cond. A2XWaY

85

Short Circuit Current Rating for 1 sec .

duration in K. Amps

With Aluminium cond With Copper cond

Ground Duct Air Ground Duct Air

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm & above : Stranded compacted circular

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km

Approx. Cond. AC Resistaance at 90°C in

Ohm/Km

App. Reactance at

50HZ in ohms/km

App. Capecitance of cable in micro F/KM

Normal *Current Rating in Amps

2875 3590

1890 2330

1240 1495

840 990

640 730

415 510

280 335

155 190

120

TABLE -18 TECHNICAL DETAIL FOR V-MARC-1.1 KV

SINGLE CORE ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Page 7: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XFY/2XFY,A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nominal Thickness of armour

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Diameter of wire

Minimum Thickeness of outer sheath.

Approx. Over all Diameter

Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY

Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.

2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 15 530 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 16 575 10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 760 16 6 6 0.7 N/A N/A N/A N/A N/A 1.40 1.40 19 895 25 6 6 0.9 0.80 1.40 20 630 945 1.60 1.40 21 1140 35 6 6 0.9 0.80 1.40 21 740 1195 1.60 1.40 23 1390 50 6 6 1.0 0.80 1.40 23 890 1490 1.60 1.40 25 1685 70 12 12 1.1 0.80 1.56 26 1080 1930 1.60 1.56 28 2230 95 15 15 1.1 0.80 1.56 29 1330 2475 2.00 1.56 31 2990 120 15 18 1.2 0.80 1.56 31 1580 3095 2.00 1.56 34 3585 150 15 18 1.4 0.80 1.72 34 1875 3740 2.00 1.72 37 4295 185 30 30 1.6 0.80 1.72 37 2230 4485 2.00 1.88 40 5190 240 30 34 1.7 0.80 1.88 42 2790 5780 2.50 2.04 45 6770 300 30 34 1.8 0.80 2.04 45 3275 6990 2.50 2.20 49 8190 400 53 53 2.0 0.80 2.36 50 4095 9035 2.50 2.36 52 10295 500 53 53 2.2 0.80 2.52 55 4990 10985 3.15 2.68 60 13275 630 53 53 2.4 0.80 2.68 63 6085 13990 3.15 2.84 66 16290

ELECTRICAL PARAMETERS

Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090

0.70

0.40 0.50 0.50 0.60 0.60 0.70

0.30 0.30 0.40 0.40

0.30 0.30 0.30 0.30 0.30 0.30

0.820

0.1590

Cu. 5.90 3.94 2.34 1.47 0.931 0.671 0.495

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

0.0489 0.0391

0.0618

0.197 0.325

0.1270 0.0976 0.0778

0.265

0.130 0.1023

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

0.0808 0.0648

0.211 0.162

0.343 0.248

0.567 0.411

Al ----

5.900 3.940 2.440 1.540 1.110

Normal *Current Rating in Amps Short Circuit Current

Rating for 1 sec . duration in K. Amps

2890 3845 4435 5340 7095 8490

With Aluminium cond With Copper cond

Ground Duct Air Ground Duct Air

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance at

90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitan

ce of cable in micro F/KM

2430

Al Cond. A2XWY

485 540 635 690 845 930 1090 1375 1835 2140

TABLE -19 TECHNICAL DETAIL FOR V-MARC-1.1 KV

TWO CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness

of Insulation

ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)

Approx. Weight of cable in kg /Km

Approx. Weight of cable in kg /Km

Minimum Thickness

of Inner Sh.

(mm)

Page 8: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XFY/2XFY,A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nominal Thickness of armour

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Diameter of wire

Minimum Thickeness of outer sheath.

Approx. Over all Diameter

Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY

Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.

2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 665 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 19 765 10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.24 20 925 16 6 6 0.7 0.80 1.24 19 590 600 1.60 1.40 20 995 25 6 6 0.9 0.80 1.40 21 775 1195 1.60 1.40 23 1440 35 6 6 0.9 0.80 1.40 23 935 1490 1.60 1.40 25 1830 50 6 6 1.0 0.80 1.40 26 1095 1995 1.60 1.56 29 2295 70 12 12 1.1 0.80 1.56 29 1430 2675 2.00 1.56 32 3290 95 15 15 1.1 0.80 1.56 32 1740 3485 2.00 1.56 35 4095 120 15 18 1.2 0.80 1.56 35 2095 4195 2.00 1.72 39 4890 150 15 18 1.4 0.80 1.72 42 2490 5180 2.00 1.88 43 5975 185 30 30 1.6 0.80 1.88 44 2985 6290 2.50 2.04 48 7495 240 30 34 1.7 0.80 2.04 49 3740 8190 2.50 2.20 53 9490 300 30 34 1.8 0.80 2.20 54 4475 9995 2.50 2.36 58 11290 400 53 53 2.0 0.80 2.52 60 5580 12990 3.15 2.68 65 15190 500 53 53 2.2 0.80 2.68 66 6890 15975 3.15 2.84 72 18495 630 53 53 2.4 0.80 2.84 74 8530 19975 4.00 3.00 81 23675

ELECTRICAL PARAMETERS

Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858 10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590 120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

0.130 0.0778

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

0.1023 0.0618 0.0808 0.0489 0.0648 0.0391

0.265 0.1590 0.211 0.1270 0.162 0.0976

0.567 0.343 0.411 0.248 0.325 0.197

1.540 0.931 1.110 0.671 0.820 0.495

5.900 3.94 3.940 2.34 2.440 1.47

Duct Al Cu. ---- 5.90

0.70 12575

Air

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance at

90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitanc e of cable in micro F/KM

Normal *Current Rating in Amps Short Circuit Current

Rating for 1 sec . duration in K. Amps

With Aluminium cond With Copper cond

Ground Duct Air Ground

0.60 5975 0.70 7940 0.70 9480

0.40 3230 0.50 4195 0.50 5095

0.30 1985 0.40 2345 0.40 2745

0.30 995 0.30 1195 0.30 1435

595

0.30 740 0.30 895

0.30 645 0.30

TABLE -20 TECHNICAL DETAIL FOR V-MARC-1.1 KV

THREE CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness

of Insulation

Minimum Thickness

of Inner Sh.

ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)

Approx. Weight of cable in kg /Km

Approx. Weight of cable in kg /Km

(mm) Al Cond. A2XWY

Page 9: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: 3.5Core - A2XFY/2XY,A2XWY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nominal Thickness of armour

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Diameter of wire

Minimum Thickeness

of outer sheath.

Approx. Over all

Diameter Phase

Al Neutral

Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY

Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.

2XWY 3x25+16 6/6 6/6 0.90/0.70 0.80 1.40 23 895 1390 1.60 1.40 25 1690 3x35+16 6/6 6/6 0.90/0.70 0.80 1.40 25 990 1790 1.60 1.40 27 1990 3x50+25 6/6 6/6 1.00/0.90 0.80 1.40 28 1190 2290 1.60 1.56 30 2695 3x70+35 12/6 12/6 1.10/0.90 0.80 1.56 32 1595 3195 2.00 1.56 35 3680 3x95+50 16/6 15/6 1.10/1.00 0.80 1.56 35 1990 4090 2.00 1.56 38 4595

3x120+70 15/12 18/12 1.20/1.10 0.80 1.72 39 2390 5075 2.00 1.72 42 5690 3x150+70 15/12 18/12 1.40/1.10 0.80 1.72 43 2795 5980 2.00 1.88 46 6785 3x185+95 30/15 30/15 1.60/1.10 0.80 1.88 47 3375 7395 2.50 2.04 51 8675 3x240+120 30/15 34/18 1.70/1.20 0.80 2.04 53 4295 9490 2.50 2.20 56 10495 3x300+150 30/15 34/18 1.80/1.40 0.80 2.20 57 4985 11495 2.50 2.36 60 12995 3x400+185 53/30 53/30 2.00/1.60 0.80 2.52 66 6390 14475 3.15 2.68 71 16985 3x500+240 53/30 53/34 2.20/1.70 0.80 2.68 74 7695 17790 3.15 2.84 79 21490 3x630+300 53/30 53/34 2.40/1.80 0.80 3.00 82 9890 22975 4.00 3.00 88 27975

ELECTRICAL PARAMETERS

Al Cu Al Cu. 3x25+16 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.35 3.58 3x35+16 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.29 5.01 3x50+25 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.70 7.15 3x70+35 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.58 10.01 3x95+50 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.93 13.59

3x120+70 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.28 17.16 3x150+70 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.10 21.45 3x185+95 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.39 26.46 3x240+120 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.56 34.32 3x300+150 0.100 0.0601 0.071 0.33 370 305 461 460 390 590 28.20 42.90 3x400+185 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.60 57.20 3x500+240 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.00 71.50 3x630+300 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.22 90.09

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

Al Cu. 1.54 0.931

0.820

Air

1.11 0.671 0.495

0.567 0.343 0.411 0.248

0.197 0.265

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance at

90°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro F/KM

Normal *Current Rating in Amps Short Circuit Current

Rating for 1 sec . duration in K. Amps

With Aluminium cond With Copper cond

Ground Duct Air Ground Duct

0.50 4675

0.70 10980 0.70 14490

0.60 5690 0.60 6680 0.70 8975

0.40 2595 0.40 3090 0.50 3580

1095

0.30 1575 0.40 2190

0.30 1280 0.30

TABLE -21 TECHNICAL DETAIL FOR V-MARC-1.1 KV

THREE & HALF CORES,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness

of Insulation

Minimum Thickness

of Inner Sh.

ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)

Approx. Weight of cable in kg /Km

Approx. Weight of cable in kg /Km

(mm) Al Cond. A2XWY

0.162

0.1023 0.0618

0.159 0.325

0.211 0.127 0.0980

0.0808 0.0648

0.0489 0.0391

0.130 0.0780

Page 10: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: A2XFY/2XFY, A2XWY/2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nominal Thickness of armour

Nominal Thickness of outer Sheath

Approx. Over all Diameter

Nominal Diameter of wire

Minimum Thickeness

of outer sheath.

Approx. Over all

Diameter

Al Cu (mm) (mm) (mm) (mm) Al Cond. A2XFY

Cu. Cond. 2XFY (mm) (mm) (mm) Cu. Cond.

2XWY 4 ----- 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 18 635 6 1 1/7 0.7 N/A N/A N/A N/A N/A 1.40 1.24 19 745

10 1 6 0.7 N/A N/A N/A N/A N/A 1.40 1.40 21 940 16 6 6 0.7 0.80 1.40 20 695 1085 1.60 1.40 22 1295 25 6 6 0.9 0.80 1.40 24 890 1495 1.60 1.40 26 1760 35 6 6 0.9 0.80 1.40 27 1095 1990 1.60 1.40 28 2195 50 6 6 1.0 0.80 1.56 30 1380 2485 1.60 1.56 32 2840 70 12 12 1.1 0.80 1.56 34 1790 3395 2.00 1.56 37 3995 95 15 15 1.1 0.80 1.56 37 2195 4390 2.00 1.72 40 5130

120 15 18 1.2 0.80 1.72 41 2680 5590 2.00 1.88 44 6295 150 15 18 1.4 0.80 1.88 46 3195 6775 2.50 2.04 49 7985 185 30 30 1.6 0.80 2.04 51 3880 8290 2.50 2.20 54 9685 240 30 34 1.7 0.80 2.20 57 4840 10490 2.50 2.36 65 11975 300 30 34 1.8 0.80 2.36 63 5830 12975 3.15 2.52 68 15390 400 53 53 2.0 0.80 2.68 71 7310 16980 3.15 2.84 76 19495 500 53 53 2.2 0.80 2.84 79 8990 20970 4.00 3.00 86 24975 630 53 53 2.4 0.80 3.00 88 10975 26985 4.00 3.00 94 30470

ELECTRICAL PARAMETERS

Al Cu Al Cu. 4 ----- 4.61 0.098 0.11 34 28 30 44 37 39 0.376 0.572 6 4.61 3.08 0.090 0.13 43 37 40 55 47 50 0.564 0.858

10 3.08 1.83 0.084 0.16 57 48 53 74 61 67 0.940 1.430 16 1.91 1.15 0.080 0.18 78 61 70 94 78 85 1.504 2.288 25 1.20 0.727 0.080 0.20 95 80 99 120 100 125 2.350 3.575 35 0.868 0.524 0.080 0.23 116 94 117 145 120 155 3.290 5.005 50 0.641 0.387 0.078 0.24 140 110 140 170 145 190 4.700 7.150 70 0.443 0.268 0.077 0.26 170 140 176 210 175 235 6.580 10.010 95 0.320 0.193 0.074 0.29 200 165 221 250 210 290 8.930 13.590

120 0.253 0.153 0.072 0.29 225 185 258 285 240 330 11.280 17.160 150 0.206 0.1240 0.072 0.29 255 210 294 315 270 375 14.100 21.450 185 0.164 0.0991 0.072 0.29 285 235 339 355 300 435 17.390 26.460 240 0.125 0.0754 0.072 0.31 325 270 402 410 350 510 22.560 34.320 300 0.100 0.0601 0.071 0.33 370 305 460 460 390 590 28.200 42.900 400 0.0778 0.0470 0.070 0.33 435 350 542 520 440 670 37.600 57.200 500 0.0605 0.0366 0.070 0.34 481 405 624 580 480 750 47.000 71.500 630 0.0469 0.0283 0.069 0.36 537 470 723 680 575 875 59.220 90.090

0.130 0.0778

Note: Normal Current rating are given in stranded condition . If site conditions are different , current rating should be multiplied by Rating Factor

0.1023 0.0618 0.0808 0.0489 0.0648 0.0391

0.265 0.1590 0.211 0.1270 0.162 0.0976

0.567 0.343 0.411 0.248 0.325 0.197

1.540 0.931 1.110 0.671 0.820 0.495

5.900 3.94 3.940 2.34 2.440 1.47

Ground Duct Al Cu. ---- 5.90

0.70 15975

Air

CONDUCTOR : MATERIAL : Aluminium / Copper *Shape:~AL. Cond.:-6 & 10 SQ MM -Solid circular , 16 sqmm & above : Stranded compacted circular ~ Copper Cond :- 4 & 6 sq.mm-solid/stranded non compacted circular ,10 sq. mm Stranded compacted circular 16 sq mm & above : Stranded compacted shaped

SIZE cross- sectional

area(Sq MM)

Max. Cond.D.C. Resistance at

20°C in Ohm/km Approx. Cond. AC Resistaance at

70°C in Ohm/Km App.

Reactance at 50HZ in

ohms/km

App. Capecitance of cable in micro F/KM

Normal *Current Rating in Amps Short Circuit Current

Rating for 1 sec . duration in K. Amps

With Aluminium cond With Copper cond

Ground Duct Air

0.70 8195 0.70 9990 0.70 13485

0.50 4495 0.50 5175 0.60 6380

0.40 2395 0.40 2895 0.50 3490

0.30 1195 0.30 1440 0.30 1735

540

0.30 660 0.30 915

0.30 595 0.30

TABLE -22 TECHNICAL DETAIL FOR V-MARC-1.1 KV

FOUR CORES ,AL/COPPER COND. XLPE INSULATED, GI WIRE/STRIP ARMOURED CABLES

SIZE Cross

Sectional Area (Sq MM)

Minimum No of Strand in

Conductor

Nominal Thickness

of Insulation

Minimum Thickness

of Inner Sh.

ARMOURING WITH FLATE STRIP(A2XFY/2XFY) ARMOURING WITH ROUND WIRES(A2XWY/2XWY)

Approx. Weight of cable in kg /Km

Approx. Weight of cable in kg /Km

(mm) Al Cond. A2XWY

Page 11: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are

Cable Code: 2XY,2XFY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nom. Thick. of

outer Sheath

Nominal Thickness of armour

Minimum Thickness of outer Sheath

Nominal Diameter

of wire

Minimum Thickeness

of outer sheath.

(mm) (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. 2 0.70 0.30 1.80 11 12 175 182 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 13 313 327 3 0.70 0.30 1.80 11 12 202 203 N/A N/A N/A N/A N/A N/A 1.40 1.24 13 13 356 371 4 0.70 0.30 1.80 12 13 236 238 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 14 410 427 5 0.70 0.30 1.80 13 14 274 276 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15 466 485 6 0.70 0.30 1.80 14 15 313 315 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 16 524 545 7 0.70 0.30 1.80 14 15 343 346 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 16 551 571 10 0.70 0.30 1.80 17 18 470 475 N/A N/A N/A N/A N/A N/A 1.60 1.40 19 20 746 774 12 0.70 0.30 1.80 18 19 537 542 0.80 1.40 18.3 19 743 768 1.60 1.40 20 21 819 848 14 0.70 0.30 1.80 18 20 607 613 0.80 1.40 19.1 20 821 847 1.60 1.40 21 22 899 929 16 0.70 0.30 2.00 20 21 696 703 0.80 1.40 20.0 21 902 929 1.60 1.40 22 23 1042 1079 19 0.70 0.30 2.00 21 22 799 807 0.80 1.40 21.0 22 1011 1040 1.60 1.40 23 24 1158 1196 24 0.70 0.30 2.00 24 26 990 1001 0.80 1.40 24.2 25 1238 1273 1.60 1.40 26 27 1409 1456 27 0.70 0.30 2.00 24 26 1087 1099 0.80 1.40 24.7 26 1333 1370 1.60 1.40 26 28 1506 1554 30 0.70 0.30 2.00 25 27 1188 1202 0.80 1.40 25.5 27 1439 1477 2.00 1.40 27 28 1617 1667 37 0.70 0.30 2.00 27 30 1424 1440 0.80 1.40 27.4 29 1684 1725 2.00 1.56 29 31 1928 1985 40 0.70 0.40 2.00 28 31 1528 1546 0.80 1.56 28.8 30 1823 1868 2.00 1.56 30 32 2048 2108 44 0.70 0.40 2.20 31 33 1732 1751 0.80 1.56 31.1 33 2026 2076 2.00 1.56 34 35 2454 2533 52 0.70 0.40 2.20 32 35 1994 2016 0.80 1.56 32.4 34 2285 2338 2.00 1.56 35 37 2728 2810 61 0.70 0.40 2.20 34 37 2294 2320 0.80 1.56 34.3 36 2588 2645 2.00 1.56 37 39 3055 3143

TECHNICAL DETAIL FOR V-MARC-1.1 KV

2.5 SQ MM COPPER COND. XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES

No of Cores

Minimum Thick. of

Inner Sheath

UNARMOURED(2XY) ARMOURING WITH FLATE STRIP(2XFY) ARMOURING WITH ROUND WIRES(2XWY)

Approx. Overall Dimeter (mm)

Approx Net Wt. of cable(Kg/Km)

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

Approx. Over all Diameter

Approx. Weight of cable in kg /Km

Nominal Thickness

of Insulation

Cable Code: 2XY,2XFY,2XWY REF SPEC : IS : 7098 (PT-1) : 1988 PHYSICAL PARAMETERS

Nom. Thick. of

outer Sheath

Nominal Thickness of armour

Minimum Thickness of outer Sheath

Nominal Diameter of wire

Minimum Thickeness

of outer sheath.

(mm) (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. (mm) (mm) Solid cond. Std. cond. Solid cond. Std. cond. 2 0.70 0.30 1.80 9.8 10.2 138 144 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 12.2 275 288 3 0.70 0.30 1.80 10.2 10.7 153 158 N/A N/A N/A N/A N/A N/A 1.40 1.24 12 12.7 307 322 4 0.70 0.30 1.80 11.0 11.5 174 179 N/A N/A N/A N/A N/A N/A 1.40 1.24 13 13.5 349 365 5 0.70 0.30 1.80 11.8 12.3 198 204 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 14.3 393 411 6 0.70 0.30 1.80 12.6 13.2 223 230 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15.2 438 458 7 0.70 0.30 1.80 12.6 13.2 241 248 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15.2 456 476

10 0.70 0.30 1.80 15.4 16.2 325 334 N/A N/A N/A N/A N/A N/A 1.40 1.24 17 18.2 602 629 12 0.70 0.30 1.80 15.8 16.7 366 375 N/A N/A N/A N/A N/A N/A 1.40 1.24 18 18.7 652 680 14 0.70 0.30 1.80 16.5 17.4 409 419 0.80 1.40 18 20 634 654 1.60 1.24 19 19.4 711 740 16 0.70 0.30 1.80 17.4 18.3 454 464 0.80 1.40 19 21 693 713 1.60 1.40 20 20.7 829 864 19 0.70 0.30 1.80 18.2 19.2 516 527 0.80 1.40 22 22 769 790 1.60 1.40 21 21.6 913 950 24 0.70 0.30 2.00 21.4 22.6 656 671 0.80 1.40 22 25 936 961 1.60 1.40 23 24.6 1105 1150 27 0.70 0.30 2.00 21.8 23.1 714 729 0.80 1.40 23 25 1001 1026 1.60 1.40 24 25.1 1174 1219 30 0.70 0.30 2.00 22.5 23.8 776 792 0.80 1.40 25 26 1074 1100 1.60 1.40 25 25.8 1254 1301 37 0.70 0.30 2.00 24.2 25.6 920 937 0.80 1.40 26 28 124 1272 1.60 1.40 26 27.6 1439 1491 40 0.70 0.30 2.00 25.1 26.6 985 1003 0.80 1.40 27 29 1323 1352 1.60 1.40 27 28.6 1526 1580 44 0.70 0.30 2.00 27.0 28.6 1078 1098 0.80 1.40 29 31 1447 1477 1.60 1.40 29 30.6 1666 1725 52 0.70 0.30 2.00 28.1 29.8 1234 1254 0.80 1.40 31 32 1620 1652 1.60 1.56 30 31.8 1850 1912 61 0.70 0.30 2.20 30.2 32.0 1441 1465 0.80 1.56 35 34 1827 1891 2.00 1.56 33 34.7 2250 2329

Approx. Weight of cable in kg /Km

Approx. Over all Diameter

TECHNICAL DETAIL FOR V-MARC-1.1 KV

1.5 SQ MM COPPER COND. XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES

No of Cores

ARMOURING WITH FLATE STRIP(2XFY) ARMOURING WITH ROUND WIRES(2XWY)

Approx. Weight of cable in kg /Km

Minimum Thick. of Inner Sh. Approx. Overall

Dimeter (mm) Approx Net Wt. of

cable(Kg/Km)

UNARMOURED(2XY)

Approx. Over all Diameter

Nominal Thickness

of Insulation

Page 12: TABLE -13 - V-marc (Asian Galaxy Private Limited ...v-marc.com/.../LT-XLPE-Armoured-Un-Armoured-Power-Control-Cables..pdfNormal *Current Rating in Amps. ... Normal Current rating are