Systems Guide

237
Grundfos System Guide Commercial Building Services Version 3 GRUNDFOS FLOW THINKING Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence Grundfos System Guide Commercial Building Services Version 3 96 47 97 83 0905 – GB www.grundfos.com

description

Systems Guide

Transcript of Systems Guide

  • Grundfos System GuideCommercial Building Services

    Version 3

    GRUNDFOS FLOW THINKINGBeing responsible is our foundation

    Thinking ahead makes it possibleInnovation is the essence

    Grundfos System

    Guide Com

    mercial Building Services Version 3

    96 4

    7 97

    83

    0905

    G

    B

    www.grundfos.com

  • Introduction

    Heating

    Air-Condition

    Pressure Boosting

    Wastewater

    Tool box

    Reference project

  • FLOW THINKING

  • FLOW THINKING

    How to use

    Drawing library

    Introduction

  • FLOW THINKING

    4 5

    How to use How to use

    The Flow THINKING is a concept especially developed for our partners in commercial building services

    FLOW THINKING means: > Focusing on the customer > Embracing system knowledge > Being a competent partner & adviser > Finding the right solutions > Providing tools for your daily work

    As an element of this concept we have developed The Gundfos System Guide

    The Grundfos System Guide is an extensive reference book, which goes through the standard systems within:

    heating air-conditioning pressure boosting wastewater

    The systems are evaluated, and the Guide gives recommendations on how to prepare the most energy-optimal, reliable and comfortable system, considering the components, which form your system.

    ContentsThe Guide contains a short review of a few theoretical areas within the mentioned systems. This is meant as a tool box, which can be used across of systems.

    Overview: Here a short overview is given of the individual systems, and which Grundfos pumps are recom-mended for use in the system.

    System description: In this paragraph the specific systems are reviewed in details. Suggestions are given of how to build up the system, so that the interaction between the components in the system is optimised with regard to comfort, safety and energy. Here we focus on how speed-regulated pumps are used in the systems.

    How to select: Here it is shown how the pump/pump system is dimensioned and selected, provided the system is built up as described under system description.

    A Guide not a collection of formulasThe System Guide is designed to be a practical tool for professionals, who already have the theoretical knowledge about systems. So the System Guide is not a completely slavish going through the structure of all systems, but it can with advantage be used as a source of inspiration or a checklist.

    The System Guide has been designed in co-operation with system specialists from all over Europe. Even though many areas have been harmonized, there may still be examples of system constructions, which traditionally are not used locally

    Always updatedGrundfos will in future continue to design and spread competences within systems. So regularly there will be supplements to the Grundfos System Guide.

  • FLOW THINKING

    4 5

    How to use How to use

    Pump

    Chiller

    Cooling Tower

    Cooling Tower

    Cooling Tower

    Buffer Tank

    Fan Coil2 pipe type

    Fan Coil4 pipe type

    Fan CoilCombination type

    Air UnitIn-let

    Air UnitOut-let

    CoolingSurface

    HeatingSurface

    Heat/CoolRecoveringSurface

  • FLOW THINKING FLOW THINKING

    M

    MMMM

    MMM

    -++

    6

    How to use

    D

    PressureraizingUnit

    DiaphragmTank

    Exspansion tankOpen Type

    Hot WaterTankWith Heat Element

    Hot WaterStorage Tank

    Boiler

    Heat excanger

    Radiator

    Termastaticradiator valve

    Throttle valve

    Isolation valve

    Non return valve

    2 way motor valve

    3 way motor valve(divide)

    3 way motor valve(collecting)

    Pressure controlvalve

    Pressure relief valve

    Safety valve

  • FLOW THINKING FLOW THINKING

    6

    How to use

    Overview

    System/products Product description

    Application System

    Main pumps Boiler shunt Mixing loops Heat surfaces Heat recovery DHW circulation DHW production

    How to select

    Main pumps Boiler shunts Mixing loops Heat surfaces Heat recovery DHW circulation DHW production

    2. Heating

  • FLOW THINKING

    8 9

    2. Heating 2. Heating

    Main pumps O X X O X O X

    Boiler shunts O O X O X

    Mixing loops O O X X

    Heat surfaces O O X X

    Heat recovery O X O X O

    DHW circulation X X X X X X

    DHW production X X X

    UPS

    Ser

    ies

    100

    UPS

    Ser

    ies

    200

    UPE

    Ser

    ies

    200

    0

    TPE

    Seri

    es 2

    00

    0

    TP TPE

    Seri

    es 1

    00

    0

    NB/

    NK

    NB

    E/N

    KE

    Seri

    es 1

    00

    0

    First choice = X Second choice = O

    Product Type

    System Type

    S /

    Overview

    Heat recovery

    Heating surfaces

    Main Pumps

    Boiler shunts

    HeatProduction

    Mixingloop

    HW HWC CW

    DWH

  • FLOW THINKING

    8 9

    2. Heating 2. Heating

    P /

    Overview

    PC User level(BMS supply)

    Sub-station level(BMS supply)

    Component level(Grundfos)

    PMU G10M t p

    External alarm X X X X X

    Remote control X X X X X

    GENIbus X X X X X

    LONbus X X X X X

    External Start/Stop X X X X X

    Analog input X X X X

    External sensor X X

    UPS

    Ser

    ies

    100

    UPS

    Ser

    ies

    200

    UPE

    Ser

    ies

    200

    0

    TPE

    Seri

    es 2

    00

    0

    TP TPE

    Seri

    es 1

    00

    0

    NB/

    NK

    NB

    E/N

    KE

    Seri

    es 1

    00

    0

    First choice = X Second choice = O

    Product Type

    Communication

  • FLOW THINKING

    10 11

    2. Heating 2. Heating

    P /

    Overview

    PMU

    PFU

    Delta Control

    PCU

    Management unit for up to 8 pumps

    Preset controllerfor up to 4 pumps

    Complete controlpanel for up to

    4 pumps

    Contact unit forup to 4 pumps

    UPE Series 2000TPE Series 2000

    Inline E-pumps

    Inline E-pumpsEndsuction E pumpsInline (Endsuction)

    PMUPFU

    2.2 kW22 kW

    2.2 kW22 kW

    22 kW630 kW (315 kW)

    Functionality Used in Max. kW connection pump size with

    p

  • FLOW THINKING

    250

    H[m]

    200

    150

    100

    807060

    50

    40

    30

    20

    15

    109876

    5

    4

    3

    22 3 4 6 8 10 15 20 30 40 60 80 100 150 200 300 400 600 1000 2000 4000 6000

    Q [m3/h]

    10 11

    2. Heating 2. Heating

    P

    Overview

    Heating Product RangeSurvey curve 50 Hz

    NB: 0,37 - 30 kWNK: 0,37 - 315 kWTP: 0,37 - 630 kW

    TPE Series 20000,37 - 7,5 kWTPE/NBE/NKE Series 10000,37 - 22 kW

    UPS Series 100UPS Series 200UPE Series 20000,06 - 2,2 kW

  • FLOW THINKING

    12 13

    2. Heating 2. Heating

    F /

    Features

    S

    Wide product range

    Wide system range

    Support tools

    I

    Easy electrical connection

    Easy access to speed regulator

    Clear user interface

    Integrated frequency converter

    No need for motor protection

    O

    Very low noise level

    High quality material

    Varible speed

    High efficiency

    Benefits

    S

    Only one supplier

    Easy selection

    Safe selection

    I

    Easy/safe installation

    Safe/quick commencement Quick commencement Safe installation

    Low installation cost

    O

    High comfort

    Long lifetime

    Energy saving

    Low operation cost

    Overview

  • FLOW THINKING

    12 13

    2. Heating 2. Heating

    UPS S 100

    T D Temperature -25 to +110C Pressure PN 10 (10 bar) Power range 25W to 250W Speed 1 to 3 speed Connections Unions; Flanges Port to port 130 to 250 mm Pump housing Cast iron; Bronze Stainless Steel

    C None

    M P F

    Easy electrical connection Easy access to speed regulator Very low noise level High quality material High efficiency No need for motor protection Wide product range Wide application range

    M C B

    Installer: Easy installation Only one supplier 2 years warranty End user: Maintenance free Long lifetime Low operating cost High comfort

    Overview

    UPS Series 100

    Q[m/h]

    H[m]

  • FLOW THINKING

    14 15

    2. Heating 2. Heating

    UPS S 200

    T D

    Temperature -10 to +120C Pressure PN 10 (10 bar) Power range 250W to 2200W Speed 3 speed Connections Flanges (PN6/10) Port to port 220 to 450 mm Pump housing Cast iron; Bronze

    C Alarm module (accessories) GENIbus module (accessories)

    M P F Easy electrical connection Water lubricated bearings Very low noise level High quality material High efficiency Motor protection module Wide product range Wide application range

    M C B

    Installer: Easy installation Only one supplier Easy to start-up End user: Long lifetime Maintenance free Low operating cost High comfort

    Overview

    UPS Series 200

    Q[m/h]

    H[m]

  • FLOW THINKING

    14 15

    2. Heating 2. Heating

    UPE S 2000

    T D

    Temperature +2 to +95C Pressure PN 10 (10 bar) Power range 60W to 2200W Speed Variable speed Connections Unions; Flanges Port to port 130 to 450 mm Pump housing Cast iron; Bronze

    C

    Alarm relay Digital input Analog input GENIbus

    M P F

    Easy electrical connection Water lubricated bearings Very low noise level High quality material High efficiency Integrated frequency converter No need for motor protection Wide product range Communication

    M C B

    Installer: Easy installation Only one supplier Easy start-up End user: Long lifetime Very low operating cost Very high comfort Access to operation data

    Overview

    UPE Series 2000

    Q[m/h]

    H[m]

  • FLOW THINKING

    16 17

    2. Heating 2. Heating

    TPE S 2000

    T D

    Temperature -25 to +140C Pressure PN 16 (16 bar) Power range 1.1kW to 7.5kW Speed Variable speed Connections Flanges Port to port 280 to 450 mm Pump housing Cast iron

    C

    Alarm relay Digital input Analog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter Integrated diff. pressure sensor High quality material High efficiency No need for motor protection Wide product range Cataphoresis treated Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    Overview

    TPE Series 2000

    Q[m/h]

    H[m]

  • FLOW THINKING

    16 17

    2. Heating 2. Heating

    TP

    T D

    Temperature -25 to +150C Pressure PN 10/16/25 Power range 0.37kW to 630kW Speed 1 speed Connections Flanges Port to port 280 to 1400 mm Pump housing Cast iron; Bronze

    C

    None

    M P F

    High quality material High efficiency Wide product range Twin head pumps Wide application range Standard motor Cataphoresis treated

    M C B

    Installer: Easy installation Only one supplier End user: Long lifetime Low operating cost High comfort

    Overview

    TP

    Q[m/h]

    H[m]

  • FLOW THINKING

    18 19

    2. Heating 2. Heating

    TPE S 1000

    T D

    Temperature -25 to + 140C Pressure PN 16 (16 bar) Power range 1.1kW to 22kW Speed Variable speed Connections Flanges Port to port 280 to 450 mm Pump housing Cast iron

    C

    Alarm relay Digital input Analog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter High quality material High efficiency No need for motor protection Wide product range Cataphoresis treated Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    Overview

    TPE Series 1000

    Q[m/h]

    H[m]

  • FLOW THINKING

    18 19

    2. Heating 2. Heating

    NB/NK

    T D

    Temperature -10 to + 140C Pressure PN 16 ( 16 bar ) Power range 0.37 KW to 315 KW Speed 1 speed Connections DN 32 - 300 Pump housing Cast iron, Bronze

    C

    None

    M P F

    Flexibility High quality material High efficiency Wide product range Spacer coupling Wide system range Standard motor

    M C B

    Installer: Easy installation Only one supplier End user: Long lifetime Low operating cost

    Overview

    NB/NK

    Q[m/h]

    H[m]

  • FLOW THINKING

    20 21

    2. Heating 2. Heating

    NBE/NKE S 1000

    T D

    Temperature -10 to +140C Pressure PN 16 ( 16 bar ) Power range 0.75 KW to 7.5 KW Speed Variable Connections DN 32 - 125 Pump housing Cast iron

    C

    Alarm relay Digital input Analog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter High quality material High efficiency No need for motor protection Wide product range Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    Overview

    NBE/NKE Series 1000

    Q[m/h]

    H[m]

  • FLOW THINKING

    20 21

    2. Heating 2. Heating

    M

    F

    Due to variation in the heat demand and the flow, we recommend to use speed controlled pumps in parallel as main pumps. Maximum 3 pumps plus 1 as standby pump. By speed controlling all the pumps it is possible to obtain the maximum energy saving.

    D

    Flow per Pump Pump type m3/h

    0 - 60 UPE Series 2000

    60 - 100 TPE Series 2000

    100 - 300 TPE Series 1000, NBE/NKE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    It is important to check the efficiency at the duty point where the system has a high number of operating hours.

    I

    Using UPE and TPE Series 2000, no external pres-sure sensor and motor protection is necessary, only a PMU is needed for parallel operation. It is possible to have proportional pressure without a sensor placed in the system.For pumps above 22 kW both external sensor, motor protection and a pump control unit is necessary.

    System description

    Flow variation in areference year (8760 hours)

    Flow%

    Hours/year

    Duty point with a high numberof operating hours

    Flow

    When pumps are installed in parallelnon-return valves must be installed

  • FLOW THINKING

    22 23

    2. Heating 2. Heating

    B

    F

    The primary task of the boiler shunt pump is to ensure that the temperature differences between top and bottom of the boiler are not too big, big temperature differences cause tension in the mate-rial and thus reduce the life of the boiler.For certain types of fuel there is a risk of corrosion at too low temperatures at the bottom of the boiler. Maximum safety is ensured when using a control-led pump, and the energy saving is optimal.

    D

    Flow per Pump Pump type m3/h

    0 - 300 TPE Series 1000

    150 - 1000 NK + External freq. converter

    150 - 3000 TP + External freq. converter

    Often the pumps have high flow and low head, and then it is important to check the NPSH value of the pump.

    I

    TPE Series 1000: The pumps have an integrated frequency converter and a motor protection. A temperature transmitter with an output signal of 0/5-10V or 0/4-20 mA should be used. R100 remote control is used for start-up and later reading out of operating data.TP/NK: The mentioned pump types require an exter-nal frequency converter and an external regulator.

    System description

    tF90C

    tR50C

    t = 40C

    Head m

    NPSHm

    Max. flow

    Flow

    Flow

    Placing of temperature sensor

    t

  • FLOW THINKING

    22 23

    2. Heating 2. Heating

    M

    F

    Due to variation in use and heat demand in differ-ent parts of the building, the system is divided into zones controlled by a mixing loop. The flow temperature will be lower than in the mains sup-ply, which will result in a higher flow in the zone than in the mains supply. This will help obtain a better hydraul-ic balance in the total system. Speed controlling the pump makes it possible to obtain the maximum energy saving.

    D

    Flow per Pump Pump type m3/h

    5 - 60 UPE Series 2000

    60 - 100 TPE Series 2000

    When using a two-way valve, the pressure lost in the valve will be managed by the main pump. When using a three-way valve, the pump in the mixing loop also has to manage the pressure lost in the valve.

    I

    Using UPE and TPE Series 2000 there is no need for an external pressure sensor and a motor protection. It is possible to have proportional pressure without a sensor placed in the system.

    System description

    Q = 4.3 m3/h

    tF = 60C

    tF = 80C

    Q = 2.15 m3/h

    tF = 40C

    tF = 40C

    = 100kW

    MM

    ppump

    Mixing loop with 2 way valve

    M

    ppump

    Mixing loop with 2 way valve

  • FLOW THINKING

    24 25

    2. Heating 2. Heating

    H

    F

    A heating surface heats the air which through the ventilation system is blown into the building. The temperature in the heating surface depends on the outdoor temperature and is controlled by way of the ventilation systems control unit. The system has a constant flow and variable temperature, where it is important that the flow is correct. Normally the flow is adjusted by a regulating valve, it may also be an advantage to use an adjustable pump (E-pump).

    D

    Flow per Pump Pump type m3/h

    0 - 60 UPE Series 2000

    60 - 300 TPE Series 1000

    I

    UPE Series 2000:The pump is set to constant curve and then adjusted to the correct flow. TPE Series 1000:The pump is set at uncontrolled mode, and then adjusted to the correct flow.This is easily done with remote control R100.

    System description

    Flow adjustedwith a valve

    Flow adjustedwith a pump

    M

    M

    Head

    Power

    Max. speed

    Flow adjustedwith a valve

    Correct flow

    Flow

    p valve

    Head

    Power

    Max. speed

    Correct flow

    Flow

    Reduced speed

    Flow adjustedwith a pump

  • FLOW THINKING

    24 25

    2. Heating 2. Heating

    H

    F

    The purpose of the system is to recover the heat of the outlet air. The primary task of the pump is to ensure an optimal flow between the heating surfaces. The pump/valve is controlled from the general control unit of the ventilation system. The saving potential of using a controlled pump in stead of a three-way valve to reach the correct temperature is very big.

    D

    Flow per Pump Pump type m3/h

    0 - 300 TPE Series 1000

    The total efficiency of the system depends onwhether the circulated quantity of water is correct. If there is a risk of temperatures below 0C in the air intake of the system, the system must be applied with an antifreeze agent. If a 37% glocyl mixture is used, this will protect against frost down to 20C.

    I

    The pump is set at uncontrolled, and the signal from the central control unit is connected to the analog entry (0/5-10v or 0/4-20 mA). R100 remote control must be used in connection with setting up the pump.

    System description

    M

    3 way valve controlled system

    Pump controlled system

    System efficiency = t2 - t1t3 - t1

    Air out Air in

    t1

    t2t3

  • FLOW THINKING

    26 27

    2. Heating 2. Heating

    H

    F

    The purpose of the system is domestic hot water heating. The function of the circulator pump is to ensure that hot water is always available as close to the tapping point as possible, in order to reduce waste of water and increase the comfort. In certain installations (loading circuits) the pump can at the same time ensure the circulation between the inverter and the storage tank.

    D

    Flow per Pump Pump type m3/h Uncontrolled Controlled

    0.5 - 6 UPS Series 100 TPE Series 1000

    6 - 60 UPS Series 200 TPE Series 1000

    60 - 300 TP TPE Series 1000

    Normally uncontrolled pumps are used, because usually the flow variation is only small. It may be advantageous to use controlled pumps for adjust-ment of the flow when starting up the system, though.In large systems it will also be an advantage to use a temperature controlled pump.

    I

    Because of the contents of gasses in water, it is important that this gas is not gathered in the pump, thus reducing the lifetime of the pump. Therefore it is always recommended to install the pump with upward flow direction, and minimum horizontal flow direction.

    System description

    Cold water

    Hotwater

    Hotwater

    circulation

    Temperaturetransmitter

    Cold water

    Hotwater

    Hotwater

    circulation

    Cold water

    Air-vent

  • FLOW THINKING

    26 27

    2. Heating 2. Heating

    H

    F

    To make the system as flexible as possible, the heating and storage of the domestic hot water are divided into two units, one for heating and one for accumulation of the hot water. The construction of the systems among others depends on the kind of heat exchanger (charger) used. The pump is con-trolled by the temperature in the storage tank, either ON/OFF or variable speed.

    D

    Flow per Pump Pump type m3/h Uncontrolled Controlled

    0.5 - 6 UPS Series 100 TPE Series 1000

    6 - 60 UPS Series 200 TPE Series 1000

    60 - 300 TP TPE Series 1000

    If one pump is used for both accumulation and circulation, the minimum flow of the pump must be the same as the required flow for circulation.

    I

    If the pump is installed on the hot side of the exchanger, it must be ensured that the temperature does not exceed required max. temperature, as this may cause lime depositing in the pump. Because of the contents of gasses in water, it is important that this gas is not gathered in the pump, thus reducing the lifetime of the pump. Therefore it is always recommended to install the pump with upward flow direction, and minimum horizontal flow direction.

    System description

    Recirculation pump

    Charge pump

    Hot waterstorage tank

    M

    HWC

    CW

    HW

    Recirculation andcharge pump

    M

    Hot waterstorage tank

    HWC

    CW

    HW

    Chargeexchanger

    Recirculationexchanger

    Charge pump Recirculation pump

    Hot waterstorage tank

    HW

    CW

    HWC

    M M

  • FLOW THINKING

    28 29

    2. Heating 2. Heating

    M

    Q

    Step 1: Define total m2 heated area ex. 20,000 m2

    Step 2: Define heat loss per m2 ex. 50 W/m2 (total heat loss 1,000 kW) Step 3: Define t of the system ex. t 20C (flow 43 m3/h) Step 4: Define p of the pump ex. 10 m Step 5: Find the exact pump in the data booklet ex. TPE 80-180 3.0 kW

    How to select

    100 W/m2 = Old building (low insulation)

    75 W/m2 = Old building (medium insulation)

    50 W/m2 = New building (high insulation)

    t = 40C ex. (tF 90C - tR 50C)t = 30C ex. (tF 80C - tR 50C)t = 20C ex. (tF 70C - tR 50C)t = 10C ex. (tF 60C - tR 50C)

    W/m2 = 100W/m2 = 75W/m2 = 50

    t = 40Ct = 30C

    t = 20C

    t = 10C

    = 1 pump + 1 stand-by pump (wet runner)

    = 1 pump + 1 stand-by pump (dry runner)

    = 2 pumps + 1 stand-by pump (dry runner)

    = 3 pumps + 1 stand-by pump (dry runner)

    Hea

    ting

    dem

    and

    in [k

    W]

    Hea

    t in

    [m]

    Heated area in [m2]

    Flow in [m3/h]

  • FLOW THINKING

    28 29

    2. Heating 2. Heating

    M

    Q

    Step 1: Define total m2 heated area Step 2: Define heat loss per m2

    Step 3: Define t of the system Step 4: Define p of the pump Step 5: Find the exact pump in the data booklet

    How to select

    100 W/m2 = Old building (low insulation)

    75 W/m2 = Old building (medium insulation)

    50 W/m2 = New building (high insulation)

    t = 40C ex. (tF 90C - tR 50C)t = 30C ex. (tF 80C - tR 50C)t = 20C ex. (tF 70C - tR 50C)t = 10C ex. (tF 60C - tR 50C)

    W/m2 = 100W/m2 = 75W/m2 = 50

    t = 40Ct = 30C

    t = 20C

    t = 10C

    = 1 pump + 1 stand-by pump (wet runner)

    = 1 pump + 1 stand-by pump (dry runner)

    = 2 pumps + 1 stand-by pump (dry runner)

    = 3 pumps + 1 stand-by pump (dry runner)

    Hea

    ting

    dem

    and

    in [k

    W]

    Hea

    t in

    [m]

    Heated area in [m2]

    Flow in [m3/h]

  • FLOW THINKING

    30 31

    2. Heating 2. Heating

    M

    S 1:

    Calculate the flow required in the system: x 0.86 (tF-tR) = Heat demand in [kW] Q = Volume flow rate in [m3/h] tF = Dimensioning flow pipe temperature in [C] tR = Dimensioning return-pipe temperature in [C] 0.86 is the conversion factor (kcal/h to kW)

    Calculate the heat required in the system:The value to the end farthest off or the high value of the system is the basis for pump dimensioning.

    S 2:

    Lay down the flow variation of the system: Ex. of variation in the flow: 100% flow for 5% hours

    75% flow for 10% hours

    50% flow for 35% hours

    25% flow for 50% hours

    S 3:

    Lay down the operating hours per year: System with domestic hot water production:8,760 hours/year.System without domestic hot water production, depending on the location: ex. 5,500 hours/year.

    S 4:

    Define if it is profitable to speed control the pump depending on variation in flow and duration of variation.

    How to select

    = QHead[m]

    Max.duty point

    Systemcharacteristics

    Requiredhead

    Flow required Flow [m3/h]

    = Variation in flow= Calculation profile

    Operating hours in %

    Flow in %

    %

    Profitable to speedcontrol the pump

    Unprofitable to speedcontrol the pump

    Max

    . var

    iati

    on in

    flow

    Duration of variation in flow%

  • FLOW THINKING

    30 31

    2. Heating 2. Heating

    M

    S 5:

    Define number of pumps in the system

    Systems with constant flow:Pumps in operation and stand-by pumps.When there is no variation in the flow, 1 pump in operation and 1 stand-by pump are probably the solution. Here, the efficiency in the duty point is very important.

    Systems with variable flow:

    Having variation, it can be profitable to choose more than 1 pump together with 1 stand-by pump. Here it is also important to check the efficiency in the duty point where there are a lot of operating hours.

    S 6:

    Where to place the transmitter:

    Define where to place the differential pressure transmitter. For smaller systems it is possible to use pumps (pumps up to 7.5kW) with integrated transmitter and controller; the pressure loss compensation will be managed by the built-in controller.For larger systems the differential pressure trans-mitter can be placed either over the pump or at a critical point in the system.

    How to select

    Head in[m]

    Flow in [m/h]

    Duty point with a lot of operating hours

    p pump

    p system

    Flow

  • FLOW THINKING

    32 33

    2. Heating 2. HeatingHow to select

    M .

    S D:

    80,000 m2 old renovated building 75 W/m2

    Heat demand: (80,0000 m2 x 0.075 W/m2) 6,000 kW Flow temperature (tF): 90C Return temperature (tR): 50C t : (90C 50C) 40C Flow ((6,000x0.86)/40) 129 m3/h p at max. flow (129 m3/h): 18 m

    S:

    1 constant speed pump + 1 stand-by pump Selected pump: 2 x NK 80-250/259 Motor size: 2 x 11.0 kW

    Variation in flow:

    100% flow for 5% hours 75% flow for 10% hours

    50% flow for 35% hours

    25% flow for 50% hours

    Operating hours per year: 8,760 hours

    E :

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 438 9.8 4,292

    75 876 8.3 7,270

    50 3,066 6.6 20,235

    25 4,380 4.8 21,024

    Total 8,760 Total 52,821

    Heating production

    Distribution net

    tF

    tR

    poutlet pinlet pinlet poutlet =p pump system

    Q[m/h]

    H[m]

    NK

  • FLOW THINKING

    32 33

    2. Heating 2. Heating

    M .

    How to select

    S D:

    80,000 m2 old renovated building 75 W/m2

    Heat demand: (80,0000 m2 x 0.075 W/m2) 6,000 kW Flow temperature (tF): 90C Return temperature (tR): 50C t : (90C 50C) 40C Flow ((6,000 x 0.86)/40) 129 m3/h p at max. flow (129 m3/h): 18 m

    S:

    2 speed controlled pumps + 1 stand-by pump Selected pump: 3 x TPE 80-240 Motor size: 3 x 5.5 kW

    Variation in flow:

    100% flow for 5% hours 75% flow for 10% hours

    50% flow for 35% hours

    25% flow for 50% hours

    E :

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 438 10.3 4,551

    75 876 5.9 5,168

    50 3,066 3.62 11,099

    25 4,380 1.31 5,738

    Total 8,760 Total 26,516

    Heat production

    Distribution net

    tF

    tR

    poutlet pinlet pinlet poutlet =p pump system

    Flow in [m/h]

    Head in[m]

  • FLOW THINKING

    34 35

    2. Heating 2. Heating

    M

    S 1:

    1 constant speed pump + 1 stand-by pump Selected pump: 2 x NK 80-250/259 Motor size: 2 x 11.0 kW Control panel: Motor protection Change-over switch Access to system data: No Price index: 100 (4,500 EURO)

    S 2:

    2 speed controlled pumps + 1 stand-by pump Selected pump: 3 x TPE 80-240 Motor size: 3 x 5.5kW Controller: PMU Access to system data: Yes Price index: 162 (7,290 EURO)

    C/:

    The comparison of the two systems makes it clear that the large savings are gained by reduced flow. Already at a flow of 75% the savings are 29%. In addition to the energy saving there is also an in-crease in comfort, due to the reduced pressure and thereby reduced noise in the system valves.Depending on the energy price the pay-back time is very short for the extra costs of the speed controlled pump system. At a cost of 0.1 EURO per kWh, the pay-back time is approximately 1.1 years.

    How to select

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 438 9.8 4,292

    75 876 8.3 7,270

    50 3,066 6.6 20,235

    25 4,380 4.8 21,024

    Total Total 8,760 52,821

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 438 10.3 4,551

    75 876 5.9 5,168

    50 3,066 3.62 11,099

    25 4,380 1.31 5,738

    Total Total 8,760 26,516

    Flow Sys.1 Sys. 2 Savings Savings [%] [kWh] [kWh] [kWh] % 100 4,292 4,551 -259 -6

    75 7,270 5,168 2,102 29

    50 20,235 11,099 9,136 45

    25 21,024 5,738 15,286 72

    Total 52,821 26,516 26,305 50

  • FLOW THINKING

    34 35

    2. Heating 2. Heating

    B .

    How to select

    S D:

    Boiler effect: 2,000 kW Flow temperature (tF): 90C Return temperature (tR): 50C Return temperature (tRB): 70C Flow (QSH): 86 m3/h p with max. flow (129 m3/h): 8 m

    S:

    1 Constant speed pumpSelected pump: 1 x CLM 125-211Motor size: 1 x 4,0 kW

    Variation in flow:

    100% flow for 33% hours 75% flow for 33% hours

    50% flow for 33% hours

    E : Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 1,833 3.7 6,782

    75 1,833 3.7 6,782

    75 1,833 3.7 6,782

    Total 5,500 Total 20,346

    tF90C

    tR50C

    tRB70C

    H

    Q

    Max. loadmain system Min. load

    main system

    pvalve

  • FLOW THINKING

    36 37

    2. Heating 2. Heating

    B .

    How to select

    S D:

    Boiler effect: 2,000 kW Flow temperature (tF): 90C Return temperature (tR): 50C Return temperature (tRB): 70C Flow (QSH): 86 m3/h p with max. flow (129 m3/h): 8 m

    S:

    1 Constant speed pumpSelected pump: 1 x CLME 125-211Motor size: 1 x 4,0 kW

    Variation in flow:

    100% flow for 33% hours 75% flow for 33% hours

    50% flow for 33% hours

    E : Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 1,833 3.5 6,415

    75 1,833 1.3 2,383

    50 1,833 0.4 773

    Total 5,500 Total 9,571

    tF90C

    tR50C

    tRB70C

    H

    Q

    Max. loadmain system Min. load

    main system

    t

  • FLOW THINKING

    36 37

    2. Heating 2. Heating

    M .

    S D:

    Example with two-way valve: Heat demand in the zone: 60 kW Flow temperature main system (tF): 90C Flow temperature in the zone (tFZ): 70C Return temperature in the zone (tRZ): 40C Flow ((60 x 0.86)/30): 1.72 m3/h p zone at max. flow (1.72 m3/h): (radiators+RTV+pipes/valves)(0.2+0.8+1.0): 2 m

    S:

    1 speed controlled pump Selected pump: UPE 25-40 Motor size: 1 x 60 W Operating hours per year: 5,500

    With an MC module it is possible to have an alarm from the pump.With an MB module it is possible to have GENIbus communication, + G10 (gateway) being LONWORK.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh] 100 275 54 14.9

    75 550 44 24.2

    50 1,925 36 69.3

    25 2,750 29 79.8

    Total 5,500 Total 118.2

    How to select

    Q zone:1.72 m/h

    tFZ 70C

    tRZ 50C

    p pump:2.0 m

    tF 90C

    Q main1.03 m/h

    M

    Alarm: outputMin./Max. curve: inputStop/start: inputAnalog 0-10V: input

    Min./Max. curve: inputStop/start: inputGENIbus: in/output+ G10 LONWORK: in/output

    MB40/60

    MB40/60

    Powersupply

    Powersupply

    G10

  • FLOW THINKING

    38 39

    2. Heating 2. Heating

    M .

    S D:

    Example with three-way valve: Heat demand in the zone: 60 kW Flow temperature main system (tF): 90C Flow temperature in the zone (tFZ): 70C Return temperature in the zone (tRZ): 40C Flow ((60 x 0.86)/30): 1.72 m3/h p zone at max. flow (1.72 m3/h): three-way valve: 2.0 m (radiators+RTV+pipes/valves)(0.2+0.8+1.0): 2.0 m Total p: 4.0 m

    S:

    1 speed controlled pump Selected pump: UPE 25-80 Motor size: 1 x 250 W Operating hours per year: 5,500

    With an MC module it is possible to have an alarm from the pump.With an MB module it is possible to have GENIbus communication, + G10 (gateway) being LONWORK.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 275 130 35.8

    75 550 107 58.9

    50 1,925 89 171.3

    25 2,750 78 214.5

    Total 5,500 Total 480.5

    How to select

    Q zone:1.72 m/h

    tFZ 70C

    tRZ 50C

    p pump:4.0 m

    tF 90C

    Q main1.03 m/h

    M

    Alarm: outputMin./Max. curve: inputStop/start: inputAnalog 0-10V: input

    Min./Max. curve: inputStop/start: inputGENIbus: in/output+ G10 LONWORK: in/output

    MB80

    MB80

    Powersupply

    Powersupply

    G10

  • FLOW THINKING

    38 39

    2. Heating 2. Heating

    H .

    S D:

    Example with constant speed pump: Heat demand: 100 kW Flow temperature main system (tF): 75C Flow temperature (tFS): 50C Return temperature (tR): 25C Flow ((100 x 0.86)/25): 3.4 m3/h p at max. flow (3.4 m3/h): (surface+pipes/valves)(1.5+0.8+1.0): 3.3 m

    S:

    1 constant speed pump Selected pump: UPS 25-80 Motor size: 1 x 250 W Operating hours per year: 5,500

    The pump is set at speed 3, and the flow is adjusted to calculated flow. At speed 3 and a flow of 3.4 m3/h the head is 5.8 m. The pressure loss over the adjustment valve has to be (5.8 3.3) = 2.5 m more than at fully open valve.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 5,500 221 1,216

    Total 5,500 Total 1,216

    How to select

    Air flow Adjustmentvalve

    Constantspeed pump

    tR

    tFS tF

    M

    Head

    Flow

    Adjustmentvalve

    5.8 m

    3.3 m

    3.4 m/h

  • FLOW THINKING

    40 41

    2. Heating 2. Heating

    H .

    S D:

    Example with variable speed pump: Heat demand: 100 kW Flow temperature main system (tF): 75C Flow temperature (tFS): 50C Return temperature (tR): 25C Flow ((100 x 0.86)/25): 3.4 m3/h p at max. flow (3.4 m3/h): (surface+pipes/valves)(1.5+0.8): 2.3 m

    S:

    1 constant speed pump Selected pump: UPE 25-80 Motor size: 1 x 250 W Operating hours per year: 5,500

    The pump is set at constant curve and adjusted to the right flow. The total head is lower due to no adjustment valve in the system. At the same time it is possible to communicate with the pump.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 5,500 140 770

    Total 5,500 Total 770

    S:

    The energy saving compared to an installationwith an adjustment valve:(1,216-770) = 446 kWh = 27%Moreover, an adjustment valve is not required(costs saved).

    How to select

    Air flow

    Variablespeed pump

    tR

    tFS tF

    M

    Head

    Flow

    Max. curve

    2.3 m

    3.4 m/h

    Reduced speed

  • FLOW THINKING

    40 41

    2. Heating 2. Heating

    H .

    S D:

    Example with three-way valve: Heat transfer: 200 kW Temperature air (t1): - 12C Temperature air (t2): +10C Temperature air (t3): +22C Temperature liquid (tF): +12C Temperature liquid (tR): + 0C t liquid system (12-0): +12C Anti-freeze protection down to: -20C Calculation of flow: Flow water((200 x 0.86)/12): 14.3 m3/h Compensation factor for anti-freeze: 1.14 (The specific heat drops by 20%) (Density increase 6%) Flow with anti-freeze liquid (14.3x1.14): 16.3 m3/h p system at max. flow three-way valve: 3.3 m (heat surface+pipes/valves)(2.3+1.0): 3.3 m Compensation factor for anti-freeze: 1.3 Total p: ((3.3+3.3) x 1.3) 8.6 m

    S:

    1 constant speed pump Selected pump: TP 65-120 Motor size: 1 x 1.1 kW Operating hours per year: 5,500

    Due to higher density the power consumption P2 will increase from 675 W to 715 W (P1=890W). To prevent overload of the motor it is important to check the max. P2 value of the motor. In this case the value is 1100 W, which gives a good safety margin. A dry-runner has been selected to avoid problems with condensation in the motor, and the shaft seal is of the RUUE type due to the liquid with glycol.

    How to select

    Air flowoutlet

    Air flowinlet

    t3

    tR

    tF

    t1

    t2M

    Freezing pointPropylene glycol

    Ethylene glycol

    Glycol

    Glycol

    Ethylene glycol 0C 10C 0C 10CPropylene glycol

    Density kg/m3

    C

  • FLOW THINKING

    42 43

    2. Heating 2. Heating

    H .

    S D:

    Example speed controlled pump: Heat transfer: 200 kW Temperature air (t1): -12C Temperature air (t2): +10C Temperature air (t3): +22C Temperature liquid (tF): +12C Temperature liquid (tR): + 0C t liquid system (12-0): +12C Anti-freeze protection down to: -20C Calculation of flow: Flow water((200 x 0.86)/12): 14.3 m3/h Compensation factor for anti-freeze: 1.14 (The specific heat drops by 20%) (Density increase 6%) Flow with anti-freeze liquid (14.3 x 1.14): 16.3 m3/h p system at max. flow (heat surface+pipes/valves)(2.3+1.0): 3.3 m Compensation factor for anti-freeze: 1.3 Total p: (3.3 x 1.3) 4.3 m

    S:

    1 speed contolled pump Selected pump: TPE 65-60 Motor size: 1 x 0.55 kW Operating hours per year: 5,500

    The pump is set at uncontrolled mode, and via the 0-10V analog input it is controlled by the air handling unit controller.Due to higher density the power consumption P2 will increase from 360 W to 385 W (P1=511W). To prevent overload of the motor it is important to check the max. P2 value of the motor. In this case the value is 550 W, which gives a good safety margin. A dry-runner has been selected to avoid problems with condensation in the motor, and the shaft seal is of the RUUE type due to the liquid with glycol.

    How to select

    Air flowoutlet

    Air flowinlet

    t3

    tR

    tF

    t1

    t2

    Freezing pointPropylene glycol

    Ethylene glycol

    Glycol

    Glycol

    Ethylene glycol 0C 10C 0C 10CPropylene glycol

    Density kg/m3

    C

  • FLOW THINKING

    42 43

    2. Heating 2. Heating

    H .

    S 1:

    1 constant speed pump Selected pump: TP 65-120 Motor size: 1 x 1.1 kW Operating hours per year: 5,500 Three-way valve: Yes Access to system data: No Price index: 100 (570 EURO)

    S 2:

    1 speed controlled pump Selected pump: TPE 65-60 Motor size: 1 x 0.55 kW Three-way valve: No Operating hours per year: 5,500 Access to system data: Yes Price index: 150 (860 EURO)

    C/:

    Using a speed controlled pump, the total pressure loss in the system drops dramatically, and it is pos-sible to get a variable flow in the system depending on the actual situation. When the flow is readjusted the pump will follow the system characteristics giving high savings. On top of the energy savings there is also a saving in investment and installation costs, as there is no need for the motor valve and the by-pass.Depending on the energy price the pay-back time is very short for the extra costs of the speed controlled pump system. At a cost of 0.1 EURO per kWh the pay-back time is 1 year.

    How to select

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 5,500 890 4,895

    Total Total 5,500 4,895

    Flow Hours Effect Energy [%] [h] [kW] [kWh]

    100 2,200 511 1,124

    75 2,200 308 678

    50 1,100 173 190

    Total Total 5,500 1,992

    Flow Sys.1 Sys. 2 Saving Saving [%] [kWh] [kWh] [kWh] % 100 4,895 1,124

    75 678

    50 190

    Total 4,895 1,992 2,903 59

  • FLOW THINKING

    44 45

    2. Heating 2. Heating

    H .

    S D:

    Example with fixed speed pump: Hotel with 320 rooms. Circulation loss per room: 200 W Total loss: 64 kW Hot water temperature (tH): 55C Circulation return temperature (tC): 45C t system: 10C Flow ((64 x 0.86)/10): 5.5 m3/h p at max. flow (5.5 m3/h): (tank+pipes/valves)(1.0+2.5+3.0): 7.0 m

    S:

    1 constant speed pump Selected pump: UPS 32-120 FB Motor size: 1 x 400 W Operating hours per year: 8,760

    With a relay module built into the terminal box, there is no need for external motor protection, and at the same time the pump will have an alarm relay.Due to risk of corrosion the pump housing is made of bronze.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 2,920 295 861

    80 2,920 277 809

    60 2,920 253 739

    Total 8,760 Total 2,409

    How to select

    55C

    45C

    5.5 m/h

    7.0 m

    Hotwater

    Hotwater

    circulation

    Heat loss

    Thermostaticvalve

    Cold water

    Air-vent

    Heat loss

  • FLOW THINKING

    44 45

    2. Heating 2. Heating

    H .

    S D:

    Example with fixed speed pump: Hotel with 320 rooms Circulation loss per room: 200 W Total loss: 64 kW Hot water temperature (tH): 55C Circulation return temperature (tC): 45C t system: 10C Flow ((64 x 0.86)/10): 5.5 m3/h p at max. flow (5.5 m3/h): (tank+pipes/valves)(1.0+2.5+1.0): 5.0 m

    S:

    1 speed controlled pump Selected pump: TPE 40-60 Motor size: 1 x 370 W Operating hours per year: 8,760

    There is no need for motor protection, and at the same time the pump will have an alarm relay.The pump is set at controlled mode, and the signal from the temperature transmitter is connected directly to the terminal box.

    E :

    Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 2,920 260 760

    80 2,920 185 540

    60 2,920 126 368

    Total 8,760 Total 1,668

    Savings compared to a system with thermostatic valves are 30%. Furthermore, investment and total installation costs are lower.

    How to select

    55C

    45C

    5.5 m/h

    5.0 m

    Hotwater

    Hotwater

    circulation

    Heat loss

    Temperaturetransmitter

    Cold water

    Air-vent

    Heat loss

  • FLOW THINKING FLOW THINKING

    storage

    46

    2. Heating

    H .

    S D:

    Example with fixed speed pump: Hotel with 320 rooms. Total effect (9,600/10): 800 kW Hot water temperature (tH): 55C Cold water temperature (tCO): 8C t system: 47C Flow ((800 x0.86)/47): 14.6 m/h p at max. flow (14.6 m3/h): (tank/exchanger+pipes/valves) (1.0+3.5+0.5+1.5): 6.5 m

    S:

    1 speed controlled pump Selected pump: TPE 50-120 Motor size: 1 x 1.1 kW Operating hours per year: 5,110

    There is no need for motor protection, and at the same time the pump will have an alarm relay. The pump is set at controlled mode, and the signal from the temperature transmitter is connected directly to the terminal box. The ON/OFF thermostat in the storage tank is also connected direcly to the terminal box.

    E : Flow Hours Effect Energy [%] [h] [W] [kWh]

    100 730 606 442

    80 2,190 374 819

    60 2,190 168 368

    Total 5,110 Total 1,629

    How to select

    HW

    HWC

    CWCharge pump

    Hot waterstorage tank

    Temp. transmitter

    ON/OFF thermostatM

    = Water consumption= Variation in flow charge pump= Calculation profileFlow in %

    Day-and-night

  • FLOW THINKING FLOW THINKING

    46

    2. Heating

    Overview

    System/products Product description

    System description

    Primary pumps Cooling towers Dry cooler Secondary pumps Cooling surfaces Cooling ceilings/floors Fan coils Heat recovery Pressure holding

    How to select

    Primary pumps Cooling towers Dry cooler Secondary pumps Cooling surfaces Cooling ceilings/floors Fan coils

    3. Air-conditioning

  • FLOW THINKING

    48 49

    3. Air-conditioning 3. Air-conditioning

    S/

    Overview

    Cooling tower Fan coilsCooling ceiling

    Pressureholding

    ChillerM

    Primarypump

    Heat recovery

    Cooling surface

    SecondarypumpsBuffer

    tank

    M

    M

    M

    Primary pumps - chiller pumps

    Secondary pumps - main pumps

    Cooling tower

    Dry coolers

    Cooling surfaces

    Cooling ceiling/floors

    Fan coils

    Heat recovery

    Pressure holding

    UPS

    Ser

    ies

    100

    UPS

    Ser

    ies

    200

    TPE

    Seri

    es 2

    00

    0

    TP TPE

    Seri

    es 1

    00

    0

    NB/

    NK

    NBE

    /NKE

    Ser

    ies

    1000

    HS

    CR/C

    RE

    First choice = X Second choice = O

    Product Type

    System Type

    X X X X X

    X O X O X X

    O O X O X X

    O X O X

    O O O X

    X O O

    X O O

    X X X X X

    X X

  • FLOW THINKING

    48 49

    3. Air-conditioning 3. Air-conditioning

    P /

    Overview

    PC User level(BMS supply)

    Sub-station level(BMS supply)

    Component level(Grundfos)

    PMU G10M t p

    External alarm

    Remote control

    GENIbus

    LONbus

    External Start/Stop

    Analog input

    External sensor

    UPS

    Ser

    ies

    100

    UPS

    Ser

    ies

    200

    UPE

    Ser

    ies

    200

    0

    TPE

    Seri

    es 2

    00

    0

    TP TPE

    Seri

    es 1

    00

    0

    NB/

    NK

    NB

    E/N

    KE

    Seri

    es 1

    00

    0

    HS

    CR CRE

    First choice = X Second choice = O

    Product Type

    Communication

    X X X X X X

    X X X X X X

    X X X X X X

    X X X X X X

    X X X X X X

    X X X X X

    X X X

  • FLOW THINKING

    50 51

    3. Air-conditioning 3. Air-conditioning

    P /

    Overview

    PMU

    PFU

    Delta Control

    PCU

    Management unit for up to 8 pumps

    Preset controllerfor up to 4 pumps

    Complete controlpanel for up to

    4 pumps

    Contact unit forup to 4 pumps

    TPE Series 2000

    Inline E-pumps

    In-Line E-pumpsEndsuction E-Pumps

    In-Line

    PMUPFU

    22 kW

    22 kW

    22 kW630 kW

    Functionality Used in Max. kW connection pump size with

    p

  • FLOW THINKING

    50 51

    3. Air-conditioning 3. Air-conditioning

    P

    Overview

    Air-conditioning Product RangeSurvey curve 50 Hz

    H[m]

    Q[m3/h]

    NB: 0,37 - 30 kWNK: 0,37 - 315 kWTP: 0,37 - 630 kW

    TPE Series 20000,37 - 7,5 kWTPE/NBE/NKE Series 10000,37 - 22 kW

    UPS Series 100UPS Series 200TPE Series 1000TPE Series 20000,06 - 2,2 kW

    HS: 110 - 1300 kW

  • FLOW THINKING

    52 53

    3. Air-conditioning 3. Air-conditioning

    F /

    Overview

    Features

    S

    Wide product range

    Wide system range

    Support tools

    I

    Easy electrical connection

    Easy access to speed regulator

    Clear user interface

    Integrated frequency converter

    No need for motor protection

    O

    Very low noise level

    High quality materials

    Variable speed

    High efficiency

    Benefits

    S

    Only one supplier

    Easy selection

    Safe selection

    I

    Easy/safe installation

    Safe/quick start up

    Quick start up

    Safe installation

    Lower installation cost

    O

    High comfort

    Durability and Reliability

    Energy saving and Controllability

    Low operation cost

  • FLOW THINKING

    52 53

    3. Air-conditioning 3. Air-conditioning

    Benefits

    S

    Only one supplier

    Easy selection

    Safe selection

    I

    Easy/safe installation

    Safe/quick start up

    Quick start up

    Safe installation

    Lower installation cost

    O

    High comfort

    Durability and Reliability

    Energy saving and Controllability

    Low operation cost

    UPS S 100

    Overview

    T D Temperature -25 to +110C Pressure PN 10 (10 bar) Power range 25W to 250W Speed 1 to 3 speed Connections Unions; Flanges Port to port 130 to 250 mm Pump housing Cast iron; Bronze Stainless Steel

    C No

    M P F

    Easy electrical connection Easy access to speed switch Very low noise level High quality material High efficiency No need for motor protection Wide product range Wide application range

    M C B

    Installer: Easy installation Only one supplier 2 years warranty End user: Maintenance free Durability Low operating cost High comfort

    UPS Series 100

    Q[m/h]

    H[m]

  • FLOW THINKING

    54 55

    3. Air-conditioning 3. Air-conditioning

    UPS S 200

    Overview

    T D

    Temperature -10 to +120C Pressure PN 10 (10 bar) Power range 250W to 2200W Speed 3 speed Connections Flanges (PN6/10) Port to port 220 to 450 mm Pump housing Cast iron; Bronze

    C Alarm module (accessories) GENIbus module (accessories)

    M P F Easy electrical connection Water lubricated bearings Very low noise level High quality material High efficiency Motor protection module Wide product range Wide application range

    M C B

    Installer: Easy installation Only one supplier Easy to start-up End user: Long lifetime Maintenance free Low operating cost High comfort

    UPS Series 200

    Q[m/h]

    H[m]

  • FLOW THINKING

    54 55

    3. Air-conditioning 3. Air-conditioning

    TPE S 2000

    Overview

    T D

    Temperature -25 to +140C Pressure PN 16 (16 bar) Power range 0.37kW to 7.5kW Speed Variable speed Connections Flanges Port to port 280 to 450 mm Pump housing Cast iron

    C

    Alarm relay Digital input Anlog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter Integrated diff. pressure sensor High quality material High efficiency No need for motor protection Wide product range Catephoresis coated Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    TPE Series 2000

    Q[m/h]

    H[m]

  • FLOW THINKING

    56 57

    3. Air-conditioning 3. Air-conditioning

    TP

    Overview

    T D

    Temperature -25 to +150C Pressure PN 10/16/25 Power range 0.37kW to 630kW Speed 1 speed Connections Flanges Port to port 280 to 1400 mm Pump housing Cast iron; Bronze

    C

    None

    M P F

    High quality material High efficiency Wide product range Twin head pumps Wide application range Standard motor Cataphoresis treated

    M C B

    Installer: Easy installation Only one supplier End user: Long lifetime Low operating cost High comfort

    TP

    Q[m/h]

    H[m]

  • FLOW THINKING

    56 57

    3. Air-conditioning 3. Air-conditioning

    TPE S 1000

    Overview

    T D

    Temperature -25 to + 140C Pressure PN 16 (16 bar) Power range 1.1kW to 22kW Speed Variable speed Connections Flanges Port to port 280 to 450 mm Pump housing Cast iron

    C

    Alarm relay Digital input Anlog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter High quality material High efficiency No need for motor protection Wide product range Catephoresis coated Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    TPE Series 1000

    Q[m/h]

    H[m]

  • FLOW THINKING

    58 59

    3. Air-conditioning 3. Air-conditioning

    NB/NK

    Overview

    T D

    Temperature -10 to + 140C Pressure PN 16 ( 16 bar ) Power range 0.37 KW to 315 KW Speed 50 Hz, 2 - 4 and 6 pol Connections DN 32 - 300 Pump housing Cast iron; Bronze

    C

    None

    M P F

    Flexibility High quality material High efficiency Wide product range Spacer coupling Wide application range Standard motor

    M C B

    Installer: Easy installation Only one supplier End user: Long lifetime Low operating cost

    NB/NK

    Q[m/h]

    H[m]

  • FLOW THINKING

    58 59

    3. Air-conditioning 3. Air-conditioning

    NBE/NKE

    Overview

    T D

    Temperature -10 to +140C Pressure PN 16 ( 16 bar ) Power range 0.75 KW to 7.5 KW Speed Variable Connections DN 32 - 125 Pump housing Cast iron

    C

    Alarm relay Digital input Anlog input GENIbus

    M P F

    Easy electrical connection Integrated frequency converter High quality material High efficiency No need for motor protection Wide product range Communication

    M C B

    Installer: Easy installation Easy start-up Only one supplier End user: Long lifetime Very low operating cost High comfort Access to operation data

    NBE/NKE

    Q[m/h]

    H[m]

  • FLOW THINKING

    60 61

    3. Air-conditioning 3. Air-conditioning

    HS

    Overview

    T D

    Temperature -8 to + 120C Pressure PN 16 ( 16 bar ) Power range 1.5 KW to 900 KW Speed 50 Hz, 60 Hz, 2 and 4 pol Flanges 50 - 350 mm Pump housing Cast iron

    C

    None

    M P F

    Flexibility High quality material High efficiency Wide product range Mechanical seal Spacer coupling Wide application range Standard motor Available in special material and flange options

    M C B

    Installer: Easy installation and maintenance Only one supplier End user: Long lifetime Low operating cost

    HS

    Q[m/h]

    H[m]

  • FLOW THINKING

    60 61

    3. Air-conditioning 3. Air-conditioning

    P (C )

    System description

    F

    Application with one chiller.The chiller is fitted with temperature sensors which control the temperature difference depending on the cooling load. Care must be taken to ensure that there is no freezing up of the evaporator coils. Because of this, a constant water flow is required and usually a fixed speed pump is installed.Control is normally via a regulating valve, but it may be possible to use a variable speed pump which is controlled according to the start/stop sequence of the chiller.

    D

    Flow per Pump Pump type m/h

    0 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    I

    Pump is set to uncontrolled operation and then adjusted to the correct flow. It is easily done with the remote control R100.Pump terminals for start/stop input are connected. To secure a high comfort a standby pump can be added. Controller PFU will be used for alternation between two pumps.

    Chiller pump

    Chiller pump

    Flow adjustedwith a valve

    Flow adjustedwith a pump

    Flow adjustedwith a valveHead

    Power

    Max. speed

    Flow

    Correct flow

    pvalve

    Flow adjustedwith a variable

    speed pumpHead

    Power

    Max. speed

    Flow

    Correct flow

    Reduced speed

  • FLOW THINKING

    62 63

    3. Air-conditioning 3. Air-conditioningSystem description

    F

    2 chillers are connected in parallel, each having their own pump.The chillers have their own control systems and as there is a risk of ice forming inside the evaporators, a constant water flow is recommended.The chillers run in cascade with the pumps being controlled by a start/stop signal from the chillers. On start, pumps start before the chillers start. On stop, pumps stop just after the chillers stop. With fixed speed (uncontrolled) pumps there is a varia-tion of pressure in the circuit hence a flow varia-tion. See diagram Solution: Using variable speed pumps the pressure drops through the evaporators are controlled by differential pressure sensors. In order to keep this pressure constant, pump performances are controlled, the right flow attained and energy consumption minimized.

    D

    Flow per Pump Pump type m/h

    0 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    I

    Pump is set to controlled operation (p control). It is easily done with the remote control R100.Pump terminals for start/stop input are connected. To secure a high comfort, a standby pump can be added. Controller PFU will be used for alternation between two pumps.

    p will increase when2 pumps are running

    p

    p

    Duty point when2 pumps are running

    Duty point when1 pump is running

    Uncontrolled pump

    QQ2 Q1

    H

    H2

    H1

    H

    H2

    H1

    Q2 Q

    Duty point when2 pumps are running

    Duty point when1 pump is running

    Variable speed pump

  • FLOW THINKING

    62 63

    3. Air-conditioning 3. Air-conditioning

    D

    System description

    F

    The chiller varies its performance according to the cooling demand of the system. It is recommended that the system has a constant flow, normally adjusted by an regulating valve. It may be an advan-tage to use a variable speed pump which can pro-vide a financially viable alternative.

    D

    Flow per Pump Pump type m/h

    0 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    In such systems, risk of frost will involve the use of glycol mixture.

    I

    Pump is set to uncontrolled operation and then adjusted to the correct flow. It is easily done with the remote control R100.To secure a high comfort, a standby pump can be added. Controller PFU has to be used for alternation between two pumps.

    Flow adjusted with a valve

    Flow adjusted with a pump

    Flow adjustedwith a valveHead

    Power

    Max. speed

    Flow

    Correct flow

    pvalve

    Flow adjustedwith a pumpHead

    Power

    Max. speed

    Flow

    Correct flow

    Reduced speed

    T

    T

  • FLOW THINKING

    64 65

    3. Air-conditioning 3. Air-conditioning

    C

    System description

    F

    The chiller varies its performance according to the cooling demand of the system. The cooling tower has to be controlled, in order to keep a constant return water temperature for the condenser. Usually, the cooling tower water flow is controlled by a three-way valve. The condenser has a constant flow, normally adjusted by a regulating valve.As an alternative, we recommend control of cooling tower water flow by variable speed pumps. Pumps adapt their speed according to the return water temperature measured by the sensor. The complete system has a variable flow, and therefore maximum energy savings can be obtained.

    D

    Flow per Pump Pump type m/h

    0 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    In such systems, risk of frost will involve the use of glycol mixture.

    I

    Temperature sensor is placed on the return pipe. When using TPE Series 1000, no motor protection is necessary, but for bigger systems, a pump control unit must be added for parallel operation. For big-ger systems, motor protection and pump control unit are necessary.An open cooling tower must be located on the upper point of the circuit. This in order to obtain a sufficient inlet pressure to avoid cavitation in the pump.

    Parallel operation

    T

    M

    T

    Hours/year

    Flow

    in %

    Flow

  • FLOW THINKING

    64 65

    3. Air-conditioning 3. Air-conditioning

    S (M )

    System description

    F

    Installation with 2 way valves.The demand for cooling varies greatly during the year. When the installation is equipped with two-way valves, the flow is variable. In this case we rec-ommend the use of variable speed pumps installed in parallel as main pumps. Using a PFU controller a maximum of 4 pumps can be controlled. By vary-ing the speed of all the pumps, maximum energy savings can be obtained.

    D

    Flow per Pump Pump type m/h

    5 - 100 TPE Series 2000

    100 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    It is important to check the efficiency at the duty point, where the system has a high number of operating hours.

    I

    Using TPE Series 2000, no external pressure sensor and motor protection is necessary, only a PMU is needed for parallel operation. It is possible to have proportional pressure without a sensor placed in the system.For bigger systems, both external sensor, motor protection and a pump control unit is necessary.

    Hours/year

    Flow

    in %

    Duty point with a high number of operating hours

    When pumps are installed in parallelnon-return valves must be installed

    Flow

    Buffer tank

  • FLOW THINKING

    66 67

    3. Air-conditioning 3. Air-conditioning

    S (M )

    System description

    F

    The demand for cooling varies greatly during the year. When the installation is equipped with three-way valves, the flow around the primary circuit is constant, with the flow to the room coolers being controlled by the three way valves. When the cool-ing demand is low, water coming from the chiller is by-passed and the return temperature is reduced.If the chiller is not controlled by this return tem-perature, we recommend the use of variable speed pumps mounted in parallel up to a maximum of 4 pumps.By controlling the speed of all the pumps, the return temperature is maintained, and maximum energy savings obtained.

    D

    Flow per Pump Pump type m/h

    0 - 300 TPE Series 1000

    300 - 1000 NK + External freq. converter

    300 - 3000 TP + External freq. converter

    1000 - 3500 HS + External freq. converter

    I

    Temperature sensor is placed on the return pipe after the last connecting point. Using TPE Series 1000, no motor protection is necessary, but for bigger systems, a pump control unit must be added for parallel operation. For bigger systems, motor protection and pump control unit are necessary.

    Parallel operation

    t

    M

    Hours/year

    Flow

    in %

    Flow

    M M M

  • FLOW THINKING

    66 67

    3. Air-conditioning 3. Air-conditioning

    C

    System description

    F

    A cooler battery cools the air, which is blown into the building through the air conditioning system. The temperature in the cooler battery is dependent on the outside temperature and is controlled via the air conditioning systems control unit. To ensure a good heat transmission coefficient, the system requires a constant flow. The cooler battery output is controlled by a tem-perature controller, using a mixing circuit equipped with either a two-way