T1 - DWA Construct
Transcript of T1 - DWA Construct
NO
TE
3
NO
TE
5
"D
"
NO
TE
3
NO
TE
5
NOTE 3NOTE 5
NOTE 5
NOTE 3
TYPICAL HORIZONTAL WALL
REINFORCING AS SHOWN ON
DRAWINGS, LAP WITH
CORNER AND INTERSECTION
REINFORCING
NOTE 3
NOTE 5
"D"
STD HOOK OR AS
NOTED ON THE DWGS
"D"
STD ACI-318 90°
HOOK OR AS NOTED
ON THE DWGS
"A" BARS SEE PLANS
"B" BARS
"C" BARS
"E" BARS
"D" BARS
"F" BARS
"G" BARS
© COPYRIGHT DESIGN WEST ARCHITECTS 201854321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
MARK
:DA
TE:
DESC
RIPT
ION:
THE
CHUR
CH O
F JE
SUS
CHRI
ST O
F LA
TTER
-DAY
SAI
NTS
218036
05.08.2019
BID
SET
S
STE
TA
UTRS CT
R P
UR
F OE
G
OF UT HA
ERE
NI
NISO
L
EN
A LA
No. 295553RASMUSSENCRAIGL.
05/08/19
GARD
EN C
ITY
ASSE
MBL
Y HA
LL10
0 SO
UTH
PARA
DISE
PAR
KWAY
, GAR
DEN
CITY
, UT
1. ALL DESIGN, CONSTRUCTION, AND INSPECTION SHALL BE IN CONFORMANCE
WITH THE 2015 INTERNATIONAL BUILDING CODE (IBC) AND REFERENCED
STANDARDS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE
SITE.
3. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE
WORKING DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
4. DRAWINGS INDICATE THE FINISHED PRODUCT. THEY DO NOT INDICATE A
METHOD OF CONSTRUCTION. CONTRACTOR SHALL TAKE ALL PRECAUTIONS
NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH
PRECAUTIONS SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING
FOR CONSTRUCTION EQUIPMENT, ETC..
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPENSATING THE OWNER
FOR ANY CHANGES MADE AS A RESULT OF A DEVIATION FROM THE CONTRACT
DOCUMENTS, DEVIATION FROM THE SPECIFICATIONS, FAULTY MATERIALS, OR
FAULTY WORKMANSHIP.
6. OPTIONS ARE FOR THE CONTRACTOR'S CONVENIENCE. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR COORDINATING ALL REQUIRED DESIGN CHANGES.
COST ASSOCIATED WITH ANY DESIGN WORK INITIATED BY THE OPTION SHALL
BE BORN BY THE CONTRACTOR.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY AND PROTECTION WITHIN
AND ADJACENT TO THE JOB SITE.
8. TEMPORARY SHORING AND BRACING SHALL BE PROVIDED WHEREVER
NECESSARY TO TAKE CARE OF ALL LOADS TO WHICH THE STRUCTURE MAY BE
SUBJECTED INCLUDING WIND. SUCH BRACING SHALL BE LEFT IN PLACE AS
LONG AS MAY BE REQUIRED FOR SAFETY OR UNTIL ALL THE STRUCTURAL
ELEMENTS ARE COMPLETE.
9. DURING AND AFTER CONSTRUCTION THE CONTRACTOR AND/OR OWNER SHALL
KEEP LOADS ON THE STRUCTURE WITHIN THE LIMITS OF THE DESIGN LOADS.
10. THE GENERAL CONTRACTOR SHALL HAVE SHOP DRAWINGS REVIEWED BY THE
ENGINEER PRIOR TO THE FABRICATION OR ERECTION FOR THE FOLLOWING
ITEMS: REINFORCING STEEL, STRUCTURAL STEEL, AND MISCELLANEOUS
METALS.
11. ALL DETAILS, SECTIONS, AND NOTES ARE INTENDED TO BE TYPICAL AND SHALL
APPLY TO SIMILAR SITUATIONS UNLESS NOTED OR SHOWN OTHERWISE.
12. OBSERVATION VISITS TO THE JOB SITE BY THE OWNER, ENGINEER OR FIELD
REPRESENTATIVES OF THE ENGINEER SHALL NEITHER BE CONSTRUED AS
INSPECTION NOR APPROVAL OF CONSTRUCTION.
13. SIZES, LOCATIONS, AND ANCHORAGE'S OF EQUIPMENT SHALL BE VERIFIED IN
THE FIELD WITH EQUIPMENT MANUFACTURERS (SUPPLIERS) PRIOR TO PLACING
CONCRETE OR FABRICATING STEEL.
1. FOOTING ELEVATIONS SHOWN ON PLAN ARE TOP OF FOOTINGS AND ARE
MINIMUM DEPTH. DIFFERENT OR UNUSUAL CONDITIONS SHALL BE REPORTED
TO THE ENGINEER.
2. EXTERIOR WALL FOOTINGS SHALL BEAR AT A MINIMUM DEPTH OF 36" BELOW
FINISHED EXTERIOR GRADE.
3. NO FOOTINGS SHALL BE PLACED IN WATER OR ON FROZEN GROUND.
4. ANY SOIL CONDITION ENCOUNTERED DURING EXCAVATION THAT IS CONTRARY
TO THE CONDITIONS USED FOR DESIGN OF FOOTINGS, OR ON THE DRAWINGS
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE
PROCEEDING.
5. WHERE 6" DIAMETER OR LARGER PIPE PASSES THROUGH AN INTERIOR OR
EXTERIOR FOUNDATION WALL, STEP THE FOOTING DOWN TO PASS BELOW PIPE
AND THEN STEP BACK UP TO INDICATED ELEVATION. PROVIDE PIPE SLEEVE
THROUGH FOUNDATION WALL. PLACE BOTTOM OF PIPE SLEEVE 12" ABOVE TOP
OF FOOTING.
6. COMPACT SOIL UNDER FOOTINGS TO AT LEAST 90% OF MAXIMUM DRY DENSITY
AS DETERMINED BY (MODIFIED PROCTOR) ASTM D1557.
7. FOUNDATION SUBGRADE SHALL BE PREPARED IN ACCORDANCE WITH THE
RECOMMENDATIONS OF THE GEOTECHNICAL EVALUATION REPORT PREPARED
BY GSH GEOTECHNICAL DATED DECEMBER 17, 2018.
8. ALLOWABLE BEARING CAPACITY = 3000 PSF
1. ALL CONCRETE SHALL MEET THE REQUIREMENTS OF ACI-301, “SPECIFICATION
FOR STRUCTURAL CONCRETE FOR BUILDINGS.” PROPORTIONING OF
INGREDIENTS FOR EACH CONCRETE MIX SHALL BE BY METHOD 2 OR THE
ALTERNATE PROCEDURE GIVEN IN ACI-301. PLACE CONCRETE PER ACI-304 AND
CONFORM TO ACI-604 (306) FOR COLD WEATHER PLACEMENT AND ACI-605 (305)
FOR HOT WEATHER PLACEMENT, USE INTERIOR MECHANICAL VIBRATORS WITH
7,000 RPM MINIMUM FREQUENCY. DO NOT OVER-VIBRATE. CONCRETE SHALL BE
PLACED MONOLITHICALLY BETWEEN CONSTRUCTION AND CONTROL JOINTS.
PROTECT ALL CONCRETE FROM PREMATURE DRYING, EXCESSIVE HOT OR COLD
TEMPERATURE FOR SEVEN DAYS AFTER PLACING.
2. STRENGTH
TWENTY-EIGHT DAY COMPRESSIVE STRENGTH SHALL BE:
4000 PSI
SLUMP: 4 INCH + 1 INCH.
MAX. WATER/CEMENT RATIO: 0.45
3. STRUCTURAL CONCRETE EXPOSURE CLASS: F2
4. MATERIALS
CEMENT: ASTM 150, TYPE I.
COARSE AND FINE AGGREGATE: ASTM C33.
WATER SHALL BE CLEAN AND POTABLE.
5. ADMIXTURES
WATER REDUCING ADMIXTURE: ASTM C494, ADMIXTURES SHALL BE USED IN
EXACT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
SYNERGIZED PERFORMANCE SYSTEMS: CONCRETE USING ADMIXTURES TO
PRODUCE FLOWABLE CONCRETE MAY BE USED SUBJECT TO
ENGINEER'S APPROVAL.
6. AIR ENTRAINMENT:ASTM C260 AND ASTM C494, ENTRAIN 6% PLUS/MINUS 1 1/2%
BY VOLUME IN ALL EXPOSED CONCRETE.
7. NO OTHER ADMIXTURE PERMITTED UNLESS APPROVED BY THE ENGINEER OF
RECORD.
8. THE FLATNESS AND LEVELNESS OF CONCRETE FLOORS SHALL BE MEASURED
PER ASTM E 1155:STANDARD TEST METHOD FOR DETERMINING FLOOR FLATNESS
AND LEVELNESS USING THE F-NUMBER SYSTEM.
SPECIFIED OVERALL F-NUMBER FF 25/FL 20
MINIMUM LOCAL F-NUMBER FF 15/FL 12
9. A STATEMENT OF MIX DESIGN FOR ALL CONCRETE SHALL BE SUBMITTED TO AND
REVIEWED BY THE ENGINEER PRIOR TO COMMENCING WORK.
10. ALL CONCRETE WORK SHALL BE PLACED, CURED, STRIPPED, AND PROTECTED
AS DIRECTED BY THE SPECIFICATIONS AND ACI STANDARDS AND PRACTICES.
11. DOWEL VERTICAL BARS THE DEVELOPMENT LENGTH INTO STRUCTURE ABOVE
AND FOOTINGS BELOW. PROVIDE 90 DEGREE HOOK WHERE DEVELOPMENT
LENGTH IS NOT POSSIBLE. LAP ALL REINF. IN CONCRETE THE LISTED LENGTH
U.N.O.
12. BEFORE CONCRETE IS POURED CHECK WITH ALL TRADES TO ENSURE PROPER
PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS,
ETC. RELATIVE TO WORK.
13. REFER TO DRAWINGS FOR TYPICAL CONSTRUCTION JOINT DETAILS. UNLESS
NOTED IN DRAWINGS, ALL REINFORCEMENT SHALL BE CONTINUOUS THROUGH
JOINTS AND EACH CONSTRUCTION JOINT SHALL BE KEYED.
14. WHERE EXTERIOR SLABS ON GRADE ABUT FOUNDATIONS OR COLUMNS PROVIDE
3/8" PREFORMED EXPANSION JOINT WITH SEALANT.
1. ALL REINFORCEMENT SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH
BP-66(04): ACI DETAILING MANUAL - 2004, ACI 350-06, AND ACI 318-14.
2. REINFORCING STEEL SHALL BE ASTM A615 GRADE 60. WELDED WIRE FABRIC
SHALL CONFORM TO ASTM A82 AND ASTM A185.
3. ALL REINFORCEMENT SHALL BE SECURELY TIED AND HELD IN PLACE.
4. REINFORCING BARS THAT ARE TO BE WELDED, INCLUDING DEFORMED BAR
ANCHORS (D.B.A.) SHALL COMPLY WITH ASTM A706 OR ANOTHER APPROVED
WELDABLE GRADE AND SHALL BE WELDED IN ACCORDANCE WITH THE A.W.S.
RECOMMENDATIONS.
5. ALL CONTINUOUS REINFORCEMENT SHALL TERMINATE WITH A 90 DEG. TURN OR
A SEPARATE CORNER BAR. ALL SPLICES IN CONCRETE SHALL LAP THE LISTED
LAP LENGTH.
6. THE FOLLOWING CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCEMENT:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
B. ALL OTHER CONCRETE:2"
7. PRIOR TO FABRICATION AND PLACEMENT, SHOP DRAWINGS FOR ALL
REINFORCING STEEL SHALL BE REVIEWED BY THE ENGINEER.
8. REFER TO WALL CORNER AND WALL INTERSECTION REINFORCING DETAIL. IN
GENERAL, THE WALL CORNER REINFORCING SIZES AND SPACING SHALL BE
CALLED OUT ON THE PLANS AND REFERENCED TO THESE DETAILS AND THE
TYPICAL HORIZONTAL WALL REINFORCING SHALL LAP WITH THE HORIZONTAL
REINFORCING.
9. ALL BENDS, UNLESS OTHERWISE SHOWN, SHALL BE A 90 DEGREE STANDARD
HOOK. REFER TO STANDARD CONCRETE HOOK DETAILS.
10. ALL WALL CORNER AND WALL INTERSECTION REINFORCEMENT BARS SHALL BE
CONTINUOUS AROUND CORNERS AND THROUGH COLUMNS OR PILASTERS.
REINFORCEMENT SHALL BE EXTENDED INTO CONNECTING WALLS AND LAPPED
ON THE OPPOSITE FACE OF THE CONNECTING WALLS.
11. UNLESS INDICATED OTHERWISE, CONTRACTOR MAY SPLICE CONTINUOUS SLAB
OR LONGITUDINAL BEAM BARS AT LOCATION OF HIS CHOOSING, EXCEPT THAT
TOP BAR SPLICES SHALL BE LOCATED AT MIDSPAN AND BOTTOM BAR SPLICES
SHALL BE LOCATED AT SUPPORTS. STAGGER SPLICES IN HORIZONTAL WALL
BARS SO THAT NO TWO ADJACENT BARS IN THE SAME OR OPPOSITE CURTAIN
ARE SPLICED AT THE SAME LOCATION. ALL REINFORCEMENT BENDS AND LAPS,
UNLESS OTHERWISE NOTED, SHALL SATISFY THE REQUIREMENTS OF THE STD.
CONCRETE HOOK SCHEDULE AND THE CONCRETE REINFORCEMENT LAP AND
DEVELOPMENT SCHEDULES.
THE FOLLOWING STRUCTURAL DESIGN LOADS APPLY U.N.O.:
ROOF LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . L
r
= 20 PSF
MEZZANINE LIVE LOAD . . . . . . . . . . . . . . . . . . . . L = 40 PSF
STRUCTURE RISK CATEGORY . . . . . . . . . . . . . . III
SNOW LOAD:
GROUND SNOW LOAD. . . . . . . . . . . . . . . . P
g
= 80 PSF
SNOW IMPORTANCE FACTOR. . . . . . . . . I
s
= 1.1
SNOW EXPOSURE FACTOR. . . . . . . . . . . C
e
= 1.0
SNOW THERMAL FACTOR . . . . . . . . . . C
t
= 1.0
FLAT ROOF SNOW LOAD. . . . . . . . . . . . . P
f
= 62 PSF
SLOPED ROOF SNOW LOAD . . . . . . . . . . P
s
= 62 PSF
WIND:
BASIC WIND SPEED . . . . . . . . . . . . . . . . . . V = 120 MPH
WIND IMPORTANCE FACTOR. . . . . . . . . . . Iw = 1.00
WIND EXPOSURE. . . . . . . . . . . . . . . . . . . . C
SEISMIC:
SEISMIC IMPORTANCE FACTOR. . . . . . . . . . . . I
E
= 1.25
SPECTRAL RESPONSE ACCELERATION. . . . . S
S
= 1.121
SPECTRAL RESPONSE ACCELERATION. . . . . S
1
= 0.339
SEISMIC SOIL SITE CLASS . . . . . . . . . . . . . . . . D
SPECTRAL RESPONSE COEFFICIENT . . . . . . S
DS
= 0.786
SPECTRAL RESPONSE COEFFICIENT . . . . . . S
D1
= 0.389
SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . D
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
BASIC SEISMIC FORCE RESISTING SYSTEM:
LIGHT FRAME (WOOD) WALLS SHEATHED WITH WOOD PANELS
RESPONSE MODIFICATION COEFFICIENT. . . . . R = 6.5
OVERSTRENGTH FACTOR . . . . . . . . . . . . . . . . . . Ω
0
= 3
GENERAL CONCRETE
REINFORCING STEEL
FOOTINGS
DESIGN CRITERIA
PLYWOOD DIAPHRAGM FASTENERS
1. SUBSTITUTION OF FASTENERS OTHER THAN THOSE SPECIFIED IN THE
STRUCTURAL NOTES OR THE PLYWOOD DIAPHRAGM SCHEDULE IS NOT
ALLOWED.
2. NAILS SHALL BE PLACED NOT LESS THAN 3/8" FROM THE EDGE OF PLYWOOD
PANELS. STAGGER NAILS EACH SIDE OF PANEL EDGE.
3. AT ROOF AND FLOOR DIAPHRAGMS, APPLY NAILS AT PANEL EDGE SPACING TO
ALL DRAG STRUTS, TENSION CHORDS, BLOCKING OVER BEARING AND SHEAR
WALLS, AND ANY OTHER SPECIAL DIAPHRAGM MEMBERS NOTED ON PLANS.
4. AT PLYWOOD SHEAR WALLS, APPLY NAILS AT PANEL EDGE SPACING TO TOP
AND BOTTOM PLATES, END POSTS, ALL VERTICAL ELEMENTS AT HOLD DOWN
ANCHORS, AND HORIZONTAL BLOCKING.
5. ALL PANEL EDGES OF PLYWOOD SHEAR WALLS MUST BE BLOCKED.
6. NAILS SHALL BE COATED AND SHALL COMPLY WITH THE REQUIREMENTS OF
ASTM F 1667 NLCMS AND IBC SECTION 2303.6.
1. REFER TO STRUCTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILS,
ADDITIONAL NOTES AND SCHEDULES PERTAINING TO PLYWOOD ROOF.
2. STRUCTURAL FRAMING LUMBER SHALL BE CLEARLY MARKED AND MEET THE
FOLLOWING MINIMUM GRADES AS DEFINED BY THE 2015 EDITION OF THE
NATIONAL DESIGN SPECIFICATION:
A. 2" TO 4" THICK
5" AND WIDER: DOUGLAS FIR-LARCH GRADE NO.2
3. ALL ROOF AND FLOOR JOISTS SHALL BE SUPPORTED LATERALLY AT THE ENDS
AND AT EACH SUPPORT BY SOLID BLOCKING 2" THICK AND THE FULL DEPTH OF
THE JOIST, EXCEPT WHERE THE END OF THE JOIST IS ATTACHED TO A HEADER
OR BOND BEAM WITH METAL ANCHORS OR HANGERS.
4. ALL NAILS SPECIFIED ON DETAILS OR SCHEDULED SHALL BE COMMON STEEL
WIRE NAILS (COATED) UNLESS NOTED OTHERWISE AND SHALL COMPLY WITH
REQUIREMENTS OF ASTM F 1667 AND IBC SECTION 2303.6.
5. HOLES FOR NAILS, WHERE NECESSARY TO PREVENT SPLITTING, SHALL BE
BORED OF A DIAMETER SMALLER THAN THAT OF THE NAILS.
6. ALL JOISTS AND BEAM HANGERS, FRAMING ANCHORS, STRAP TIES, AND OTHER
METAL FASTENERS FOR WOOD FRAMING SHALL BE SIMPSON BRAND (OR
EQUIV.).
7. UNLESS NOTED OTHERWISE, ANCHOR ALL TRUSSES, RAFTERS AND JOISTS TO
SUPPORTS WITH GALVANIZED FRAMING ANCHORS.
8. UNLESS NOTED OTHERWISE, PROVIDE 2 X CONTINUOUS BLOCKING BETWEEN
MAIN MEMBERS AT ALL RIDGES, HIPS AND VALLEYS.
9. CUTTING AND NOTCHING OF STUDS. IN EXTERIOR WALLS AND BEARING
PARTITIONS, ANY WOOD STUD IS PERMITTED TO BE CUT OR NOTCHED TO A
DEPTH NOT EXCEEDING 25% OF ITS WIDTH. CUTTING OR NOTCHING OF STUDS
TO A DEPTH NOT GREATER THAN 40% OF THE WIDTH IS PERMITTED IN
NONBEARING PARTITIONS SUPPORTING NO LOADS OTHER THAN THE WEIGHT
OF THE PARTITION.
10. BORED HOLES IN STUDS. A HOLE NOT GREATER IN DIAMETER THAN 40% OF THE
STUD WIDTH IS PERMITTED TO BE BORED IN ANY WOOD STUD. BORED HOLES
NOT GREATER THAN 60% OF THE WIDTH OF THE STUD ARE PERMITTED IN
NONBEARING PORTIONS OR IN ANY WALL WHERE EACH BORED STUD IS
DOUBLED, PROVIDED NOT MORE THAN TWO SUCH SUCCESSIVE DOUBLED
STUDS ARE SO BORED.
11. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE NEARER THAN 5/8" TO
THE EDGE OF THE STUD.
12. NAILING AND CONNECTION SHALL BE IN CONFORMANCE W/ IBC AND AITC.
REFER TO IBC 2015, TABLE 2304.10.1 FOR FASTENING SCHEDULE.
13. P.T. LUMBER SHALL BE IN CONFORMANCE WITH IBC SECTION 2303.1.9
14. NAILS IN CONTACT WITH P.T. LUMBER SHALL BE STAINLESS STEEL.
15. GLUE-LAMINATED BEAMS SHALL CONFORM TO I.B.C COMBINATION 24F-V4 FOR
SIMPLE SPANS, 24F-V8 FOR MULTIPLE SPANS OR CANTILEVERED BEAMS PER
ICBO REPORT 2519 (UNLESS SHOWN OR NOTED OTHERWISE ON DRAWINGS).
LUMBER SHALL BE DOUGLAS FIR 2400 PSI. CAMBER FOR DEAD LOAD AS SHOWN
ON DRAWINGS. WATERPROOF GLUE ALL BEAMS.
WOOD FRAMING
STRUCTURAL STEEL
1. ALL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH
AMERICAN INSTITUTE OF STEEL CONSTRUCTION SPECIFICATION FOR THE
DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDING,
LATEST EDITION. OBTAIN APPROVAL OF THE ENGINEER OF RECORD PRIOR TO
SITE CUTTING, MAKING ADJUSTMENTS OR PERFORMING FIELD WELDS NOT
SCHEDULED OR SHOWN ON PLANS OR DETAILS. ALL ASTM A325 BOLTING
MATERIAL SHALL BE PROVIDED WITH CERTIFIED DIRECT TENSION INDICATOR
WASHERS AND HARDENED WASHERS FOR FIELD BOLTED CONNECTIONS.
2. STRUCTURAL L SHAPED STEEL TO MEET ASTM A36 GRADE 36.
1. FOLLOW RECOMMENDED PRACTICE FOR CONCRETE FORMWORK (ACI-347-14).
2. ALL SHORING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
FORMWORK SUPPORTS AND SHORING SHALL BE DESIGNED TO PROVIDE
FINISHED CONCRETE SURFACES OF ALL FACES LEVEL, PLUMB, AND TRUE TO
THE DIMENSIONS AND ELEVATIONS SHOWN. TOLERANCES AND VARIATIONS
SHALL BE AS SPECIFIED.
FORM WORK
1. CONCRETE ANCHOR RODS SHALL MEET THE QUALITY OF ASTM F1554 GRADE 36 KSI,
GALVANIZED (ASTM A153, CLASS C) RODS AND SHALL HAVE A STANDARD BOLT HEAD OR AN
EQUAL DEFORMITY IN THE EMBEDDED PORTION.
2. MACHINE BOLTS SHALL BE ASTM A307 BOLTS, UNLESS NOTE AS ASTM A307 ON THE DRAWINGS
OR DETAILS.
3. WELDED-HEADED STUDS SHALL BE “NELSON” STUDS CONFORMING TO ASTM A108.
ANCHOR BOLTS
S-000
STRUCTURAL
NOTES
9 5 W E S T 1 0 0 S O U T H , S T E . 1 1 5 , L O G A N , U T 8 4 3 2 1
PH: 435.227.0333 FAX: 435.227.0334
DLB
CLR
NOTES FOR CORNER AND INTERSECTION REINFORCING DETAILS
1. TYPICAL HORIZONTAL WALL CORNER AND INTERSECTION REINFORCING LAYOUT IS SHOWN TO AVOID CONGESTION AND PERMIT PROPER PLACEMENT, FOR SIZE AND
SPACING SEE PLANS. ALL HORIZONTAL REINFORCING AT CORNERS AND INTERSECTIONS SHALL BE FABRICATED AND INSTALLED WITH SPLICES LOCATED WHERE
SHOWN REGARDLESS OF BAR SIZE AND SPACING.
2. WHERE THE CORNER OR INTERSECTION REINFORCING SIZE AND SPACING IS NOT SHOWN, NOTED OR TABULATED ON THE PLANS, THE SIZE AND SPACING SHALL BE THE
SAME AS THE WALL HORIZONTAL REINFORCING SHOWN ON THE WALL SECTIONS OR AS NOTED FOR THE REINFORCING BETWEEN THE CORNERS OR INTERSECTIONS.
3. EXCEPT WHERE OTHERWISE SHOWN ON THE DRAWINGS, THE LENGTH INDICATED AS "NOTE 3" SHALL BE THE LESSER OF D/4, 10 FEET, OR 1.0 TIMES THE HEIGHT OF THE
WALL, EXCEPT THAT IN NO CASE SHALL IT BE LESS THAN THE SPLICE LENGTH.
4. D = LENGTH OF WALL PARALLEL TO THE BAR LENGTH IN QUESTION.
5. EXCEPT WHERE OTHERWISE SHOWN ON THE DRAWINGS, THE LENGTH INDICATED AS "NOTE 5" SHALL BE EQUAL TO ONE "LAP LENGTH" AS REQUIRED BY THE GENERAL
STRUCTURAL NOTES. USE THE LAP LENGTH AS REQUIRED FOR THE SMALLER OF THE TWO REINFORCING BARS BEING SPLICED.
6. HORIZONTAL BARS IN WALLS SHALL HAVE SPLICES STAGGERED ONE LAP LENGTH AS DEFINED IN NOTE 5.
7. ALTERNATE SPLICE LOCATIONS OF HORIZONTAL BARS IN WALLS BETWEEN THE TWO CURTAINS SO THAT NO SPLICES AT THE SAME ELEVATION ARE LOCATED
TOGETHER.
ALL SHEAR WALLS TO HAVE 3” X 3” X 1/4” (MINIMUM SIZE, GALVANIZED WHEN IN CONTACT WITH PRESSURE TREATED WOOD) PLATE
WASHER AT EACH ANCHOR BOLT.
MINIMUM FOR CAST IN PLACE ANCHOR BOLT EMBEDMENT SHALL BE 7”.
PROVIDE A MINIMUM OF 2 ANCHOR BOLTS PER FOUNDATION PLATE MEMBER WITH ONE BOLT LOCATED NOT MORE THAN 12” OR
LESS THAN 4” BOLT DIAMETERS FROM EACH END OF EACH PLATE MEMBER.
USE HOT DIPPED GALVANIZED NAILS WITH SIZE AND SPACING AS LISTED IN THE SHEAR WALL SCHEDULE FOR NAILING TO
PRESSURE TREATED MATERIAL. CONNECTORS IN CONTACT WITH PRESSURE TREATED WOOD SHALL BE CORROSION RESISTANT
WITH FINISHES PER THE MANUFACTURES RECOMMENDATIONS.
1. MAXIMUM SHEAR = 260 P.L.F.
USE 7/16” APA RATED SHEATHING ONE SIDE OF WALL WITH FRAMING MEMBERS AT 16” O/C MAXIMUM SPACING. NAIL ALL
PANEL EDGES WITH 8D COMMON NAILS (D=.131”, MIN. FASTENER PENETRATION INTO FRAMING 1 3/8”) AT 6” O.C. FOR FRAMING
USE 2” NOMINAL WIDTH DF #2. PROVIDE 5/8” DIAMETER ANCHOR BOLTS AT 32” O.C. MAXIMUM SPACING AT THE
FOUNDATION. SEE PLANS FOR LOCATIONS AND SIZES OF HOLDOWNS.
2. MAXIMUM SHEAR = 350 P.L.F.
USE 7/16” APA RATED SHEATHING ONE SIDE OF WALL WITH FRAMING MEMBERS AT 16” O/C MAXIMUM SPACING. NAIL ALL
PANEL EDGES WITH 8D COMMON NAILS (D=.131”, MIN. FASTENER PENETRATION INTO FRAMING 1 3/8”) AT 4” O/C. FOR FRAMING
USE 2” NOMINAL WIDTH DF#2. PROVIDE 5/8” DIAMETER ANCHOR BOLTS AT 32” O/C MAXIMUM SPACING AT THE
FOUNDATION. SEE PLANS FOR LOCATIONS AND SIZES OF HOLDOWNS.
3. MAXIMUM SHEAR = 490 P.L.F.
USE 7/16” APA RATED SHEATHING ONE SIDE OF WALL WITH FRAMING MEMBERS AT 16” O/C MAXIMUM SPACING. NAIL ALL
PANEL EDGES WITH 8D COMMON NAILS (D=.131”, MIN. FASTENER PENETRATION INTO FRAMING 1 3/8”) AT 3” O/C. FOR FRAMING
AT VERTICAL AND HORIZONTAL PANEL EDGES USE 3” NOMINAL OR WIDER DF#2. ALTERNATIVELY, AT ABUTTING PANEL EDGES
DOUBLE 2” NOMINAL MEMBERS MAY BE USED WHEN FASTENED (FACE NAILED) WITH 10D COMMON OR 16D
SINKER (D=.148”) NAILS AT 3-1/2” O.C. STAGGERED. USE A 2” NOMINAL SILL PLATE WITH 5/8” DIAMETER ANCHOR BOLTS
AT 32” O/C MAXIMUM SPACING AT THE FOUNDATION. SEE PLANS FOR LOCATIONS AND SIZES OF HOLDOWNS.
SHEAR WALL SCHEDULE
CORNER AND INTERSECTION REINFORCING DETAIL
1
10
5-1
6-2
01
9A
DD
EN
DU
M #
1
© COPYRIGHT DESIGN WEST ARCHITECTS 201854321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
MARK
:DA
TE:
DESC
RIPT
ION:
THE
CHUR
CH O
F JE
SUS
CHRI
ST O
F LA
TTER
-DAY
SAI
NTS
218036
05.08.2019
BID
SET
S
STE
TA
UTRS CT
R P
UR
F OE
G
OF UT HA
ERE
NI
NISO
L
EN
A LA
No. 295553RASMUSSENCRAIGL.
05/08/19
GARD
EN C
ITY
ASSE
MBL
Y HA
LL10
0 SO
UTH
PARA
DISE
PAR
KWAY
, GAR
DEN
CITY
, UT
1. SPECIAL INSPECTION SHALL BE PROVIDED ACCORDING TO IBC
CHAPTER 17 FOR THE ITEMS IDENTIFIED IN THIS SECTION AND ON
THE CONTRACT DOCUMENTS.
2. THE NAMES AND CREDENTIALS OF SPECIAL INSPECTORS TO BE
USED SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT WHEN
APPLYING FOR A BUILDING PERMIT.
3. SPECIAL INSPECTION REPORTS SHALL BE DELIVERED TO THE
OWNER BI-WEEKLY OR MORE FREQUENTLY AS REQUIRED BY THE
INSPECTOR OR BUILDING OFFICIAL.
4. OFF-SITE FABRICATION: WHERE FABRICATION OF STRUCTURAL
LOAD-BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED
ON THE PREMISES OF A FABRICATORS SHOP, SPECIAL INSPECTION
OF THE FABRICATED ITEMS SHALL BE IN ACCORDANCE WITH IBC
SECTION 1704.2.5 UNLESS THE FABRICATOR IS APPROVED
ACCORDING TO IBC SECTION 1704.2.5.1.
5. CONCRETE CONSTRUCTION: SPECIAL INSPECTIONS AND
VERIFICATIONS SHALL BE PROVIDED IN ACCORDANCE WITH TABLE
1705.3.
6. THE FOLLOWING ELEMENTS OF THE SEISMIC-FORCE-RESISTING
SYSTEM IN ACCORDANCE WITH IBC SECTION 1705.12:
A. STRUCTURAL WOOD (IBC 1705.12.2)
7. SOILS: SPECIAL INSPECTION SHALL BE PROVIDED FOR PLACEMENT
OF FILL 12 INCHES OR MORE DEEP IN ACCORDANCE WITH SECTION
1705.6.
8. EPOXY ANCHORS: PRIOR TO AND DURING EPOXY INJECTION TO
INSURE PROPER INSTALLATION AS PER MANUFACTURERS
REQUIREMENTS. CONTRACTOR SHALL SUBMIT PROPOSED EPOXY
MANUFACTURERS I.C.B.O. REPORT TO ENGINEER PRIOR TO
INSTALLATION.
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A
SEISMIC-FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM,
OR COMPONENT LISTED IN THE QUALITY ASSURANCE PLAN SHALL
SUBMIT A WRITTEN CONTRACTOR'S STATEMENT OF RESPONSIBILITY
TO THE BUILDING OFFICIAL AND TO THE OWNER PRIOR TO THE
COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT IN
ACCORDANCE WITH IBC SECTION 1704.4. THE CONTRACTOR'S
STATEMENT OF RESPONSIBILITY SHALL CONTAIN THE FOLLOWING:
A. ACKNOWLEDGMENT OF AWARENESS OF THE SPECIAL
REQUIREMENTS CONTAINED IN THE QUALITY ASSURANCE
PLAN.
B. ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED TO
OBTAIN CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS APPROVED BY THE BUILDING OFFICIAL.
C. PROCEDURES FOR EXERCISING CONTROL WITHIN THE
CONTRACTOR'S ORGANIZATION, THE METHOD AND
FREQUENCY OF REPORTING, AND THE DISTRIBUTION OF
REPORTS.
D. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S)
EXERCISING SUCH CONTROL AND THE POSITION(S) IN THE
ORGANIZATION.
QUALITY ASSURANCE
CONTRACTOR RESPONSIBILITY
QUALITY ASSURANCE PLAN
NOTES
NO
FASTENERS
BOUNDARY
40/2019/32"
SHEATHING
DIAPHRAGM SCHEDULE
MARK
WD-1
ALL GRADES OF STEEL (MIN. YIELD STRENGTHS)
D = FINISHED INSIDE BEND DIAMETER
d = BAR DIAMETER
D = 6d FOR #3 THROUGH #8
D = 8d FOR #9, #10 AND #11
D = 10d FOR #14 AND #18
d
B
4d or
2
1
2
" MIN.
D
HOOK A
DETAILING
DIMENSION
180° HOOK
d
12
d
A
D
DETAILING
DIMENSION
90° HOOK
RECOMMENDED END HOOKS
BAR
SIZE
D
180° HOOKS
A B
90° HOOKS
A
#3 2
1
4
" 5" 3" 6"
#4 3" 6" 4" 8"
NOTES:
1. ALL REINFORCEMENT LAPS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE MINIMUM
REQUIREMENTS SHOWN IN THE TABLE "REINFORCEMENT LAP LENGTHS."
2. TOP BARS SHALL BE DEFINED AS ANY HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12"
OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE BAR, IN ANY SINGLE POUR.
HORIZONTAL WALL BARS ARE CONSIDERED TOP BARS.
CONCRETE REINFORCEMENT LAP & DEVELOPMENT SCHEDULES
NTS
DIAPHRAGM LAYOUT
TYPICAL PLYWOOD ROOF
BLOCKING IF REQ'D
FRAMING, SEE PLAN
INTERMEDIATE SUPPORTS
DIAPHRAGM
BOUNDARIES (SHEAR
WALLS, TENSION
CHORDS)
CONT. PANEL EDGE
PANEL EDGES
NOTES:
1. USE ONLY APA RATED SHEATHING MEETING THE REQUIREMENTS
OF IBC SECTION 2303.1.4.
2. USE ONLY COMMON WIRE NAILS FOR FASTENERS.
3. FACE GRAIN OF PLYWOOD PANELS TO BE PERPENDICULAR TO
SUPPORTS.
4. NAILS SHALL BE PLACED NOT LESS THAN 3/8" IN FROM PANEL
EDGES.
MINIMUM
FASTENER
PENETRATION
IN FRAMING
MINIMUM
NOMINAL
PANEL
THICKNESS
CONTINUOUS
PANEL EDGE
OTHER
PANEL
EDGES
BLOCKING
DIAPHRAGM
1 1/2"
HOOK EMBED
DEPTH
7"
9"
#5 3
3
4
" 7" 5" 10"
#6 4
1
2
" 8" 6" 1'-0"
1'-7"11
3
4
"1'-3"9
1
2
"#9
1'-4"8"11"6"#8
1'-2"7"10"5
1
4
"#7
1'-10"1'-1
1
4
"1'-5"10
3
4
'#10
#11 12" 1'-7" 1'-2
3
4
" 2'-0"
#14 18
1
4
" 2'-3" 1'-9
3
4
" 2'-7"
#18 24" 3'-0" 2'-4
1
2
" 3'-5"
(IN ACCORDANCE WITH ACI 318-14)
NTS
STD. CONCRETE HOOK SCHEDULE
12"
14"
23"
21"
18"
26"
31"
41"
16"
NOTE: EMBED BARS WITH HOOKS TO THE DEPTH
SHOWN.
SPAN
RATING
PANEL
FIELD
10d @ 4"
D=.148"
10d @ 6"
D=.148"
10d @ 6"
D=.148"
10d @ 12"
D=.148"
VERIFICATION AND INSPECTION
CONTINUOUS DURING
TASK LISTED
PERIODICALLY DURING
TASK LISTED
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER
MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
-- X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE
HAS BEEN PREPARED PROPERLY.
-- X
-- X
X --
-- X
TABLE 1705.6 REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND
VERIFY PLACEMENT.
3. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS.
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a.
4. VERIFYING USE OF REQUIRED DESIGN MIX.
-- X ACI 318 CH. 20,
25.2, 25.3,
26.6.1-26.6.3
1908.4
--X
ACI 318:17.8.2.4
--
-- X
ACI 318: CH. 19,
26.4.3, 26.4.4
1904.1,
1904.2,
1908.2,
1908.3
5. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE.
X --
ASTM C172,
ASTM C31,
ACI 318: 26.4, 26.12
1908.10
6. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES.
X --ACI 318: 26.5
1908.6,
1908.7,
1908.8
7. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES.
-- X
ACI 318:
26.5.3-26.5.5
1908.9
8. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED. -- X
ACI 318:
26.11.1.2(b)
--
TABLE 1705.3 REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
2. INSPECT ANCHORS CAST IN CONCRETE.
-- X
ACI 318:17.8.2
--
-- X
ACI 318: 17.8.2
--
VERIFICATION AND INSPECTION
CONTINUOUS DURING
TASK LISTED
PERIODICALLY DURING
TASK LISTED
1. VERIFY APPROPRIATE SHEATHING, FRAMING MEMBERS AT PANEL EDGES AND
FASTENERS ARE USED
2. VERIFY PROPER NAILING, BOLTING, ANCHORING AND OTHER FASTENING OF ELEMENTS
OF LATERAL FORCE RESISTING SYSTEM INCLUDING WOOD SHEAR WALLS, WOOD
DIAPHRAGMS, DRAG STRUTS, BRACES AND HOLD-DOWNS.
-- X
-- X
IBC SECTION 1705.11.1 REQUIRED SPECIAL INSPECTIONS FOR STRUCTURAL WOOD FRAMING
3. VERIFY THAT PROPER BOLTING AND SPACING ARE USED ON TIMBER TRUSSES
-- X
5'-7"5'-1"4'-6"4'-0"3'-6"2'-5"2'-0"1'-7"1'-3"
7'-3"6'-7"5'-10"5'-2"4'-6"3'-1"2'-7"2'-1"1'-7"
#11#10#9#8#7#6#5#4#3
OTHER BAR
TOP BAR
BAR SIZE
REINFORCEMENT LAP LENGTHS
CONCRETE DESIGN STRENGTH - 4000 PSI
NO40/2023/32"WD-2 1 1/2"
10d @ 6"
D=.148"
10d @ 6"
D=.148"
10d @ 6"
D=.148"
10d @ 12"
D=.148"
S-001
STRUCTURAL
NOTES
9 5 W E S T 1 0 0 S O U T H , S T E . 1 1 5 , L O G A N , U T 8 4 3 2 1
PH: 435.227.0333 FAX: 435.227.0334
DLB
CLR
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC IBC SECTION
TMS 402/ACI
530/ASCE 5"
TMS 602/ACI
530.1/ASCE 6"
1. VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS
2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE:
5. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS.
-- X -- -- ART. 1.5
--
ART.
1.4 B.2.a.3,
1.4 B.2.b.3,
1.4 B.2.c.3,
1.4 B.3,
1.4 B.4
ACI 530-13, TABLE 3.1.2 - LEVEL B QUALITY ASSURANCE MINIMUM TESTS & SPECIAL INSPECTIONS
--
MINIMUM SPECIAL INSPECTIONS
MINIMUM TESTS
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH SPECIFICATION
ARTICLE 1.5 B.1.b.3 FOR SELF-CONSOLIDATING GROUT.
VERIFICATION OF f'
m
AND f'
AAC
IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO CONSTRUCTION, EXCEPT WHERE SPECIFICALLY
EXEMPTED BY IBC 2015.
A. PROPORTIONS OF SITE-PREPARED MORTAR AND GROUT.
B. CONSTRUCTION OF MORTAR JOINTS.
C. LOCATION OF REINFORCEMENT AND CONNECTORS.
-- X -- --
ART. 2.1,
2.6 A
-- X -- -- ART. 3.3 B
X-- -- --ART. 3.4,
3. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE:
A. GROUT SPACE
B. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR
BOLTS.
C. PLACEMENT OF REINFORCEMENT AND CONNECTORS.
D. PROPORTIONS OF SITE-PREPARED GROUT.
E. CONSTRUCTION OF MORTAR JOINTS.
-- X -- --
ART. 3.2 D,
3.2 F
-- X -- SEC. 6.1ART. 2.4, 3.4
-- X --
ART. 3.2 E,
3.4
X-- -- -- ART. 2.6 B
X-- -- -- ART. 3.3 B
4. VERIFY DURING CONSTRUCTION:
A. SIZE AND LOCATION OF STRUCTURAL ELEMENTS
B. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER
DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL
MEMBERS, FRAMES, OR OTHER CONSTRUCTION.
C. WELDING OF REINFORCEMENT
D. PREPARATION, CONSTRUCTION, AND PROTECTION OF
MASONRY DURING COLD WEATHER (TEMPERATURE BELOW
40°F) OR HOT WEATHER (90°F).
F. PLACEMENT OF GROUT.
G. PLACEMENT OF MASONRY UNITS.
-- X -- -- ART. 3.3 F
-- X --
SEC. 1.2.1(e),
6.1.4.3, 6.2.1
--
SEC. 8.1.6.7.2,
9.3.3.4 (c),
11.3.3.4 (b)
-- --
ART. 1.8 C,
1.8 D
-- -- ART. 3.5
--
ART. 3.3 B.9, 3.3
F.1.b
SEC. 6.1, 6.2.1,
6.2.6-7
X --
X --
-- X
-- X
XX
--
--
--
PRE-CAST CONCRETE LINTEL TO BE PROVIDED AT DOORS AND WINDOWS FOR BRICK VENEER
SUPPORT AT LOCATIONS SHOWN ON ARCHITECTURAL PLANS. PRE-CAST LINTEL TO BE 6" WIDE BY
8" TALL WITH (2) #3 LONGITUDINAL REINFORCEMENT BARS LOCATED 2" FROM BOTTOM OF
CONCRETE LINTEL.
MAX SPAN = 6'
PROVIDE 6” (MIN.) OF BEARING AT EACH END.
USE 7/8” 22 GA. GALVANIZED MASONRY TIES PER IBC 2103.4 AT 16” O/C HORIZONTAL AND 16” O/C
VERTICAL. 9 GA ANNEALED WIRE SHALL BE INSTALLED IN EACH HORIZONTAL COURSE CONTAINING
MASONRY TIES. LAP WIRE 3” MINIMUM. ANCHOR TIES SHALL HAVE A LIP OR HOOK ON THE
EXTENDED LEG THAT WILL ENGAGE OR ENCLOSE A HORIZONTAL JOINT REINFORCEMENT WIRE.
CONCRETE LINTELS FOR FASCIA BRICK
BRICK VENEER
1
10
5-1
6-2
01
9A
DD
EN
DU
M #
1
T
1
T
3
T
2
T
3
T
4
BW
2
14'-0"
BW
310'-0"
C2C2
C2C2
PRE-ENGINEERED,
PRE-MANUFACTURED
TRUSSES AT OVERBUILD
PRE-ENGINEERED,
PRE-MANUFACTURED
TRUSSES AT OVERBUILD
H1H1 H1 H1
H1
H4
H3
H1 H1
H1H1 H1 H1
H1
H4
H1
H1
H1
H1
10'-0"
14'-0"
TYP, AT ENTRY
SEE SHEET
S-502 FOR
LOADS TO
TRUSS
T
2
APPROXIMATE LOCATION
OF CAP TRUSS PER
PRE-ENGINEERED,
PRE-MANUFACTURED
TRUSSES
© COPYRIGHT DESIGN WEST ARCHITECTS 201854321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
MARK
:DA
TE:
DESC
RIPT
ION:
THE
CHUR
CH O
F JE
SUS
CHRI
ST O
F LA
TTER
-DAY
SAI
NTS
218036
05.08.2019
BID
SET
S
STE
TA
UTRS CT
R P
UR
F OE
G
OF UT HA
ERE
NI
NISO
L
EN
A LA
No. 295553RASMUSSENCRAIGL.
05/08/19
GARD
EN C
ITY
ASSE
MBL
Y HA
LL10
0 SO
UTH
PARA
DISE
PAR
KWAY
, GAR
DEN
CITY
, UT
SCALE: 1/8"=1'-0"
ROOF FRAMING PLAN
NOTES:
HEADER & BEAM SCHEDULE
MARK MEMBER
(2) 2x8 DF #2
H2
H1
H3 (2) 1 3/4X 9 1/2 MICROLAM LVL 1.9 E
ALL HEADERS H1 U.N.O.
BEARING WALLS & COLUMNS
NOTES:
ALL COLUMNS ARE C1 U.N.O.
ALL BEARING WALLS ARE BW1 U.N.O.
BW3
2X6 DF #2 AT 12" O.C.
1 3/4"X5 1/2" MICROLAM LVL 1.9E AT 16" O.C.
BW1 2X6 DF #2 AT 16" O.C.
BW2
MemberMark
PRE-ENGINEERED/PRE-MANUFACTURED TRUSSES AT 19.2" O.C. w/ CAP TRUSS
PRE-ENGINEERED/PRE-MANUFACTURED GIRDER TRUSS
TRUSS, RAFTER, & GIRDER TRUSS SCHEDULE
NOTES:
T1
GT
STRUCTURAL KEY NOTES
1. 2x10 DF#2 OUTLOOKERS AT 24" O.C.
2. INSTALL SIMPSON CMSTC12 AT RIDGE PER DETAIL 12
SHEET S500.
3. INSTALL L6X3 1/2X1/2 STEEL LINTEL OVER FRONT
ENTRY. STEEL LINTEL TO BEAR ON A MINIMUM 6
INCHES OF MASONRY.
4. SEE DETAIL 1 SHEET S-501 FOR MEZZANINE FLOOR
FRAMING.
5. INSTALL SIMPSON CMSTC12 AT ALL TOP PLATE
SPLICES ALONG THE LENGTH OF WALL NOTED.
6. PRE-MANUFACTURED STEEPLE.
7. SEE DETAIL 1 SHEET S502 FOR SPACING AND LOADING
FOR PRE-ENGINEERED, PRE-MANUFACTURED
TRUSSES UNDER PRE-MANUFACTURED STEEPLE.
8. PROVIDE BLOCKING AT ROOF PANEL DIAPHRAGM
EDGES w/ 4" BOUNDARY NAILING AND 4" EDGE
NAILING.
9. PROVIDE LGT4-SDS3 AT BOTH ENDS OF EACH (4) PLY
TRUSS w/ (4) 2x6 DF #2 BUILT-UP COLUMN BELOW
TRUSSES.
10. PROVIDE H2.5A AT (2) PLY TRUSS.
#
GENERAL NOTES
1. REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL
DIMENSIONS AND ELEVATIONS NOT SHOWN.
2. REFER TO SHEET S-000 FOR SHEAR WALL SCHEDULE AND
NOTES. ALL SHEAR WALLS ARE TO BE TYPE 1 U.N.O.
3. REFER TO SHEET S-001 FOR WOOD DIAPHRAGM SCHEDULE
AND NOTES. ALL DIAPHRAGMS ARE TO BE TYPE 1 U.N.O.
4. ALL DOUBLE TOP PLACE SPLICES TO BE SPLICE TYPE 1
U.N.O. SEE DETAIL 10 SHEET S5OO FOR SPLICE SCHEDULE.
5. PROVIDE 2x NAILER AT EACH TRUSS FOR ANCHORING SHEET
VAPOR RETARDER. SEE DETAIL D2 SHEET A-561 FOR NAILER
LOCATION ON TRUSS.
C2
C1 (2) 2X6 DF #2
(3) 2X6 DF #2
(2) 1 3/4X5 1/2 MICROLAM LVL 1.9 E
PRE-ENGINEERED/PRE-MANUFACTURED TRUSSES AT 24" O.C.T2
PRE-ENGINEERED/PRE-MANUFACTURED MONO TRUSSES AT 19.2" O.C.T3
PRE-ENGINEERED/PRE-MANUFACTURED TRUSSES AT 19.2" O.C.T4
S-101
ROOF
FRAMING
PLAN
9 5 W E S T 1 0 0 S O U T H , S T E . 1 1 5 , L O G A N , U T 8 4 3 2 1
PH: 435.227.0333 FAX: 435.227.0334
7
S-500
6
S-500
6
S-500
2
S-501
4
S-501
8
S-500
6
S-500
9
S-500
H4 (2) 1 3/4X11 7/8 MICROLAM LVL 1.9 E
11
S-500
2
3
1
1
3
S-501
22
4
5
6
7
TYP ALL EXT. CORNERS
1
8
8
1
1
4
S-502
DLB
CLR
8 8
13
S-500
N
TYP AT OPP. SIDE
1
S-502
9
9
10
10
1
10
5-1
6-2
01
9A
DD
EN
DU
M #
1
3" M
IN
.
6"
MIN
.
FINISHED
GRADE
36" M
IN
FOOTING AND
REINF. PER PLAN
#4 VERT. AT 18" O.C.
EACH FACE. STD.
HOOK AT END
1'
(3) EQUALLY SPACED
#4 HORIZ. EACH FACE
ARCHITECTURAL
VENEER
P.T SILL PLATE
SLAB PER PLAN
ANCHOR BOLTS PER PLAN
WALL PER PLAN
NOTE: AT ROSTRUM AREA,
TOP OF FOUNDATION WALL
2" ABOVE TOP OF SLAB
3" M
IN
.
P.T SILL PLATE
6"
MIN
.
FINISHED
GRADE
36
" M
IN
.
FOOTING AND
REINF. PER PLAN
#4 VERT. AT 18" O.C.
EACH FACE. STD.
HOOK AT END
SLAB PER PLAN
ANCHOR BOLTS PER PLAN
WALL PER PLAN
1'-1"
(3) EQUALLY SPACED
#4 HORIZ. EACH FACE
ARCHITECTURAL
VENEER
NOTE: AT ROSTRUM AREA,
TOP OF FOUNDATION WALL
2" ABOVE TOP OF SLAB
FOOTING
WIDTH PER
PLAN
P.T SILL PLATE
WALL PER PLAN. AT SIMILAR -
SEE ARCH. PLAN FOR WALL
TYPE
THICKENED SLAB
FOOTING AND REINF.
PER PLAN
SLAB AND REINF.
PER PLAN
ANCHOR BOLT PER
SHEAR WALL
SCHEDULE
ST
EP
P
ER
P
LA
N
6"
SLAB AND REINF.
PER PLAN
SLAB AND REINF.
PER PLAN
4
5
°
8"
EXTERIOR SLAB
PER PLAN
THICKENED SLAB
AT DOOR OPENING
FOOTING AND STEM
WALL PER PLAN
STD. HOOK
EXPANSION
JOINT
FOOTING AND
REINF. PER PLAN
6"
SLAB AND REINF.
PER PLAN
SLAB AND REINF.
PER PLAN
4
5
°
SLOPE RAMP PER PLAN
#4 AT 18" O.C. EACH WAY#4 AT 18" O.C. EACH WAY
MIN LAP
LENGTH
MIN LAP
LENGTH
2x10 OUTLOOKER
TYP.
2x10
(3) 16d
(2) SIMPSON LS50'S
AT CORNERS
2x FASCIA, MUST BE
8'-0" MIN CONTINUOUS
AT CORNERS
SIMPSON H1
TYP. AT
OUTLOOKERS
SIMPSON A34 AT
CORNER & EACH
TRUSS
BLOCKING
NOTE: ALL 2x10'S ARE DF #2
FOR ROOF CORNER
2x10
ROOF TRUSS
PER PLAN
SIMPSON
H2.5A AT
TRUSS
SIMPSON A34
TYP. AT ALL
OUTLOOKER
SPACES
SIMPSON
LS50'S TYP.
2x FASCIA, MUST BE
8'-0" MIN CONTINUOUS
AT CORNERS
SOLID
BLOCKING
SOLID
BLOCKING
SIMPSON
A34 TYP.
BOUNDARY NAILING
PER PLAN (2) ROWS
SHEATHING PER PLAN
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
BLOCKING PER PLAN
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
SIMPSON H1 EACH
OUTLOOKER
BOUNDARY NAILING
PER PLAN
2X10 DF#2
OUTLOOKER
SHEATHING PER PLANSIMPSON A34 AT EACH BLOCKING
DROP CHORD TRUSS
TRUSS BRACING AS
REQUIRED BY
TRUSS MANUFACTURER
PROVIDE 2x BLOCKING FOR
SHEAR WALL BOUNDARY NAILING
NUMBER FASTENER
EACH SIDE OF SPLICE
NUMBER FASTENER
EACH SIDE OF SPLICE
SPLICE TYPE
STAGGER ROWS
OF FASTENERS
END DIST.
ED
GE
D
IS
T.
OTHER DIST.
DIS
T.
BE
TW
EE
N
RO
WS
34 1 1/4
MINIMUM DISTANCES
(INCHES)
FASTENER
FASTENERS
EA. SIDE
OF SPLICE
END EDGE ROWS OTHER
DIA.
(INCH)
0.1621 16d COMMON 1/41/4 3/4
SIMPSON CMSTC12
AT RIDGE
DOUBLE TOP PLATE
WALL PER PLAN
SHEATHING AND
NAILING PER PLAN
BOUNDARY NAILING
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
SIMPSON A34 AT
EACH TRUSS BLOCK
SIMPSON H1 AT
EACH TRUSS
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
BLOCKING TO MATCH HEEL
HEIGHT
TRUSS BLOCKING
SHEAR TRANSFER
LOAD = 180 PLF
(ASD SEISMIC)
2x NAILER FOR ANCHORAGE
OF SHEET VAPOR RETARDER.
SEE DETAIL D2 SHEET A-561
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
SIMPSON H1 EACH
OUTLOOKER
BOUNDARY NAILING
PER PLAN
2X10 DF#2 OUTLOOKERSIMPSON A34 EACH
OUTLOOKER
SHEATHING PER PLAN
SIMPSON A34 AT EACH BLOCK
INSTALL BLOCKING
AT SHEATHING JOINT
SHEATHING PER PLAN
PRE-ENGINEERED,
PRE-MANUFACTURED
CAP TRUSS
PRE-ENGINEERED,
PRE-MANUFACTURED TRUSS
PROVIDE 2x6 NAILER PLATE w/
(2) SDS25300 SCREWS AT
EACH TRUSS TOP CHORD
SHEATHING TO RUN
CONTINUOUS AT CAP
TRUSS TRANSITION
SIMPSON H3 AT EACH END
OF EACH CAP TRUSS
2x NAILER FOR ANCHORAGE
OF SHEET VAPOR RETARDER.
SEE DETAIL D2 SHEET A-561
© COPYRIGHT DESIGN WEST ARCHITECTS 201854321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
MARK
:DA
TE:
DESC
RIPT
ION:
THE
CHUR
CH O
F JE
SUS
CHRI
ST O
F LA
TTER
-DAY
SAI
NTS
218036
05.08.2019
BID
SET
S
STE
TA
UTRS CT
R P
UR
F OE
G
OF UT HA
ERE
NI
NISO
L
EN
A LA
No. 295553RASMUSSENCRAIGL.
05/08/19
GARD
EN C
ITY
ASSE
MBL
Y HA
LL10
0 SO
UTH
PARA
DISE
PAR
KWAY
, GAR
DEN
CITY
, UT
1A
EXTERIOR FOUNDATION WALL
SCALE: 3/4"=1'-0"
S-500
STRUCTURAL
DETAILS
9 5 W E S T 1 0 0 S O U T H , S T E . 1 1 5 , L O G A N , U T 8 4 3 2 1
PH: 435.227.0333 FAX: 435.227.0334
1B
EXTERIOR FOUNDATION WALL
SCALE: 3/4"=1'-0"
3
INTERIOR THICKENED SLAB
SCALE: 3/4"=1'-0"
4
STEP IN SLAB
SCALE: 3/4"=1'-0"
2
THICKENED SLAB AT OPENINGS
SCALE: 3/4"=1'-0"
5
CONCRETE RAMP
SCALE: 3/4"=1'-0"
11
ROOF FRAMING AT SHEAR WALL
SCALE: 3/4"=1'-0"
9
ROOF CORNER FRAMING
SCALE: 3/4"=1'-0"
7
DROP CHORD TRUSS
SCALE: 3/4"=1'-0"
10
TOP PLATE SPLICE
SCALE: 3/4"=1'-0"
12
TENSION STRAP AT RIDGE
SCALE: 3/4"=1'-0"
6
TYP TRUSS CONNECTION
SCALE: 3/4"=1'-0"
8
OUTLOOKER AT EXT. BEARING WALL
SCALE: 3/4"=1'-0"
13
CAP TRUSS CONNECTION
SCALE: 3/4"=1'-0"
DLB
CLR
10
5-1
6-2
01
9A
DD
EN
DU
M #
1
1
1
1
1