Intelligent System Solutions®
PARTNERSHIPPROFILE
Armstrong InternationalNorth America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rimarmstronginternational.com
© Armstrong International, Inc.PP_Marriott-C.indd 7/11
Marriott International, Inc. Washington, D.C.
Marriott International has selected The Brain® Model DRV80 Digital Re-Circulating Valve from Armstrong International, as its corporate standard domestic hot water temperature control device for all Marriott branded hotels. The DRV80 is a fully digital recirculating valve (DRV) designed specifically to be the primary water temperature controller in a continuously pumped recirculating hot water system. The DRV80 will control within +/- 2°F (1°C) accuracy and provide flow capacities from 0-188 gpm (0-712 lpm). The Marriott Design Standard pertains to New Construction and Engineered Renovation projects.
Digital Re-Circulating Valve (DRV): For systems with a maximum simultaneous demand (MSD) ≤ 94 gpm (356 lpm) provide one (1) each The Brain® Model DRV80R-BS1-DS Digital Re-Circulating Valve from Armstrong. For systems with a MSD up to 188 gpm (712 lpm) provide two DRV80R-BS1-DS piped in parallel.
Valves shall be installed exactly as indicated in the following installation schematics:One DRV80R-BS1-DS – Installation Schematic Number S10782-1Two DRV80R-BS1-DS – Installation Schematic Number S10782-2Three DRV80R-BS1-DS - Installation Schematic Number S10782-3
DRV shall have integral remote set point adjustment capability and programmable two level high temperature alert feature, one of which shall, if enabled, both alert and cause the valve to enter “safe mode”. DRV shall have integral LED display which indicates set point temp, operating temp and self diagnostic error messages.
Each DRV80 shall be supplied with an independent hot water monitoring system (BrainScan 1 - suffix BS1) which connects directly to the valves integral serial port. HW monitoring system shall offer hot inlet, cold inlet and mixed outlet temperature readings with a web interface and shall be configurable to connect directly to a resident BAS via BACnet®, LonWorks and Modbus protocols.
Designer and installer may also consider a fully pre-piped “Digital Mixing Center” (DMC1-BS1-DS & DMC2-BS1-DS).
Thermostatic Mixing Valves: Provide two Armstrong DRV80 digital mixing valves piped in parallel for each hot water system. Installation to be piped and pressure tested and complete with isolation valves, strainers, mixed return flow indicator, check valves, thermometers, mixed outlet water sensor per manufacturer. System to have remote set point adjustment capability for connection to Building Automation System (BAS).
Please contact the following individuals if you have questions:
Customer:
Location:
Scope of Agreement:
Marriott Design Standard:
Former Design Standard:
Contacts:
System Solutions
Terry C. SmithVP Engineering and Technical ServicesMarriott International, Inc.Architecture & Construction DivisionOffice: (301) [email protected]
Larry FreySenior Corporate Director of EngineeringMarriott International, Inc.Architecture & Construction DivisionOffice: (301) [email protected]
Will GrindallDirector of Institutional MarketsArmstrong InternationalOffice: (269) [email protected]
ASSE 1017 CSA B125 and CE certified
Outlet Temperature to system +/- 2°F/1°C
4-20mA Connection Port
Hot water shutoff upon power failure
Serial data port for BAS Module (BrainScan™) connectivity. Transmits/receives all field programmable and LED display features
IRDA Port for PC programming
Field programmable Set point High temperature alert High temperature hot water shutoff Thermal disinfection
Battery back-up for emergency shutdown and default setting retention
316L Stainless steel construction
LED Display
Indicates Set point °C or °FOperating Temp °C or °F
Integral relay for auxiliary connection (alarm, solenoid)
Self diagnostics. Digital valve runs internal component check and reports out of specification performance on display
Port to port travel in 2.6 seconds
The Brain® Model: DRV80R-BS1-DS
Armstrong InternationalNorth America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim
armstronginternational.com
The Brain®
For Drawings and Piping Schematics, please visit:
armstronginternational.com/marriott
DRV80
BrainScan 1
Check Valves
Marriott International, Inc.Corporate Headquarters
Marriott DriveWashington, D.C. 20058
December 22, 2010
Mr. Will GrindallDirector of Institutional MarketsArmstrong International221 Armstrong Blvd.Three Rivers, MI 49093
Will,
Marriott International has selected The Brain DRV80 Digital Re-Circulating Valve from Armstrong International, as its corporate standard domestic hot water temperature control device for all brands of Marriott Hotels. We have selected the DRV80 since it is a fully digital recirculation valve (DRV) designed specifically to be the primary water temperature controller in a continuously pumped recirculating hot water system.
The sizing criteria, as stated in Module 15B in the January 2011 Marriott Design Standards for all brands requires one Model DRV80R-BS1-DS Digital Re-Circulating Valve from Armstrong for hot water systems with a maximum simultaneous demand (MSD) < 94 GPM. For systems with a MSD up to 188 GPM provide two DRV80R-BS1-DS valves piped in parallel. Designer and installer may also consider a fully pre-piped “Digital Mixing Center” (DMC1-BS1-DS & DMC2-BS1-DS).
The previous Marriott Design Standards called for two Armstrong DRV80 digital mixing valves piped in parallel for each hot water system. Installation to be piped and pressure tested and complete with isolation valves, strainers, mixed return flow indicator, check valves, thermometers, mixed outlet water sensor per manufacturer. System to have remote set point adjustment capability for connection to Building Automation System (BAS).
Please feel free to advise all parties involved in hot water system design and installation for all Marriott projects that, Module 15B of the 2011 Marriott Design Standard, is now in effect and should be strictly adhered to.
Marriott International Contacts:
Terry C. Smith Larry FreyVP Engineering & Technical Services Senior Corporate Director of EngineeringArchitecture & Construction Division Architecture & Construction DivisionOffice: (301) 380-2571 Office: (301) [email protected] [email protected]
Sincerely,
Terry C. SmithVP of Engineering & Technical Services
Terry C. SmithVice President Engineering and Technical ServicesMobile: (571) 277-9970Phone: (301) 380-2571Fax: (301) 644-7812E-Mail: [email protected]
NO
NC
NO
MIXED WATER
BYPASSBRAINSCAN
BS-1
HOT WATER SUPPLY
NO
NO
NOHX
COLD WATER SUPPLY
RECIRCULATION RETURN
RETURN TOHEATER
COLD WATER SUPPLY
NO
BRAINSCANBS-1
COLD WATER SUPPLYCOLD WATER SUPPLY
RECIRCULATIONRETURN
RETURN TO HEATER
NONO
NO
NO
NO
NO
NO
NO
NO
RETURN TOHEATER
NCMIXED WATER
BYPASS
HOT WATERSUPPLY
BRAINSCANBS-1
BYPASS
NC
DRV80R-BS1-DS - Installation Schematic Number S10782-1
DRV80R-BS1-DS - Installation Schematic Number S10782-2
-LEGEND-
THERMOMETER
SHOWER
SINK
120-240V PSUW/ “PLUG” STYLEDISCONNECT
STOP VALVE
ISOLATION VALVE
CHECK VALVE
RECIRCULATION PUMPIN-LINE CHECK VALVE
LOCKING BALL VALVE
STRAINER
NC-NORMALLY CLOSED
NO-NORMALLY OPEN
SWING CHECK VALVE
WAFER STYLESPRING CHECK VALVE
BALANCE VALVE
Armstrong InternationalNorth America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim
armstronginternational.com