EM powerLED 2 W / 4 W System overview

Transcript of System overview EM powerLED 2 W / 4 W - Tridonic … · System overview © 2014 Tridonic 1 / 20...

EM powerLED 2 W / 4 W System overview

© 2014 Tridonic 1 / 20

System components overview

LED light modules

TALEXXmodule STARK QLE G3 CLASSIC / TALEXXmodule STARK QLE G3 CLASSIC EM LED light modules for general and emergency lighting

Designation variants and article number Most important facts Images

CLASSIC LED light module for general lighting STARK-QLE-G3-270-1250-830-CLA, 28000384 STARK-QLE-G3-270-1250-840-CLA, 28000385 STARK-QLE-G3-270-1250-850-CLA, 28000386 STARK-QLE-G3-250-1250-830-CLA, 28000387 STARK-QLE-G3-250-1250-840-CLA, 28000388 CLASSIC EM Combined LED light modules for general and emergency lighting with integrated separate wired emergency LEDs operated by EM powerLED STARK-QLE-G3-270-1250-830-CLA-EM, 28000389 STARK-QLE-G3-270-1250-840-CLA-EM, 28000390

� Ra > 80 � MacAdam 3 � Push terminals � Self cooling � 270 x 270 x 5.5 mm Typ. luminous flux at tp 45°C: 250 mA /

7.8 W 300 mA / 9.5 W

350 mA / 11.3 W

3.000 K 1,210 lm 1,430 lm 1,670 lm

4.000 K 1,250 lm 1,480 lm 1,730 lm

5.000 K 1,300 lm 1,540 lm 1,790 lm

QLE G3 CLASSIC

QLE G3 CLASSIC EM

© 2014 Tridonic 2 / 20

TALEXXmodule STARK LLE G3 24 CLASSIC / TALEXXmodule STARK LLE G3 24 CLASSIC EM LED light modules for general and emergency lighting

Designation variants and article number Most important facts Images

CLASSIC LED light module for general lighting STARK-LLE-G3-24-280-1250-830-CLA, 28000395 STARK-LLE-G3-24-280-1250-840-CLA, 28000396 STARK-LLE-G3-24-280-1250-850-CLA, 28000397 CLASSIC EM Combined LED light module for general and emergency lighting with integrated separate wired emergency LEDs operated by EM powerLED STARK-LLE-G3-24-280-1250-830-CLA-EM, 28000402 STARK-LLE-G3-24-280-1250-840-CLA-EM, 28000403

� Ra > 80 � MacAdam 3 � Push terminals � Cooling: see database � 279,70 x 23,80 x 6,1 mm Typ. luminous flux at tp 65°C: 250 mA /

7,8 W 300 mA / 9,6 W

350 mA / 11,4 W

3.000 K 1.130 lm 1.320 lm 1.500 lm

4.000 K 1.170 lm 1.360 lm 1.550 lm

5.000 K 1.220 lm 1.420 lm 1.610 lm

LLE G3 24 CLASSIC

LLE G3 24 CLASSIC EM

© 2014 Tridonic 3 / 20

TALEXXmodule STARK CLE CLASSIC EM Combined LED light module for general and emergency lighting

Designation variants and article number Most important facts Images

CLASSIC EM Combined LED light module for general and emergency lighting with integrated separate wired emergency LEDs operated by EM powerLED STARK-CLE-220-1500-830-CLA-EM, 28000106 STARK-CLE-220-1500-840-CLA-EM, 28000107 STARK-CLE-220-1500-830-CLA-EM-SO, 28000108 STARK-CLE-220-1500-840-CLA-EM-SO, 28000109 STARK-CLE-315-4000-830-CLA-EM, 28000303 STARK-CLE-315-4000-840-CLA-EM, 28000304 STARK-CLE-315-4000-830-CLA-EM-SO, 28000305 STARK-CLE-315-4000-840-CLA-EM-SO, 28000306 STARK-CLE-360-4000-830-CLA-EM, 28000114 STARK-CLE-360-4000-840-CLA-EM, 28000115 STARK-CLE-360-4000-830-CLA-EM-SO, 28000116 STARK-CLE-360-4000-840-CLA-EM-SO, 28000117

� Ra > 80 � MacAdam 3 � Push terminals � Self cooling � 193.5 x 191 x 6.1 mm STARK-CLE-220-1500… Typ. luminous flux at tp 65°C: 350 mA /

10,3 W 470 mA / 14,3 W

500 mA / 15,3 W

3.000 K 1.300 lm 1.650 lm 1.750 lm

4.000 K 1.350 lm 1.700 lm 1.800 lm

STARK-CLE-315-4000… Typ. luminous flux at tp 65°C: 700 mA /

21,7 W 1.050 mA / 34,1 W

3.000 K 2.500 lm 3.700 lm

4.000 K 2.650 lm 3.900 lm

STARK-CLE-360-4000… Typ. luminous flux at tp 65°C: 700 mA /

21,7 W 1.050 mA / 34,1 W

3.000 K 2.500 lm 3.550 lm

4.000 K 2.650 lm 3.750 lm

STARK-CLE-220-EM

STARK-CLE-220-EM-SO

STARK-CLE-315-EM

STARK-CLE-315-EM-SO

STARK-CLE-360-EM

STARK-CLE-360-EM-SO

© 2014 Tridonic 4 / 20

TALEXXmodule SLE GEN3 CLASSIC / TALEXXmodule SLE GEN3 CLASSIC EM LED light modules for general and emergency lighting

Designation variants and article number Most important facts Images

CLASSIC LED light module for general lighting STARK-SLE-G3-19-2000-830-CLA, 89601800 STARK-SLE-G3-19-2000-840-CLA, 89601801 STARK-SLE-G3-23-3000-830-CLA, 89601802 STARK-SLE-G3-23-3000-840-CLA, 89601803 CLASSIC EM Combined LED light module for general and emergency lighting with integrated separate wired emergency LEDs operated by EM powerLED STARK-SLE-G3-19-2000-830-CLA-EM, 89601868 STARK-SLE-G3-19-2000-840-CLA-EM, 89601869 STARK-SLE-G3-23-3000-830-CLA-EM, 89601870 STARK-SLE-G3-23-3000-840-CLA-EM, 89601871

� MacAdam 3 � Fixing holes for M3 screws � Cooling: see data sheet � Ø 50 mm, height: 7,2 mm STARK-SLE-G3-19-2000… Typ. luminous flux at tp 65°C:: 350 mA /

11,9 W 1050 mA / 40,9 W

3.000 K 1.300 lm 3.250 lm

4.000 K 1.500 lm 3.750 lm

STARK-SLE-G3-23-3000… Typ. luminous flux at tp 65°C: 500 mA /

16,9 W 1400 mA / 52,8 W

3.000 K 1.900 lm 4.459 lm

4.000 K 2.100 lm 5.100 lm

SLE GEN3 CLASSIC / SLE GEN3 24 CLASSIC EM

© 2014 Tridonic 5 / 20

LED emergency control gears

EM powerLED 2 W LED emergency control gear for single battery

Designation variants and article number Most important facts Images

Screw fixing EM powerLED 2 W BASIC, 89899859 EM powerLED 2 W ST, 89899861 EM powerLED 2 W PRO EZ-3, 89800030 Clip fixing EM powerLED 2 W BASIC, 89899866 EM powerLED 2 W ST, 89899868 EM powerLED 2 W PRO EZ-3, 89800032

� For mains and emergency operation � Output current: 600 mA (1 LED), 350 mA

(2 LED in series) � 1 h, 2 h und 3 h rated duration � NiMH batteries � SELV � For luminaire installation � 139 x 30 x 21 mm (Screw fixing) � 127 x 30 x 21 mm (Clip fixing) Test variants: � Manually tested (BASIC) � Automatically self tested (SELFTEST) � Automatically tested by a controller

(DALI)

Screw fixing

Clip fixing

EM powerLED 4 W LED emergency control gear for single battery

Designation variants and article number Most important facts Images

Screw fixing EM powerLED 4 W BASIC, 89800122 EM powerLED 4 W ST, 89800124 EM powerLED 4 W PRO EZ-3, 89800126 Clip fixing EM powerLED 4 W BASIC, 89800121 EM powerLED 4 W ST, 89800123 EM powerLED 4 W PRO EZ-3, 89800125

� Non maintained operation � Output current: 1,000mA (1 LED), 700

mA (2 LED in series) � 1h, 2h und 3 h rated duration � NiMH and NiCd batteries � SELV � For luminaire installation � 139 x 30 x 21 mm (Screw fixing) � 127 x 30 x 21 mm (Clip fixing) Test variants: � Manually tested (BASIC) � Automatically self tested (SELFTEST) � Automatically tested by a controller

(DALI)

Screw fixing

Clip fixing

LED control gear for mains operation Vide „Selecting compatible mains control gear…” on the following pages. For technical details go to the product’s data sheet at www.tridonic.com

© 2014 Tridonic 6 / 20

Possible combinations Notice: The decision which variant of the EM powerLED (2W or 4W) is used for emergency lighting depends on the demanded emergency power. Typically the emergency power is approximately 10% of the power achieved in general lighting. If the resulting luminous flux maintenance factor of the EM powerLED 2W in emergency mode is too low, the EM powerLED 4W can be used instead. However the higher light output requires more battery power.

TALEXXmodule QLE

LED light modules for general and emergency lightin g

Light module for general lighting

Combined light module for general and

emergency lighting Mains control gear Emergency control

gear

STARK QLE CLASSIC

+

STARK QLE CLASSIC

EM

+ See

“Selecting compatible mains control gear”

+

EM powerLED 2 W / EM powerLED 4 W

Operation parameter for different numbers of LED mo dules The number of LED modules depends on the design of the luminaire. As a rule in emergency operation one LED module of the luminaire is set up as a combined module with separate emergency LEDs (QLE EM). The emergency LEDs are operated with EM powerLED.

© 2014 Tridonic 7 / 20

Mains operation Emergency operation*

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 45 °C for

Light output ratio EM powerLED 2W

Light output ratio EM powerLED 4W

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Number [mA] [W] [lm] [%] [%]

250 7,8 1.210 1.250 310 320 590 600

1 250 7,8 1.210 1.250 25,6 25,6 48,8 48,0

2 250 15,6 2.420 2.500 12,8 12,8 24,4 24,0

3 250 23,4 3.630 3.750 8,5 8,5 16,3 16,0

4 250 31,2 4.840 5.000 6,4 6,4 12,2 12,0

5 250 39 6.050 6.250 5,1 5,1 9,8 9,6

6 250 46,8 7.260 7.500 4,3 4,3 8,1 8,0

Number [mA] [W] [lm] [%] [%]

300 9,5 1.430 1.480 310 320 590 600

1 300 9,5 1.430 1.480 21,7 21,6 41,3 40,5

2 300 19 2.860 2.960 10,8 10,8 20,6 20,3

3 300 28,5 4.290 4.440 7,2 7,2 13,8 13,5

4 300 38 5.720 5.920 5,4 5,4 10,3 10,1

5 300 47,5 7.150 7.400 4,3 4,3 8,3 8,1

6 300 57 8.580 8.880 3,6 3,6 6,9 6,8

Number [mA] [W] [lm] [%] [%]

350 11,3 1.670 1.730 310 320 590 600

1 350 11,3 1.670 1.730 18,6 18,5 35,3 34,7

2 350 22,6 3.340 3.460 9,3 9,2 17,7 17,3

3 350 33,9 5.010 5.190 6,2 6,2 11,8 11,6

4 350 45,2 6.680 6.920 4,6 4,6 8,8 8,7

5 350 56,5 8.350 8.650 3,7 3,7 7,1 6,9

6 350 67,8 10.020 10.380 3,1 3,1 5,9 5,8

* One LED module of the luminaire acts as a combined module with separate emergency LEDs

© 2014 Tridonic 8 / 20

Selecting compatible mains control gear for TALEXXm odule QLE A list of compatible mains control gear can be found in the LED lamp matrix: http://www.tridonic.com/com/en/lamp-matrix.asp

Wiring example

STARK QLE + STARK QLE EM + Mains control gear + EM powerLED

Note: For manually tested emergency lighting Due to the fact that independent circuits are used for normal and emergency lighting it is important that the normal supply of the mains control gear is switched off together with the permanent emergency supply prior to checking the operation of the emergency LEDs. If this is not done then it may not be possible to see that the emergency LEDs are operating. Please refer to the EM powerLED 2W resp. EM powerLED 4W datasheet for further information.

Note: For emergency lighting with EM powerLED 2W: With the mains operation function of EM powerLED 2W a simple Corridor Function can be realised. Please refer to the EM powerLED 2W datasheet for further information.

© 2014 Tridonic 9 / 20

TALEXXmodule LLE24

LED light modules for general and emergency lightin g

Light module for general lighting

Combined light module for general and

emergency lighting Mains control gear Emergency control

gear

STARK LLE24

CLASSIC

+

STARK LLE24 CLASSIC EM

+ See

“Selecting compatible mains control gear”

+

EM powerLED 2 W / EM powerLED 4 W

© 2014 Tridonic 10 / 20

Operation parameter for different numbers of LED mo dules

Mains operation Emergency operation*

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 45 °C for

Light output ratio EM powerLED 4W

3,000K 4,000K 3,000K 4,000K

Number [mA] [W] [lm] [%]

250 7,8 1.130 1.170 550 560

1 250 7,8 1.130 1.170 48,7 47,9

2 250 15,6 2.260 2.340 24,3 23,9

3 250 23,4 3.390 3.510 16,2 16,0

4 250 31,2 4.520 4.680 12,2 12,0

5 250 39 5.650 5.850 9,7 9,6

6 250 46,8 6.780 7.020 8,1 8,0

Number [mA] [W] [lm] [%]

300 9,6 1.320 1.360 550 560

1 300 9,6 1.320 1.360 41,7 41,2

2 300 19,2 2.640 2.720 20,8 20,6

3 300 28,8 3.960 4.080 13,9 13,7

4 300 38,4 5.280 5.440 10,4 10,3

5 300 48 6.600 6.800 8,3 8,2

6 300 57,6 7.920 8.160 6,9 6,9

Number [mA] [W] [lm] [%]

350 11,4 1500 1550 550 560

1 350 11,4 1500 1550 36,7 36,1

2 350 22,8 3000 3100 18,3 18,1

3 350 34,2 4500 4650 12,2 12,0

4 350 45,6 6000 6200 9,2 9,0

5 350 57 7500 7750 7,3 7,2

© 2014 Tridonic 11 / 20

6 350 68,4 9000 9300 6,1 6,0

* One LED module of the luminaire acts as a combined module with separate emergency LEDs

Selecting compatible mains control gear for TALEXXm odule LLE24 A list of compatible mains control gear can be found in the LED lamp matrix: http://www.tridonic.com/com/en/lamp-matrix.asp

Wiring example

STARK LLE24 + STARK LLE24 EM + Mains control gear + EM powerLED

Note: For manually tested emergency lighting Due to the fact that independent circuits are used for normal and emergency lighting it is important that the normal supply of the mains control gear is switched off together with the permanent emergency supply prior to checking the operation of the emergency LEDs. If this is not done then it may not be possible to see that the emergency LEDs are operating. Please refer to the EM powerLED 2W resp. EM powerLED 4W datasheet for further information.

Note: For emergency lighting with EM powerLED 2W: With the mains operation function of EM powerLED 2W a simple Corridor Function can be realised. Please refer to the EM powerLED 2W datasheet for further information.

© 2014 Tridonic 12 / 20

TALEXXmodule CLE EM

LED light modules for general and emergency lightin g

Combined light module for general and

emergency lighting Mains control gear Emergency control

gear

STARK-CLE-220-EM

- or -

STARK-CLE-220-EM-

SO - or -

STARK-CLE-315-EM

- or -

STARK-CLE-315-EM-

SO - or -

STARK-CLE-360-EM

- or -

STARK-CLE-360-EM-

SO

+

See “Selecting compatible mains control gear”

+

EM powerLED 2 W

© 2014 Tridonic 13 / 20

Operation parameter for one LED module

STARK CLE 220-1500 CLASSIC EM

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED NM 1 W

BASIC / EM powerLED 15 W

BASIC CLE NiCD

Lichtstrom-Verhältnis EM powerLED 15 W BASIC CLE NiMH

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

350 10,3 1.300 1.350 120 125 145 150

1 350 10,3 1.300 1.350 9,2 9,3 11,2 11,1

2 350 20,6 2.600 2.700 4,6 4,6 5,6 5,6

3 350 30,9 3.900 4.050 3,1 3,1 3,7 3,7

4 350 41,2 5.200 5.400 2,3 2,3 2,8 2,8

5 350 51,5 6.500 6.750 1,8 1,9 2,2 2,2

6 350 61,8 7.800 8.100 1,5 1,5 1,9 1,9

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 1 W

Light output ratio EM powerLED 2 W

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

350 10,3 1.300 1.350 130 135 210 220

1 350 10,3 1.300 1.350 10,0 10,0 16,2 16,3

2 350 20,6 2.600 2.700 5,0 5,0 8,1 8,1

3 350 30,9 3.900 4.050 3,3 3,3 5,4 5,4

4 350 41,2 5.200 5.400 2,5 2,5 4,0 4,1

5 350 51,5 6.500 6.750 2,0 2,0 3,2 3,3

6 350 61,8 7.800 8.100 1,7 1,7 2,7 2,7

© 2014 Tridonic 14 / 20

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED NM 1 W

BASIC / EM powerLED 15 W

BASIC CLE NiCD

Light output ratio EM powerLED 15 W BASIC CLE NiMH

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

470 14,3 1.650 1.700 120 125 145 150

1 470 14,3 1.650 1.700 7,3 7,4 8,8 8,8

2 470 28,6 3.300 3.400 3,6 3,7 4,4 4,4

3 470 42,9 4.950 5.100 2,4 2,5 2,9 2,9

4 470 57,2 6.600 6.800 1,8 1,8 2,2 2,2

5 470 71,5 8.250 8.500 1,5 1,5 1,8 1,8

6 470 85,8 9.900 10.200 1,2 1,2 1,5 1,5

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 1 W

Light output ratio EM powerLED 2 W

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

470 14,3 1.650 1.700 130 135 210 220

1 470 14,3 1.650 1.700 7,9 7,9 12,7 12,9

2 470 28,6 3.300 3.400 3,9 4,0 6,4 6,5

3 470 42,9 4.950 5.100 2,6 2,6 4,2 4,3

4 470 57,2 6.600 6.800 2,0 2,0 3,2 3,2

5 470 71,5 8.250 8.500 1,6 1,6 2,5 2,6

6 470 85,8 9.900 10.200 1,3 1,3 2,1 2,2

© 2014 Tridonic 15 / 20

Mains op eration Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED NM 1 W

BASIC / EM powerLED 15 W

BASIC CLE NiCD

Light output ratio EM powerLED 15 W BASIC CLE NiMH

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

500 15,3 1.750 1.800 120 125 145 150

1 500 15,3 1.750 1.800 6,9 6,9 8,3 8,3

2 500 30,6 3.500 3.600 3,4 3,5 4,1 4,2

3 500 45,9 5.250 5.400 2,3 2,3 2,8 2,8

4 500 61,2 7.000 7.200 1,7 1,7 2,1 2,1

5 500 76,5 8.750 9.000 1,4 1,4 1,7 1,7

6 500 91,8 10.500 10.800 1,1 1,2 1,4 1,4

Mains operation Emergency operation

Typ. forward current

Typ. power

consumption

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 1 W

Light output ratio EM powerLED 2 W

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

500 15,3 1.750 1.800 130 135 210 220

1 500 15,3 1.750 1.800 7,4 7,5 12,0 12,2

2 500 30,6 3.500 3.600 3,7 3,8 6,0 6,1

3 500 45,9 5.250 5.400 2,5 2,5 4,0 4,1

4 500 61,2 7.000 7.200 1,9 1,9 3,0 3,1

5 500 76,5 8.750 9.000 1,5 1,5 2,4 2,4

6 500 91,8 10.500 10.800 1,2 1,3 2,0 2,0

© 2014 Tridonic 16 / 20

STARK CLE 315-4000 CLASSIC EM / STARK CLE 360-4000 CLASSIC EM

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 2W

Light output ratio EM powerLED 4W

3,000K 4,000K 3,000K 4,000K 3,000K 4,000K

Anzahl [mA] [W] [lm] [%] [%]

700 21,7 2.500 2.650 235 240 355 365

1 700 21,7 2.500 2.650 9,4 9,1 14,2 13,8

2 700 43,4 5.000 5.300 4,7 4,5 7,1 6,9

3 700 65,1 7.500 7.950 3,1 3,0 4,7 4,6

4 700 86,8 10.000 10.600 2,4 2,3 3,6 3,4

5 700 108,5 12.500 13.250 1,9 1,8 2,8 2,8

6 700 130,2 15.000 15.900 1,6 1,5 2,4 2,3

Anzahl [mA] [W] [lm] [%] [%]

1.050 34,1 3.600 3.750 235 240 355 365

1 1.050 34,1 3.600 3.750 6,5 6,4 9,9 9,7

2 1.050 68,2 7.200 7.500 3,3 3,2 4,9 4,9

3 1.050 102,3 10.800 11.250 2,2 2,1 3,3 3,2

4 1.050 136,4 14.400 15.000 1,6 1,6 2,5 2,4

5 1.050 170,5 18.000 18.750 1,3 1,3 2,0 1,9

6 1.050 204,6 21.600 22.500 1,1 1,1 1,6 1,6

© 2014 Tridonic 17 / 20

Selecting compatible mains control gear for TALEXXm odule CLE A list of compatible mains control gear can be found in the LED lamp matrix: http://www.tridonic.com/com/en/lamp-matrix.asp

Wiring example

STARK CLE EM + Mains control gear + EM powerLED

Note: For manually tested emergency lighting Due to the fact that independent circuits are used for normal and emergency lighting it is important that the normal supply of the mains control gear is switched off together with the permanent emergency supply prior to checking the operation of the emergency LEDs. If this is not done then it may not be possible to see that the emergency LEDs are operating. Please refer to the EM powerLED 2W resp. EM powerLED 4W datasheet for further information.

Note: For emergency lighting with EM powerLED 2W: With the mains operation function of EM powerLED 2W a simple Corridor Function can be realised. Please refer to the EM powerLED 2W datasheet for further information.

© 2014 Tridonic 18 / 20

TALEXXmodule SLE GEN3 CLASSIC / TALEXXmodule SLE GEN3 CLASSIC EM

LED light modules for general and emergency lightin g

Light module for general lighting

Combined light module for general and

emergency lighting Mains control gear Emergency control

gear

STARK-SLE-CLA

+

STARK-SLE-CLA-EM

+

Siehe Übersicht “Auswahl von kompatiblen

Netzbetriebsgeräten”

+

EM powerLED 2 W / EM powerLED 4 W

© 2014 Tridonic 19 / 20

Operation parameter for one LED module

STARK-SLE-G3-19-2000

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 2W

3.000K 4.000K 3.000K 4.000K

Number [mA] [W] [lm] [%]

350 11,9 1.300 1.500 225 240

1 350 11,9 1.300 1.500 17,3 16,0

Anzahl [mA] [W] [lm] [%]

1.050 40,9 3.250 3.750 225 240

1 1.050 40,9 3.250 3.750 6,9 6,4

STARK-SLE-G3-23-3000

Mains operation Emergency operation

Typ. forward current

Typ. power

consump-tion

Typ. luminous flux at tp = 65 °C for

Light output ratio EM powerLED 4W

3.000K 4.000K 3.000K 4.000K

Number [mA] [W] [lm] [%]

500 16,9 1.900 2.100 420 440

1 500 16,9 1.900 2.100 22,1 21,0

Anzahl [mA] [W] [lm] [%]

1.400 52,8 4.450 5.100 420 440

1 1.400 52,8 4.450 5.100 9,4 8,6

© 2014 Tridonic 20 / 20

Selecting compatible mains control gear for TALEXXm odule SLE GEN3 CLASSIC A list of compatible mains control gear can be found in the LED lamp matrix: http://www.tridonic.com/com/en/lamp-matrix.asp

Wiring example

STARK SLE GEN3 CLASSIC + mains control gear + EM po werLED

Note: For manually tested emergency lighting Due to the fact that independent circuits are used for normal and emergency lighting it is important that the normal supply of the mains control gear is switched off together with the permanent emergency supply prior to checking the operation of the emergency LEDs. If this is not done then it may not be possible to see that the emergency LEDs are operating. Please refer to the EM powerLED 2W resp. EM powerLED 4W datasheet for further information.

Note: For emergency lighting with EM powerLED 2W: With the mains operation function of EM powerLED 2W a simple Corridor Function can be realised. Please refer to the EM powerLED 2W datasheet for further information.

Wiring Cable: AWG24; length 300 mm

Pin 1 2 3 4 5 6

Function colour

+ (LED) red

- (LED) black

+ (EM) red

- (EM) black

NTC (LED) grey

NTC (LED) grey

Technical Sales November 2014